HomeMy WebLinkAboutFire District Plan ReviewST LUCIE COUNTY FIRE DISTRICT
BUREAU OF FIRE PREVENTION
PLAN REVIEW
2460 Rhode Island Avenue
Telephone: 561-462-2312
Ft
Ft Pi ce, FL. 34950
FAX: 561-462-2323
( New
( )Tenant Improvement ( )Addition
( )Renovation/alterations
( )Shell Only
Jurisdiction:
SLC
F.P.B.:
B-01-68
Occupancy:
PGA Education Center
Building Dept:
21020196
Address:
8555 Commerce Center Dr.
Number of stories:
1
Contractor
Mosley and Son Const.
Phone #
561-287-6962
Contractor's Address:
1400 Se Monterey Rd.
City:
Stuart
Arch itect/Engineer:
David -Miller and Assoc.
Phone #
561-697-4700
Building Owner:
Review Date:
4/27/2001
Occupancy Type:
Assembly/Business
Automatic sprinklers:
Required
Gross sq ft:
24,218
Net sq ft:
Occupant Load:
Based On:
Construction Type:
SBCCI Type:
IV unp
Rim
1. All revisions must be in compliance before the final inspection.
2. The Fire Marshal requires 24 hour notice on all inspections.
3. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
4. Permit fees are- required -to be paid in full prior to any inspections.
5. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. A copy of the required revision/s have been transmitted to the Architect () Contractor ( ).
7. Penetrations through rated assemblies shall be of proper UL design.
8. UL design criteria shall be submitted with the construction plans.
REVISIONS REQUIRED
KNOX BOX IS REQUIRED (XX) KNOX KEY SWITCH REQUIRED ( )
1. Sheet CS-1 "General Notes" indicates the incorrect Standard Building Code edition.
2. A separate permit is required for the installation of the fire alarm and fire sOpinkler'systems.
NFPA 13 and 72, 1999 editions
3. Door numbers 102B and 104B shall be,a 3/4 hr. rated with self -closing devices.
4. Prep. Kitchen: Continue the 1 hr. wall from door number 121C through door number 122E to the point
it intersects with the men's restroom wall.
5. Door number 122E shall have a 3/4 hr. rating with 'a self closing device.
f� 6. Separate the storage rooms that are located in the pre -function area with one hour construction and
v. and 3/4 hr. door and jamb assemblies. Self -closing devices are required.
7. Provide one 2A-10B:C rated fire extinguisher every 75 feet of travel distance throughout.
All extinguisher shall be accessible at all times.
8. Penetrations through rated assemblies shall be of proper UL design.
9. HVAC shutdown is indicated although see attached requirements.
10. Classrooms 1 through 6: Provide exit light fixtures.
Reviewed by: - Date: 4/27/2001