HomeMy WebLinkAboutFIRE DEPARTMENTSAINT LUCIE COUNTY FIRE DISTRICT
PLAN REVIEW FORM
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
Telephone: 772-621-3322
Fax: 772-621-3604
Web Address: www.slcfd.com
Building Dept. SLC FMO Permit # 1B-20 298
Project Name Love's Travel Stops BLDG Permit # E2O08:0:35=4:��
Address 200 South Kings Hwy —_ City Ft Pierce
Contractor
Address
JC Curtis Construction Company
I1507Wilder Street City Chattanoga
i
I TN Zip 137406 Telephone (423) 894-5480
Architect/Engineer I Telephone
Occupancy Type
Load
Mercantile — Construction Type F Square Feet 9512
i
--, --
80 per plans Number of Stories Access Box Required Access Key Switch
AFSPermit lRequired FA Permit
;Required FFP Permit
General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. A Radio coverage Pre -Survey Signal Strength inspection is required before any final inspection is scheduled.
5. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
6. Failed inspections require payment of fee prior to rescheduling of further inspections.
7. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
8. Fire alarm panels shall be located indoors within air conditioned space.
9. Plans and construction are subject to corrections in the field to maintain code compliance.
10. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
11. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2012 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
(1. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity. Provide a remote test and
!Inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector. HVAC duct smoke detector(s)
shall be tied into the fire alarm system.
2. A separate review and permit is required for the installation or alteration of the fire alarm and fire sprinkler systems.
Page 11
1 of Ili
Reviewed by !Tony .Jerger Date 09-23-2020