HomeMy WebLinkAboutMANJCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jul-30 09:30:08 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1 ...soft HVAC\QUINTEROS RESIDENCE- HEADER CANAL.rup Calc = MJ8 Front Door faces: E Job:Project Summary Jul 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information QUINTEROS RESIDENCEFor: 4637 S. HEADER CANAL ROAD, FORT PIERCE, FL Notes: Design Information Fort Pierce, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F42 Outside db °F90 Inside db °F70 Inside db °F75 Design TD °F28 Design TD °F15 Daily range M Relative humidity %50 Moisture difference gr/lb61 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh34768 Struc ture Btuh26751 Ducts Btuh9278 Ducts Btuh8560 Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none) Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh44046 Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load Btuh33545 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average 0Fireplaces Structure Btuh3577 Ducts Btuh3646 Central vent (0 cfm)Btuh0 CoolingHeating (none) 28132813Area (ft²)Equipment latent load Btuh7222 3210832108Volume (ft³) Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh40768 Equiv. AVF (cfm)86171 Req. total capacity at 0.70 SHR ton4.0 Heating Equipment Summary Cooling Equipment Summary Make Make Carrier Trade Trade CARRIER Model Cond CA16NA04800G0B0 AHRI ref Coil FX4DNF049L AHRI ref 202025346 Efficiency 100 EFF Efficiency 13.5 EER, 16 SEER Heating input kW12.5 Sensible cooling Btuh32550 Heating output Btuh42791 Latent cooling Btuh13950 Temperature rise °F25 Total cooling Btuh46500 Actual air flow cfm1550 Actual air flow cfm1550 Air flow factor cfm/Btuh0.035 Air flow factor cfm/Btuh0.044 Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 0.83 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jul-30 09:30:08 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1 ...soft HVAC\QUINTEROS RESIDENCE- HEADER CANAL.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Jul 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House GAME RM TOILET 2 Exposed wall 239.2 ft 13.0 ft 3 Room height 11.4 ft 10.0 heat/coolft 4 Room dimensions ft7.0x6.0 5 Room area 2813.0 ft²42.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 290 285 1140 623 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 5 0 95 78 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 57 45 180 98 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 12 0 212 314 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 546 446 1785 975 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 60 9 1092 1945 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 40 4 732 1317 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 57 45 180 98 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 12 12 212 246 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 654 588 2355 1287 70 70 280 153 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 4 8 71 58 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 40 80 732 603 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.6810.68 22 43 394 231 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 968 765 3061 1673 60 60 240 131 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 28.5728.57 8 4 142 223 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 25.7925.79 22 3 394 559 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 26.0526.05 80 9 1463 2094 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.6824.68 54 6 976 1323 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.2320.23 40 6 728 809 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 2813 2813 4460 3849 42 42 67 57 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 2813 239 9094 0 42 13 494 0 6 c) AED excursion 985 -25 Envelope loss/gain 29499 19389 1081 317 12 a) Infiltration 5270 1411 266 71 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 5950 0 Subtotal (lines 6 to 13)34768 26751 1348 389 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 34768 26751 1348 389 15 Duct loads 27%32%9278 8560 27%32%360 124 Total room load 44046 35311 1708 513 Air required (cfm)Air required (cfm)1550 1550 60 23 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jul-30 09:30:08 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 2 ...soft HVAC\QUINTEROS RESIDENCE- HEADER CANAL.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Jul 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name GAME RM BATH 2 2 Exposed wall 27.0 ft 5.0 ft 3 Room height 12.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft357.0x1.0 ft5.0x11.0 5 Room area 357.0 ft²55.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 144 144 577 315 50 46 185 101 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 4 4 71 58 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 180 126 506 277 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 28.5728.57 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 25.7925.79 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.6824.68 54 3 976 1323 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.2320.23 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 357 357 566 488 55 55 87 75 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 357 27 1027 0 55 5 190 0 6 c) AED excursion 505 -25 Envelope loss/gain 3651 2908 533 210 12 a) Infiltration 664 178 102 27 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 150 Subtotal (lines 6 to 13)4315 3085 635 387 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 23 18 9 7 14 Subtotal 4338 3104 644 395 15 Duct loads 27%32%1157 993 27%32%172 126 Total room load 5495 4097 816 521 Air required (cfm)Air required (cfm)193 180 29 23 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jul-30 09:30:08 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 3 ...soft HVAC\QUINTEROS RESIDENCE- HEADER CANAL.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Jul 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 3 WIC 2 2 Exposed wall 31.0 ft 0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft204.0x1.0 ft6.0x6.0 5 Room area 204.0 ft²36.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 20 20 80 44 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 150 130 521 284 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 20 1 364 648 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 140 140 561 306 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 28.5728.57 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 25.7925.79 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.6824.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.2320.23 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 204 204 323 279 36 36 57 49 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 204 31 1179 0 36 0 0 0 6 c) AED excursion -93 -3 Envelope loss/gain 3027 1469 57 46 12 a) Infiltration 635 170 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)3663 1639 57 46 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 9 7 14 11 14 Subtotal 3672 1647 71 57 15 Duct loads 27%32%980 527 27%32%19 18 Total room load 4652 2174 90 76 Air required (cfm)Air required (cfm)164 95 3 3 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jul-30 09:30:08 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 4 ...soft HVAC\QUINTEROS RESIDENCE- HEADER CANAL.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Jul 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name WIC 3 BEDROOM 2 2 Exposed wall 8.0 ft 14.6 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft7.0x6.0 ft209.0x1.0 5 Room area 42.0 ft²209.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 20 20 80 44 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 28 22 90 49 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 6 0 106 157 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 60 60 240 131 90 70 280 153 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 20 1 364 648 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 28 22 90 49 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 6 3 106 123 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 28.5728.57 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 25.7925.79 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.6824.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.2320.23 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 42 42 67 57 209 209 331 286 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 42 8 304 0 209 15 555 0 6 c) AED excursion -17 -95 Envelope loss/gain 691 216 1922 1370 12 a) Infiltration 164 44 300 80 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 250 Subtotal (lines 6 to 13)855 260 2223 1701 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 9 7 14 Subtotal 855 260 2232 1708 15 Duct loads 27%32%228 83 27%32%596 547 Total room load 1083 343 2827 2255 Air required (cfm)Air required (cfm)38 15 99 99 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jul-30 09:30:08 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 5 ...soft HVAC\QUINTEROS RESIDENCE- HEADER CANAL.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Jul 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name HALL FOYER 2 Exposed wall 0 ft 9.0 ft 3 Room height 10.0 heat/coolft 14.0 heat/coolft 4 Room dimensions ft4.0x10.0 ft15.0x9.0 5 Room area 40.0 ft²135.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 126 86 344 188 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 40 2 732 1317 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 28.5728.57 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 25.7925.79 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.6824.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.2320.23 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 40 40 63 55 135 135 214 185 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 40 0 0 0 135 9 342 0 6 c) AED excursion -3 -71 Envelope loss/gain 63 51 1631 1619 12 a) Infiltration 0 0 258 69 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)63 51 1890 1688 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -63 -51 0 0 14 Subtotal 0 0 1890 1688 15 Duct loads 27%32%0 0 27%32%504 540 Total room load 0 0 2394 2228 Air required (cfm)Air required (cfm)0 0 84 98 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jul-30 09:30:08 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 6 ...soft HVAC\QUINTEROS RESIDENCE- HEADER CANAL.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Jul 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name LIVING RM PANTRY 2 Exposed wall 22.0 ft 0 ft 3 Room height 14.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft19.0x22.0 ft4.0x5.0 5 Room area 418.0 ft²20.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 308 206 825 451 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 28.5728.57 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 25.7925.79 22 2 394 559 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 26.0526.05 80 4 1463 2094 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.6824.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.2320.23 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 418 418 663 572 20 20 32 27 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 418 22 837 0 20 0 0 0 6 c) AED excursion 1100 -2 Envelope loss/gain 4181 4776 32 26 12 a) Infiltration 631 169 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)4813 4945 32 26 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 3 2 14 Subtotal 4813 4945 35 28 15 Duct loads 27%32%1284 1582 27%32%9 9 Total room load 6097 6527 44 37 Air required (cfm)Air required (cfm)215 287 2 2 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jul-30 09:30:08 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 7 ...soft HVAC\QUINTEROS RESIDENCE- HEADER CANAL.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Jul 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name KITCHEN DEN 2 Exposed wall 0 ft 14.6 ft 3 Room height 14.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft263.0x1.0 ft157.0x1.0 5 Room area 263.0 ft²157.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 28 22 90 49 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 6 0 106 157 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 90 70 280 153 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 20 1 364 648 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 28 22 90 49 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 6 3 106 123 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 28.5728.57 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 25.7925.79 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.6824.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.2320.23 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 263 263 417 360 157 157 249 215 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 263 0 0 0 157 15 555 0 6 c) AED excursion -201 -91 Envelope loss/gain 417 159 1840 1303 12 a) Infiltration 0 0 300 80 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 3000 250 Subtotal (lines 6 to 13)417 3159 2140 1634 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 11 9 11 9 14 Subtotal 428 3168 2152 1643 15 Duct loads 27%32%114 1014 27%32%574 526 Total room load 543 4182 2726 2169 Air required (cfm)Air required (cfm)19 184 96 95 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jul-30 09:30:08 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 8 ...soft HVAC\QUINTEROS RESIDENCE- HEADER CANAL.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Jul 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name DEN CLST DINING 2 Exposed wall 0 ft 21.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft2.0x8.0 ft94.0x1.0 5 Room area 16.0 ft²94.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 80 58 234 128 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.6810.68 0 0 0 0 22 22 394 231 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 130 90 360 197 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 28.5728.57 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 25.7925.79 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.6824.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.2320.23 0 0 0 0 40 3 728 809 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 16 16 25 22 94 94 149 129 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 16 0 0 0 94 21 799 0 6 c) AED excursion -1 329 Envelope loss/gain 25 21 2664 1823 12 a) Infiltration 0 0 430 115 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)25 21 3094 1938 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -25 -21 14 12 14 Subtotal 0 0 3108 1949 15 Duct loads 27%32%0 0 27%32%830 624 Total room load 0 0 3938 2573 Air required (cfm)Air required (cfm)0 0 139 113 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jul-30 09:30:08 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 9 ...soft HVAC\QUINTEROS RESIDENCE- HEADER CANAL.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Jul 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M HALL UTILITY RM 2 Exposed wall 0 ft 0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft6.0x4.0 ft8.0x11.0 5 Room area 24.0 ft²88.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 28.5728.57 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 25.7925.79 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.6824.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.2320.23 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 24 24 38 33 88 88 140 120 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 24 0 0 0 88 0 0 0 6 c) AED excursion -2 -46 Envelope loss/gain 38 31 140 74 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 650 Subtotal (lines 6 to 13)38 31 140 724 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -38 -31 14 12 14 Subtotal 0 0 154 736 15 Duct loads 27%32%0 0 27%32%41 235 Total room load 0 0 195 971 Air required (cfm)Air required (cfm)0 0 7 43 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jul-30 09:30:08 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 10 ...soft HVAC\QUINTEROS RESIDENCE- HEADER CANAL.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Jul 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name MASTER BEDROOM M WIC 2 Exposed wall 32.0 ft 24.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft263.0x1.0 ft10.0x14.0 5 Room area 263.0 ft²140.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 100 100 400 219 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 170 130 520 284 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 40 40 732 603 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 150 142 569 311 140 140 561 306 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 28.5728.57 8 2 142 223 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 25.7925.79 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.6824.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.2320.23 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 263 263 417 360 140 140 222 192 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 263 32 1217 0 140 24 913 0 6 c) AED excursion -164 -51 Envelope loss/gain 3596 1616 2096 666 12 a) Infiltration 656 176 492 132 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1500 0 Subtotal (lines 6 to 13)4252 3292 2587 798 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 10 8 0 0 14 Subtotal 4262 3300 2587 798 15 Duct loads 27%32%1137 1056 27%32%690 255 Total room load 5399 4356 3278 1053 Air required (cfm)Air required (cfm)190 191 115 46 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Jul-30 09:30:08 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 11 ...soft HVAC\QUINTEROS RESIDENCE- HEADER CANAL.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Jul 30, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M BATH M TOILET 2 Exposed wall 11.0 ft 7.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft182.0x1.0 ft4.0x7.0 5 Room area 182.0 ft²28.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 110 105 420 229 40 40 160 88 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 5 0 95 78 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 30 30 120 66 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 21.0721.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 28.5728.57 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 25.7925.79 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.6824.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.2320.23 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 182 182 289 249 28 28 44 38 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 182 11 418 0 28 7 266 0 6 c) AED excursion -46 -14 Envelope loss/gain 1221 510 591 178 12 a) Infiltration 225 60 143 38 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 150 0 Subtotal (lines 6 to 13)1447 721 734 216 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1447 721 734 216 15 Duct loads 27%32%386 231 27%32%196 69 Total room load 1833 951 930 285 Air required (cfm)Air required (cfm)64 42 33 13 2020-Jul-30 09:30:17 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1 ...soft HVAC\QUINTEROS RESIDENCE- HEADER CANAL.rup Calc = MJ8 Front Door faces: E Job:Duct System Summary Jul 30, 2020Date: Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information QUINTEROS RESIDENCEFor: 4637 S. HEADER CANAL ROAD, FORT PIERCE, FL CoolingHeating External static pressure in H2O1.00in H2O1.00 Pressure losses in H2O0in H2O0 Available static pressure in H2O1.00in H2O1.00 Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500 Lowest friction rate in/100ft1.000in/100ft1.000 Actual air flow cfm1550cfm1550 Total effective length (TEL)ft228 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st5155.058.8VlFx0x05.01.0002329816hBATH 2 st4135.044.7VlFx0x07.01.00099992827hBEDROOM 2 st5155.063.0VlFx0x07.01.000951644652hBEDROOM 3 st2115.021.7VlFx0x07.01.00095962726hDEN st3115.017.5VlFx0x07.01.0001131393938hDINING st2115.028.4VlFx0x07.01.00098842228cFOYER st5155.061.6VlFx0x07.01.00090972748hGAME RM st5155.073.2VlFx0x05.01.00023601708hGAME RM TOILET st5155.064.2VlFx0x07.01.00090972748hGAME RM-A st2115.023.4VlFx0x07.01.00092102091cKITCHEN st3115.012.4VlFx0x07.01.00092102091cKITCHEN-A st3115.031.5VlFx0x08.01.0001431073263cLIVING RM st4135.046.9VlFx0x08.01.0001431073263cLIVING RM-A st1115.022.2VlFx0x06.01.00042641833hM BATH st1115.032.7VlFx0x04.01.0001333930hM TOILET st1115.027.0VlFx0x06.01.000461153278hM WIC st1115.022.2VlFx0x07.01.00096952178cMASTER BEDROOM st1115.029.6VlFx0x07.01.00096952178cMASTER BEDROOM -A st2115.023.9VlFx0x04.01.0002237cPANTRY st1115.026.4VlFx0x06.01.000437971cUTILITY RM st4135.049.6VlFx0x04.01.0003376cWIC 2 st4135.053.7VlFx0x04.01.00015381083hWIC 3 2020-Jul-30 09:30:17 Right-Suite® Universal 2019 19.0.08 RSU08101 Page 2 ...soft HVAC\QUINTEROS RESIDENCE- HEADER CANAL.rup Calc = MJ8 Front Door faces: E Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st5 Peak AVF 446 321 1.000 818 10.0 0x0 VinlFlx st4 st4 Peak AVF 694 581 1.000 884 12.0 0x0 VinlFlx st2 st2 Peak AVF 885 868 1.000 828 14.0 0x0 VinlFlx st1 Peak AVF 409 334 1.000 751 10.0 0x0 VinlFlx st3 Peak AVF 255 348 1.000 638 10.0 0x0 VinlFlx Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb1 0x 15500 1550 0 0 0 0 x0 0 VlFx ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� �����������������������������������������������������