HomeMy WebLinkAboutDuct Sealing CertificationDate: 10/08/2019 Contractor: Planning & Development Services Building & Code Regulation Division 2300 Virginia Ave, Rm 201 Fort Pierce, FL 34982 772-462-2165 Fax 772-462-6443 RECEIVED OCT as 1019 FBC ENERGY CONSERVATION CODE Permitting Department Duct Sealing Certification St. Lucie County Prescripti/vv1e1 and Performance erf2or�manceMethod % Permit #: ITS, l 'o q Lot #: 49 Address: S 2 2- % D A 106 A-,,1 6l � A -/'cam C � ' . Construction: A Post Construction Test ❑ Rough -in Test Test Conditions: Date: 09/27/2019 Floor Area (ft2): 2195 Time: 10:00am Primary Location of Supply Ductwork Attic Indoor Temperature (F): 75 Primary Location of Return Ductwork Attic Outdoor Temperature (F): $5 Total Leakage Test (Outside) Duct Leakage: o Default ❑ Prop. Leak Free 9 Proposed On = .04 Test Pressure: 25 (Pa) Baseline Duct Pressure (optional) (Pa) Duct Press. (Pa) Flow Ring Fan Press Flow (cfm) Results: 8 Pass ❑ Fail Installed Pa 25 2 0 25 Total Leakage (cfm): 206 Total Leakage per 100 sgft: 49 CFM25 x 100 divided by the CFA = Duct Leakage CFM/100 sgft. `9 Testing Company Company Name: PEG LLC Address: I hereby certify that the above Duct Sealing Leakage results demonstrate compliance with 6t5 Edition FBC Energy Conservation requirements in accordance with Section R403.2.2. �Z Signature: 1 4 L-4- Printed Name: Oluwafemi Benedict License/Certificate #: 0453377