EVALUATION REPORT
Eagle Roofing Products Florida LLC.
1575 East Country Road 470
Sumterville, FL 33585
(800) 400-3245
Evaluation Report E1322.09.06-R5
FL7473-R8
Date of Issuance: 02/24/2009
Revision 5: 10/16/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 6th Edition (2017) Florida Building Code
(NON-HVHZ) sections noted herein.
DESCRIPTION: Eagle Roof Tiles
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity|ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words “Evaluated by Robert Nieminen, P.E.” may be
displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its
entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 5.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The facsimile seal appearing was authorized by Robert Nieminen,
P.E. on 10/16/2017. This does not serve as an electronically signed
document. Signed, sealed hardcopies have been transmitted to the
Product Approval Administrator and to the named client
CERTIFICATION OF INDEPENDENCE:
1. Trinity|ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinity|ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval proc ess of the
product.
5. This is a building code evaluation. Neither Trinity|ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless r etained
specifically for that purpose.
Exterior Research and Design, LLC. 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Evaluation Report E1322.09.06-R5
Certificate of Authorization #9503 Eagle Roofing Products Florida LLC.; (800) 400-3245 FL7473-R8
Revision 5: 10/16/2017
Page 2 of 5
ROOFING SYSTEM EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub-Category: Roofing Tiles
Compliance Statement: Eagle Roof Tiles, as produced by Eagle Roofing Products Florida LLC, have demonstrated
compliance with the following sections of the 6th Edition (2017) Florida Building Code (NON-HVHZ) through testing
in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations /
Conditions of Use set forth herein.
2. STANDARDS:
Section Property Standard Year
1507.3.5, R905.3.5 Physical Properties ASTM C1492 2003(2009)
1507.3.7, R905.3.7 Attachment Requirements FRSA/TRI April 2012 (04-12) 2012
1504.2.1.1 Overturning Moment SSTD 11 1997
3. REFERENCES:
Entity Examination Reference Date
ATL (TST 3782) ASTM C1492 RT0310.01-17, 02-17, 03-17 03/15/2017
ATL (TST 3782) ASTM C1492 – Freeze/thaw RT0706.01-17, 02-17, 03-17 09/25/2017
Tile Roof Institute SSTD 11 Membership Letter 11/29/2005
ATI (QUA 1844) Quality Assurance Inspection Report 06/07/2017
4. PRODUCT DESCRIPTION:
4.1 ASTM C1492, Type III (Low Profile): BEL AIR
Exterior Research and Design, LLC. 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Evaluation Report E1322.09.06-R5
Certificate of Authorization #9503 Eagle Roofing Products Florida LLC.; (800) 400-3245 FL7473-R8
Revision 5: 10/16/2017
Page 3 of 5
4.2 ASTM C1492, Type II (Medium Profile): MALIBU
4.3 ASTM C1492, Type I (High Profile): CAPISTRANO
5. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity|ERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire classification is not part of this evaluation; refer to FBC 1505.2, Exception 2 (for non-combustible
deck) or listing by an approved testing agency for fire rating of this product.
5.4 Underlayment shall be that which holds Florida Product Approval for use with tile roofing systems. The
underlayment Product Approval shall specify allowable method(s) of tile installation (mec hanical
attachment, mortar-set and/or adhesive-set) for use with the specific underlayment. For mortar-set or
adhesive-set tile roofing applications, the underlayment Product Approval shall specify attachment
methods for the underlayment system to resist wind uplift design loads in accordance with Table 1A of
FRSA/TRI April 2012 (04-12).
5.5 ”Color-Bonded” or “Slurry-Coated” files are limited to use on projects in areas subjected to weathering
indices of 50 or less (negligible weathering), as outlined in Figure 1 of ASTM C1492-03(2009)i, reproduced
below for reference. This limitation does not apply to the “Color-Through” product offering.
5.6 All products in the roof assembly shall have quality assurance audit in accordance with FAC Rule 61G20-3.
Exterior Research and Design, LLC. 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Evaluation Report E1322.09.06-R5
Certificate of Authorization #9503 Eagle Roofing Products Florida LLC.; (800) 400-3245 FL7473-R8
Revision 5: 10/16/2017
Page 4 of 5
6. INSTALLATION:
6.1 Eagle Roof Tiles may be mechanically fastened, mortar-set or adhesive-set. Installation shall comply with
manufacturer’s current published instructions, but not less than the requirements of FBC 1507.3 and the
FRSA/TRI Florida High Wind Concrete and Clay Tile Installation Manual.
6.2 Underlayment shall be installed in accordance with FRSA/TRI April 2012 (04-12) or the underlayment
manufacturer’s current Product Approval. For mortar-set or adhesive-set tile roofing applications, the
underlayment current Product Approval shall specify attachment methods for the underlayment system to
resist wind uplift design loads in accordance with Table 1A of FRSA/TRI April 2012 (04-12).
6.3 Tile Attachment:
6.3.1 Mechanically Attached Tile:
Wind load resistance shall be in accordance with Table 3 of FRSA/TRI April 2012 (04 -12) to resist the Uplift
Moment determined in Table 2A or 2B of FRSA/TRI April 2012 (04-12) or FBC 1609.5.3.
6.3.2 Mortar-Set Tile:
Wind load resistance shall be in accordance with Table 2A or 2B of FRSA/TRI April 2012 (04-12) or FBC
1609.5.3 in conjunction with the mortar manufacturer’s Product Approval.
6.3.3 Adhesive-Set Tile:
Wind load resistance shall be in accordance with Table 2A or 2B of FRSA/TRI April 2012 (04-12) or FBC
1609.5.3 in conjunction with the adhesive manufacturer’s current Product Approval. Refer to the current
version of the referenced Florida Product Approval for paddy-placement details and performance data.
TILE ADHESIVES FOR ADHESIVE-SET TILE SYSTEMS
Manufacturer Product(s) Florida Product Approval
DAP Foam, Inc.
“Touch N’ Seal Storm Bond” FL14506
“Touch N’ Seal Storm Bond 2” FL21374
Dow Chemical “TILE BOND™” FL22525
ICP Adhesives & Sealants, Inc.
“Polyset® AH-160” FL6332
“Polyset® RTA-1” FL6276
6.3.4 Hip and Ridge Tile:
Tile shall be installed in accordance with FRSA/TRI April 2012 (04-12). For hip and ridge tile installations
atop hip and ridge metal, refer to the hip and ridge metal manufacturer’s current Product Approval (e.g.,
FL5374) or test report in accordance with SSTD 11 for allowable loads to resist those determined in
accordance with Table 1A of FRSA/TRI April 2012 (04-12).
Exterior Research and Design, LLC. 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Evaluation Report E1322.09.06-R5
Certificate of Authorization #9503 Eagle Roofing Products Florida LLC.; (800) 400-3245 FL7473-R8
Revision 5: 10/16/2017
Page 5 of 5
7. LABELING:
7.1 Each unit shall bear the imprint or identifiable marking of the manufacturer’s name or logo . Tile lots shall
be labeled in accordance with the requirements of the Accredited Quality Assurance Agency noted herein.
7.2 Tile not tested for freeze-thaw shall state clearly that the lot has not been tested for freeze-thaw
acceptance on all lot tags or certification.
8. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
9. MANUFACTURING PLANTS:
Sumterville, FL
10. QUALITY ASSURANCE ENTITY:
Architectural Testing, Inc. – QUA1844; (717) 764-7700
- END OF EVALUATION REPORT -