HomeMy WebLinkAboutLetter; Automatic Fan Shut Down RequirementsUNr
FIRE MARSHAL'S \� Z/1' .
OFFICE
cn: a,
St. Lucie County
Fire District
(561) 462-2312 • FAX (561) 462-2323
AUTOMATIC FAN SHUTDOWN REQUIREMENTS
FOR AIR HANDLING SYSTEMS.
2400 Rhode Island Ave.
Fort Pierce, FL 34950
The requirements for•anteniatic fan shut down -in air handling systems are the
requirements of the Standard Mechanical Code, 1997 Edition, Chapter 4, Section 406,
and the National Fire Protection Association, Life Safety Code NFPA 101.
In determining which code to comply with, the following information is necessary.
1. A/C units make up a system and is referred to in the codes as an air
handling system.
2. The NFPA Life Safety Code, Occupancy Chapters 8 through 31 references
Heating, Ventilation, and air Conditioning and shall comply with Section
101-7-2 of the Life Safety Code.
3. Section 101-7-2 requires air conditioning, heating, ventilating ductwork,
and related equipment to be installed in accordance with NFPA 90A,
Standard For The Installation Of Air Conditioning and. Ventilation
Systems, or NFPA 90B, Standard For The Installation of Warm Air
Heating and Air Conditioning Systems.
4. NFPA 90A. Scope: This standard applies to all systems for the movement
of environmental air in structures that:
a. Serves spaces over 25,000 cubic feet in total volume, or
b. Serve buildings of Type III, IV, and V construction over three
stories in height, regardless of volume: .The construction types
indicated are in accordance with NFPA 220.
5. NFPA 90A. For the purpose of this standard, a space is considered as the
entire building or a portion thereof separated from other portions of the
building_by fire resistance rated construction and whose environmental air
does not mix with that of any other space. For spaces not exceeding
25,000 cubic feet in volume, reference the Standard Mechanical Code,
Chapter 4, Section 406.
6. Spaces not exceeding 25,000 cubic feet in total volume shall be in
accordance with the Standard Mechanical Code, 1997 Edition.
7. Automatic fan shut down requirements. NFPA 90A.
a. Location: Smoke detectors listed for use in air distribution systems
shall be located:
1.) Downstream of the air filters and ahead of any branch
connections in air. supply systems of greater than 2,000 cfin
capacity.
2.) At each story prior to the connection to a common return
and prior to any recirculation or fresh air inlet connection in
air return systems over 15,000 cfin capacity and serving
more than one story.
Exception #1; Return systems smoke detectors are not
required when the entire space served by the air distribution
system is protected by a system of area smoke detectors.
Exception #2: Fan units whose sole function is to remove
air from inside the building to outside the building.
b. Function. Required smoke detectors shall automatically stop their
respective fan(s) upon detecting the presence of smoke.
Exception: Where the return air fan is functioning as part of an
engineered smoke control system and a different mode is required.
C. Installation. Listed duct type smoke detectors shall be installed in
accordance with NFPA 72, National Fire Alarm Code.
1.) When an approved protective signaling system (fire alarm)
is installed in the building the smoke detectors shall be
connected to the protective signaling system in accordance
with NFPA 72. Activation of any air distribution system
smoke detector will cause a supervisory signal to be
indicated at a constantly attended location or will cause an
alarm signal.
2.) All detection devices used for the operation of smoke
dampers, fire dampers, fan control, smoke doors, and fire
doors shall be monitored for integrity in accordance with
NFPA 72, 1-5.8 where connected to the fire alarm system
serving the protected premises.
3.) When smoke detectors are installed in a building not
equipped with an approved protective signaling system,
the system shall
a.) cause a visual and audible signal in a normally
occupied area, and
b.) smoke detector trouble conditions shall be indicated
visually or audibly in a normally occupied area and
shall be identified as air detector trouble.
c.) The above signal requirements can be annunciated
with a simple remote test station with a sounder..
8. Smoke detectors having power supplied separately from the signaling
system (fire alarm) for the sole function of stopping fans do not require
standby power.
STANDARD MECHANICAL CODE
Automatic Fan Shutdown Requirements:
a. Systems serving buildings or spaces less than 25,000 cubic
feet in volume shall comply with the requirements of the
Standard Mechanical Code, Chapter 4, Section 406, 1997
Edition.
b. Capacity greater than 2,000 cfin.
Recirculating air systems with a fan capacity greater than 2,000
cfin shall automatically shut down by means- of an approved smoke
detector placed in the return air stream prior to any exhausting
from the building or mixing with fresh air makeup.
C. Capacity 2,000 cfrn or less.
Reciculating air systems with a fan capacity of 2,000 cfm or less,
but serving an area used for egress, shall have automatic fan
shutdown. This would be foyers, lobbies, stairways, corridors, and
passageways.