HomeMy WebLinkAboutDUCT SEALINGPlanning & Development Services
Building & Code Regulation Division
2300 Virginia Ave, Sim 201
Fort Pierce, FL 34982
772-462-2165 Fax 772-462-6443
MENENWMNNNIIN FBC ENERGY CONSERVATION CODE
Duct Sealing Certification
Prescriptive and Performance Method
Date: I I3'� 2�1 � Permit#: " 9 - DZ'I j
p ( Lot #:
Contractor: Address:'4,k" i.ep. O`r, Lr� ei" FOY18+,
Construction: -.Post Construction Test ❑ Rough -in Test C Gr CA C'4-f°) /
Test Conditions:
Date: ( 3 ' I 2a I' Floor Area (ft2):
Time: 12 -00 Primary Location of Supply Ductwork
Indoor Temperature (F): "l 1 Primary Location of Return Ductwork
Outdoor Temperature(F): 1 a
Duct Leakage: ❑ Default Leak Free ^1
Test Pressure: L f (Pa) p Proposed On
Baseline Duct Pressure (optional) c • I (Pa)
Duct Press. (Pa) I Flow Ring I Fan Press I Flow (chi I Resuks iP.ee c,a
Total Leakage (cfm): 2-6
Total Leakage per 100 sgft: 1---1 - 0 , 0 2_5L
CFM25 x too divided by the CFA = Duct Leakage CFM/1o0 sqft.
Testina Comaanv
Company Name: Pro -Duct Services Address: 131f ki y,s+tL a-P�• <e ,F�3'S�Y'E4
I hereby certify that the above Dud Sealing Leakage results demonstrate compliance with 5e Edition FBC Energy Conservation requirements in accordance with
Section R403.2.2. �,r f
Signature: /.1 /�6� __
Printed Name: Martin Klein License/Certificate #: 5061633