FBC ENERGY CONSERVATION CODE Permitting Department
Duct Sealing Certification St. Lucie County
Prescripti/vv1e1 and Performance
erf2or�manceMethod
%
Permit #: ITS, l 'o q Lot #: 49
Address: S 2 2- % D A 106 A-,,1 6l � A -/'cam C � ' .
Construction: A Post Construction Test ❑ Rough -in Test
Test Conditions:
Date: 09/27/2019 Floor Area (ft2): 2195
Time: 10:00am Primary Location of Supply Ductwork Attic
Indoor Temperature (F): 75 Primary Location of Return Ductwork Attic
Outdoor Temperature (F): $5
Total Leakage Test (Outside)
Duct Leakage: o Default ❑ Prop. Leak Free 9 Proposed On = .04
Test Pressure: 25 (Pa)
Baseline Duct Pressure (optional) (Pa)
Duct Press. (Pa) Flow Ring Fan Press Flow (cfm) Results: 8 Pass ❑ Fail
Installed Pa
25 2 0 25 Total Leakage (cfm): 206
Total Leakage per 100 sgft: 49
CFM25 x 100 divided by the CFA = Duct Leakage CFM/100 sgft.
`9
Testing Company
Company Name: PEG LLC
Address:
I hereby certify that the above Duct Sealing Leakage results demonstrate compliance with 6t5 Edition FBC Energy Conservation requirements in accordance with
Section R403.2.2. �Z