HomeMy WebLinkAboutAPPROVED, Plantation Tile
BOR18003.1 FL28328-R1 Page 1 of 12
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
EVALUATION REPORT FLORIDA BUILDING CODE 6TH EDITION (2017)
Manufacturer: BORAL ROOFING LLC Issued February 19, 2019
7575 Irvine Center Drive
Irvine, CA 92618
(800) 669-8453
www.boralamerica.com
Manufacturing Plants: Lake Wales, FL
Okeechobee, FL
Quality Assurance: PRI Construction Materials Technologies (QUA9110)
SCOPE
Category: Roofing
Subcategory: Roofing Tiles
Code Sections: 1507.3.5, 1507.3.7, 1523.6.5, 1523.6.5.2, 1523.6.5.2.2, 1523.6.5.2.3
Properties: Physical Properties, Attachment Requirements, Wind Driven Rain, Static Uplift
Resistance
REFERENCES
Entity Report No. Standard Year
American Test Lab of South Florida Inc (TST3782) RT0201.01-19 TAS 112
ASTM C 1492
1995
2003(2009)
American Test Lab of South Florida Inc (TST3782) RT0130.01-14 TAS 112
ASTM C 1492
1995
2003(2009)
American Test Lab of South Florida Inc (TST3782) RT0426.01-14 TAS 112
ASTM C 1492
1995
2003(2009)
American Test Lab of South Florida Inc (TST3782) RT0615.02-11 TAS 112
ASTM C 1492
1995
2003(2009)
American Test Lab of South Florida Inc (TST3782) RT0615.03-11 TAS 112
ASTM C 1492
1995
2003(2009)
American Test Lab of South Florida Inc (TST3782) RT0615.04-11 TAS 112
ASTM C 1492
1995
2003(2009)
American Test Lab of South Florida Inc (TST3782) RT0617.02-16 TAS 112
ASTM C 1492
1995
2003(2009)
American Test Lab of South Florida Inc (TST3782) RT0617.03-16 TAS 112
ASTM C 1492
1995
2003(2009)
American Test Lab of South Florida Inc (TST3782) RT0617.04-16 TAS 112
ASTM C 1492
1995
2003(2009)
American Test Lab of South Florida Inc (TST3782) RT0623.04-14 TAS 112
ASTM C 1492
1995
2003(2009)
American Test Lab of South Florida Inc (TST3782) RT0624.04-14 TAS 112
ASTM C 1492
1995
2003(2009)
American Test Lab of South Florida Inc (TST3782) RT0624.05-14 TAS 112
ASTM C 1492
1995
2003(2009)
American Test Lab of South Florida Inc (TST3782) RT1210.02-15 TAS 112
ASTM C 1492
1995
2003(2009)
American Test Lab of South Florida Inc (TST3782) RT1210.03-15 TAS 112
ASTM C 1492
1995
2003(2009)
Miami-Dade BCCO (CER1592) 14-0408.06 FBC (HVHZ) 2017
Miami-Dade BCCO (CER1592) 14-0416.12 FBC (HVHZ) 2017
Miami-Dade BCCO (CER1592) 15-0721.04 FBC (HVHZ) 2017
Miami-Dade BCCO (CER1592) 16-0112.07 FBC (HVHZ) 2017
Miami-Dade BCCO (CER1592) 16-0112.08 FBC (HVHZ) 2017
Miami-Dade BCCO (CER1592) 18-0509.15 FBC (HVHZ) 2017
Miami-Dade BCCO (CER1592) 18-0509.16 FBC (HVHZ) 2017
Miami-Dade BCCO (CER1592) 18-0509.17 FBC (HVHZ) 2017
BOR18003.1 FL28328-R1 Page 2 of 12
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
BORAL ROOFING LLC
Concrete Roof Tiles
Entity Report No. Standard Year
Tile Roof Institute Membership Confirmation TAS 100
TAS 101
TAS 102 & 102(A)
1995
1995
1995
BOR18003.1 FL28328-R1 Page 3 of 12
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
BORAL ROOFING LLC
Concrete Roof Tiles
PRODUCT DESCRIPTION
Bermuda (Okeechobee)
Profile/Description: ASTM C 1492, TAS 112 Type 3a, flat profile, interlocking, class III concrete roof tile
Allowable Applications: For mechanically fastened (direct deck or batten), mortar set or adhesive set applications
Dimensions:
Figure 1. Bermuda
Plantation (Okeechobee)
Profile/Description: ASTM C 1492, TAS 112 Type 3a, flat profile, interlocking, class III concrete roof tile
Allowable Applications: For mechanically fastened (direct deck or batten), mortar set or adhesive set applications
Dimensions: 16-
Figure 2. Plantation
BOR18003.1 FL28328-R1 Page 4 of 12
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
BORAL ROOFING LLC
Concrete Roof Tiles
Saxony 900 Slate, Shake and Split Shake (Lake Wales and Okeechobee)
Profile/Description: ASTM C 1492, TAS 112 Type 3a, flat profile, interlocking, class III concrete roof tile
Allowable Applications: For mechanically fastened (direct deck or batten), mortar set or adhesive set applications
Dimensions: 17 13 1-5/32 (Slate) or 1-9/plit Shake)
Figure 3. Saxony 900 Slate
Figure 4. Saxony 900 Shake
Figure 5. Saxony 900 Split Shake
BOR18003.1 FL28328-R1 Page 5 of 12
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
BORAL ROOFING LLC
Concrete Roof Tiles
Estate (Okeechobee)
Profile/Description: ASTM C 1492, TAS 112 Type 1b, low profile, interlocking, class III concrete roof tile
Allowable Applications: For mechanically fastened (direct deck or batten), mortar set or adhesive set applications
Dimensions: 16-
Figure 6. Estate
Villa 900 (Lake Wales)
Profile/Description: ASTM C 1492, TAS 112 Type 1b, low profile, interlocking, class III concrete roof tile
Allowable Applications: For mechanically fastened (direct deck or batten), mortar set or adhesive set applications
Dimensions: -
Figure 7. Villa 900
BOR18003.1 FL28328-R1 Page 6 of 12
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
BORAL ROOFING LLC
Concrete Roof Tiles
Barcelona 900 (Lake Wales)
Profile/Description: ASTM C 1492, TAS 112 Type 1a, high profile, interlocking, class III, concrete
roof tile
Allowable Applications: For mechanically fastened (direct deck or batten), mortar set or adhesive set applications
Dimensions: 17 3-5/8
Figure 8. Barcelona 900
Galena (Okeechobee)
Profile/Description: ASTM C 1492, TAS 112 Type 2a, high profile, concrete
roof tile
Allowable Applications: For mechanically fastened (direct deck), mortar set or adhesive set applications
Dimensions: 17 10 2.7
Figure 9
BOR18003.1 FL28328-R1 Page 7 of 12
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
BORAL ROOFING LLC
Concrete Roof Tiles
(Lake Wales)
Profile/Description: ASTM C 1492, TAS 112 Type 2a, high profile, interlocking, class III concrete
roof tile
Allowable Applications: For mechanically fastened (direct deck or batten), mortar set or adhesive set applications
Dimensions: 17 9-3/4 2-27/32
Figure 10
APPLICATION METHOD
Installation
Slope:
Limited to slopes 3:12 or greater in the HVHZ; Outside the HVHZ, shall be in accordance
with the recommendations of the FRSA/TRI Florida High Wind Concrete and Clay Roof
Tile Installation Manual, Fifth Edition Revised or RAS 118, RAS 119, or RAS 120, as
applicable.
Roof Deck:
Solid or closely fitted min. 15/32-inch plywood sheathing for new and existing construction
at max. 24 in. span; In the HVHZ, new construction shall be min. 19/32 in. plywood at max.
24 in. span; Designed by others in accordance with FBC requirements.
Underlayment: Installed in accordance with FBC requirements. In the HVHZ, the minimum underlayment
shall be installed as described in RAS 118, RAS 119, or RAS 120, as applicable.
BOR18003.1 FL28328-R1 Page 8 of 12
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
BORAL ROOFING LLC
Concrete Roof Tiles
Data for Attachment Calculations for Direct to Deck Applications
Roof Tile
Nominal Weight (W) and
Dimensions (l x w)
Aerodynamic
Multipliers
(ft3)
Restoring Moments due to Gravity - Mg (ft-lbf)
Direct Deck
W (lbf) l (ft) w (ft) Direct Deck
Application >
Bermuda 9.7 1.33 0.833 0.205 6.97 6.86 6.71 6.54 6.35
Plantation 11.6 1.375 1.08 0.289 7.79 7.67 7.52 7.32 7.04
Saxony 900 10.9 1.417 1.08 0.315 7.62 7.5 7.34 7.16 6.95
Estate 10.0 1.375 1.08 0.289 6.74 6.64 6.50 6.33 6.14
Villa 900 10.9 1.42 1.08 0.315 7.62 7.50 7.34 7.15 6.95
Barcelona
900 11.5 1.417 1.08 0.301 7.00 6.90 6.76 6.60 6.42
Galena
8.5 1.42 0.833 0.235 6.13 6.03 5.89 5.74 5.57
Nuevo 8.95 1.417 0.8125 0.233 5.93 5.83 5.70 5.56 5.39
Data for Attachment Calculations for Batten Applications
Roof Tile
Nominal Weight (W) and
Dimensions (l x w)
Aerodynamic
Multipliers 3)
Restoring Moments due to Gravity - Mg (ft-lbf)
Direct Deck
W (lbf) l (ft) w (ft) Batten
Application >
Bermuda 9.7 1.33 0.833 0.189 6.53 6.43 6.29 6.14 5.97
Plantation 11.6 1.375 1.08 0.267 6.85 6.75 6.61 6.44 6.26
Saxony 900 10.9 1.417 1.08 0.291 - 6.61 6.48 6.31 6.13
Estate 10.0 1.375 1.08 0.267 5.91 5.82 5.70 5.56 5.40
Villa 900 10.9 1.42 1.08 0.291 - 6.56 6.42 6.26 6.08
Barcelona
900 11.5 1.417 1.08 0.286 6.19 6.19 6.06 5.92 5.76
Nuevo 8.95 1.417 0.8125 0.215 5.30 5.21 5.09 4.96 4.82
BOR18003.1 FL28328-R1 Page 9 of 12
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
BORAL ROOFING LLC
Concrete Roof Tiles
Attachment Resistance Expressed as a Moment for Mechanically Fastened Applications
Roof Tile
Tile Fastener Mf (ft-lbf)
Type Count Size Shank Clip Direct Deck
plywood)
Direct Deck
plywood)
Battens
Bermuda,
Plantation or
Saxony 900
Nail 2 10d Ring N/A 30.9 38.1 17.2
Nail 1 10d Smooth
or Screw N/A 7.3 9.8 4.9
Nail 2 10d Smooth
or Screw N/A 14.0 18.8 7.4
Screw 1 #8 N/A N/A 30.8 30.8 18.2
Screw 2 #8 N/A N/A 51.7 51.7 24.4
Nail 1 10d Smooth
or Screw Field 24.3 24.3 24.2
Nail 1 10d Smooth
or Screw Eave 19.0 19.0 22.1
Nail 2 10d Smooth
or Screw Field 35.5 35.5 34.8
Nail 2 10d Smooth
or Screw Eave 31.9 31.9 32.2
Nail1 2 10d Ring N/A 50.3 65.5 48.3
2,
Villa 900
Nail 2 10d Ring N/A 27.8 37.4 28.8
Nail 1 10d Smooth
or Screw N/A 8.8 11.8 4.1
Nail 2 10d Smooth
or Screw N/A 16.4 21.9 7.1
Screw 1 #8 N/A N/A 25.8 25.8 22.9
Screw 2 #8 N/A N/A 47.1 47.1 49.1
Nail 1 10d Smooth
or Screw Field 24.3 24.3 24.2
Nail 1 10d Smooth
or Screw Eave 19.0 19.0 22.1
Nail 2 10d Smooth
or Screw Field 35.5 35.5 34.8
Nail 2 10d Smooth
or Screw Eave 31.9 31.9 32.2
Nail1 2 10d Ring N/A 43.0 67.5 50.9
Continued on following page
BOR18003.1 FL28328-R1 Page 10 of 12
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
BORAL ROOFING LLC
Concrete Roof Tiles
Attachment Resistance Expressed as a Moment for Mechanically Fastened Applications
Roof Tile
Tile Fastener Mf (ft-lbf)
Type Count Size Shank Clip Direct Deck
plywood)
Direct Deck
plywood)
Battens
Barcelona 900,
Galena3 or
Nuevo
Nail 2 10d Ring N/A 28.6 41.2 19.4
Nail 1 10d Smooth
or Screw N/A 5.1 6.8 2.8
Nail 2 10d Smooth
or Screw N/A 6.9 9.2 7.3
Screw 1 #8 N/A N/A 20.7 20.7 18.1
Screw 2 #8 N/A N/A 43.2 43.2 29.8
Nail 1 10d Smooth
or Screw Field 23.1 23.1 19.0
Nail 1 10d Smooth
or Screw Eave 29.3 29.3 24.0
Nail 2 10d Smooth
or Screw Field 27.6 27.6 38.6
Nail 2 10d Smooth
or Screw Eave 38.1 38.1 41.8
Nail1 2 10d Ring N/A 33.1 48.1 45.2
Notes: 1) Not for Saxony 900, Villa 900 or Barcelona 900. located a min. 2-
from head of tile.
2) When using only one fastener, use the hole that is approximately 4- interlocking edge.
3) Direct Deck applications only.
Attachment Resistance Expressed as a Moment for Adhesive or Mortar Set
Roof Tile Adhesive Product Approval 1 Paddy
Count Average Paddy
Weight (grams) Mf (ft-lbf)
Bermuda,
Planation and
Saxony 900
Dow NOA 16-0222.01 2 13.9 31.3
ICP Adhesives Polyset AH-160 NOA 17-0322.03
2 8 31.3
1 24 40.4
1 45 118.9
Saxony 900 -Component NOA 17-0829.12
2 8 59.0
1 24 45
1 45 93
Premix Marbletite, Inc. TILE-TITE NOA 17-1016.07 N/A N/A 43.9
Villa 900
NOA 16-0222.01 2 11.4 26.1
ICP Adhesives Polyset AH-160 NOA 17-0322.03
2 8 26.1
1 24 45.5
1 54 86.61
Premix Marbletite, Inc. TILE-TITE NOA 17-1016.07 N/A N/A 20.6
Villa 900 -Component NOA 17-0829.12
2 8 55
1 30 40
1 60 70
BOR18003.1 FL28328-R1 Page 11 of 12
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
BORAL ROOFING LLC
Concrete Roof Tiles
Attachment Resistance Expressed as a Moment for Adhesive or Mortar Set
Roof Tile Adhesive Product Approval 1 Paddy
Count Average Paddy
Weight (grams) Mf (ft-lbf)
Barcelona 900,
Galena Spanish
NOA 16-0222.01 2 10.7 29.3
ICP Adhesives Polyset AH-160 NOA 17-0322.03
2 8 29.3
1 24 38.7
1 63 66.5
Premix Marbletite, Inc. TILE-TITE NOA 17-1016.07 N/A N/A 24.5
Barcelona 900 -Component NOA 17-0829.12
2 8 66.0
1 30 63
1 60 82
Notes: 1)
LABELING
1)
OR
BOR18003.1 FL28328-R1 Page 12 of 12
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
BORAL ROOFING LLC
Concrete Roof Tiles
LIMITATIONS
1) Fire Classification is not within the scope of this evaluation.
2) Installation of the evaluated products shall comply with FBC Section 1507.3, FRSA/TRI Florida High Wind
Concrete and Clay Roof Tile Installation Manual, Fifth Edition Revised
application instructions. Installations in the HVHZ shall comply with RAS 118, RAS119 and RAS 120.
3)All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61G20-3.
4)All product listed in this shall tested quarterly in accordance with TAS 112 Appendix A.
5)Installation of the evaluated products shall be limited to projects in areas subjected to weathering indices of
50 or greater as illustrated in ASTM C 1492-03, figure 1 (see below).
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R Priest P.E. have demonstrated compliance with the Florida Building
Code, 6th Edition (2017) as evidenced in the referenced documents submitted by the named manufacturer.
Zachary R. Priest, P.E.
Florida Registration No. 74021
Organization No. ANE9641
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
END OF REPORT