HomeMy WebLinkAboutcarrier_dhmshaq09xa3_article_2140342170249591_en_ssProduct Data
DHMSHA
High Wall Ductless System
Sizes 09 to 36
NOTE: Images are for illustration purposes only. Actual models
may differ slightly.
TABLE OF CONTENTS
PAGE
MODEL NUMBER NOMENCLATURE 3.................
STANDARD FEATURES AND ACCESSORIES 4...........
DIMENSIONS 5......................................
CLEARANCES 8.....................................
SPECIFICATIONS 9...................................
COMPATIBILITY 9...................................
APPLICATION DATA 10...............................
WIRING DIAGRAMS 13...............................
GUIDE SPECIFICATIONS 16...........................
INDUSTRY LEADING
FEATURES / BENEFITS
A PERFECT BALANCE BETWEEN
BUDGET LIMITS, ENERGY SAVINGS AND
COMFORT.
The DHMSHA series ductless systems are a matched combination
of an outdoor condensing unit and an indoor fan coil unit
connected only by refrigerant tubing and wires.
The fan coil is mounted on the wall, near the ceiling. This selection
of fan coils permits creative solutions to design problems such as:
Add-ons to current space (an office or family room
addition)
Special space requirements
When changes in the load cannot be handled by the
existing system
When adding air conditioning to spaces that are heated
by hydronic or electric heat and have no ductwork
Historical renovations or any application where
preserving the look of the original structure is essential.
The ideal compliment to your ducted system when it is impractical
or prohibitively expensive to use ductwork.
These compact indoor fan coil units take up very little space in the
room and do not obstruct windows. The fan coils are attractively
styled to blend with most room decors. Advanced system
components incorporate innovative technology to provide reliable
cooling performance at low sound levels.
2
LOW SOUND LEVELS
When noise is a concern, the ductless systems are the answer. The
indoor units are whisper quiet. There are no compressors indoors,
either in the conditioned space or directly over it, and there is
none of the noise usually generated by air being forced through
ductwork.
SECURE OPERATION
If security is an issue, outdoor and indoor units are connected only
by refrigerant piping and wiring to prevent intruders from crawling
through ductwork. In addition, since the outdoor units can be
installed close to an outside wall, coils are protected from vandals
and severe weather.
FAST INSTALLATION
This compact ductless system is simple to install. A mounting
bracket is standard with the indoor units and only wire and piping
need to be run between the indoor and outdoor units. These units
are fast and easy to install ensuring minimal disruption to
customers in the home or workplace. This makes the DHMSHA
ductless systems the equipment of choice, especially in retrofit
situations.
SIMPLE SERVICING AND MAINTENANCE
Removing the top panel on outdoor units provides immediate
access to the control compartment, providing a service technician
access to check unit operation. In addition, the draw-thru design of
the outdoor section means that dirt accumulates on the outside
surface of the coil. Coils can be cleaned quickly from the inside
using a pressure hose and detergent.
On all indoor units, service and maintenance expense is reduced
due to easy-to-use cleanable filters. In addition, these high wall
systems have extensive self-diagnostics to assist in
troubleshooting.
BUILT-IN RELIABILITY
Ductless system indoor and outdoor units are designed to provide
years of trouble-free operation.
The high wall indoor units include protection against freeze-up
and high evaporator temperatures on heat pumps.
The condensing units on heat pumps are protected by a three
minute time delay before the compressor starts the over-current
protection and the high temperature protection.
INDIVIDUAL ROOM COMFORT
Maximum comfort is provided because each space can be
controlled individually based on usage pattern. The air sweep
feature provided permits optimal room air mixing to eliminate hot
and cold spots for occupant comfort. In addition, year-round
comfort can be provided with heat pumps.
ECONOMICAL OPERATION
The ductless system design allows individual room heating or
cooling when required. There is no need to run large supply-air
fans or chilled water pumps to handle a few spaces with unique
load patterns. In addition, because air is moved only in the space
required, no energy is wasted while air moves through the ducts.
EASY-TO-USE CONTROLS
The high wall units have microprocessor-based controls to provide
the ultimate in comfort and efficiency. The user friendly wireless
remote control provides the interface between the user and the unit.
ACCESSORIES
Customizing these ductless systems to your application is easily
accomplished.
Adding a condensate pump accessory to the high wall fan coil
provides installation flexibility.
OPTIONAL WIRED CONTROLLER
AGENCY LISTINGS
All systems are listed with AHRI (Air Conditioning, Heating &
Refrigeration Institute), and ETL.
3
MODEL NUMBER NOMENCLATURE
AH09
A = MAJOR SERIES
INDOOR FAN COIL TYPE
H = HIGH WALL
NOT USED
INDOOR UNIT
DH M 3Q
DH = FAN COIL UNIT
MS = MODEL
VOLTAGE
1 =115-1-60
3 = 208/230-1-60
SYSTEM TYPE
Q = HEAT PUMP
NOMINAL CAPACITY
09 - 3/4 TON
12 - 1 TON
18 - 1-1/2 TONS
24 - 2 TONS
30 - 2 -1/2 TONS
36 - 3 TONS
X A
VARIATIONS
A = STANDARD
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
4
STANDARD FEATURES AND ACCESSORIES
Ease Of Installation
Mounting Brackets S
Low Voltage Controls S
Comfort Features
Microprocessor Controls S
Wired Remote Control A
Wireless Remote Control S
Automatic Up-Down Airflow Louver Swing S
Air Direction Control S
Auto Restart Function S
Cold Blow Protection On Heat Pumps S
Freeze Protection Mode On Heat Pumps S
Turbo Mode S
Silence Mode S
Auto Changeover On Heat Pumps S
Follow Me S
Energy Saving Features
Sleep Mode S
Stop/Start Timer S
46°F Heating Mode (Heating Setback)S
Safety And Reliability
Indoor Coil Freeze Protection S
Indoor Coil High Temp Protection in Heating Mode S
Aluminum Blue Hydrophilic pre-coated fins S
Ease Of Service And Maintenance
Cleanable Filters S
Diagnostics S
Carbon Filter S
Application Flexibility
Condensate Pumps A
Legend
S Standard
A Accessory
ACCESSORIES
ACCESSORY NO.DESCRIPTION FOR MODELS
53DS-900---117 CONDENSATE PUMP
(115V)SIZES 09, 12 (115V)
53DS-900---118 CONDENSATE PUMP
(208-230V)
SIZES 09, 12, 18, 24,
30 (208-230V)
KSACN0101AAA
WIRED REMOTE
CONTROL WITH
TIMER FUNCTION
ALL SIZES
KSACN0401AAA
WIRED REMOTE
CONTROL 7 DAY
PROGRAMMABLE*
ALL SIZES
KSAIC0101115 24V INTERFACE KIT
115V 115V MODELS**
KSAIC0101230 24V INTERFACE KIT
230V 208/230V MODELS**
53DS-900---089 INSULATED 25’ LINE
SET - 1/4” X 3/8”SIZE 09
53DS-900---008 INSULATED 25’ LINE
SET - 1/4“ X 1/2”SIZES 12, 18
NOTE: *KSACN0401AAA Wired Remote Control 7 Day
programmable compatible with High Walls Units starting with
Serial Number 0216V10001.
**24V Interface compatible with High Walls Units starting with
Serial Number 4316V10001.
INDOOR UNITS
Fig. 1 – Condensate Pump Accessory
On high wall fan coils, the condensate pump has a lift capability
of 12 ft. (3.6 m) on the discharge side with the pump mounted in
the fan coil or 6 ft. (1.8 m) on the suction side if the pump is
remote mounted. The pump is recommended when an adequate
drain line pitch cannot be provided, or when the condensate must
move up to exit.
NOTE: An external 115v power source is required to run the
pump on unit sizes 9k and 12k.
5
DIMENSIONS - INDOOR
Fig. 2 – Indoor Unit
HIGH WALL UNIT SIZE 9K 12K 9K 12K 18K 24K 30K 36K
Voltage (115V)(115V)(208/230V)(208/230V)(208/230V)(20/230V)(208/230V)(20/230V)
Height In (mm)11.02 (280)11.02 (280)11.02 (280)11.02 (280)12.40 (315)13.39 (343)13.39 (343)13.39 (343)
Width In (mm)32.87 (835)32.87 (835)32.87 (835)32.87 (835)38.98 (990)46.69 (1186)46.69 (1186)46.69 (1186)
Depth In (mm)7.80 (198)7.80 (198)7.80 (198)7.80 (198)8.58 (218)10.16 (258)10.16 (258)10.16 (258)
Weight-Net Lbs (kg)19.18 (8.7)19.18 (8.7)19.18 (8.7)19.18 (8.7)24.46 (12.0)40.12 (18.2)40.12 (18.2)40.12 (18.2)
9.46 [240]
9.46 [240]
9.25 [235]
9.24 [235]
8.10 [206]
8.15 [207]
6.88 [175]
7.05 [179]5.87 [149]
5.36 [136]
1.86 [47]
7.83[199]8.36 [212]
9.12 [232]
11.03 [280]
1.90 [48]
4.00 [101]12.94 [329]
32.88 [835]
32.88 [835]
13.07 [332]2.87 [73]
11.03 [280]
8.49 [216]
8.49 [216]
1.78 [45]
7.96 [202]
8.28 [210]
32.88 [835]
8.29 [210]
9.17 [233]11.02 [280]
9.61 [244]
1.92 [49]
2.14 [54]
0.31 [8]
Units: Inch (mm)
Drain Hose Ø0.625 (16) L=21 (538)
Fig. 3 – 9K and 12K
6
DIMENSIONS - INDOOR (CONT)
13.29 [337]
12.58 [319]
11.73 [298]
9.54 [242]
7.25 [184]
6.21 [158]
5.08 [129]
4.13 [105]
3.23 [82]
1.08 [27]
10.39 [264]
9.57 [243]
8.78 [223]
11.32 [287]7.53 [191]
5.98 [152]
5.08 [129]
3.15 [80]
4.13 [105]
1.08 [27]
20.42 [519]13.52 [343]
38.98 [990]
0.92 [23]
12.41 [315]
10.21 [259]10.66 [271]
12.40 [315]
5.03 [128]
8.86 [225]
38.98 [990]
12.40 [315]
2.37 [60]
2.16 [55]
0.44 [11]
0.64 [16]
9.68 [246]
10.63 [270]
38.98 [990]
11.32 [287]
Units: Inch (mm)
Drain Hose Ø0.625 (16) L=21 (538)
Fig. 4 – 18K
7
DIMENSIONS - INDOOR (CONT)
14.98 [380]
14.26 [362]
12.54 [319]
11.05 [281]
14.97 [380]
14.25 [362]
12.53 [318]
9.70 [246]
4.33 [110]4.34 [110]
4.53 [115]
12.01 [305]
2.28 [58]
6.65 [169]20.16 [512]18.96 [482]
1.23 [31]
2.13 [54]
13.51 [343]
10.68 [271]
47.00 [1194]
47.01 [1194]
13.51 [343]
11.77 [299]
2.53 [64]
2.40 [61]
0.65 [16]
0.42 [11]
2.19 [56]
10.30 [262]
10.98 [279]
10.68 [271]
Units: Inch (mm)
Drain Hose Ø0.625 (16) L=21 (538)
Fig. 5 – 24K, 30K, 36K
8
CLEARANCES - INDOOR
6" (0.15m) min.
5"
(0.13m)
min.
6'
5"
(0.13m)
min.
(1.8m)
CEILING
FLOOR
Fig. 6 – Indoor Unit Clearance
NOTE: The top clearance recommended for proper return airflow is 5.9in (15cm). Reduction of this clearance may decrease unit
performance. This may be reduced to 3.2in (80mm) as long as the right and left clearances are achieved.
9
SPECIFICATIONS
HEAT PUMP
System
Size 9 12 9 12 18 24 30 36
Indoor Model DHMSHAQ09XA1 DHMSHAQ12XA1 DHMSHAQ09XA3 DHMSHAQ12XA3 DHMSHAQ18XA3 DHMSHAQ24XA3 DHMSHAQ30XA3 DHMSHAQ36XA3
Electrical
Voltage,
Phase,
Cycle
V/Ph/
Hz 115-1-60 115-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Power
Supply Indoor unit powered from outdoor unit
MCA A.0.4 0.4 0.2 0.2 0.27 0.4 0.4 0.4
Controls
Wireless Remote
Controller
(°F/°C Convertible)
Standard Standard Standard Standard Standard Standard Standard Standard
Wired Remote
Controller
(°F/°C Convertible)
Optional Optional Optional Optional Optional Optional Optional Optional
Operating
Range
Cooling
Indoor DB
Min - Max
°F
(° C)
63~86 (17~30)63~86 (17~30)63~86 (17~30)63~86 (17~30)63~86 (17~30)63~86 (17~30)63~86 (17~30)63~86 (17~30)
Heating
Indoor DB
Min - Max
°F
(° C)
32~86 (0~30)32~86 (0~30)32~86 (0~30)32~86 (0~30)32~86 (0~30)32~86 (0~30)32~86 (0~30)32~86 (0~30)
Piping
Pipe
Connection
Size -
Liquid
in
(mm)1/4 (6.35)1/4 (6.35)1/4 (6.35)1/4 (6.35)1/4 (6.35)3/8 (9.52)3/8 (9.52)3/8 (9.52)
Pipe
Connection
Size -
Suction
in
(mm)3/8 (9.52)1/2 (12.7)3/8 (9.52)1/2 (12.7)1/2 (12.7)5/8 (16)5/8 (16)5/8 (16)
Indoor
Coil
Face Area
(sq. ft.)Sq. Ft.2.2 2.2 2.2 2.2 2.6 3.7 3.7 3.7
No. Rows 2 2 2 2 2 3 3 3
Fins per
inch 20 20 20 20 20 18 18 18
Circuits 3 3 3 3 4 7 7 7
Indoor
Unit Width in
(mm)32.87 (835)32.87 (835)32.87 (835)32.87 (835)38.98 (990)46.69 (1186)46.69 (1186)46.69 (1186)
Unit Height in
(mm)11.02 (280)11.02 (280)11.02 (280)11.02 (280)12.40 (315)13.39 (343)13.39 (343)13.39 (343)
Unit Depth in
(mm)7.80 (198)7.80 (198)7.80 (198)7.80 (198)8.58 (218)10.16 (258)10.16 (258)10.16 (258)
Net Weight lbs
(kg)19.18 (8.7)19.18 (8.7)19.18 (8.7)19.18 (8.7)26.46 (12.0)40.12 (18.2)40.12 (18.2)40.12 (18.2)
Fan Speeds 4 4 4 4 4 4 4 4
Airflow
(lowest to
highest)
CFM 210/290/360/380 210/300/360/380 210/290/360/380 210/300/360/380 310/450/650/680 520/620/780/870 520/620/780/870 520/620/780/870
Sound
Pressure
(lowest to
highest)
dB(A)27/34/42 27/34/42 27/34/42 27/34/42 33/40/46 39/45/50 39/45/50 39/45/50
Air throw
Data ft (m)23 (7)23 (7)23 (7)23 (7)30 (9)36 (11)36 (11)36 (11)
Moisture
Removal
Pint/h
(L/h)1.5 (0.7)2.8 (1.3)1.1 (0.5)2.3 (1.1)3.8 (1.8)5.4 (2.6)8.1 (3.9)11.7 (5.6)
Field Drain
Pipe Size
O.D.
in
(mm)0.625 (16)0.625 (16)0.625 (16)0.625 (16)0.625 (16)0.625 (16)0.625 (16)0.625 (16)
Performance may vary based on the Outdoor unit matched to. See compatible Outdoor Units pages for Performance Data
COMPATIBILITY TABLE
Indoor Unit DHMSHAQ09XA1 DHMSHAQ12XA1 DHMSHAQ09XA3 DHMSHAQ12XA3 DHMSHAQ18XA3 DHMSHAQ24XA3 DHMSHAQ30XA3 DHMSHAQ36XA3
Outdoor Unit
Single Zone 38MAQB09R--1 38MAQB12R--1 38MAQB09R--3 38MAQB12R--3 38MAQB18R--3 38MAQB24R--3 38MAQB30R--3 38MAQB36R--3
Outdoor Unit
Multi-zone
38MGRQ18B--3
38MGRQ24C--3
38MGRQ30D--3
38MGRQ36D--3
38MGRQ48E--3
NOTE: Backward compatible with 38MAQ Single Zone and 38MGQ Multi-zone Systems
10
APPLICATION DATA
UNIT SELECTION
Select equipment that either matches or is supports slightly more
than the anticipated peak load. This provides better humidity
control, fewer unit cycles, and less part-load operation.
For units used in spaces with high sensible loads, base equipment
selection on unit sensible load, not on total anticipated load. Adjust
for anticipated room wet bulb temperature to avoid undersizing the
equipment.
UNIT MOUNTING (INDOOR)
Refer to the unit’s installation instructions for further details.
Unit leveling - For reliable operation, units should be level in all
planes.
Clearance - Provide adequate clearance for airflow (see Fig. 6).
Unit location - Select a location which provides the best air
circulation for the room. These units should be positioned as high
as possible on the wall for the best air circulation. The unit return
and discharge should not be obstructed by furniture, curtains, or
anything which may cause unit short cycling or air recirculation.
Place the unit in the middle of the selected wall (if possible). Use
an outside wall, if available, to make piping easier, and place the
unit so it faces the normal location of room occupants.
UNIT MOUNTING (OUTDOOR)
Refer to the unit’s installation instructions for further details.
Do not install the indoor or outdoor units in a location with special
environmental conditions. For those applications, contact your
Carrier representative.
MOUNTING TEMPLATE
Refer to the unit’s installation instructions for further details.
The fan coil units are furnished with mounting to mark the location
of the wiring, and the refrigeration line hole locations.
SUPPORT
Adequate support must be provided to support the weight of all
the fan coils. Refer to the Physical Data section for fan coil
weights, and the base unit dimensional drawings for the mounting
bracket locations.
SYSTEM OPERATING CONDITIONS
OPERATING RANGE
MIN / MAX °F (°C)
COOLING HEATING
Indoor DB 63 / 90 (17 / 32)32 / 86 (0 / 30)
Indoor WB 59 / 84 (15 / 29)
NOTE: Reference the product installation instructions for more
information.
DRAIN CONNECTIONS
Install drains to meet the local sanitation codes. If adequate gravity
drainage cannot be provided, the unit should be equipped with an
accessory condensate pump. The high wall fan coil unit condensate
pumps have a maximum lift of 10’ (3.05 m) for 9k and 12k units
and 25’ (7.62 m) for 18k and 30k units.
See the physical dimension tables for the drain sizes.
NOTE: High wall fan coil units have internal condensate traps.
A trap is not required.
Drain connections may be routed through alternate locations on
most fan coils (see Fig. 7).
Pipe holder
Pipe cover
Right piping
Left piping
Pipe cover
Right back piping
Left back piping
1 2
3
4
Fig. 7 – Piping Locations
11
WIRING
All wires must be sized per NEC (National Electrical Code) or
CEC (Canadian Electrical Code) and local codes. Use Electrical
Data table MCA (minimum circuit amps) and MOCP (maximum
over current protection) to correctly size the wires and the
disconnect fuse or breakers respectively.
Per the caution note, only stranded copper conductors with a 600
volt insulation rating wire must be used.
Recommended Connection Method for Power and
Communication Wiring:
The main power is supplied to the outdoor unit. The field supplied
14/3 stranded wire with ground with a 600 volt insulation rating,
power/communication wiring from the outdoor unit to indoor unit
consists of four (4) wires and provides the power for the indoor
unit. Two wires are line voltage AC power, one is communication
wiring (S) and the other is a ground wire. Wiring between indoor
and outdoor unit is polarity sensitive. The use of BX wire is NOT
recommended.
If installed in a high Electromagnetic field (EMF) area and
communication issues exists, a 14/2 stranded shielded wire can be
used to replace L2/N and (S) between outdoor unit and indoor unit
landing the shield onto ground in the outdoor unit only.
CAUTION!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Wires should be sized based on NEC and local codes.
Use copper conductors only with a 600 volt insulation
rating wire.
CAUTION!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Be sure to comply with local codes while running wire from
the indoor unit to the outdoor unit.
Every wire must be connected firmly. Loose wiring may cause
the terminal to overheat or result in unit malfunction. A fire
hazard may also exist. Ensure all wiring is tightly connected.
No wire should touch the refrigerant tubing, compressor or
any moving parts.
Disconnecting means must be provided and shall be located
within sight and readily accessible from the air conditioner.
Connecting cable with conduit shall be routed through the
hole in the conduit panel.
CONTROL SYSTEM
The indoor unit is equipped with a microprocessor control to
perform two functions:
1. Provide safety for the system
2. Control the system and provide optimum levels of comfort
and efficiency.
The main microprocessor is located on the control board of the
fan coil unit (outdoor units also have a microprocessor) with
thermistors located in the fan coil air inlet and on the indoor coil.
Heat pump units have a thermistor on the outdoor coil. These
thermistors monitor the system operation to maintain the unit
within acceptable parameters and controls the operating mode.
WIRELESS REMOTE CONTROLLER
Fig. 8 – Wireless remote controller
1. A wireless remote control is supplied for system operation
for system operation of all high wall units.
2. Each battery operated wireless (infrared) remote control
may be used to control more than one unit.
WIRED REMOTE CONTROL (OPTIONAL)
P/N KSACN0101AAA (Timer Function) or KSACN0401AAA
(7 day programmable)
1. Optional wired remote controller used
for system operation of all high wall
units.
2. Kit includes a wired remote controller
and a connecting cable.
3. Connect with wire terminal between
remote controller and indoor unit.
4. Display in F or C and temperature
increments every 1 F or every 1 C.
Fig. 9 – Wired Remote Control
24 INTERFACE
P/N KSAIC0101115 for 115V models
P/N KSAIC0101230 for 208-230Vmodels
Allows the Ductless System to be controlled using a Third Party
Thermostat*
NOTE: 24V Interface compatible with High Walls Units starting
with Serial Number 4316V10001.
12
AIR FLOW DATA
SIZE
9K 12K 9K 12K 18K 24K 30K 36K
(115V)(115V)(208-230V)(208-230V)(208-230V)(208-230V)(208-230V)(208-230V)
Indoor
(CFM)
Turbo 380 380 380 380 680 870 870 870
High 360 360 360 360 650 780 780 780
Medium 290 300 290 300 450 620 620 620
Low 210 210 210 210 310 520 520 520
AIR THROW DATA
SIZE MAX APPROXIMATE AIR THROW ft. (m)APPROXIMATE AIR THROW ft. (m) RANGE
9K, 12K 23 (7)11 (3.5) - 23 (7)
18K 30 (9)13 (4) - 30 (9)
24K, 30K ,36K 36 (11)16 (5) - 36 (11)
AIR MOISTURE
SIZE 9 12 9 12 18 24 30 36
Voltage, Phase, Cycle V/Ph/Hz 115-1-60 115-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Dehumidifying Volume L/h 0.68 1.28 0.5 1.08 1.76 2.55 3.82 5.52
Dehumidifying Volume PINT/h 1.44 2.71 1.06 2.28 3.72 5.39 8.07 11.67
SOUND PRESSURE
SIZE
9K 12K 9K 12K 18K 24K 30K 36K
(115V)(115V)(208-230V)(208-230V)(208-230V)(208-230V)(208-230V)(208-230V)
Indoor Sound Pressure cooling mode (at different speeds)dBa 42/34/27 42/34/27 42/34/27 42/34/27 46.5/40/33 50/45/39 50/45/39 50/45/39
Indoor Sound Pressure heating mode (at different speeds)dBa 40/33/26 41/34/27 40/33/26 41/34/27 45/39/32 47/44/38 47/44/38 47/44/38
ELECTRICAL DATA
SIZE INDOOR FAN MAX FUSE CB AMPV-Ph-Hz FLA HP
9K 115-1-60 0.33 0.053
Refer to outdoor unit installation instructions –
Indoor unit powered by the outdoor unit
12K 0.33 0.053
9K
208/230-1-60
0.33 0.053
12K 0.33 0.053
18K 0.49 0.067
24K 0.61 0.16
30K 0.61 0.16
36K 0.61 0.16
LEGEND
FLA - Full Load Amps
FAN AND MOTOR SPECIFICATIONS
SIZE 9K 12K 9K 12K 18K 24K 30K 36K
(115V)(115V)(208-230V)(208-230V)(208-230V)(208-230V)(208-230V)(208-230V)
INDOOR
FAN
material AS AS AS AS AS AS AS AS
Type GL-98*655-N GL-98*655-N GL-98*655-N GL-98*655-N GL-107.5*760-IN GL-118*895-IN GL-118*895-IN GL-118*895-IN
Diameter inch 3.8 3.8 3.8 3.8 4.2 4.6 4.6 4.6
Height inch 25.8 25.8 25.8 25.8 30 35.2 35.2 35.2
INDOOR
FAN
MOTOR
Model WZDK20-38M WZDK20-38M WZDK20-38G WZDK20-38G WZDK58-38G WZDK60-38G WZDK60-38G WZDK60-38G
Type DC DC DC DC DC DC DC DC
Phase 3 3 3 3 3 3 3 3
FLA 0.17 0.17 0.07 0.07 0.17 0.23 0.23 0.23
Insulation class E E E E E E E E
Safe class IPX0 IPX0 IPX0 IPX0 IPX0 IPX0 IPXO IPX0
Input W 25 25 22 22 52 72 72 72
Output W 20 20 20 20 58 60 60 60
Range of
current Amps 0.17±10%0.17±10%0.07±10%0.07±10%0.17±10%0.23±10%0.23±10%0.23±10%
Rated current Amps 0.17 0.17 0.07 0.07 0.17 0.23 0.23 0.23
Rated HP HP 0.027 0.027 0.027 0.027 0.077 0.08 0.08 0.08
Speed rev/min 1300/1170/900/
700
1300/1170/900/
700
1300/1170/900/
700
1300/1170/900/
700
1300/1170/900/
700
1250/1200/1100/
900
250/1200/1100/
900
250/1200/1100/
900
Rated RPM rev/min 1350 1350 1350 1350 1350 1350 1350 1350
Max. input W 25 25 22 22 52 72 72 72
13
WIRING DIAGRAMS
INDOOR WIRING DIAGRAM
M
CN5
YELLOW
RED
M
5
CN4
N
CN16
L-IN
CN2
P_1
BLUE(BLACK)
INDOOR UNIT
OUTDOOR UNIT
JX1
Y/G
L N S
8(7)
Wire Contoller OPTIONAL
Fig. 10 – Wiring Diagram Sizes 09-12 (115V)
INDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
L_IN Power Voltage: AC 115V
CN11 Power Voltage: AC115V
CN16 Relative to the N terminal voltage:DC 24V
CN15 Maximum voltage:DC5V
CN4 Indoor fan interface,Maximum voltage:DC310V
CN5 Stepper motor interface,Maximum voltage between the lines:DC12V
P_1 Ground
CN8 Room temperature sensor interface,maximum voltage:DC5V
CN9 Pipe temperature sensor interface,maximum voltage:DC5V
CN10A Display interface,maximum voltage between the lines:DC5V
INDOOR WIRING DIAGRAM
M
CN5
YELLOW
RED
M
5
CN4
N
CN11
CN16
L-IN
CN2
P_1
BLUE(BLACK)
INDOOR UNIT
OUTDOOR UNIT
JX1
Y/G
L1L2 S
8(7)
Wire Contoller OPTIONAL
Fig. 11 – Wiring Diagram Sizes 09-12 (208-230V)
INDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
L_IN Power Voltage :AC 230V
CN11 Power Voltage :AC230V
CN16 Relative to the N terminal voltage:DC 24V
CN15 Maximum voltage:DC5V
CN4 Indoor fan interface,Maximum voltage:DC310V
CN5 Stepper motor interface,Maximum voltage between the lines:DC12V
P_1 Ground
CN8 Room temperature sensor interface,maximum voltage:DC5V
CN9 Pipe temperature sensor interface,maximum voltage:DC5V
CN10A Display interface,maximum voltage between the lines:DC5V
14
WIRING DIAGRAMS (CONTINUED)
INDOOR WIRING DIAGRAM
M
CN5
YELLOW
RED
M
5
CN4
N
CN16
L-IN
CN2
P_1
BLUE(BLACK)
INDOOR UNIT
OUTDOOR UNIT
JX1
Y/G
L1L2 S
8(7)
Wire Contoller OPTIONAL
Fig. 12 – Wiring Diagram Size 18 (208-230V)
INDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
L_IN Power Voltage :AC 230V
CN11 Power Voltage :AC230V
CN16 Relative to the N terminal voltage:DC 24V
CN15 Maximum voltage:DC5V
CN4 Indoor fan interface,Maximum voltage:DC310V
CN5 Stepper motor interface,Maximum voltage between the lines:DC12V
P_1 Ground
CN8 Room temperature sensor interface,maximum voltage:DC5V
CN9 Pipe temperature sensor interface,maximum voltage:DC5V
CN10A Display interface,maximum voltage between the lines:DC5V
INDOOR WIRING DIAGRAM
M
CN5
YELLOW
RED
M
5
CN4
N
CN16
L-IN
CN2
P_1
BLUE(BLACK)
INDOOR UNIT
OUTDOOR UNIT
JX1
Y/G
L N S
8(7)
Wire Contoller OPTIONAL
Fig. 13 – Wiring Diagram Size 24 (208-230V)
INDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
L_IN Power Voltage :AC 230V
CN11 Power Voltage :AC230V
CN16 Relative to the N terminal voltage:DC 24V
CN15 Maximum voltage:DC5V
CN4 Indoor fan interface,Maximum voltage:DC310V
CN5 Stepper motor interface,Maximum voltage between the lines:DC12V
P_1 Ground
CN8 Room temperature sensor interface,maximum voltage:DC5V
CN9 Pipe temperature sensor interface,maximum voltage:DC5V
CN10A Display interface,maximum voltage between the lines:DC5V
15
WIRING DIAGRAMS (CONTINUED)
INDOOR WIRING DIAGRAM
M
CN5
YELLOW
RED
M
5
CN4
N
CN16
L-IN
CN2
P_1
BLUE(BLACK)
INDOOR UNIT
OUTDOOR UNIT
JX1
Y/G
L1L2 S
8(7)
Wire Contoller OPTIONAL
Fig. 14 – Wiring Diagram Size 30 and 36 (208-230V)
INDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
L_IN Power Voltage :AC 230V
CN11 Power Voltage :AC230V
CN16 Relative to the N terminal voltage:DC 24V
CN15 Maximum voltage:DC5V
CN4 Indoor fan interface,Maximum voltage:DC310V
CN5 Stepper motor interface,Maximum voltage between the lines:DC12V
P_1 Ground
CN8 Room temperature sensor interface,maximum voltage:DC5V
CN9 Pipe temperature sensor interface,maximum voltage:DC5V
CN10A Display interface,maximum voltage between the lines:DC5V
16
GUIDE SPECIFICATIONS
INDOOR WALL-MOUNTED DUCTLESS UNITS
Size Range: 3/4 to 3 Ton Nominal Cooling and Heating Capacity
Model Number: DHMSHA
PART 1 - GENERAL
1.01 System Description
Indoor, wall-mounted, direct-expansion fan coils are matched with
the heat pump outdoor unit.
1.02 Agency Listings
Unit shall be rated per AHRI Standards 210/240 and listed in the
AHRI directory as a matched system.
1.03 Delivery, Storage, And Handling
Units shall be stored and handled per the unit manufacturer’s
recommendations.
1.04 Warranty (For Inclusion By Specifying
Engineer)
PART 2 - PRODUCTS
2.01 Equipment
A. General: Indoor, direct-expansion, wall-mounted fan coil
Unit shall be complete with a cooling/heating coil, fan, fan motor,
piping connectors, electrical controls, microprocessor control
system, and integral temperature sensing. Unit shall be furnished
with an integral wall mounting bracket and mounting hardware.
B. Unit Cabinet:
Cabinet discharge and inlet grilles shall be attractively styled,
high-impact polystyrene. Cabinet shall be fully insulated for
improved thermal and acoustic performance.
C. Fans:
1. Fan shall be the tangential direct-drive blower type with air
intake at the top of the unit and discharge at the bottom
front. An automatic, motor-driven vertical air sweep shall
be provided as standard equipment.
2. The air sweep operation shall be user selectable. The
vertical sweep may be adjusted (using the remote control).
The horizontal air direction may be set manually.
D. Coil:
The coil shall be a copper tube with aluminum fins and galvanized
steel tube sheets. The fins shall be bonded to the tubes by mechanical
expansion and blue hydrophilic pre-coated. A drip pan under the coil
shall have a drain connection for the hose attachment to remove
condensate. The condensate pan shall have an internal trap.
E. Motors:
Motors shall be open drip-proof, with a permanently lubricated
ball bearing. The fan motors shall be 4-speed.
F. Controls:
Controls shall consist of a microprocessor-based control system
which shall control space temperature, determine optimum fan
speed, and run self diagnostics. The temperature control range
shall be from 62 F to 86 F (17 C to 30 C) in increments of 1 F
or 1 C, and have 46 F Heating Mode (Heating Setback). The
wireless remote controller shall have the ability to act as the
temperature sensing location for room comfort.
The unit shall have the following functions as a minimum:
1. An automatic restart after a power failure at the same
operating conditions as at the failure.
2. A timer function to provide a minimum 24-hour timer
cycle for system Auto Start/Stop.
3. Temperature-sensing controls shall sense return air
temperature.
4. Indoor coil freeze protection.
5. Wireless infrared remote control to enter set points and
operating conditions.
6. Automatic air sweep control to provide on or off activation
of air sweep louvers.
7. Dehumidification mode shall provide increased latent
removal capability by modulating the system operation and
the set point temperature.
8. Fan-only operation to provide room air circulation when no
cooling is required.
9. Diagnostics shall provide continuous checks of unit
operation and warn of possible malfunctions. Error
messages appear on the unit.
10. Fan speed control is user-selectable: turbo, high, medium,
low, or microprocessor controlled automatic operation
during all operating modes.
11. Automatic heating-to-cooling changeover in the heat pump
mode. Control shall include deadband to prevent rapid
mode cycling between heating and cooling.
12. Indoor coil high temperature protection shall be provided to
detect excessive indoor discharge temperature when the unit
is in the heat pump mode.
G. Filters:
Unit shall have filter track with factory-supplied cleanable filters.
H. Electrical Requirements:
Indoor fan motor to operate on 115V on model sizes 09-12 and on
208-230V on model sizes 09-36, as specified. Power is supplied
by the outdoor unit.
I. Operating Characteristics:
The 40MA system shall have a minimum SEER (Seasonal Energy
Efficiency Ratio) and HSPF at AHRI conditions, as listed on the
specifications table.
J. Refrigerant Lines:
All units should have refrigerant lines that can be oriented to
connect from the left, right or back of unit. Both refrigerant lines
need to be insulated.
K. Special Features (Field Installed):
1. Condensate Pump:
The condensate pump shall remove condensate from the
drain pan when gravity drainage cannot be used. The pump
shall be designed for quiet operation. The pump shall
consist of two parts: an internal reservoir/sensor assembly,
and a remote sound-shielded pump assembly. A liquid
level sensor in the reservoir shall stop the cooling operation
if the liquid level in the reservoir is unacceptable.
Copyright 2017 CAC / BDP 7310 W. Morris St. Indianapolis, IN 46231 Edition Date: 11/17
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: SS-DHMSHA-01
Replaces: NEW