HomeMy WebLinkAboutProject Information-- Project Summary ry Job: 17BI17
wrightsofto
Date: 10 NOV 2018
Entire House By: J.E.G.
JAMES E. GILGENBACH, ARCHITECT
9009 ONE PUTT PLACE, PORT ST LUCIE, FL 34986 Phone: (561)8098491
For. PEREZ GUEST HOUSE
ORANGEAVENUE & BRIDLEWOOD WAY, FORT PIERCE, FL
Notes: SINGLE FAMILY RESIDENCE - GUEST HOUSE
Weather. St Lucie Co Intl, FL, US
Winter Design Conditions
Outside db 41 OF
Inside db 68 OF
Design TD 27 OF
Heating Summary
Structure 15169 Btuh
Ducts 2388 Btuh
Central vent (50 cfm) 1484 Btuh
Outside air
Humidification 0 Btuh
Piping 0 Btuh
Equipment load 19041 Btuh
Infiltration
Method
Construction quality
Fireplaces
Simplified
Averagee
Area (ft2)
Heatingg Coolingg
712 712
Volume (ft3)
6408
6408
Air changes/hour
0.61
0
Equiv.AVF (ctn)
65
0
Heating Equipment
Summary
Make
Trade
Model
AHRI ref
Efficiency
Heating Input
Heating output
Temperature rise
Actual air flow
Air flow factor
Static pressure
Space thermostat
100 EFF
4.1 kW
139996 Btuh
800 cfm
0.046 cfrnBtuh
0 in H2O
Heat/Cool
Summer Design Conditions
Outside db
90
OF
Inside db
75
OF
Design TD
15
OF
Daily range
L
Relative humidity
50
%
Moisture difference
57
gr/lb
Sensible Cooling Equipment
Load
Sizing
Structure
10295
Btuh
Ducts
2564
Btuh
Central vent (50 cfm)
846
Btuh
Outside air
Blower
0
Btuh
Use manufacturers data
Rate/swin multiplier
n
0.95
Equipmen sensible bad
13075
Btuh
Latent Cooling Equipment Load Sizing
Structure
400
Btuh
Ducts
1032
Btuh
Central vent (50 cfm)
1932
Btuh
Outside air
Equipment latent load
3364
Btuh
Equipment Total Load (Sen+Lat)
16439
Btuh
Req. total capacity at 0.65 SHR
1.7
ton
Cooling Equipment Summary
Make
GREE ELECTRIC APPLIANCES INC. OF ZHUHAI
Trade
GREE
Cond
HW13024NNA D
Coil
HNF13024/A D
AHRI ref
5360566
Efficiency
Sensible cooling
Latent cooling
Total cooling
Actual air flow
Air flow factor
Static pressure
Load sensible heat ratio
11.4 EER,13 SEER
15600 Btuh
8400 Btuh
24000 Btuh
800 cfm
0.062, � cfml8tuh
, '1-0` in H2O'-
\.-0.80
Boldrdalk values have been manually ovendden
Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -
* wrightsoftw Right-Sute®Univmd20l7l7.0.23RSU09592
neDrive'hM-J CALCSIMAN-J CALCSfBiR GUESI.rup Calc = MJ8 Front Doorfaces: S
15:15:16
Page 1
.' i .
+ wrightsoft®
Load Short Form
Entire House
JAMES E. GILGENBACH, ARCHITECT
9009 ONE PUTT PLACE, PORT ST LUCIF- FL 34986 Phone (561)809-8491
iLroject Intormation
For. PEREZ GUEST HOUSE
ORANGEAVENUE & BRIDLEWOOD WAY FORT PIERCE, FL
Job: 17B117
Date: 10 NOV 2018
By: J.E.G.
Design Information
Htg Clg Infiltration
Outside db (OF) 41 90 Method Simplified
Inside db (OF) 68 75 Construction quality Average
Design TD (OF) 27 15 Fireplaces 0
Daily range - L
Inside humidity (%) 50 50
Moisture difference (gr/Ib) 21 57
HEATING EQUIPMENT COOLING EQUIPMENT
Make
Make GREE ELECTRIC APPLIANCES INC. OF ZHUHAI
Trade
Trade GREE
Model
Cond HW13024NNA D
AHRI ref
Coil HNF13024/A D
AHRI ref 5360566
Efficiency
100 EFF
Efficiency 11 A EER,13 SEER
Heating input
4.1
kW
Sensible cooling
16600
Btuh
Heating output
13999
Btuh
Latent cooling
8400
Btuh
Temperature rise
16
OF
Total cooling
24000
Btuh
Actual air flow
800
cfr
Actual air flow
800
cfm
Air flow factor
0.046
chffituh
Air flow factor
0.062
c#TVBtuh
Static pressure
0
in H2O
Static pressure
0
in H2O
Space thermostat
Heat/Cool
Load sensible heat ratio
0.80
ROOM NAME
Area
Htg load
Cig load
Htg AVF
Cig AVF
(ft2)
(Btuh)
(Btuh)
(cfm)
(cfm)
BEDRM
180
4379
3259
200
203
BATH
66
2486
1443
113
90
LIVING
180
4647
2890
212
180
UTILITY
70
1039
700
47
44
KITCHEN/DINE
216
5006
4568
228
284
Entire House
712
17557
12859
800
800
Other equip loads
1484
846
Equip. @ 0.95 RSM
13075
Latent cooling
3364
TMAI C
747
4nnA4
4&A9n
onn
r - 1 vv 1 r V•fJA
Soldwallc values hew been manuaW overridden
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
A- + wrightsoft° Rghl-BrieVUniuersal201717.0.23RSU09592
neDrNeWM-JCALCSIMAN-JCALCSVrEREZGUESLrup Cdc=MJ8 FrontDoorbow. S
oov OVU
2018-Now0915:15:16
Page 1