HomeMy WebLinkAboutdetails 9650 S Ocean Dr1106 North , Ste B E L L I S Lakeke Worth, FL 33460 , ��•� ���� CONSULTING 561 .370.3300 phone www.ellis.consultin 9 WIND LOADS PER ASCE 7-10 Project Address: 9650 S. Ocean Dr., Jensen Beach, FL 34957 OPN: 20005 Princess Condo Boilers Structure Type: Building Structure Category: IV ASCE 1.5-1 Exposure Category: C ASCE 10 - 26.7 Enclosure Classification: Closed Building Closed Building Wind Speed: 170 MPH FBC 1620 Roof Slope: 0 Type of Roof: Concrete Mean Roof Height: 210 Feet Building Width: 355 Feet Building Length: 75 Feet Height of equipment above Ground: 213 Feet Parameters for Wind Pressure Calculations: Kz = 0.95 ASCE Table 30.3-1 Kh = 1.48 Kzt = 1 ASCE 26.8 Kd = 1 ASCE 26.6 Velocity Pressure at Mean Roof height: qh 309.47 PSF ASCE 30 - 30.3.2 ROOF TOP EQUIPMENT LOAD ASCE 10, Equation 29.5-2 ASCE 10 Equation 29.5-3 w/ FBC Amendments Structure Size Horizontal Wind Force (Lbs). Vertical Uplift Force (Lbs) Height (in) Length (in) Depth (in) 42.0 44.0 22.0 2612.94 257.26 Equip weight: 1 405 lResultant Force: 1# Fasteners Force Each Unit Model#: Lochinvar OKN801 1375.7 Ibs 2 687.9 Conclusion: 1. Fastener calc is for boiler to c-channel and c-channel to existing stand and is figuregl6n worst case scenario. 2. Use a minimum of 1 fastener in each corner 2" from edges through base of boiletand c-channel, and two additional through c-channel and existing beam. 3. Fasteners to be ASTM325 bolts, 1/2", with SS tenser washers both sides. o i :9 =u F Berljip��PE Page 1 ,�''iSs/ONA le! ejA7568 NOTE THIS SITE SPECIFl ENGINEERING DETAIL IS C TO ACCOMPANY THE AT1 WIND LOAD CALCULATION NEW 4" X 2" X 3/8" C—CHANNEL TO SPAN EXISTING FRAME (MAX SPAN 24"), TWO PER BOILER EXISTING 8" WIDE FLANGE BEAM TO REMAIN FASTEN BOILER TO C—CHANNEL WITH FOUR (4) 1/2" ASTM325 BOLTS AND FENDER WASHERS EACH CHANNEL, 2 EACH SIDE, 4 TOTAL PER UNIT FASTEN C—CHANNEL TO EXISTING 8" WIDE FLANGE BEAM WITH TWO (2) 1/2" ASTM325 BOLTS AND FENDER WASHERS EACH CHANNEL, 1 EACH SIDE RACK MOUNTED BOILER DETAIL 1 NTS 0.04 SELLIS�J�o�i���''�. QE LLI /[�)))r'�'�•�{ ''• �( CONSULTINCy i ENOINEERINO FOR TODAY'8I BUILT ENVIit RENT Wes- PROJECT ADDRESS: 9650 S. OCEAN DR., JENSEN BEACH FL 31951 PRINCESS CONDO ROOFTOP BOILER ATTACHMENT DETAIL SHEET TITLE: UNIT FASTENING DETAIL BE ELLIS PE LIB o aNATI EER p6]sB OEM. Of AUTH. p3pB5B �'(' GLO—fi1 �t� \ ( ♦ ,•• DATE C'J \L•� �• •• ��� SHEET: g K 1 �' Y0005 TE: 2020.OT•21 RAWN BY: BJE SCALE' AS NOTED IY3 STREET, SUITE B. Lake W—h, FL 33460 -3300 phone ww w.el liagri„. r. Qom 1 OF 1