HomeMy WebLinkAboutAPPROVED, FL11651_2_R3-032_ALUMINUM_1inchFLORIDA PRODUCT APPROVAL
0.032” ALUMINUM GULFLOKTM 16” WIDE ROOF PANEL OVER 15/32” PLYWOOD
FLORIDA PRODUCT APPROVAL NO. 11651.2 R3
GULFLOKTM
COLOR STANDARDS
Light Blue:
CMYK: 60, 7, 0, 0
PMS: 2915 (This is the closest match to the CMYK colors)
Dark Blue:
CMYK: 100,100,30,20
PMS: 2757 (This is the closest match to the CMYK colors)
Grey
CMYK: 35,15,10,30
PMS: 7544 (This is the closest match to the CMYK colors)
3rd Blue
CMYK: 85,45,15,15
PMS: XXXX (This is the closest match to the CMYK colors)
SPOT COLORS
PRODUCT EVALUATION REPORT
Approve
ENERGY
TAX CREDIT
Approve
ENERGY
TAX CREDIT
KUHN ENGINEERING, LLC
1200 CLINT MOORE RD. SUITE 9, BOCA RATON, FL 33487 • FL COA #30464
FL# 11651.2 R3 • OCTOBER 5, 2017
Product Evaluation Report
GULF COAST SUPPLY & MANUFACTURING, LLC.
0.032” Aluminum GulfLok™ 16” Wide Roof Panel over 15/32” Plywood
Florida Product Approval #11651.2 R3
Florida Building Code 2017
Per Rule 61G20-3
Method: 1 –D
Category: Roofing
Subcategory: Metal Roofing
Compliance Method: 61G20-3.005(1)(d)
NON HVHZ
Product Manufacturer:
Gulf Coast Supply & Manufacturing, LLC.
14429 SW 2nd Place, Suite G30
Newberry, FL 32669
Engineer Evaluator:
Dan Kuhn, P.E. #75519
Florida Evaluation ANE ID: 10743
Validator:
Locke Bowden, P.E. #49704
9450 Alysbury Place
Montgomery, AL 36117
Contents:
Evaluation Report Pages 1 – 5
10/05/2017
FLORIDA PRODUCT APPROVAL
0.032” ALUMINUM GULFLOKTM 16” WIDE ROOF PANEL OVER 15/32” PLYWOOD
FLORIDA PRODUCT APPROVAL NO. 11651.2 R3
GULFLOKTM
COLOR STANDARDS
Light Blue:
CMYK: 60, 7, 0, 0
PMS: 2915 (This is the closest match to the CMYK colors)
Dark Blue:
CMYK: 100,100,30,20
PMS: 2757 (This is the closest match to the CMYK colors)
Grey
CMYK: 35,15,10,30
PMS: 7544 (This is the closest match to the CMYK colors)
3rd Blue
CMYK: 85,45,15,15
PMS: XXXX (This is the closest match to the CMYK colors)
SPOT COLORS
PRODUCT EVALUATION REPORT
Approve
ENERGY
TAX CREDIT
Approve
ENERGY
TAX CREDIT
KUHN ENGINEERING, LLC
1200 CLINT MOORE RD. SUITE 9, BOCA RATON, FL 33487 • FL COA #30464
FL# 11651.2 R3 • OCTOBER 5, 2017
Compliance Statement: The product as described in this report has demonstrated compliance with the
Florida Building Code 2017, Sections 1504.3.2.
Product Description:GulfLok™, 7/8” Nailstrip Roof Panel, Minimum 0.028” Aluminum, Maximum 16”
Coverage, Roof panel restrained with fasteners into minimum 15/32” plywood
decking. Non Structural application.
Panel Material/Standards: Material: Minimum 0.028” Aluminum 3105 H-24 conforming to Florida Building
Code 2017 Section 1507.4.3.
Paint Finish Optional
Corrosion Resistance: Panel Material shall comply with Florida Building
Code 2017, Section 1507.4.3.
Panel Dimension(s): Thickness: 0.028” Minimum
Width: 16” Coverage Maximum
Female Rib: 7/8” Tall
Male Rib: 3/4” Tall Rib with Slotted Strip
Panel Seam: Snap Lock
Panel Seam Sealant:
Panel Fastener:
Substrate Description:
Titebond Weathermaster Metal Roof Sealant apply 1/4”-5/16” diameter continuous
bead on the male rib for Assembly B only.
Through Panel Slot: (1) #10-12x1” Pancake Type A
1/4” Minimum Penetration through Plywood.
Corrosion Resistance: Per Florida Building Code 2017, Section 1506.6, 1507.4.4
Minimum 15/32” thick, APA Rated plywood over supports at maximum 24” O.C.
Design of plywood and plywood supports are outside the scope of this
evaluation. Must be designed in accordance w/ Florida Building Code 2017.
Design Uplift Pressures:Table “A”
Panel Assembly A B
Maximum Total Uplift Design Pressure 52.5 psf 116.0 psf
Panel Slot Fastener Spacing 5 3/16” O.C.5 3/16” O.C.
Sealant on Male Rib NOT USED USED
*Design Pressure includes a Safety Factor = 2.0.
FLORIDA PRODUCT APPROVAL
0.032” ALUMINUM GULFLOKTM 16” WIDE ROOF PANEL OVER 15/32” PLYWOOD
FLORIDA PRODUCT APPROVAL NO. 11651.2 R3
GULFLOKTM
COLOR STANDARDS
Light Blue:
CMYK: 60, 7, 0, 0
PMS: 2915 (This is the closest match to the CMYK colors)
Dark Blue:
CMYK: 100,100,30,20
PMS: 2757 (This is the closest match to the CMYK colors)
Grey
CMYK: 35,15,10,30
PMS: 7544 (This is the closest match to the CMYK colors)
3rd Blue
CMYK: 85,45,15,15
PMS: XXXX (This is the closest match to the CMYK colors)
SPOT COLORS
PRODUCT EVALUATION REPORT
Approve
ENERGY
TAX CREDIT
Approve
ENERGY
TAX CREDIT
KUHN ENGINEERING, LLC
1200 CLINT MOORE RD. SUITE 9, BOCA RATON, FL 33487 • FL COA #30464
FL# 11651.2 R3 • OCTOBER 5, 2017
Code Compliance: The product described herein has demonstrated compliance with the
Florida Building Code 2017, Sections 1504.3.2.
Evaluation Report Scope: The product evaluation is limited to compliance with the structural wind load
requirements of the Florida Building Code 2017, as relates to Rule 61G20-3.
Performance Standards: The product described herein has demonstrated compliance with:
•UL 580-06 - Test for Uplift Resistance of Roof Assemblies
• UL 1897-12 - Uplift Test for Roof Covering Systems.
Reference Data: 1.UL 580-94 / 1897-98 Uplift Test
Force Engineering & Testing, Inc. (FBC Organization # TST-5328)
Report No. 117-0337T-10 Dated 03/07/2011
2.Certificate of Independence
By Dan Kuhn, P.E. (FL# 75519) @ Kuhn Engineering, LLC
(FBC Organization # ANE ID: 10743)
Test Standard Equivalence: 1.The UL 580-94 test standard is equivalent to the UL 580-06 test standard.
2.The UL 1897-98 test standard is equivalent to the UL 1897-12 test
standard.
Quality Assurance Entity:
Minimum Slope Range:
Installation:
Underlayment:
The manufacturer has established compliance of roof panel products in
accordance with the Florida Building Code and Rule 61G20-3.005(3) for
manufacturing under a quality assurance program audited by an approved quality
assurance entity.
Minimum Slope shall comply with Florida Building Code 2017, including
Section 1507.4.2 and in accordance with Manufacturers recommendations.
Install per Manufacturer’s recommended details.
Shall comply with Florida Building Code 2017 section 1507.1.1.
Roof Panel Fire Classification: Fire classification is not part of this acceptance.
Shear Diaphragm: Shear Diaphragm values are outside the scope of this report.
FLORIDA PRODUCT APPROVAL
0.032” ALUMINUM GULFLOKTM 16” WIDE ROOF PANEL OVER 15/32” PLYWOOD
FLORIDA PRODUCT APPROVAL NO. 11651.2 R3
GULFLOKTM
COLOR STANDARDS
Light Blue:
CMYK: 60, 7, 0, 0
PMS: 2915 (This is the closest match to the CMYK colors)
Dark Blue:
CMYK: 100,100,30,20
PMS: 2757 (This is the closest match to the CMYK colors)
Grey
CMYK: 35,15,10,30
PMS: 7544 (This is the closest match to the CMYK colors)
3rd Blue
CMYK: 85,45,15,15
PMS: XXXX (This is the closest match to the CMYK colors)
SPOT COLORS
PRODUCT EVALUATION REPORT
Approve
ENERGY
TAX CREDIT
Approve
ENERGY
TAX CREDIT
KUHN ENGINEERING, LLC
1200 CLINT MOORE RD. SUITE 9, BOCA RATON, FL 33487 • FL COA #30464
FL# 11651.2 R3 • OCTOBER 5, 2017
Design Procedure: For roofs within the parameters listed on the load table, fastening pattern must
at a minimum meet those listed for the applicable wind zone. For all roofs outside
the parameters listed on the load table, design wind loads shall be determined
for each project in accordance with FBC 2017 Section 1609 or ASCE 7-10
using allowable stress design. The maximum fastener spacing listed herein shall
not be exceeded. This evaluation report is not applicable in High Velocity
Hurricane Zone. Refer to current NOA or HVHZ evaluation report for use of this
product in High Velocity Hurricane Zone.
0.032” ALUMINUM GULFLOKTM 16” WIDE ROOF PANEL OVER 15/32” PLYWOOD
FLORIDA PRODUCT APPROVAL NO. 11651.2 R3
GULFLOKTM
COLOR STANDARDS
Light Blue:
CMYK: 60, 7, 0, 0
PMS: 2915 (This is the closest match to the CMYK colors)
Dark Blue:
CMYK: 100,100,30,20
PMS: 2757 (This is the closest match to the CMYK colors)
Grey
CMYK: 35,15,10,30
PMS: 7544 (This is the closest match to the CMYK colors)
3rd Blue
CMYK: 85,45,15,15
PMS: XXXX (This is the closest match to the CMYK colors)
SPOT COLORS
PRODUCT EVALUATION REPORT
Approve
ENERGY
TAX CREDIT
Approve
ENERGY
TAX CREDIT
KUHN ENGINEERING, LLC
1200 CLINT MOORE RD. SUITE 9, BOCA RATON, FL 33487 • FL COA #30464
FL# 11651.2 R3 • OCTOBER 5, 2017
ENGINEER LOAD TABLE: 0.032” Aluminum GulfLok™ 16” Wide Roof Panel over 15/32” Plywood
Buildings having a Roof Mean Height ≤ 20’-0”; Roof Slope: 2”/12” - 12”/12” Gable or Hip Roof; Wind Speeds 120-
180mph, Exposure C, Risk Category II, Enclosed Building, based on Florida Building Code 2017.
WIIND
SPEED
FASTENER
(MIN. 1/4”
Penetration)
SUBSTRATE
(MIN. 15/32”)
120 130 140 150 160 170 180
ON CENTER
SPACING
ON CENTER
SPACING
ON CENTER
SPACING
ON CENTER
SPACING
ON CENTER
SPACING
ON CENTER
SPACING
ON CENTER
SPACING
ZONE 1 #10-12x1”CDX PLYWOOD Assembly A Assembly A Assembly A Assembly A Assembly A Assembly A Assembly A
ZONE 2 #10-12x1”CDX PLYWOOD Assembly A Assembly A Assembly A Assembly A Assembly B Assembly B Assembly B
ZONE 3 #10-12x1”CDX PLYWOOD Assembly A Assembly B Assembly B Assembly B Assembly B Assembly B Assembly B
1.) PANEL DESCRIPTION: GULFLOK™, MIN. 0.028” ALUMINUM, 7/8” RIB, 16” MAXIMUM COVERAGE, SNAP SEAM.
2.) PANEL FASTENER: THROUGH PANEL SLOT: (1) #10-12X1”PANCAKE TYPE A, 1/4” MIN. PENETRATION THROUGH PLYWOOD.
3.) MAXIMUM ALLOWABLE PANEL UPLIFT PRESSURE: ASSEMBLY A: 52.5 PSF PANEL FASTENERS AT 51/8” O.C.; ASSEMBLY B:116.0 PSF
PANEL FASTENERS AT 51/8” O.C. WITH 1/4”-5/16” DIAMETER CONTINUOUS BEAD OF TITEBOND WEATHERMASTER METAL ROOF
SEALANT ON THE MALE RIB. PRESSURE BASED ON UL 580/UL 1897 TESTING BY FORCE ENGINEERING & TESTING.
4.) PLYWOOD DECKING: MIN. 15/32” THICK, APA RATED PLYWOOD, GRADE C-D. MUST BE DESIGNED IN ACCORDANCE WITH FLORIDA
BUILDING CODE 2017.
5.) LOAD TABLE BASED ON WIND PRESSURES CALCULATED PER ASCE 7-10 (KD = 0.85) MULTIPLIED BY 0.6 PER FLORIDA BUILDING
CODE 2017.
ENGINEER’S LOAD TABLE SPEC
Note: Dimension (a) is defined as 10% of the minimum width of the building or
40% of the mean height of the roof, whichever is smaller, however, (a) cannot be
less than either 4% of the minimum width of the building or 3 feet.