St. Lucie County Building Department Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Ft. Pierce, FL 34982
April 22, 2020
RE: Stefanakis Residence
4531 S. Indian River Dr.
Permit # 2003-0642
To Whom It My Concern
Please accept the following responses to the comments dated 3/25/2020 from your agency. Response shown on
plans corresponding (if required) to these comments are noted.
COMMENT: Product review affidavit on plan page A-1 Therma Tru door FL# 20468.8 Design pressure is not filled in
Design pressure required on plan page A-1 product review affidavit zone 5 is 53.6 and FL # 20468.8 only has a
design pressure of -50.
Response: The design pressure was added to the product review and zone 5 has been removed since the door is
in zone 4 see revised product review sheet A-1.
COMMENT: Design wind load on plan page a-1 specifies wind velocity as 200 mph is the house designed to 200
mph? The lot falls in wind speed zone 160-162 please clarify.
Response: Yes the house was designed for 200 mph wind zone.
COMMENT: Plan page A-1 neither bathroom meets the accessibility requirement one bathroom has to be
accessible per 2017 FRD R320.1.
Response: See revised bathroom door size sheet A-1
COMMENT: Product review affidavit plan page A-1 specifies image ii standing seam roof panels plan page A-4 wall
sections specify 5v crimp.
Response: The wall sections on sheet A-4 have been revised to match the product review.
COMMENT: Porch section and typical wall section plan page A-4 do not meet the requirements of section R403.1.4
the FRC 2017 minimum depth exterior footings shall be 12 inches below undisturbed surface.
Response: See sheet A-4 for footing dimensions which show the footings at 12 inches below undisturbed surface.
COMMENT: Design professional of record truss plan was not submitted with permit.
Response: See attached truss layout.
COMMENT: Truss manufacture truss plan reviewed and approved by design professional of record were not
submitted with permit.
Response: See attached truss layout.
COMMENT: Lot survey with elevation and proposed finished floor is required and was not submitted with permit.
Response: Contractor to provide.
806 Delaware Avenue Tel: 772 460 7751 www.architectonicinc.com
Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg #AA26003348 1 of 2
Architectonic Inc
ZONNING
COMMENT: Please provide a survey with the proposed construction setbacks, proposed finish floor elevation,
elevation of the crown of road, min. floor elevation is 18" above crown of road and min. required setbacks front
25' side 10' rear 15' .
Response: Contractor to provide
COMMENT: The slab for the future detached garage is not attached to the house therefore requires a separate
permit. The two permits can share one set of plans. Please submit a second application and refer to this permit
and plans.
Response: Contractor to provide.
COMMENT: Pleas provide a survey and floor plan with approval stamp Health Dept.
Response: Contractor to provide
COMMENT: Please be aware the additional comments might be applicable as soon as w have received above
information.
Response: Yes.
COMMENT: Please be aware that the above comments only reflects the zoning review comments, the plans
examiner might have additional comments.
Response: Yes