Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-18 11:52:29 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Load Short Form Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Santana Autry Residence, Groza Builders, IncFor: TBD S Brocksmith Rd, Ft Pierce, FL 34945 Design Information InfiltrationClgHtg Blower doorMethod9041Outside db (°F) 3 (partial) / 1Shielding / stories7570Inside db (°F) 50 Pa / 0 cfmPressure / AVF1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond 14ACXS036-230A** AHRI ref Coil CBA27UHE-036-230*++TDR AHRI ref 10259480 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW6.7 Sensible cooling Btuh24220 Heating output Btuh22895 Latent cooling Btuh10380 Temperature rise °F18 Total cooling Btuh34600 Actual air flow cfm1153 Actual air flow cfm1153 Air flow factor cfm/Btuh0.047 Air flow factor cfm/Btuh0.050 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.76 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Bed 4 161 2508 1314 117 66 Bed 3 154 1481 1079 69 54 Laundry 46 611 904 29 45 Bed 2 154 2885 1968 135 98 Bath 82 1757 645 82 32 M Bath 130 2494 1451 117 73 WIC 65 1073 396 50 20 Clst 18 0 0 0 0 M Hall 47 0 0 0 0 Master Bedroom 293 4282 2539 200 127 Foyer 74 749 358 35 18 Dining Rm 182 3135 1913 147 96 Kitchen 193 698 3422 33 171 Pantry 6 0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-18 11:52:29 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N Hall 63 0 0 0 0 Living Room 378 2969 7061 139 353 House d 2045 24643 23050 1153 1153 Other equip loads 1847 981 Equip. @ 0.95 RSM 22925 Latent cooling 7447 TOTALS 2045 26490 30372 1153 1153 2020-Sep-18 11:52:29 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Building Analysis Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Santana Autry Residence, Groza Builders, IncFor: TBD S Brocksmith Rd, Ft Pierce, FL 34945 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) Blower doorMethod)L(15-Daily range (°F) 3 (partial) / 1Shielding / stories77-Wet bulb (°F) 50 Pa / 0 cfmPressure / AVF7.515.0Wind speed (mph) Heating Walls Glazing Other Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 15.440852.7Walls 6.818109.1Glazing 0.61523.7Doors 12.232241.6Ceilings 22.559662.92.9Floors 11.229542.1Infiltration 24.46453Ducts 00Piping 00Humidification 7.01847Ventilation0Adjustments 100.026490Total Cooling Walls Glazing Other Ceilings Infiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 10.324641.6Walls 18.2437022.0Glazing 0.61533.7Doors 10.324841.2Ceilings 000Floors 3.78800.6Infiltration 30.07199Ducts 4.1981Ventilation 22.95500Internal gains 00Blower 0Adjustments 100.024031Total Latent Cooling Load = 7447 Btuh Overall U-value = 0.205 Btuh/ft²-°F Data entries checked. 2020-Sep-18 11:52:29 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Component Constructions Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Santana Autry Residence, Groza Builders, IncFor: TBD S Brocksmith Rd, Ft Pierce, FL 34945 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) Blower doorMethod)L(15-Daily range (°F) 3 (partial) / 1Shielding / stories77-Wet bulb (°F) 50 Pa / 0 cfmPressure / AVF7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Block R-9 Wall: Blk Wall, Stucco Ext, 8" Thk, R-9 Foam Fill, 1/2" DW 9922.589.00.089385n 6341.65 3891.656072.589.00.089236e 3711.655802.589.00.089225s 5561.658692.589.00.089337w 19501.6530482.589.00.0891183all Partitions Frm Wall, 1/2" DW Ext, R-11 Cav Ins, 1/2" DW Int Fnsh, 2"x4" Wood Frm, 16" OC STUD 5151.4610372.9411.00.101353 Windows Impact: Impact; NFRC rated (SHGC=0.19); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 1097.021408.9900.31016n 4289.154218.9900.31047s 32220.61408.9900.31016w 85911.07018.9900.31078all Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 50522.02008.7000.30023e Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 7.6 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 2119.172008.7000.30023e Impact: Impact; NFRC rated (SHGC=0.19); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (5.2 ft window ht, 1 ft sep.); 8 ft head ht 29919.11408.9900.31016w Impact: Impact; NFRC rated (SHGC=0.26); foreground = green grass (0.23); 1 ft overhang (6.6 ft window ht, 1 ft sep.); 6.8 ft head ht 190532.15689.5700.33059w Doors Door, Mtl Fbrgl Type 783.73773.697.00.12721n 753.73743.697.00.12720e 1533.731523.697.00.12741all Ceilings 2020-Sep-18 11:52:29 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N Attic, Shngl Roof, R-20 Roof Deck Ins, 5/8" DW 0.3862045 24841.2132241.5821.0 Floors On Grade Depth, Tile Flr Fnsh 00596628.700.989208 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-18 11:52:29 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Project Summary Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Santana Autry Residence, Groza Builders, IncFor:TBD S Brocksmith Rd, Ft Pierce, FL 34945 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh18190 Structure Btuh15851 Ducts Btuh6453 Ducts Btuh7199Central vent (58 cfm) 1847 Btuh Central vent (58 cfm) Btuh981 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh26490 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh22925 Method Latent Cooling Equipment Load SizingBlower door Shielding / stories 3 (partial) / 150 Pa / 0 cfmPressure / AVF Structure Btuh3008 Ducts Btuh2199Central vent (58 cfm) Btuh2240 CoolingHeating Outside air20452045Area (ft²) Equipment latent load Btuh7447 1781517815Volume (ft³)Air changes/hour 0.180.31 Equipment Total Load (Sen+Lat)Btuh30372 Equiv. AVF (cfm) 5293 Req. total capacity at 0.70 SHR ton2.7 Heating Equipment Summary Cooling Equipment Summary Make Make LennoxTrade Trade LENNOX Model Cond 14ACXS036-230A**AHRI ref Coil CBA27UHE-036-230*++TDR AHRI ref 10259480Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW6.7 Sensible cooling Btuh24220Heating output Btuh22895 Latent cooling Btuh10380 Temperature rise °F18 Total cooling Btuh34600Actual air flow cfm1153 Actual air flow cfm1153 Air flow factor cfm/Btuh0.047 Air flow factor cfm/Btuh0.050Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.76 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-18 11:52:29Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name House Bed 4 2 Exposed wall 208.0 ft 25.5 ft 3 Room height 8.7 dft 8.0 heat/coolft 4 Room dimensions ft11.5x14.0 5 Room area 2045.4 ft²161.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 422 385 992 634 0 0 0 0 .GG ImpactImpact 0.3100.310 nn 8.998.99 7.027.02 16 0 140 109 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nn 3.693.69 3.733.73 21 21 77 78 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 302 236 607 389 0 0 0 0 11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 23 0 200 505 0 0 0 0 GG ImpactImpact 0.3000.300 ee 8.708.70 9.179.17 23 23 200 211 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 ee 3.693.69 3.733.73 20 20 74 75 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 272 225 580 371 92 76 197 126 GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 47 40 421 428 16 13 140 143 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 428 337 869 556 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 20.6220.62 16 0 140 322 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 19.1519.15 16 2 140 299 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 32.0732.07 59 0 568 1905 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 353 353 1037 515 112 112 329 163 CC Attic, Shngl Roof, R 0.386Attic, Shngl Roof, R 0.386 --1.581.58 1.211.21 2045 2045 3224 2484 161 161 254 196 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 2045 208 5966 0 161 26 731 0 6 c) AED excursion 591 -38 Envelope loss/gain 15236 9471 1651 590 12 a) Infiltration 2954 880 191 57 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 5 1150 0 0 Appliances/other 4350 250 Subtotal (lines 6 to 13)18190 15851 1842 897 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 9 7 14 Subtotal 18190 15851 1851 904 15 Duct loads 35%45%6453 7199 35%45%657 410 Total room load 24643 23050 2508 1314 Air required (cfm)Air required (cfm)1153 1153 117 66 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-18 11:52:29Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 3 Laundry 2 Exposed wall 11.0 ft 7.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft11.0x14.0 ft46.3x1.0 5 Room area 154.0 ft²46.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.3100.310 nn 8.998.99 7.027.02 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3000.300 ee 8.708.70 9.179.17 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 88 72 187 119 0 0 0 0 GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 16 13 140 143 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 20.6220.62 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 19.1519.15 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 32.0732.07 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 0 0 0 0 56 56 165 82 CC Attic, Shngl Roof, R 0.386Attic, Shngl Roof, R 0.386 --1.581.58 1.211.21 154 154 243 187 46 46 73 56 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 154 11 315 0 46 7 201 0 6 c) AED excursion -30 -26 Envelope loss/gain 885 419 438 112 12 a) Infiltration 183 54 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 500 Subtotal (lines 6 to 13)1068 723 438 612 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 25 19 13 10 14 Subtotal 1093 742 451 622 15 Duct loads 35%45%388 337 35%45%160 282 Total room load 1481 1079 611 904 Air required (cfm)Air required (cfm)69 54 29 45 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-18 11:52:29Right-Suite® Universal 2019 19.0.20 RSU27054 Page 3... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 2 Bath 2 Exposed wall 25.5 ft 17.3 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft153.5x1.0 ft81.9x1.0 5 Room area 153.5 ft²81.9 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 68 47 121 77 .GG ImpactImpact 0.3100.310 nn 8.998.99 7.027.02 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nn 3.693.69 3.733.73 0 0 0 0 21 21 77 78 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3000.300 ee 8.708.70 9.179.17 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 92 76 197 126 0 0 0 0 GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 16 13 140 143 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 112 96 248 159 70 70 180 115 GG ImpactImpact 0.3100.310 ww 8.998.99 20.6220.62 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 19.1519.15 16 2 140 299 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 32.0732.07 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.386Attic, Shngl Roof, R 0.386 --1.581.58 1.211.21 154 154 242 186 82 82 129 99 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 154 26 731 0 82 17 495 0 6 c) AED excursion 60 -18 Envelope loss/gain 1699 972 1003 352 12 a) Infiltration 423 126 286 85 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 0 Subtotal (lines 6 to 13)2122 1348 1289 437 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 7 5 8 6 14 Subtotal 2129 1353 1297 443 15 Duct loads 35%45%755 615 35%45%460 201 Total room load 2885 1968 1757 645 Air required (cfm)Air required (cfm)135 98 82 32 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-18 11:52:29Right-Suite® Universal 2019 19.0.20 RSU27054 Page 4... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name M Bath WIC 2 Exposed wall 23.0 ft 10.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft10.0x13.0 ft10.0x6.5 5 Room area 130.0 ft²65.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 80 80 206 132 80 80 206 132 .GG ImpactImpact 0.3100.310 nn 8.998.99 7.027.02 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3000.300 ee 8.708.70 9.179.17 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 104 88 228 146 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 20.6220.62 16 0 140 322 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 19.1519.15 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 32.0732.07 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.386Attic, Shngl Roof, R 0.386 --1.581.58 1.211.21 130 130 205 158 65 65 102 79 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 130 23 660 0 65 10 287 0 6 c) AED excursion 112 -10 Envelope loss/gain 1439 869 595 200 12 a) Infiltration 382 114 166 49 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1821 983 761 250 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 20 15 31 23 14 Subtotal 1841 997 792 273 15 Duct loads 35%45%653 453 35%45%281 124 Total room load 2494 1451 1073 396 Air required (cfm)Air required (cfm)117 73 50 20 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-18 11:52:29Right-Suite® Universal 2019 19.0.20 RSU27054 Page 5... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Clst M Hall 2 Exposed wall 0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.0x3.0 ft47.0x1.0 5 Room area 18.0 ft²47.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.3100.310 nn 8.998.99 7.027.02 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3000.300 ee 8.708.70 9.179.17 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 20.6220.62 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 19.1519.15 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 32.0732.07 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.386Attic, Shngl Roof, R 0.386 --1.581.58 1.211.21 18 18 28 22 47 47 74 57 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 18 0 0 0 47 0 0 0 6 c) AED excursion -1 -2 Envelope loss/gain 28 21 74 55 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)28 21 74 55 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -28 -21 -74 -55 14 Subtotal 0 0 0 0 15 Duct loads 35%45%0 0 35%45%0 0 Total room load 0 0 0 0 Air required (cfm)Air required (cfm)0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-18 11:52:29Right-Suite® Universal 2019 19.0.20 RSU27054 Page 6... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Master Bedroom Foyer 2 Exposed wall 35.5 ft 5.5 ft 3 Room height 8.6 heat/coolft 10.0 heat/coolft 4 Room dimensions ft22.5x13.0 ft13.5x5.5 5 Room area 292.5 ft²74.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 194 178 458 293 0 0 0 0 .GG ImpactImpact 0.3100.310 nn 8.998.99 7.027.02 16 0 140 109 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 112 89 229 146 55 35 90 58 11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3000.300 ee 8.708.70 9.179.17 23 23 200 211 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 ee 3.693.69 3.733.73 0 0 0 0 20 20 74 75 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 20.6220.62 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 19.1519.15 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 32.0732.07 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.386Attic, Shngl Roof, R 0.386 --1.581.58 1.211.21 293 293 461 355 74 74 117 90 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 293 36 1018 0 74 6 158 0 6 c) AED excursion -73 -10 Envelope loss/gain 2507 1042 439 212 12 a) Infiltration 634 189 114 34 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13)3140 1731 553 246 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 20 15 0 0 14 Subtotal 3161 1746 553 246 15 Duct loads 35%45%1121 793 35%45%196 112 Total room load 4282 2539 749 358 Air required (cfm)Air required (cfm)200 127 35 18 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-18 11:52:29Right-Suite® Universal 2019 19.0.20 RSU27054 Page 7... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Dining Rm Kitchen 2 Exposed wall 28.5 ft 3.5 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft13.5x13.5 ft11.0x17.5 5 Room area 182.3 ft²192.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.3100.310 nn 8.998.99 7.027.02 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 135 112 289 185 0 0 0 0 11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 23 0 200 505 0 0 0 0 GG ImpactImpact 0.3000.300 ee 8.708.70 9.179.17 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 20.6220.62 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 19.1519.15 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 32.0732.07 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 150 150 441 219 35 35 103 51 CC Attic, Shngl Roof, R 0.386Attic, Shngl Roof, R 0.386 --1.581.58 1.211.21 182 182 287 221 193 193 303 234 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 182 29 817 0 193 4 100 0 6 c) AED excursion 103 -98 Envelope loss/gain 2034 1232 507 187 12 a) Infiltration 280 83 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 2 460 Appliances/other 0 1700 Subtotal (lines 6 to 13)2314 1316 507 2347 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 9 6 14 Subtotal 2314 1316 515 2353 15 Duct loads 35%45%821 598 35%45%183 1069 Total room load 3135 1913 698 3422 Air required (cfm)Air required (cfm)147 96 33 171 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-18 11:52:29Right-Suite® Universal 2019 19.0.20 RSU27054 Page 8... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Pantry Hall 2 Exposed wall 0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft2.5x2.5 ft18.0x3.5 5 Room area 6.3 ft²63.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.3100.310 nn 8.998.99 7.027.02 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nn 3.693.69 3.733.73 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.3000.300 ee 8.708.70 21.9921.99 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3000.300 ee 8.708.70 9.179.17 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ss 8.998.99 9.159.15 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 20.6220.62 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3100.310 ww 8.998.99 19.1519.15 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 32.0732.07 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.386Attic, Shngl Roof, R 0.386 --1.581.58 1.211.21 6 6 10 8 63 63 99 77 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 6 0 0 0 63 0 0 0 6 c) AED excursion 0 -3 Envelope loss/gain 10 7 99 73 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)10 7 99 73 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -10 -7 -99 -73 14 Subtotal 0 0 0 0 15 Duct loads 35%45%0 0 35%45%0 0 Total room load 0 0 0 0 Air required (cfm)Air required (cfm)0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Sep-18 11:52:29Right-Suite® Universal 2019 19.0.20 RSU27054 Page 9... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Right-J® Worksheet Date:House Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Living Room 2 Exposed wall 15.8 ft 3 Room height 9.0 heat/coolft 4 Room dimensions ft18.0x21.0 5 Room area 378.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Block R-9 Wall 0.089 n 2.58 1.65 0 0 0 0 .G Impact 0.310 n 8.99 7.02 0 0 0 0 .D Door, Mtl Fbrgl Type 0.127 n 3.69 3.73 0 0 0 0 .W Block R-9 Wall 0.089 e 2.58 1.65 0 0 0 0 11 G Impact 0.300 e 8.70 21.99 0 0 0 0 G Impact 0.300 e 8.70 9.17 0 0 0 0 D Door, Mtl Fbrgl Type 0.127 e 3.69 3.73 0 0 0 0 W Block R-9 Wall 0.089 s 2.58 1.65 0 0 0 0 G Impact 0.310 s 8.99 9.15 0 0 0 0 W Block R-9 Wall 0.089 w 2.58 1.65 142 82 212 136 G Impact 0.310 w 8.99 20.62 0 0 0 0 G Impact 0.310 w 8.99 19.15 0 0 0 0 G Impact 0.330 w 9.57 32.07 59 0 568 1905 P Frm Wall, 1/2" DW Ex 0.101 -2.94 1.46 0 0 0 0 C Attic, Shngl Roof, R 0.386 -1.58 1.21 378 378 596 459 F On Grade Depth, Tile 0.989 -28.68 0.00 378 16 452 0 6 c) AED excursion 627 Envelope loss/gain 1828 3127 12 a) Infiltration 294 88 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 3 690 Appliances/other 900 Subtotal (lines 6 to 13)2122 4805 Less external load 0 0 Less transfer 0 0 Redistribution 69 51 14 Subtotal 2191 4856 15 Duct loads 35%45%777 2205 Total room load 2969 7061 Air required (cfm)139 353 2020-Sep-18 11:52:30 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Duct System Summary Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Santana Autry Residence, Groza Builders, IncFor: TBD S Brocksmith Rd, Ft Pierce, FL 34945 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.448 / 0.252 in H2O in H2O0.448 / 0.252 Lowest friction rate in/100ft0.129in/100ft0.129 Actual air flow cfm1153cfm1153 Total effective length (TEL) ft544 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st4300.033.3VlFx0x06.00.13439991757hBath st4300.033.1VlFx0x08.00.1341181622885hBed 2 st4300.035.3VlFx0x06.00.13465831481hBed 3 st2200.013.1VlFx0x07.00.210791412508hBed 4 st1200.032.1VlFx0x08.00.1931151763135hDining Rm st1200.030.9VlFx0x04.00.1942142749hFoyer st1200.026.4VlFx0x06.00.198103201711cKitchen st1200.026.2VlFx0x06.00.198103201711cKitchen-A st2200.013.5VlFx0x04.00.2105434904cLaundry st4300.039.4VlFx0x09.00.132212833530cLiving Room st3300.047.7VlFx0x09.00.129212833530cLiving Room-A st3300.048.1VlFx0x08.00.129871402494hM Bath st1200.036.7VlFx0x07.00.189761202141hMaster Bedroom st3300.046.3VlFx0x07.00.129761202141hMaster Bedroom-A st3300.040.0VlFx0x05.00.13224601073hWIC Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st3 Peak AVF 404 399 0.129 514 12.0 0x0 VinlFlx st1 st1 Peak AVF 781 817 0.129 764 14.0 0x0 VinlFlx st4 Peak AVF 427 434 0.132 552 12.0 0x0 VinlFlx st2 st2 Peak AVF 602 567 0.132 563 14.0 0x0 VinlFlx Bold/italic values have been manually overridden 2020-Sep-18 11:52:30 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb5 0x 3010 176 196.2 0.129 551 10.0 x0 0 VlFx rt1 rb1 0x 6970 946 165.6 0.152 535 18.0 x0 0 VlFx rt1 rb4 0x 1620 118 169.8 0.149 464 8.0 x0 0 VlFx rt1 rb3 0x 830 65 163.9 0.154 423 6.0 x0 0 VlFx rt1 rb2 0x 1410 79 164.3 0.154 527 7.0 x0 0 VlFx rt1 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 1384 1384 0.129 634 20.0 0x0 VinlFlx 2020-Sep-18 11:52:30 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ... HVAC\TBD S Brocksmith Rd Santana Autry GBI.rup Calc = MJ8 Front Door faces: N 751Job:Manual S Compliance Report Date:House Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Santana Autry Residence, Groza Builders, IncFor: TBD S Brocksmith Rd, Ft Pierce, FL 34945 Cooling Equipment Design Conditions °F76.9Entering coil DB:Btuh24031Sensible gain:°F90.4Outdoor design DB: °F64.1Entering coil WB:Btuh7447Latent gain:°F77.4Outdoor design WB: Btuh31477Total gain:°F75.0Indoor design DB: cfm1153Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: 14ACXS036-230A**+CBA27UHE-036-230*++TDRModel:LennoxManufacturer: cfm1153Actual airflow: % of load101Btuh24220Sensible capacity: % of load139Btuh10380Latent capacity: %70SHR:% of load110Btuh34600Total capacity: Heating Equipment Design Conditions °F68.0Entering coil DB:Btuh26490Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm1153Actual airflow: °F50Temp. rise:% of load86kW6.7Output capacity: Meets all requirements of ACCA Manual S. Job #: 751 Performed by Vicki Lynne Nisa for: Santana Autry Residence TBD S Brocksmith Rd Ft Pierce, FL 34945 Air Calcs, LLC 7550 Hidden Hammock Ln Vero Beach, FL 32966 Phone: 772.800.8413 vickilynne@aircalcs.com Scale: 1 : 244 Page 1 Right-Suite® Universal 2019 19.0.20 RSU27054 2020-Sep-18 11:53:04 ...cksmith Rd Santana Autry GBI.rup N Level 1 Garage Bed 4 Bed 3 Laundry Bed 2 Bath M Bath WIC Clst M Hall Master Bedroom FoyerDining Rm Kitchen Pantry Hall Living Room 12 x 12 212 cfm 10 x 6 60 cfm 8 x 8 103 cfm 6 x 6 54 cfm 12 x 12 141 cfm 12 x 12 83 cfm 12 x 12 162 cfm 24 x 18 946 cfm 12 x 8 141 cfm 10 x 6 83 cfm 12 x 8 162 cfm 8 x 4 42 cfm 14 x 14 301 cfm 10 x 10 120 cfm 10 x 10 120 cfm 8 x 8 99 cfm 10 x 10 140 cfm 8 x 8 103 cfm 12 x 12 212 cfm 12 x 8 176 cfm 20 " 7 " 6 " 8 " 18 " 10 " 7 "4 " 9 "6 " 6 " 8 " 14 " 14 " 8 "4 " 6 "6 " 7 " 12 " 9 " 12 " 8 " 5 " 7 "