Loading...
HomeMy WebLinkAboutProject InformationWrightoW Project Summary o; Entire House By. QUICK CALCS, INC. 317 ST. LUCIE LN., Fr. PIERCE, FL 34946 Ptnre:772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information For. THE GRAND-CARLTON.IMPACT WYNNE DEVELOPMc-ENT, F.T. PIERCE, FL Notes: Design Information Weather:. Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 °F Inside.db 75 OF Design TD 28 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 61 grAb Heating Summary Sensible Cooling Equipment Load Sizing Structure 17848 Btuh Structure 17520 Btuh Ducts 5654 Btuh Duds 8536 Btuh Central vent (O cim) 0 Btuh Central vent.(0 cfm) 0 Btuh (gone) 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 23503 Btuh Use manufacturer's data n Rate/swing multiplier Equipmefilsensible.load 0.95 Infiltration 24753 Btuh Method Simplified Latent Cooling Equipment.Load Sizing. Construction quality Average Fireplaces 0 Structure 3203 Btuh Duds 2318 Btuh Central vent.(O cfm) 0 Btuh Heatingg Cooling (none).. Area (f !2) 1446 1446 Equipment latent load 5521 Btuh Volume (f?) 12511 12511 Air changes/hour OA5 0.23 Equipment Total Load (Sen+Lat) 30274 Btuh Equiv AVF (crm) 94 48 Req. total capacity at 0.70 SHR 2.9 ton Heating Equipment Summary Cooling. Equipment Summary Make Carrier Trade CARRIERAIR CONDITIONING Model 25HBC536KO30 AHRI ref .7914585 Efficiency Heating input Heating output Temperature rise Actual airflow Air flow factor Static pressure Space thermostat Capacity balance point = 32 'F 8.5 HSPF 34600 Btuh @ 470F 1160cfrn 0.049 dm/Btuh 0.50 in H2O Backup: Input =.7 kW,. Output=.23009 Btuh,100 AFUE Make Carrier Trade CARRIERAIR CONDITIONING Cond 25HBC536KO30 Coil FX4DN(BF)037 AHRI ref 79145.85 . Efficiency 12.0 EER,15 SEER Sensible cooling 24360 Btuh Latent cooling 10440 Btuh Total cooling . 34800 Btuh Actual airflow 1160 cfm Airflowfactor 0.045 cfm/Btuh Static pressure 0.50 in H2O Load sensible heat ratio 0:83 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. 2020-Jan-081620:47 Right-SLitepUriversal 20l9 l9.O.O7 RSU08101 Page 1 igWoftWAC1THEGRAND CARLTON-1446-1MPACT.np Calc=MJ8 FrontDoorfaces: N -� wlriglatsof#� Right-M Worksheet Job: Entire House Date: QUICK CALCS, INC. 317 ST. LUCIE LN., Fr.. PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House BEDROOM 2 Exposed wall 1562ft 49.0 it 3 Room height 8.7 it d 8.0 It heaftol, 4 5 . Room dimensions Room area 1445.5 ftz 1.0 x 297D ft .297.0 T Ty Construction Ll-value Or HTM Area (F) Load Area Load number (BtuhAft{°F) (Btuh/IF) or perimeter (ft) (Btuh) or perimeter (it) (Bhuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 13A-0ocs 0143 n 4.00 " 2.55 563 465 � 1862 1184 72 72 "" 288 183. �G ;AA5-2om 13AAocs 0.770 0.143 " n' a . " 21.56 4.00 19.31. 2.55 38 128 0 83 - .815 333 ° ' . 730 212 . .... 0 0 0 0 -0 0. 0 0 11 IA-clom 11D0 1270 0.390 a a 35.56 10.92 8729 11.31 24 21 2 21 848 229 2082 238 0 0 0 0 0 0 0 0 D W _ Vr-G 13A-0ois. - 13A.4 cs 6.143 0.143 -se. s 4.00 4.00 `' 2.55 2.55 .34 360 34 353 136. 1414 86' 899 " 0 216 " 0 216 .0 865 0 550 ` G 1A-c1am 13A-2tocs I 1270 . 0143 1270 s " w ' w . 35.56 4.00 35.56 34.77 , 2.55 5521 7 310 . " 32 7 231 ": 2 247 949 :.. 1140 241 603 1770 0 :104 . 32 0 •72 .2 0 288 1140 0 183 1770 c--G P A5-2om 12C-Osw . 0.770 0.091 w - 21-.56 2.55 1931 128 41 192 41 192 680 489 -788 246 ; 6 0 0 0 0 0 0 0 C " 16A-30rnd 0.032 - 0.90 2.32 1446 1446 1295 . 3354 297 297 266 689 F 22A tol 0.989 - 27.69 0.00 1446 156 4325 0 297 49 1357 0 6 c) AED excursion 918 627 Envelope loss/gain 14961 13349 4204 4003 12 a) Infiltration 2887 791 848 232 b) Roomventilation 0 0 0 0 13 Internal gains. Occupants@ 230 6 1380 3 690 Applianoes/other 20001 0 Subtotal (lines 6 to 13) 17848 17520 5053 4925 Less external load 0 0 0 0 14 Lesstransfer Redistribution Subtotal 0 0 17848 0 0 17520 0 0 5053 0 0 4925 15 Dudloads 1 32% 49% 5654 8536 32% 49% 1601 2400 Total room load Air required (dim) 23503 1160 26056 1160 1 1 6653 328 7325 326 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. y 'a'I'a" vsrriglai�sotlt^ 2020-Jan-081620:47 RightSute®Uriversal 201919.0.07 RSU08101 Page l igttsoftHVAOTHEGRAND CARLTON-1446WPACT.np Calc=MJ8.Front Door faces: N -FF wrigh soft° RighW@ Worksheet Joe Entire House By. By. QUICK CALCS, INC. 317 ST. LUCIE W., FT. PIERCE, FL 34946 Phore:772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name WIC IQTCHEN 2 Exposed wall O ft O ft 3 Room height 8.0 it heat/000l 8.0 it heaftol 4 Room dimensions 6.0 x 9.0 ft .. 1.0 x 172D It 5 Room area 54.0 W 172.0 W Ty Construction U-value Or HTM Area Load s Load number.(Bhrh/it=--°F) .(BtuW) or perimeter r (ft) A. h) or perimeter r (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W -G` 13A 0.143 n 4.00 2.55. 0' 0 = 0: 0 -0 0- 0 U 4A5 2om". _ 13A4o s . 0.770 0.143 W a ' 21M 4.00 " 19.31 2.65 _ . A 0 . - 0 0 : " 0 0 "" . 0 0 0 0 .0 0 0 0 : ' " 0 0 V�/ �G 11 IA-c'Icm 11DO 1270 0.390 a a 35.56 10.92 8729 11.31 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 L-D W; ' . ,9$A-4ocs_ 13A-4ocs 0.143 0.143 'se. s. .4.00 4.00 2.55 2.55 :. 0 0 , 0 0 . 0 0 . 0 0 . 0 0 0 0 0 0 . 0 0 -G 1A-c1om 1270 s 35.56 34.77 0 0 0 0 0 0 0 0 G I'M466s "-: 1A-clom .'. 0143 1270 w w 400 35.56. 2.55 552-1 0 .0 0 ': 0 0 0 0 % : 0 0 . 0 0 0 :0 0 0 0 '4A5 tom : . 0.770 w 21.56' 19.31 0 0. 6 .0 0 0 0 0 P 12C-Osw 0.091 2.55 1.28 0 0 0 0 64 64 163 82 C 16A-aOmd 0.032 - 0.90 2.32 54 54 48. 125 172 ' 172 154 399 F 22A tQl 0.989 27.69 0.00 54 0 0 0 172 0 0 0 6 c) AED excursion -9 -176 Envelope losstgain 48 117 317 311 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 1 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancesrother 01 2000 Subtotal (lines 6 to 13) 48 117 317 2311 Less extemalload 0 0 0 0 Lesstransier Redistribution 0 0 0 0 0 0 0 0 14 Subtotal 48 117 317 2311 15 Dud loads 32% 49% 15 57 32% 49%1 100 1126 Total room load Air required (dm) 1 64 3 174 8 416 21 3437 153 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wragiblsolt' 2020-Jarr081620:47 Rlgk-Sulte®Udversal 201919.0.07 RSU08101 igitsoftHVAMTHEGRAND CARLTON-1446-IMPACT.np Calc=MJ8 FrontDoorfaces: N Page 2 wdghft0fr Right-J® Worksheet Job: Entire House Date: QUICK CALCS, INC. sy 317 ST. LUCIE LN., Fr.. PIERCE, FL 34946 PFnre:772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@!AOL.COM 1 Room name BATH BEDROOM2 2 Exposed wall 5.0 It 342 ft 3 Room height 8A ft heaV000l 8.0 ft heaftol 4 5 Room dimensions Room area 9.0 x . 5.0 . ft 45D IF 1.0 x 203.5 ft 203.5 ft2 Ty Construclion U-value 'Or HTM Area s Load number (Bhd2-°F) (BhV) or perimeter r (ft) (Btuh) or perimeter (ft) (BWh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 G v� i4A5.2om' 13A1tacs 0.770 0143 n . n e 4.00 21:56: 4.00 2.55 ' .:19:31 2.55 40 ' 0 6 40 0 0 160 0 0 . 102 0' 0 ", 128 : 0 80 ., 128 0 56 513 0. 225 `326. 0 143 11 F-G ���DDDD 1Ac1om 11DO 1270 0.390 a a 35.56 10.92 8729 11.31 0 0 - 0 0 0 0 0 0 24 0 2 0 848 0 2082 0 W.- : y✓ �--G 13AAocs. 13AAois 0.143 0.143 - -se s . 4.00 4.00 2.55 2.55 :. 0 0 0, 0 0, 0 0 0 34 32 - 34 32 136 128 " -86 81 1Aclom 1270 s 35.56 34.77 0 0 0 0 0 0 0 0, VY G 13A 1A-c1orn - '4A5-26m' 0143 1270' yv . w 4:00 35.56 2:55 5521, 0 .0,: 0 0 0 0 0 0 0 . 0 0 0 - 0 0 0 . 12C-Osv 0.770 0.091 w 21.56 2.55 19.31 128 0 0 0 0 0 0 .0 0 6 0 0 0 0 0 0 0 P C . 16A30md 0.032 - 0.90 2.32 45 45 40 104 . 204 204 182 472 F 22Atol 0.989 - 27.69 0.00 45 5 138 0 204 34 946 0 6 c)AEDexcursion -16 -85 Envelope loss/gain 339 190 2978 3106 12 a) infiltration b) Room ventilation 87 0 24 0 593 0 162 0 13 Internal gains: Ocwpants@ 230 0 0 1 230 Appliancesrother 0 0 Subtotal (lines 6 to 13) 425 214 3571 .. 3498 14 15 Less extemalload Lesstransfer Redistribution Subtotal' Ductloads 32% 49% 0 0 0 425 135 0 0 0 214 104 32% 49% 0 0 0 3571 1131 0 0 0 3498 1704 Total room load Air required (ctm) 560 28 318 14 1 4702 232 5203. 232 Calculations approve d-byACCA to meet all requirements of Manual J 8th Ed. "A ^.` " wraglf6isryof!^ .9C� Riga-Sufe®Uriversal 201919.0.07 RSU08101 2020-Jan-08162OA7 Page 3 igMsoftFNAC1THEGRANDCARLTON-1446:IMPACT.rtp Calc=MJ8 Front Door faces: N + wlidgh%oft Right-J® Worksheet Job: Entire House Date: QUICK CALCS, INC. By 317 ST. LUCIE LN., Fr.. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS ,AOL.COM 1 Room name LAUNDRY GREAT/DINING 2 .Exp sedwall . 6.0 ft 47.0- It 3 Room height 8.0 It heaV000l 9.8 it heatl000l 4 Room dimensions 7.0 x 6D ft 1.0 x 526.0 It 5 Room area 42.0 ftz 526.0 th Ty Construction U-value. Or HTM Area s number. (Btuh/fiZ-°F) (Btuh(F) or perimeter r (ft) (Btuh) or perimeter (ft) (BWh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 �G '13A-4oc_s:, .0.143 " n 4.00 2:5 ' 5 0 - 0 0 -0 255 217 '869 552, 0546m'.. : " ,." ..0.770 h- 2.1'',56. "19:31 : - 0, 0 : 0. 0 - 38 '- : 'A : ' ' 815 ;.. 730 13A-4ocs 0.143 a 4.00 2.55 0 0 0 0 0 0 0 0 lA clom 1270 a 35.56 8729 0 0 0 0 0 0 0 0 11 D 11 DO 0.390 a 10.92 11.31 0 0 0 0 0 0 0 .0 W ::13A4acs, 0.143 -Se 4.00 2.55 0 p 0. p p p. p- p W 13A4ois 0.143 s 4.00 2.55 48 48 192 122 0 0 0 0 �G 1A-clom 1270 s 3556 34.77 0 0 0 0- 0 0 0 0 W. 1U46cs 0.143 >. W. 4:00 2.55 0 0 0 0: 206 ' 165 661 420. 1Ac1om 1270 : w 35:56 55.21 W 0- 0 0 0 .. 0 .0 ;a 0 4A5 tom . 0:776 w 21.56 19.31 0 0 0 0 41 41 880 788 P 12C-Osw 0.091 - 2.55 1.28 56. 56 143 72 0 0 0 0 Z 16A30md 0.032 . `- 6.90 2.32 '42 42 38 '• 97 .526 526 471 "' • & F 22A 1pl 0.989 - 27.69 ODD 42 6 166 0 526 47 1302 0 6 c) AED excursion -22 6W Envelope loss(gain 539 270 4997 4379 12 a) Infiltration 104 28 997 273 b) Roomventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 2 460 Applianoes(other 01 0 Subtotal (lines 6 to 13) 643 298 5994 5112 Less external load 0 b 0 0 Lesstranster 0 0 0. 0. Redistribution 0 0 0 0 14 Subtotal' 643 298 5994 5112 15 DUdloads 32% 49% 204 . 145 32% 49% 1899 2490 Total room load 846 443 7892 7602 Air recluired(cfm) 42 20 390 338 Calculations approved bVACCAto meet all requirements of Manual J 8th Ed. 2020Jarr081620.47 RightSute@) Uriversa1201919.OD7 RSU08101 At ...ightsoff WAC)THE GRAND CARLTON-1446-IMPACT.np Calc= W8 Front Door faces: N Page 4 - wrightSOW Right%l@ Worksheet Job:` Entire House Date: QUICK CALCS, INC. By 317 ST. LUCIE LN., Fr.. PIERCE, FL 34946 Phone: 772466-6799 Fax 772466-6796 Email: QUICKCALCS@AOL.COM 1 Room name FOYER PA BATH 2 .Exposedmall 7.0 ft 8.0 It 3 Room height 8.0 ft heaticool 8.0 ft heaVcool 4 5 Room dimensions Room area. 1.0 x 50.0 It 50.0 T 7.0 x 8.0 ft 56.0 ft Ty Construction number U-value (Btuh/IF--9 Or HTM (Btuh)V) Area iF or perimeter (ft) (Btuh) s (iF) orperimeter (ft) Load (Btuh) Heat Cool Gross NSS Heat Cool Gross N/P/S Heat Cool 6 W 13A.4ocs Mw2om''. 0.143 0.770 0.143 n ... h. a 4:06 21'56' 4.00 2.55 ' . '19.31 2.55 ; .8 0 48 . 8 0 27 32 0 108 : 20 ` •. 0 69 0 . 0 0 0 :. .0 0 .0 0 0 0. 0 0 L13AAocs i 1A-c1om 11DO 1270 0.390 a a 35.56 %92 8729 11.31 0 21 0 21 0 229 0 238 0 0 0 0 0 0 0 0 G D W. Y--G ,13A4ois. 13AAocs 0:143 0.143 se s 4.00 4.00. 2.55 2.55 0 0 0. 0 0 0 0 0 0 64 0 57 0 228 0 145 IA-c1om 13A-4ocs> 1Ao1om "'. 1270 0.143 1270'. s ;, w w 35.56 4.00' 35.56 34.77 2.55 5521 0 U .. 0 0 0 0 0 0 0 0 0 0 7 0 .. 0 7 0 0 247 0 0 241 0 p p 4A5-2om 126-0sw 0.770 0.091 w 21.56 2.55, 19:31' 128 0. 72 0 72 0 183 .0 92 0 0 0 0 0. 0 6 0 C . •16A30md 0.032 - 0.90 2.32 50 50 145 116 56 56 50 130 F 22A fil 0.989 - 27.69 0.00 50 7 194 0 56 8 222 0 6 c) AED excursion -39 -38 Envelope low/gain 792 496 747 478 12 a) Infiltration b) Room ventilation 121 0 33 0 138 0 38 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 p Subtotal (lines 6 to 13) 913 529 885 516 14 Less exdemalload Lesstransteer Redistribution Subtotal 0 0 0 913 0 0 0 529 0 0. 0 885 0 0 0 516 15 Dud loads 32% 49% 289 258 32% 49%1 280 251 Total room load Air required (crm) 1202 59 787 35 1166 58 768 34 Calculations approved WACCA to meet all requirements of Manual J 8th Ed. fft 2020-Jarr081620:47 PJghtSLite@)Uriversal 20l9 l9.0.07 RSU08101 Page 5 ighIsoftHVAC1THEGRAND CARLTON-1446-1MPACTrp Caic=MJ8 Front Door faces N -�' wrightsoft® Duct System Summa' Job. y Date: Entire House By. QUICK CALLS, INC. 317 ST. LUCIE LN., Fr.. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS ole7AOL.COM rroject Intormation _ .. . .. -. .. ..... -: For: THE GRAND CARLTON IMPACT WYNNE DEVELOPMENT, FT. PIERCE, FL External static pressure Pressure losses Available static pressure Supply/ return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0.50 in.H2O 0 in H2O. 0.50 in H2O 0.250/0.250 in H2O 0.285 in/100ft 1160 cfm 1.76 ft Supply Branch Detail Table Cooling 0.50 in H2O 0 in H2O 0.50 in H2O 0.250 / 0.250 in H2O 0.285 in/100ft 1160 cfm. Name Design (Btuh) Htg (cfm) Cig (cfm) Design FR Diam (in) H x W (in) Duct Matt Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH h 560 28 14 0.364 4.0 Ox 0 VIFx 22.4 115.0 st1 BEDROOM2 h 4702 232 232 0.360 7.0 Ox0 VIFx 23.9 115.0 st1 BEDROOWA h 3327 164 163 0.300 6.0 Ox 0 VIFx 31.8 135.0 st2 BEDROOM-B h 3327 164 163 0.285 6.0 Ox 0 VIFx 40.6 135.0 st2 FOYER h 1202 59. 35 0.505 4.0 0x0 VIFx 4.0 95.0 GREAVDINING h 3946 195 169 0.300 7.0 Ox 0 VIFx 31.8 135.0 st2 GREATIDINING-A h 3946 195 169 0.300 7.0 Ox 0 VIFx 31.8 135.0 st2 KrrCHEN C 3437 21 153 0.379 6.0 Ox 0 VIFx 17.0 115.0 st1 LAUNDRY h 846 42 20 0.361 4.0 Ox 0 VIFx 23.3 115.0 st1 M. BAM+A h 768 58 34 0 0 Ox 0 VIFx 0 0 WIC C 174 3 8 0.309 4.0 Ox0 VIFx 27.0 135.0 st2 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (Cfm) FR. 00m) (in) (in) Material Trunk st2 PeakAVF 721 672 0.285 918 12.0 0 x 0 VinIFIX st1 st1 PeakAVF 1043 1091 0.285 1020 14.0 0 x 0 UnlRx Wfightso 2020-Jan-0816:20A8 �r'�- �•r�..�,.RigFE-Sutc�Uriversa1201919.. 007RSU08.101 amrteumdwwsi• Page 1 ...IgHsoftWAC\THEGRAND CARLTON-1446rIMPACT.np Calc=MJ8 FrontDoorfaces: N Return Branch Detail Table Name . Grille Size (in) Htg (ch) Clg (cfm) TEL (ft) Design FR . Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mat Trunk rb1 OxO 1160 1160 0 0 0 0 Ox 0 VIFx wriightsoft- 2020-darr0816:20.48 nwwa�eewci�wn�rmmn� Rlgtt-SLite@)Uriversaf 20l9l9.0.07 RSU08101 Page 2 IghtsoftHVAC1THEGRAND CARLTON-1446=IMPACT.nQ Calc=W8 FrontDoorfaces: N