HomeMy WebLinkAboutFire District Plan ReviewST. LUCIE COUNTY FIRE DISTRICT
BUREAU OF FIRE PREVENTION
2400 RHODE ISLAND AVE. TELEPHONE
FT. PIERCE, FL. AVE. FAX NO.
PLAN REVIEW
JURISDICTION:
St Lucie County
OCCUPANCY:
Tom Donnick's Fabricated Metal
ADDRESS:
3504 Industrial 271' St
CONTRACTOR:
Metropolitan Construction Inc
CONTRACTORS ADDRESS: 1101 N Kentucky
ARCHITECT/ENGINEER:
Steve Clark
-3UILDING OWNER:
OCCUPANCY TYPE:
Industrial
GROSS SQ FT:
Total w/addition 11,000
OCCUPANT LOAD:
110
CONSTRUCTION TYPE:(
NFPA-220) Type:
New Construction: X Automatic Sprinkler: Contractor:
Tenant Improvement: Fire Alarm System Contractor:
Shell Only: Fixed Fire Suppression: Contractor:
Addition: Hood & Duct System: Contractor:
Renovation: Fuel Storage: Contractor:
(561)-462-2312
(561)-462-2323
F.P.B. B-99-16
BUILDING DEPT. 99050116
NUMBER OF STORIES: 1
PHONE NO: 407-645-0355
CITY: Winter Park, FL ZIP: 32789
PHONE NO: 561-337-2301
REVIEW DATE: 5-28-99
AUTOMATIC SP'KLRS:
NET SQ FT:
BASED ON: 100 sq ft per per
SBCCI: Type: V
1. All revisions must be in compliance before the final inspection, or so noted.
2. The Fire Marshal requires 24 hour notice on all inspections.
3. The Building Department schedule all final inspections by the Fire Marshal.
4. A copy of the required revisions has been mailed to the Architect: Contractor: Yes No X
Required Revisions:
1. Fire extinguishers - install a 2A-IOBC rated fire extinguisher every 75' of travel distance.
2. Based on the new total square feet of 11,000, the occupant load is now 110 persons. This
figure is based on 100 square foot per person for gross floor area. NFPA 101 Chapter 28-
3.4.1 requires the installation of a fire alarm system.
.ter
Reviewed By: Date: May 28, 1999
Tony Liento