HomeMy WebLinkAboutResubmit Generator Permit - Crippen Residence Generator Permit 24909 Orange Ave_000112 9/29/20P anning & Development Services
wilding & Code Regulapon Division
2300 Virginia Avenue
Fort Pierce. FL. 34982
PROPERTY INFORMATION
Address: 24909 Orange Ave
City / State / Zip: Fort Pierce, FI 34945
Parcel #: 2112-441-0002-000/9
Zoning: AG-5
APPLICATION INFORMATION
Permit Number: 2008-0759
Permit Type: GENERATOR, RESIDENTIAL
CONTRACTOR INFORMATION
Contractor Name:
Daniel J Stubbs
Business Name:
S & W Electric Inc
Business Addr:
501 W Coker Rd
City / State / Zip:
Ft Pierce, FI 34945
REVIEWS AND COMMENTS
Review Type Status
FRONT COUNTER REVIEW COMPLETE
Comment:
NOTIFIED FOR PICK UP
Comment:
PLANS EXAMINER ELECTRIC
Comment:
9/24/2020
PENDING
REVIEW COMMENTS
Page 1
Owner(s):
Lindsey A Crippen / Scott S Crippen
Jurisdiction: SAINT LUCIE COUNTY
Lot#: Block:
Stories: Automatic Sprinkler System? No
Fax Number:
Email: Stu boutelectric@Aol.Corn
Reviewed By Date Started Date Completed Date Released
Ellen Vaughn 8/29/2020 8/29/2020 8/29/2020
INCOMPLETE Doug Harvey 9/24/2020
SERVICE AND NON -SERVICE NOT TO BE IN THE SAME RACEWAY OR CABINET. GENERATOR IS NON -
SEPARATELY DERIVED AND CONDUCTORS FROM THE GENERATOR ARE FEEDERS NOT SERVICE,
DRAWING SHOWS THE SERVICE AND FEEDERS IN THE SAME CONDUIT AND ENCLOSURE. PLEASE
CORRECT. PROVIDE AIC RATINGS FOR VERIFICATION OF EQUIPMENT
1
v
Q
a
O
5y
7
c
l-
;O
�O
�c c
c
�j
0
G
P 'D
Y
Electrical Contractor: _� 4 �,J ec I r
Phone No.: 7 7;L �Z 6 t l , jy 416 6
Fax No.:
Project: Gr, o ram, /2 e S Location:
k C?
Existing Service Feeder Size: 2/ 0 G (/
Existing Panel Size: L/ 0 ,
Main Breaker Size:
Number of Breakers:
Existin Loads
1 a-S1' Sq. ft. x 3 watts per sq. ft.
r 2 V watts
oZ Appliance cir. @ 1500 watts each
3C0vwatts
/ Laundry cir. @ 1500 watts each
/ 5-00 watts
G n S Range C� S kw
watts
Dishwasher and disposal @ 1500 watts each
watts
Microwave @ 2000 watts
Q-Coo watts
c s Water heaters
watts
Tankless water heater
watts
(�� Dryer @ 5 kw
watts
/ Refrigerator @ 1500 watts
/ 5 o 0 watts
Bathroom 1 @ 1500 watts
S/ p 0 watts
Sprinkler Pump
watts
Other _
4
watts
Other
watts
Other
watts Sub 'Total O?V watts
New Loads
Pool pump
watts
_ — Pool light
watts
Heat pump
watts
Chlorine generator
watts
Air blower
watts
Boatlift
watts
Other
watts
Other
watts
Other
watts
Total watts
First 10 kw @ 100%
watts
Remainder @ 40%
p 3 O watts
A/C heat @ 100%
I 0,,POO watts
Total watts = o Divided by 240 volts = aZ Amps
Prepared by: prmi lel / S i L%_�
Date.-y
Cable Engineered by Draka
600 Volt, Tray Cable
PVC/Nylon Insulated Circuit Conductors
Overall PVC Jacket
A
B
C
D
E
Components
A: (3) - #3 AWG Class C stranded, soft drawn, bare copper circuit conductors w/40 mils (1.02 mm) heat and
moisture resistant, polyvinyl chloride (PVC) insulation and jacketed w/ 6 mils (0.15 mm) nylon applied directly
to the surface of the insulation.
B: (6) - #18 AWG Class K stranded, soft drawn, bare copper conductors w/15 mils (0.38 mm) heat and moisture
resistant, polyvinyl chloride (PVC) insulation and jacketed w/ 4 mils (0.10 mm) nylon applied directly to the
surface of the insulation.
C: (1) - #8 AWG Class C stranded, soft drawn, bare copper grounding conductor w/30 mils (0.76 mm) heat and
moisture resistant, polyvinyl chloride (PVC) insulation and jacketed w/ 5 mils (0.13 mm) nylon applied directly
to the surface of the insulation
D: Mylar binder tape.
E: 80 mils (2.03 mm) of heat and moisture resistant, polyvinyl chloride (PVC) jacket.
Print Legend
(UL) E60544 POWER AND CONTROL TRAY CABLE TYPE TC-ER-JP 3 AWG (26,7 mm2) 3/C + 8 AWG (8,37 mm2)
1/C GROUND THWN CONDS & 18 AWG (0,82 mm2) 6/C TFFN CONDS 600V 75C DRY/75C WET OIL RES 1
SUNLIGHT RESISTANCE DIRECT BURIAL JOIST PULL GENERAC P/N 1722 "sequential footage print'
Physical Characteristics
Cable Weight: 900 Ib/mft (1339 kg/km)
Copper Weight: 577 Ib/mft (859 kg/km)
Nominal Cable OD: 0.980 in (24.9 mm)
e DATE CHANGE DETAIL
v
0 02/03/17 New Issue
2
3
Approvals: I Engineering: I I Final:
Draka Cableteq USA Inc. reserves the right to modify this information without prior
notification and does not make a warranty or representation of any kind, whether implied or
expressed with respect to the information contained herein. Draka Cableteq assumes no
risks, and will not be liable for direct or indirect, special; incidental or consequential damages,
any defect or personal injury resulting from the use of this document.
--PRYSMIAN Draka Engineered Solutions
One Tamaqua Blvd
�.� Draka Schuylkill Haven PA 17972
Phone:570-385-4381 Fax:570-385-1092
Project Name: I Generac
Part Number: I 382891
Quote Number: NA
File Number: type tc thhn-pvc 3C3 1 C8 6C18 382891
GENERAC
Page Number: Page 1 of 2
EngDrawing-RevOl-Apd107
Physical Characteristics
Conductor Color Code: 3 AWG - Black, White and Red
8 AWG - Green
18 AWG - Black, Red, Yellow, Yellow/Black, Blue and White
Jacket Color: Orange
Electrical / Optical Characteristics
Voltage: 600V
Specifications
Conductors: ASTM B 3, ASTM B 8, ASTM B174
Insulation: ICEA S-95-658 (NEMA WC 70), ICEA S-73-532 (NEMA WC 57), UL 83 for Type THWN wires
Jacket: ICEA S-95-658 (NEMA WC 70), ICEA S-73-532 (NEMA WC 57), UL 1277
Ratings
UL THWN 600V
UL Type TC-ER-JP 600V
The insulation is acceptable for use in locations at 75 °C dry and 75 °C wet.
The cable is suitable for use in cable trays, aerial or direct burial installations.
Packaging
Bulk reels
R
e DATE CHANGE DETAIL
v �0RPPYSMIAN Draka Engineered Solutions
0 02/03/17 New Issue One Tamaqua Blvd
1 �..> Draka Schuylkill Haven PA 17972
Phone:570-385-4381 Fax:570-385-1092
2
3
Approvals: Engineering: Final: Project Name: Generac
Draka Cableteq USA Inc. reserves the right to modify this information without prior Part Number: 382891
notification and does not make a warranty or representation of any kind, whether implied or
expressed with respect to the information contained herein. Draka Cabletaq assumes no
risks, and will not be liable for direct or indirect, special; incidental or consequential damages, Quote Number: NA
any defect or personal injury resulting from the use of this document. type tc thhn-pvC 3C3 1 C8 6C18 382891
EngDrawing-Rev01-Apri107 File Number: GENERAC
Page Number: Page 2 of 2
ENERACO
20/22/24 kW
Switch Options
Service Rated Automatic Transfer Switch Features
Model
0007039-1, 0007039-3 (20 kW)
• Intelligently manages up to four air conditioner loads with no additional ardware.
G007043.2, G007043-3 (22 kW)
No. of poles
2
• Up to eight additional large (240 VAC) loads can be managed when d in conjunction
Current rating (amps)
200
ith Smart Management Modules (SMMS).
Voltage rating (VAC)
120/240,10
• Electrically operate , mec - c s or fast, clean connections.
Utility voltage monitor (fixed)*
• Rated for all classes of load,100% equipment rated, both inductive and resistive.
-Pick-up
-Dropout
80%
65%
• 2-pole, 250 VAC contactors.
Return to Utility`
Approx 13 sec
• Service equipment rated, dual coil design.
Exercises bi-weekly for 5 minutes'
Standard
• Rated for both aluminum and copper conductors.
ETL or UL listed
Standard
NEMA/UL 3
• Main contacts are silver plated or silver alloy to resist welding and sticking.
22,000
• NEMA/UL 3R aluminum outdoor enclosure allows for indoor or outdoor mounting flexibility.(EEEEo
250 MCM - #s
*Function er
Dimensions
Exercise can be set to weekly, bi-weekly, or monthly
200 Amps 120/240, 10
Open Transition Service Rated
Height
Width
Hi
H2
W1
W2Depth
in
26.8
30.1
10.5
13.5
6.9
cm
67.95
76.43
26.67
34.18
17.5
Wire Ranges
Conductor Lug
Neutral Lug
Ground Lug
250 MCM - #6
350 MCM - #6
2/0 - #14
PWRview Automatic Transfer Switch Features
• Integrated PWRview monitor provides real-time energy usage data through PWRview app.
• Intelligently manages up to four air conditioner loads with no additional hardware.
• Up to eight additional large (240 VAC) loads can be managed when used in conjunction
with Smart Management Modules (SMMs).
• Electrically operated, mechanically -held contacts for fast, clean connections.
• Rated for all classes of load,100% equipment rated, both inductive and resistive.
• 2-pole, 250 VAC contactors.
• Service equipment rated, dual coil design.
• Rated for both aluminum and copper conductors.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
• NEMA 3R aluminum outdoor enclosure allows for indoor or outdoor mounting flexibility.
• Heavy duty Generac Contactor is an ETL recognized device.
Dimensions
200 Amps 120/240,1a
Open Transition Service Rated
Height
width
Depth
H1
H2
W1
W2
in
26.8
30.1
10.5
13.5
6.9
cm
1 67.95
76.43
26.67
34.18
17.5
Wire Ranges
Conductor Lug
Neutral Lug
Ground Lug
250 MCM - #6
350 MCM - #6
2/0 - #14
I—w,
17 t_
rp H1
L
L DEPTH yn
Model
G007210.0 (24 kW)
No. of poles
2
Current rating (amps)
200
Voltage rating (VAC)
120/240,10
Utility voltage monitor (fixed)*
-Pick-up
80%
-Dropout
65%
Return to Utility'
Approx.13 sec
Exercises bi-weekly for 5 minutes`
Standard
ETL or UL listed
Standard
Enclosure type
NEMA 3R
Circuit breaker protected
22,000
Lug range
250 MCM - #6
*Function of Evolution controller
Exercise can be set to weekly, bi-weekly,