HomeMy WebLinkAboutEvaluation Report; Certain Teed Asphalt Roof Shingles\1 TRINITY
FVALl1ATION REPORT
EXTERIOR RESEARCH & DESIGN, I.I.C.
Certificate of Authorization #9503
353 CHRISTIAN STREET, UNIT #13
ERD OXFORD, CT 06478
(203)262-9245
CertainTeed Corporation
20 Moores Road
Malvern, PA 19355
(610)651-5847
Evaluation Report 353z.U9.U5-1(13
FL5444-R12
Date of Issuance:09/22/2005
Revision 13: 09/05/2027
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for
use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described
herein have been evaluated for compliance with the 6th Edition (2017) Florida Building Code sections noted herein.
DESCRIPTION: CertainTeed Asphalt Roof Shingles.
LABELING: Labeling shall be in accordance with the requirements of the Accredited Quality Assurance Agency noted herein
and FBC 2507.2.7.1 / R90S.2.6.1
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this
Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the
referenced Quality Assurance documentation changes. Trinity IERD requires a complete review of this Evaluation Report
relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "TrinitylERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its'
distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 12.
Prepared by:
zxo'o ��
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
1111tlrznn. —
:� •P qt The facsimile seal appearing was authorized by Robert Nieminen,
P.E. on 09/05/2017. This does not serve as an electronically signed
document.
CERTIFICATION OF INDEPENDENCE:
1. Trinity lERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. TrinitylERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity I ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
(Ti:�IINITYIERD
6.22 PATRIOT -:
LOW AND STANDARD SLOPE STEEP SLOPE
Use POUR nails for every full shingle located ac shown below.
lanl
i ������i'zrr
G-118'� __ (25am) ` (`,.;l-►
(155 mmj
(333av) (1? =1 t333anj
Use FOUR nails and four spas (A asphalt roofing cement for every full
shingle as shown below: Asphalt roofing collenl meeling AtiRI D4586
'fy13e 11 Li suggested. Apply 1 ° (25 nuu) spots of asphalt roofing
cenicni a:s shovvi3.
CAUTION: Excessive use of roofing cement can curse shingles to blister.
ttmm) I r_.
Jaeotlnp Cement
M134M 47mnn}'I
6.12.1 Hip & Ridge for Patriot—: Refer to instructions herein for Cedar Crest—, Cedar Crest— IR, Shadow Ridge—,
NorthGate or Shangle Ridge*" hip and ridge shingles.
7. LABELING:
7.1 Each unit shall bear a permanent label with the manufacturer's name, logo, city, state and logo of the
Accredited Quality Assurance Agency noted herein.
7.2 Asphalt shingle wrappers shall indicate compliance with one of the required classifications detailed in FBC Table
1507.2.7.1 / R905.2.6.1.
B. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this
product.
9. MANUFACTURING PLANTS:
Contact the named QA entity for information on which plants produce products covered by Florida Rule 61G20-3 CIA
requirements.
10. QUALITY ASSURANCEENTITY:
UL LLC—QUA9625; (414) 248-6409; karen.buchmann@us.ul.Com
- END OF EVALUATION REPORT -
Exterior Research and Design, I.I.C. Evaluation Report 3532.09.0S-R33
Certificate ofAuthori:ation #9503 CH EDITION (2017) FBC NON-HVHZ EVALUATION FL5444-R12
CertalnTeed Asphalt Roof shingles; (610) 651-5847 Revision 13: 09/05/2017
Page 12 of 12
6.10.1 Hip & Ridge for Hatteras—:,
6.10.1.1 Option 1: Accessory for Hatteras
I
t
y
I
2 3
Figure 13-14. 18 tbrae pMw snits -separate to make
54 Xa4erasAacessory shingles.
6.10.1.2 Option 2: Cut Hatteras Shingles
.(230 min) I
-- [�hlngle
LSh�iangple
4Rmm)Cap CapapShingle Shingle`,Z�mm)
Ms"X211erequvasnails SIX emir (Avo
Instell9d oresMMY
shia9nm).
aMul as i.
Figure I1-3: Use FIVE nails for every Higganit Slate sbino..
ERD
Y—� 9'--`�—Y 9'
R7omm) We.W Rb�) - InOvan)
RSImm1 R9'mm)
MiamiDale reQeuae t'p5nm1 R�el�+�+)
31%rw7a{Nrone3s � 1 �_
InMaAetl over tenor
adoulestlawni �— R00%g Ceme .
'Figure 11.-3A: Use MT nails and eigbt spots ofaspbidt
roofing came# under eacb tab comer.
"CAUTION: Excessive use of tooling cement can cause shingles
to blister.
6.11.1 Hip & Ridge for Highland Slate'"', Highland Slater"" IR: Refer to instructions herein for Cedar Crest•"', Cedar
CreStTM IR or Shangle Ridge'"" hip and ridge shingles.
Exterior Research and Design, U.C. Evaluation Report 3532.09.05-R13
Certificate of Authorization #9503 .6t" EDITION (2017) FBC NON,HVHZ EVALUATION FL5444-R12
CertainTeed Asphalt Roof Shingles; (610) 651-5847 Revision 13: 09/05/2017
Page 11 of 12
_D
r,�
TrtIMn 'J erg
ROOFING SYSTEMS EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Asphalt Shingles
Compliance Statement: CertainTeed Asphalt Roof Shingles, as produced by CertainTeed Corporation, have
demonstrated compliance with the following sections of the 6th Edition (2017) Florida Building Code and 6th Edition
(2027) Florida Building Code, Residential Volume through testing in accordance with the following Standards.
Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein.
2. STANDARDS:
Section
Property
Standard
Year
1507.2.5, R905.2.4
Physical Properties
ASTM D3462
2010
1507.2.7.1, R905.2.6.1
Wind Resistance
ASTM D3161
2016
1507.2.7.1,'R905.2.6.1
Wind Resistance
ASTM D7158
2011
3. REFERENCES:
Knfitf
Examination
Reference
Date
UL (TST 1740)
ASTM D3161
94NK9632
05/15/1998
UL (TST 1740)
ASTM D3161
99NK26506
11/23/1999
UL (TST 1740)
ASTM D3161
03CA12702
05/27/2003
UL (TST 1740)
ASTIVID3161
03CA12702
06/16/2003
UL (TST 1740)
ASTM D3161
03NK29847
10/03/2003
UL (TST 1740)
ASTM D3161
04CA11329
05/24/2004
UL (TST 1740)
ASTM D3161
04CA32986
12/03/2004
UL (TST 1740)
ASTM D3161
05NK07049
04/15/2005
UL (TST 1740)
ASTM D3161
05NK16778
05/12/2005
UL (TST 1740)
ASTM D3161
OSCA16778
05/12/2005
UL (TST 1740)
ASTM D3161
05NK14836
05/22/2005
UL (TST 1740)
ASTM D3161
OSNK22800
06/22/2005
UL (TST 1740)
ASTM D3462
R684
09/21/2005
UL (TST 1740)
ASTM D7158
OSNK08037
06/28/2006
UL (TST 1740)
ASTM D3161 & D3462
09CA28873
07/23/2009
UL (TST 1740)
ASTM D3462
IOCA41303
10/07/2010
UL (TST 1740)
ASTM D3161
10CA41303
10/08/2010
UL (TST 1740)
ASTM D7158 •
IOCA41303
10/27/2010
UL (TST 1740)
ASTM D3161 & D3462
IOCA44960
11/11/2010
UL LLC (TST 9628)
ASTM D3161, D3462 & D7158
13CA32897
11/21/2013.
UL LLC (TST 9628)
ASTM D3161, D3462
TFWZ.R684
04/22/2014
UL LLC (TST 9628)
ASTM D7158
TGAH.R684
04/22/2014
UL LLC (TST 9628)
ASTM D3161 & D3462
4786334434
09/16/2014
UL LLC (TST 9628)
ASTM D3161 & D3462
4786570826
02/12/2015
UL LLC (TST 9628)
ASTM D3161, D3462 & D7158
4786570717
12/16/2015
UL LLC (TST 9628)
ASTM D3161 & D3462
4787195678
02/09/2016
UL LLC (TST 9628)
ASTM D3161, D3462 & D7158
4787380356
10/26/2016
ULLLC (TST 9628)
ASTM D3462
4787380357
10/13/2016
ULLLC (TST 9628)
ASTM D7158
4787380357
11/08/2016
UL LLC (TST 9628)
ASTM D3161
4787380357
11/09/2016
UL LLC (TST 9628)
ASTM D3161, D3462 & D7158
4787586427
01/25/2017
UL LLC (QUA 9625)
Quality Control
Service Confirmation
Exp. 03/09/2020
Exterior Research and Design, U.C. Evaluation Report 3532.09.05-1113
Certificate of Authorisation #9503 6Tn EDITION (2017) FBC NON-HVHZ EVALUATION F1.5444-1112
CertainTeed Asphalt Roof Shingles; (610) 651-S847 Revision 13: 09/05/2017
Page 2 of 12
QOTRI'NITYIERD
4. PRODUCT DESCRIPTION:
4.1 CT20TM, XI" 25, Xrm 30 and Xr30 IR are fiberglass reinforced, 3-tab asphalt roof shingles.
4.2 Arcadia'"', Belmont®, Belmont® IR, Carriage House Shangle°, Grand Manor Shangle°, Landmark',
Landmark'"' IR, Landmark'" Pro, Landmark'"" Premium, Landmark"" TL, Landmark' Solaris and
Landmark'"' Solaris IR are fiberglass reinforced, laminated asphalt roof shingles.
4.3 NorthGate" is a fiberglass reinforced, laminated, SBS modified bitumen roof shingle.
4.4 Presidential Shake"", Presidential Shakem IR, Presidential Shake TL'"' and Presidential Solarism are
fiberglass reinforced, architectural asphalt roof shingles.
4.5 HatterasTM, Highland Slatem and Highland Slate'"" IR are fiberglass reinforced, 4-tab asphalt roof shingles.
4.6 Patriot'' is a fiberglass reinforced asphalt roof strip -shingle (with no cut-outs) providing a laminated
appearance through an intermittent shadow line with contrasting blend drops for color definition.
4.7 Presidential Accessory, Accessory for Hatteras, Shangle Ridge'"', Shadow Ridge'", Cedar Crest'"", Cedar
Crestm IR, NorthGate Ridge and NorthGate Accessory are fiberglass reinforced accessory shingles for hip
and ridge installation.
4.8 Any of the above listed shingles may be produced in AR (algae resistant) versions.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinityJERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use within FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials
Directory for fire ratings of this product.
5.4 Wind Classification:
5.4.1 All shingles noted herein are Classified in accordance with FBC Tables 1507.2.7.1 and R905.2.6.1 to ASTM
D3161, Class F and/or ASTM D7158, Class H, indicating the shingles are acceptable for us in all wind zones
UP to VaSd = 150 mph (V it = 194 mph). Refer to Section 6 for installation requirements to meet this wind
rating.
5.4.2 Presidential Accessory, Accessory,for Hatteras, Shangle. Ridge, Shadow Ridge, Cedar Crest, NorthGate Ridge
and NorthGate Accessory hip & ridge shingles have been evaluated in accordance with ASTM D3161, Class
F. All except NorthGate Ridge and NorthGate Accessory require use of BASF Sonolastic NP 1 adhesive or
Henkel PL® Polyurethane Roof & Flashing Sealant, applied as specified in manufacturer's application
instructions, for use in wind zones up to VaSd =150 mph (V It =194 mph).
5.4.3 Classification by ASTM D7258 applies to exposure category B or C and a building height of 60 feet or less.
Calculations by a qualified design professional are required for conditions outside these limitations.
Contact the shingle manufacturer for data specific to each shingle.
5.4.3.1 Analysis in accordance with ASTM D71SS indicates the measured uplift resistance (RT) for the CertainTeed
asphalt Roof shingles listed in Section 4.1 through 4.6 (except Presidential Solaris') exceeds the calculated'
uplift force (FT) at a maximum design wind speed Of VaSd = 150 mph (Vast = 194 mph) for residential
buildings located in Exposure D conditions with no topographical variations (flat terrain) having a mean
roof height less than or equal to 60 feet. The shingles are permissible under Code for installation in these
conditions using the installation procedures detailed in this Evaluation Report and CertainTeed minimum
requirements, subject to minimum codified fastening requirements established within any local
jurisdiction, which shall take precedence.
5.5 All products in the roof assembly shall have quality assurance audits in accordance with F.A.C. Rule 614320-
3.
Exterior Research and Design, I.I.C. Evaluation Report 3532.09.0S-R13
Certificate afAuthorization #9503 6t" EDITION (2017) FBC NON-HVHZ EVALUATION FL5444-R12
CertainTeed Asphalt Roof Shingles; (610) 651-5947 Revision 13: 09/05/2017
Page 3 of 12
6. INSTALLATION:
6.1 Roof deck, slope, underlayment and fasteners shall comply with FBC 1507.2 / R905.2 and the shingle
manufacturer's minimum requirements.
6.1.1 Underlayment shall be acceptable to CertainTeed Corporation and shall hold current Florida Statewide
Product Approval, or be Locally Approved per Rule 61G20-3, per FBC Sections 1507.2.3, 1507.2.4 or
R905.2.3.
6.2 Installation of asphalt shingles shall comply with the CertainTeed Corporation current published
instructions, using minimum four (4) nails per shingle in accordance with FBC 1507.2.7 or Section R905.2.6
and the minimum requirements herein.
6.2.1 Fasteners shall be in accordance with manufacturer's published requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
6.2.2 Where the roof slope exceeds 21 units vertical in 12 units horizontal, use the "Steep Slope" directions.
6.3 CertainTeed asphalt shingles are acceptable for use in reroof (tear -off) or recover applications, subject to the
limitations set forth in FBC Section 1511 or R908 and CertainTeed published installation instructions.
6.4
ENGLISH 12" 12" 12"
(305 Imm
305 mm)(305 mm)-
1
"(2Selant 1"(25mmJ ,
5 s/s" (145 mm)
5 r12 for Norwood
Pant
METRIC 131/8" . 131/e" 131/e"
1" (25 mm) — Sealant
lant 1"(25 mm) ►{
6 t1C — — — — — —
Figure 113: Usefournailsfor avvJidlshingle.
STEEP SLOPE
Use four nails and six spots of asphalt roofing cement* for every full
shingle (Figure 11-4). Asphalt roofing cement meeting ASTM D4586
Type II is suggested.
I "
Roofing Cement
Apply 1"(25 an) spots of asphalt roofing cement
under each tab corner.
Figure 11-4: csefoarnails and stz spots o, faspbaU coment on steep slopes.
*cAUTION: Excessive use of roofing cement can cause shingles
to blister.
6.4.1 Hip & Ridge for CT20'", XT'" 25, XT'"" 30, XT1" 30 IR: Cut Shingles
1" .II+2" (50 mm) Remove
(25 mm)p� III l�l I 12" (305 mm)
II II tl _ (12125mm)
Cap Cap Cap 305Imm) �i�R�an
Shingle Shingle Shingle I
Figure 11-24 Cut tabs, then trim back to make cap sbingigless
(Bnglisb dimensions shown).
Figure II-25: installation ofcwps along the hips and ridges.
6.4.1.1 For ASTM D3161, Class F performance use BASF "Sonolastic° NP11""' adhesive or Henkel "PL® Polyurethane
Roof & Flashing Sealant", in accordance with CertainTeed requirements.
Exterior Research and Design,LtC. Evaluation Report 3532.09.05-R13
Certificate afAuthorization a9503 CH EDITION (2017) FBC NON-HVHZ EVALUATION F1.5444-1112
CertainTeed Asphalt Roof Shingles; (610) 651-5847 Revision 13: 09/05/2017
Page 4 of 12
T'TpuNITYIERD
Use two (2), minimum 1%-inch long fasteners per shingle. For the starter shingle, place fastener 1-inch
from each side edge and about 2-inch up from the starter shingle's exposed butt edge, ensuring minimum
-inch embedment into the deck, or full penetration through the deck. For each full Cedar Crest shingle,
place fasteners 8-5/8-inch up from its exposed butt edge and 1-inch from each side edge.
For ASTM D3161, Class F performance use BASF "Sonolastic® NP1' " adhesive or Henkel "PL®
Polyurethane Roof & Flashing Sealant", in accordance with CertainTeed requirements, to hand -seal
Cedar Crest shingles. Apply NP 1 or PL adhesive from the middle of the shingle's raised overlay on the
top piece and extending approximately 4-inch along the sides of the headlap along a line % to 1-inch from
each side of the shingle's headlap. Immediately align and apply the overlying shingle, gently pressing tab
sides into the adhesive, and install nails. To secure the other side, apply a 1-inch diameter spot of NP 1 or
PL adhesive between the shingle layers.
Hand -sealing adhesive
4"
1/4" LL2 1
314" --► I+-
1"
Dab of asphalt
cement between
shingle layers
Exterior Research and Design,LLC. Evaluation Report 3532.09.05-R13
Certificate ofAutharizat/on 09503 CH EDITION (2017) FBC NON-HVHZ EVALUATION FL5444-1112
CertainTeed,Asphalt Roof Shingles; (510) 651-5847 Revision 13: 09/05/2017
Page 5 of 12
6.6
Low and Standard Slope
(2:12 to 21:12):
Use FIVE nails for every full Belmont shingle,
located as shown below.
o Add tiowl was
6W
t� t
Ste
Steep Slope (greater than 21:12):
Use SEVEN nails and EIGHT spots of
asphalt roofing cement" for every full
Belmont shingle. Apply asphalt roofing
cement 1" (25mm) from edge of shingle.
See below. Asphalt roofing cement meeting
ASTM D4586 Type 11 is suggested.
P M rU,$ �—,F,aoGnq C17Mfd
6.6.1 Hip & Ridge for Belmont® or Belmont" IR:
6.6.1.1 Option 1: For Belmont®, refer to instructions herein for Cedar Crest— or Cedar Crest" IR hip and ridge
shingles. For Belmont® IR, refer to instructions herein for Cedar Crest- IR hip and ridge shingles.
6.6.1.2 Option 2: For Belmont®: Shangle® Ridge
18 Exposure Remove tape
12"tfrom the right side
and Casten " 8 SECOND
Fasten the
f
Remove
left side 85f8. RIGHT
FIRST This rape FLEFT
�:==A Figure 17-19:1nsfaHation ofSbangle® Ridge sbingles
Figure 17-1& Sbanglea Ridge. on baps and ridges.
6.6.1.3 For ASTM D3161, Class F performance use BASF "Sonolastics NPi" adhesive or Henkel "PL®
Polyurethane Roof & Flashing Sealant", in accordance with CertainTeed requirements.
Exterior Research and Design,LLC. Evaluation Report 3532.09.05-1113
Certificate of Authorization #9503 67N EDITION (2017) FBC NON-HVHZ EVALUATION FL5444-R12
CertainTeed Asphalt Roof Shingles; (610) 651-5847 Revision 13: 09/05/2017
Page 6 of 12
0
6.7
6.7.1
6.8
Q0T1mNrrYjERD
CARRIAGE HOUSE SHANGLE® AND GRAND MANOR SHANGLE®:
.
STEEP SLOPE
LOW AND
STANDARD SLOPE
Use five nails for every full Shangle.
'( fp
1—(25 mm) i (25 mm)
5 855,
(16 mm) ( I m)
Figure 17-4. Usef m na(lc jorereryjdl GrandM4—Sbmrgfe,
Carriage muse Shangle, or C"Iennial Slale.
Use seven nails and three spots of asphalt roofing cement for every
full Grand Manor Shangle. Use five nails and three spots of asphalt
roofing cement for every full Carriage Rouse Shangle and Centennial
Sate. Apply asphalt roofing cement 1 (25 mm) from edge of shingle
(Figure 17.5). Asphalt roofing cement meeting ASfM D4586 Type 11
Is suggested,
1 1/2"
(38 aim)
1„ or less -�{ 1••
1+-(25mm) I (25 mm)
5/81,` 8 5/8„
(16 aim); II 1220 L
(25 nM) Rooting Gmurl
Figure 17-5. when installing ('rand Manor Shangle; on sleep slopes,
use saex nails and lbree spots ofaspball roofing cement.
Hip & Ridge for Carriage House Shangle® and Grand Manor Shangle: Refer to instructions herein for
Shangle® Ridge hip and ridge shingles
7 7.
LANDMARK,',"", LANDMARKTe".IR, LANDMARK*"" PRO,'LANDMARK-" PREMIUM, LANDMARK'"' TL, LANDNiARKr""
SOLARIS,'UINDMARKru'SOLARIS IR,.NORTHGATE:
LOW AND STANDARD SLOPE
METRIC DIMENSIONS
12 14314" 12"
�--(305 mm)-► —(375 mm)(305 mm)-►�
Iw
1 ' (25 mm) Release Tape 1" (25 mm) wl
11/2„
NailahleT
Area Et�
utnrrnwnn M
NorthGate:
QW' 13" 1392"
�—(343 mai)-► •-(330 mm)� �-(343 mm)�
— 1 -1"(25 mm) 1" (25 mm)—I �-
Figum 1.3-4. Usefour nailsfor ereq•jrll sbingle.
AVE
NAM it 14 Y4' 2'
AREA f. (3e5 mm) -+ *--- (375 mail - ► . (305 mm)
r 6arrg UrAs
�1 Upper-1Ine V (25aim)- �-
¢ P (25 aim) .ewer rW Ire
Raug arm torlow mM swdud dopes (tram 2:12 to 21:12)
Nal W'Woen upper✓! 17 , lies as shown above.
Exterior Research and Design, U.C. Evaluation Report 3532.09.05-R13
Certificate of Authorization n9503 67N EDITION (2017) FBC NON-HVHZ EVALUATION FL5444 R12
CertainTeed Asphalt Roof Shingles; (610) 651-5847 Revision 13: 09/05/2017
Page 7 of 12
QOTRINITYIERD
STEEP SLOPE
Ilse six nails and four spots of asphalt roofing cement for every full LANDMARK TL
laminated shingle. See below. Asphalt roofing cement should meet
ASTH D4586 7ypc li. Apply 1" spots of asphalt rooting cement uncle }.-13Vz^ 13rrim) --13112'L
each corner and .n about 12 to 13 in from each edge. I (343 mm') (330 mm) I (343 mm)
METRIC DIMENSIONS -• I61(25mm) I 1 1"(25mm)
12 143/4—12 I If VA
1,
(305mm) (375mm) (305mm) (25mm)I -- 7(25mm)
ROafing'Cert�M
+1'(25Min) Relea Tape 1"(25mm) �-
vi rocs
)r Steep Figure 13 3: Use slx Halls andfour spots of
, asphalt roofrngcomeat on steep slopae
(25 mm) -- — — (25 mm;
Rooting Cement.
NorthGate:
STEEP 12' 14.3W 12'
SLOPE 1-.4305 mml- l•--t375 n,1+4305 mmY►j
Mm) ( DeneT,,1 t � 11'(25
�.-_.- !� ill •:I I I'
t - t L-H-1
Roofing Cernent
Nailing areas for steep dopes (greater than 21:12)
and "Stor ilAalling"
Nail between lower 2 nal lines as shown above.
6.8.1 Hip & Ridge for Landmark'"' Landmark'" IR Landmark*" Pro Landmark'"" Premium, Landmark"" TL,
Landmark- Solaris Landmark'"' Solaris IR, NorthGate:
6.8.1.1 Option 1: Shadow Ridge'" or NothGate Accessory
12'
(305mm) 415/1(250mm) --�-415/tg
6" 0146" (125mm) I .(125mm)
(150mm) (150mm)
f Notch for
Notch for Cantering
Centering
131/4" I
(305mm) NLCtapfor
for Alignmant� (337mm);the
Notches forAlignmird� 75/3°
dge of the Previous p Edge of the Previous (195mm}
(125mm)Exposure(11 80mm) L —i
Capfor55A(141mm)Exposuie
It— English Dimension Metric Dimension
Shadow Ridge•" Shadow Ridge'"
Exterior Research and Design, I.I.C. Evaluation Report 3532.09.05-R13
Certificate ofAuthorization N9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL5444-1112
CertainTeed Asphalt Roof Shingles; (610) 651-5847 Revision 13: 09/05/2017
Page 8 of 12
9
9 27=
+--i1w,1161ill"71-20--z")
131/8"
Geared Pj=b
_ 168 mm)II 168 mm
1
13 i!A` ` ? Centedng
sa
(337 mm} alga th / Notch
notches to top 7 W 331/4° R
*4 01, (184 rM) (37 mm) \aign theseJe 7518
p>tr/ ous tout" notches to top ( mm)
of
edge of
previous course.
NorthGate Ridge NorthGate Accessory
12'
(305mm) Laying Notch
I
I
5. (125mm) I I I Ir"Ifr
Figure 13-20.- Use layingnotcbes to center sbipgles on hips and
rktges, and to hicate the correct exposure.
6.8.1.2 For ASTM D3161, Class F performance use BASF "Sonolastic® N121 " adhesive or Henkel "121.11
Polyurethane Roof & Flashing Sealant", in accordance with CertainTeed requirements.
6.8.1.3 Option 2: Refer to instructions herein for Cedar Crest'", Cedar Crest— IR hip and ridge shingles.
Exterior Research and Design, U.C. Evaluation Report 3532.09.05-R33
Certificate ofAuthorization a9503 6Te EDITION (2017) FBC NON-HVHZ EVALUATION FL5444-R12
CertainTeed Asphalt Roof Shingles; (510) 651-5947 Revision 13: 09/05/2017
Page 9 of 12
1.
6.9 PRESIDETdT1ALSHAKE`", PRESIDENTiAIJNAKE,
LOW AND STANDARD SLOPE:
For low and standard slopes, use five nails for each full Presidential
shingle as shown ,below.
Nailing 1.----- 40'
Guide Lines (1016 mot)
51f4- —�
(1331M)) 141/4"
1112` 3B mot), (362 mm)
NOTE: Apply nails on painted guideline.
Figure 16.6.. FasieningFresidmMal and Presidential TL $bake
.sbi ng(es on loot and standard slopes
QoTaINITYIERD
STEEP SLOPE:
For steep slopes, use nine nails for each full Presidential shingle and
apply 1' diameter spots of asphalt rooting cement under each shingle tab.
After applying S nails in between the nailing guide lines, apply: 4 nails 1'
above tab cutouts malting certain tabs of overlying shingle cover nails
}
1' diameter asphalt roofing cement
Figure 16-7.FastenIngFresiderrud and hesiAmlial'T/L Sbake
sbingles on steep slopes.
6.9.1 Hip & Ridge for Presidential Shake`', Presidential Shake"'' IR Presidential Shake TLT" Presidential
SolarisT":
6.9.1.1 Option 1: Presidential Accessory
PRESIDENTIAL ACCESSORY
Presidential accessory shingles can be used for covering hips and
ridges. Apply shingles up to the ridge (expose no more than'7' from
the bottom edge of the "tooth." Fasten each accessory with two fas-
teners. The fasteners must be 13/4' long or lodger, so they penetrate
either 3/4' into the deck or completely through the deck. Presidential
accessory comes in two different sizes: Accessory produced in
Birmingham, AL is 12' x 12% Portland, OR produces 97/s' x 131/4'
accessory.
6.9.1.2 For ASTM D3161, Class F performance use BASF "Sonolastic® NPlT°` adhesive or Henkel "PL®
Polyurethane Roof & Flashing Sealant", in accordance with CertainTeed requirements.
6.9.1.3 Option 2: Refer to instructions herein for Cedar CreStTM, Cedar CrestTM IR hip and ridge shingles.
6.10
LOW, STANDARD AND STEEP SLOPE:
Figure /5.3. rartenlag llallems sbing/ts on
Lour and slandard slopes
For low and standard slopes, use five nails for each fall
nauem shingle as shown above,
Exterior Research and Design, I.I.C.
Certificate ofAutharisation #9503
flgtur IS (: fialenhtg nalhaarXblgrfrs mr strepsloprs
For steep slopes, use fife nails and eight spots of asphalt roofing
cement for each full Ilmtetas shingle as shown above. Apply I*
(25mm) dimneter spots of roofing cement (AMt D 4586I1W It
suggested) under each lab comer. Press shingle into place; do not
expose cement.
CAUTION: Too mach fooling Cement can cause shingles to blister.
Evaluation Report 3532.09.05-R13
CH EDITION (2027) FBC NON-HVHZ EVALUATION FL5444-R12
CertainTeed Asphalt Roof Shingles; (610) 651-5847 Revision 23: 09/05/2017
Page 10 of 12