HomeMy WebLinkAboutBuilding PlansFinish Columns with
/8" thick cut coral
nizhed stucco bands
5/8" thick x 8"w cut
coral finished stucco bands
12
SLOPE
Gulf Coast Supply and MFG 5v Crimp Metal roofing FL 911451.12
26 ga. 5v crimp metal roofing attached to plywood deck using #9 x 1.5"
woocl screws with self sealing washer at 12" o.c. max spacing over ASTM D
(type 2) 30 lb felt underlayment Installed with min. 4 side laos and 6" end
5/8" thick x 8"w cut
coral finished stucco bands
LEFT ELEVATION
SCALE: 1/4" = 1'-0"
Gulf Coast Supply and MFG 5v Crimp Metal roofing FL #11651.12
24 ga. 5v crimp metal roofing attached to plywood deck using #9 x 1.5"
wood screws with self sealing washer at 12" o.c. max spacing over ASTM D
(type 2) 30 lb felt underlayment installed with min. 4 side laps and G" end
laps fastened with corrosion resistant tin caps and with 1.26" ring shank nails
aced 6" o.c. at all laps and two staggered rows 12" o.c. in field. Attach
eck to trusses using attachment detail on this sheet
M
RIG��T ELEVATION
ME
� 5/8" th(ck light textured
stucco on typical concrete
block construction
SCALE: 1/4" = 1'-0"
Product Approval Submittal Affidavit
Opening Schedule Swing Doors, Overhead Doors, Sliding Doors, Windows & Skylights
Opening
Type
NOA/FL
NUMBER
Product
Model #
Manufacturer
Glass
Attachment method
JEST
E rspiration
Date
Design Pressure
of Approved Tests
1.2.3
t4
FL# 239.9
Single Hun
g g
SH-1100A
I a t
PGT
5/IL"
I/4" ddia. tapcons w/ min. 1 3/e" penetration to be
space per product approval. Contractor shall adhere to
min. edge distance& specified in Product approval
+ G5.0/-80.0 PS
A
I6-0330.02
Overhead
Garage Door
Model 824/811
9'-4" max. width
IL'-0" max height
DAB
o ss t.-4,&..."s sn•: `csi•°Wft, iaLWc swum .dread ; sl 00.
h 1.16"sA�s�m�+ltG�� aa�. e.e."m. ie..i�ro& �ets"�
ma. or I.5' ails d&e.a - GC La soak &dhen to prodimt aprwa
rood" V r .n rdlor rex
10-9-21
+ 50.0/-40.0 psi
B
FL# I6L14.1
Fiberglass
Design Pro/
Smooth Pro
Jeld-Wen
Elco 1/4" die. to con with min 1.25" embedment at 3" max
from corners and'1l.5' o.c. max. thereafter in head and jambs.
+ 60.0 PSF
C
FL# 251.4
Sliding Glass
Door
Series 110
SGD
PGT
1" nom
Type "G5A"
1/4" dia. tapcons u/ min. 1 3/4' penetration to be
spaced per product approval. Contractor shall adhere to
min. 2 I/2" edge distances specified in Product approval
+ 60.0 PSF
-
Product
NOA/FL
NUMBER
Model #
Manufacturer
Attachment Method
Tag Esauatioa
Date
Design Pressure
of Approved Tests
Mullions
FLU 261.1
1" x 2 3/4" x .315"
PGT
Install per fastener type and spacings shown in Table IA and IS
in product approval on sheet 5 or 22.
+ 58.0 PSF
Roof
FL# 11651.12
5V Crimp
Metal RoofingGulf
Coast Supply
and manufacturing
2L ea. Sy crimp metal roofing attached to plywood deck using 49 x 1.5"
aood straws with self scaling washer at 12' c.c. max spacing over ASTM D
(type 2) 30 lb felt undarlagmant installed with min. 4 side laps and t' and
laps fastened with corrosion resistant tin caps and with 1.25" ring shank nails
spaced L o.c. at all laps and two staggered rows 12' o.c. in field. Attach
lack to trusses using attachment detail on roof plan
- 108.5 PSF
Siding
Stucco on Block
Soffit
FL# 12198.3
Model T4 12" vented
Vinyl Soffit
Kagcan
Install using 2" x 2" battens at L" o.c. screwed to soffit framing using
#8 x 3" wood screws at each truss. Install soffit to battens using
012" dia. x 1.5" Iona rina shank nails with 3/8" A . head.
+55.0/-35.0 PSF
Hurricane
Panels
I have reviewed the above and approved it
by my seal below. ( Architect or Engineer of Record
12
SLOPE 4
Gulf Coast Supply and MFG 5v Crimp Metal roofing FL #11651.12
26 ga. 5v crimp metal roofing attached to plywood deck using #9 x 1.5"
wood screws with self sealing washer at 12" o.c. max spacing over ASTM D
(type 2) 30 lb felt underlayment Installed with min. 4' side laps and 6" end
laps fastened with corrosion resistant tin caps and with 1.25" ring shank nails
spaced 6" o.c. at all laps and two staggered rows 12" o.c. In field. Attach
e
5/8" thick x 8"w cut
coral finished stucco bands
5/8" thick light textured
stucco on typical concrete
block construction
REAR ELEVATION
12
SLOPE 4
SCALE: 1/4" = 1'-0"
Gulf Coast Supply and MFG 5v Crimp Metal roofing FL 411451.12
26 ga. 5v crimp metal roofing attached to plywood deck using #9 x 1.5"
wood screws with self sealing washer at 12" o.c. max spacing over ASTM D
(type 2) 30 lb felt underlayment installed with min. 4 side laps and 6" end
laps fastened with corrosion resistant tin caps and with 1.25" ring shank nails
spaced V o.c. at all laps and two staggered rows 12" ox. in field. Attach
deck to trusses using attachment detail on this sheet
EGRESS
MINIMIZE: M�R-19=00
4 MY
1/8" Thick cut coral stucco over paper
backed wire lath nailed to substrate through
one layer of 15 lb felt using Bid nails. Substrate
to be 19/32" COX Plgwood nailed at V o.c.
in field and edges with IOd ring shank galvanized
nails into truss webbing.
12
SLOPE 14
5/8" thick x 8"w cut
coral finished stucco bands FRONT ELEVATION
2" x 4" top plate 1/2" drywall ceding on truss bottom cord
I/2" drywall on
" x 4" studs at 14" o.c.
base -board ----\ 11 II / 21. x 4" P-T. bottom plate
\ 4" concrete slab with fibermash OR
VxV #10/10 WWM on 6 and Visqueen over
clean compacted termite treated fill
nterlor Non-Bearina Partition
Braden t
Braden AIA, FA
Architects
- Planners
411
S.E. Coconut Avenue
Tel
(112) 281-8258
Fax
: (112) 281-8283
E-mail:
bradenalaacomcast.net
Stuart. FL
34994 #AAC000032
nts
Wynne Building Corp.
THE ROYALS
Spanish Lakes
St. Lucie County Florida
SCALE: 1/4" = 1'-0"
ALL CONTRACTOR WARRANTIES BEGIN WHEN THE CLOSING
OCCURS BETWEEN THE BUYER AND WYNNE BUILDING CORP.
AND WILL CONTINUE FOR ONE YEAR FROM THAT DATE
PERMITTING INFORMATION (FORM 100)
Florida Building Code Residential: Lth Edition and ASCE 1-10 for Wind Loading
Building Design is: Enclosed Risk Categor : II Wind Velocity: I65 mph ultimate
Mean Roof Height, ll'-!2" Roof Pitch:
Internal Pressure Coefficient: ±O_Is
Subjectability to damage from: Weathering: Negligible Termites: Very Heavy
Width of Roof End Zone: 3'-4" Wind Speed: I45 mph ultimate
Wind Exposure Classification: C 1.21 x O.L = 0.126
Adjustment factor for Exposure Height: ASD design
Load Combination: ASCE 1-10 Section 2.4 DL+LL; DL+O.LWL; O.6DL+O.6WL
Components t Cladding Wind Pressure (NET) Roof Zone: I. +20.6/-32.4 pat
Roof Zone: 2. +20.L/-51.0 pat
Roof Zone: 3. +20.4/-84.0 psf
Components It Cladding Wall End Zone Width: 3'-4"
Components it Cladding Wind Pressure (NET) Wall Zone: 4.+35.8/-38.1 pat
Wall Zone: 5. +35.8/-41.8 pat
Components t Cladding Wind Pressure (NET) on Garage Door:+32.0/-40.3pst
Shear Walls Considered for Structure? Yes
Continuous Load Path Provided? es
Are Components an Cladding Detai s Provided? Yea
Minimum Soil Bearing Pressure:2,500 psi. Presumptive: X Bg Test: psi
ROOF LIVE LOAD: 3-1 pat ROOF DEAD LOAD: 10 pat
FLOOR LIVE LOAD: --115- psf FLOOR DEAD LOAD: 10 psf
0 = Roof Zone I
Walls Zone 4
® = Roof Zone 2
Walla Zone 5
END ZONE
Corner Zones
- Roof Zone 3
JOB ADDRESS: \
MODEL: Date Drawn Rev Sheet Comm #
GARAGE 3-21-20rTLE COPY
RIGHT °raven by: �9606-d344 _ 12-101
C.C.U. VI WED FOR g
CD heckCODE COMPLIANCE OF 5
FLOOR PLAN
AREA
AREA CALCULATIONS
CRASH POST DETAIL A/C
9
= 1120 s ft.
q•
TYPICAL
NOTES: SCALE I/4" = I'-O"
I.
Contractor to verify ALL notes and dimensions prior to
N.T.S.
3"",high bg 4" diameter Back Porch
Total = 210 sq. ft.
proceeding with work-
steel crash post. Floor
Flange with 4 - 3/8°
2.
Contractor to STRICTLY enforce ALL OSHA Requirements.
Entage
expansion bolts into g =
28 ft.
s q.
3.
ALL Lumber to be used as Beam, Rafters, etc... to have
slab (3/8"t 50 ksl steel plate) Total Under
Roof= 2215 sq. ft.
a minimum 1,400 P.S.I. fiber stress.
`"
Total Cubic
Ft = 13,%0
4.
No dissimilar metals to touch.
2ih„ 2,Jry
S.
ALL Concrete used for slabs Shall be min. 2,500 PSI concrete.
2"
ALL Concrete used for vertical filled cells, cont. tie beams etc.. to
°
2' VTR
shall be 3,000 P.S.I. concrete and/or 4,000 P.S.I. grout mix
"'
13/8„
0
2�"
6.
Drywall at ceilings shall be leveled and attached to bottom chord
2 I
Of trusses With Screws per FBC R102.3.5.
p
t/
2,,
Attach buck to block wall with
1/4" dia. Elco conc screws with min.
MASTER 2111 ,
BATH
1.
ALL wood 1n contact with concrete shall be pressure treated.
° °
1 1/4" penetration at 12" o.c. max
LAV-1
8.
ALL wall dimensions are nominal and not finished wall or stud dimensions.
and 4" max from each corner thru
2" x V PT Buck
2„
LAV-'
i
Exterior face
of wall
9.
ALL plumbing fixtures to be low flow.
2"
10.
Contractor to Provide Drain at water heater in accordance
ones
2"
with the current edition of the Florida Plumbing Code.
WC-1
" LAUNDRY
"
11.
Contractor to Provide a 2'-8" wide door at one bathroom for
xe wood screws thru jamb into buck 2
handicap accessibility requirements.
2
2/'
Detail 0t Door at each hinge and 15" o.c.
prior to door attachment
max and 3„ BT-I „
12.
Lowest finished floor to be set bg Governing Building Department
h"
L" NTS
2• VTRJL 2' AAV
13.
surve or to set in field.
y
Separation between residence and garage shall be per FBC R302.6
INSTALL VULKEM BLOCK SEALANT
ON ALL JAMB, HEADER, AND
I
I 2"
s-�
KTICHBN
14.
Door between garage and residence shall be I-3/4"t 20 min. rated door
9 9
SILL BI-,OCK PRIOR TO BUCK
INSTALLATION
LAV-1
Water Heater
Install windows thru buck into
15.
Wall and Ceiling shall have a flame -spread classification of not greater than
block with 3/I6' tap -con with
1 1/2' penetration at L" o.c. max.
200 per FBC R302.9.1 from each corner and 20." o.c. max
thereafter at ambe and 20' a max
BATH #2 we -I 3"
•+„ 3"�
16. Wall and ceiling finishes shall have a smoke -developed index of not greater than 4 O per FBC R302.9.2 Exterior race at head and ell per product approval
11. All exposed attic insulation materials installed on attir- floors shall have a critical radiant or wall Buck to be I" x 4' PT
Flux not less than 0.12 watt per square centimeter. Exposed foam plastic insulation J Varies
materials exposed on the underside of the roof deck or on the attic walls shall comply
with F.B.C. R316 - see permit info box of code edition To septic
18. Gy psum board material shall conform to ASTM C36, C19, C415, C514, C630, C931 I"x4" P.T. Buck nailed to PLUMBING RISER
C960, C1002, C1041,C1111, C1118, C1218, C1395, or C1396 and shall be installed block with case hardened nails
Detail a t Windows prior to window attachment
according to the following: (FBC R102.3.5) 1" x L" P.T. Buck nailed to Masonry Beail KITS
block with case hardened nails
prior to door attachment,
Install SGD thru buck into
-; _;:;•::r,: ;'. block with 3/I4" tap -con with
If
I/2" henetration at 6" o.c. max.
from each corner and 20." o.c. max
thereafter at head per product approval
p O 0 Use 3/I4" tap -con with
1 1/2" penetration at L" o.c. max.
from each corner and 20" o.c. max
thereafter at sill per product approval
I" x L" P.T. Buck nailed to
block with case hardened nails I Oi
Head prior to door attachment \ p
r
Drywall
Thickness
Location
Orientation
Mem6e9
Max. spacing
of fasteners
Nail sizing options for
Spacing
installation of dr wall into
g
Maximum
Nails
Screws
wood framing members
2" x min. thickness
Ceiling
Perpendicular
24"
1"
12"
13ga 1 3/8" long with 19/44" head
OR
0.098' diameter x 1 1/4" long
/2
annular -ringed or 5d cooler nail
0.080" dia. 15/8" long with
walls
Either
IL"
8
IL"
Direction
IS/44" head
OR
Gypsum board nail 0.084' dia.
x 15/8" with 9/32" head.
Ceiling
Perpendicular
24"
1"
12"
13ga 1 5/8" long with 19/44" head
0.098" diameter x 1 3/8" long
i,
annular -ringed or Ld cooler nail
8
OR
0.092" dia. xx 1 1/8" long with
Walla
Either
1L"
8"
1L"
Direction
1/4' head
®R
Gypsum board nail 0.0915" dia.
x I �/8" with 19/64" head.
fixed door
sliding door
19. ALL ceramic the surfaces installed shall conform to ASTM A108.1 thru A108.6,
n Masonry Wall
A108.1, A118.1, A118.3, A136.1 and A131.1
20. Cement, fiber -cement or glass mat g psum backers in accordance with ASTM
C1288, C1325, OR CII18 and installed I.A.W. manufacturers recommendations Shall
Bottom Track Typical Flooring
be used as backer for the wall the in tub areas and wall panels in shower areas.
Sill
Install SGD thru buck into
21. Insulation includingfacings such as retarders or vapor permeable members installed
g p p
Sliding Door Detail
block with 3/I6" tap -con with
11/2" penetration at L' o.c. max.
within floor -ceiling assemblies, roof -ceiling assemblies, wall, crawl spaces and attics
from each corner and 20." o.c.
max
shall have a flame spread index not to exceed 25 with an accompanying smoke
thereafter at Jambs per product
approvalJamb
developed index not to exceed 450 when tested in accordance with ASTM E 84.
At Masonry Wall NTS
Insulation shall comply with F.B.C. R316.
Gulf Coast Supplg and MFG 5v Crimp Metal roofing FL #11451.12
24 ga. Sv crimp metal roofing attached to plywood deck using #9 x 1.5"
wood screws with self sealing washer at 12" o.c. max spacing over ASTM D
(type 2) 30 lb felt underlayment installed with min. 4 side laps and L" end
laps fastened with corrosion resistant tin caps and with 1.25" ring shank nails
spaced L" o.c. at all laps and two staggered rows 12" o.c. in field- Attach
deck to trusses using attachment detail on this sheet
Simpson HETA 20 or equal
hurricane anchor et each truss 12
with (10) IOd x 11/2" nails PRE-ENGINEERED TRUSSES
( 24' o.c.) supporting Max. 4 r- at 24"oc. TYPICAL
18101be. uplift ( h d b.P )
Aluminum Drip r
Edge E Fascia
2" x L" Sub -Fascia
Kagcan full o vent vmgl sorfit
uwn® 1/8 die shank x 15' long
roofing nails with 3/8" dia. heat
product approval - ace chart al
5/8" thick light textured
stucco on typical concrete
block construction
#5 bar vert, w/
30" overlap
at each filled cell
Grade
s op rawings g manu acturer
R-30 blown fiberglass
in bottom chord of trusses
I/2' drywall with smooth finish
Two rows of beam block filled with concrete
and (l) #5 bar cost- in each row. Substitute
ad precast lintel Filled with concrete and (1) #5
bar Cont. for bottom row over openings
a1 1/2" dryywall over I" x furringg
strips at IL" o.c. with R4.1 fi-foil
insulation on typical 8" Block walls
All drywall to be installed per FBC R102.3.1
and shall meet all pertaining ASTM codes.
ao Mortar to be Type "M" onlyg proportioned per FBC R601.1
and Mortar Jonts shall comply with FBC RL01.2.1.
Provide Dur-O-Rock at all wet areas (ex. showers, tubs etc ---
Fill cell with concrete and
(D #5 bar vert. (typical).
Max. spacing shall not exceed
Wood 48' unless otherwise noted
Base see foundation plan notes for
spacing at openings
4" concrete slab with ribermesh OR
0xV #10/10 WWM on L mil Visqueen over
clean compacted termite treated fill
III 1 ',•.4 1. IIII , IIII , IIII I
'' i lu l 11 11I � 1-IIII-�
14"
TYPiCAL SECTION
14"w x I8"d Concrete footing
with (2) #5 bars coat. and #S
transverse bars at 48" o.c.
Scale : 1/2" = I' -Off
Window Schedule
Mark
Size
Rough O en.
window Descrl tion
PRESSURE ZONE
I.
4'-Sis'x V-3%'
54Ys"x 1.3!4'
Single Hung
ZONE 4
2.
C-23'x W-3 %"
15" x 63 %;'
Single Hung
ZONE 4
3,
2'-2" x 3'-2%2"
21Y2"x 38%"
Single Hung
ZONE 4
4.
3'-1" x 5'-3%s"
38" x L31/+"
Single Hung
ZONE 4
S.
4'-5Ys"x 4'-2%'
54ka'x 54ya'
Single Hung
ZONE 4
ALL Windows to be aluminum windows w/ tint
and mullions per elevations.
ALL windows to withstand pressures in permit info box on sheet I
ALL windows in bathrooms to be tempered
All rough opening dimensions to be verified bg contractor
with manufacturer s specs prior to construction
Door Schedule
Mark
Size
Rough Opening
Door Description
PRESSURE ZONE
A
9'-0" X 1'-0"
108' x 84"
Overhead Garage Door
ZONE 4
B
3'-0' X V-8"
41"%" x 83%"
Fiberglass Panel - Inswing
ZONE 4
C
L'-O" X L'-8"
14" x 81 %;' d°„"°eL„`°"
Sliding Glass Door
ZONE 4
D
2'-0" X V-8"
Solid Core - Wood - L-Panel -Bi-Fold Finished 24' x 81 %2"
E
2'-0 X C-8'
Solid Core - Wood - L-Panel
F
5'-0" X 4'-8"
Solid Core - Wood - L-Panel - Bi-Fold
G
2'-8" x V-8" x 1 %"
Solid Core Wood, Steel, or Masonite Door
H
2'-8" X V-8'
Solid Core - Wood - L-Panel
J
2'-4" X C-8"
Solid Core - Wood - L-Panel - Bi-Fold
ALL Exterior doors to withstand pressures stated in permit info
box on sheet #I
GARAGE DOOR SPECIFIED IN PRODUCT APPROVAL FORM AND SHALL
WITHSTAND THE PRESSURES STATED IN PERMIT INFO BOX ON SHEET #1
All rough opening dimensions to be verified bg contractor
with manufacturers specs prior to construction
35'-O"
21'-0"
14'-O"
Opt.
PATIO/SLAB
3'-10Y2°
0El 1 00
3'-10Y2°
O EGRESS
12" x
12" Concrete column
O
block
filled with concrete and
(2) #1
bars vert. tied into
O
lintels
above
PORCH
a-
WIRE LATH a STUCCO
MASTER
CEILING
: BEDROOM
it
©
8'-0" A.F.F.OL
if
W0
Flat Ceiling
-
00
El I I I 1 19 1 1 1 1 IE0
00 °
0
0
T
4"
I
,a
in
©
I
l
8'-0" to 9' 8" A.F.F.
Vaulted Ceiling
Vanity to be
I
I 34 Y2"high
o
I
I®
°
I
Rod t Shelf
GREAT
I
I
CAROOM
in
1
°
1
2" x
below
C knee -wall
counter top
i
w 1 L O S E
irr
r
Of - - -
LINEN
ad t Shelf O
ao
BiNET
©
DINING 1
ROOM 1
_
-O"
to T-8" A.F.F. 141" HIGH
WALL
Vaulted Ceding
0
1
I 8'-0" A.F.F. OIL
°
THIRD
BEDROOM
N O
8'-0" A.F.F. OL
W
Flat Ceiling
w
a-
J
urn
qUL
u v
�r a: LL
Braden ill
Braden MIAs, FA
Wynne
Building
Corp.
Architects
- Planners
411
S.E. Coconut Avenue
T H E
R O Y A L S
Tel
(112) 281-8258
Fax
E-mail:
: (112) 28�1-8283
bradenaia comcast.net
S anish
p
St. Lucie
Lakes
County Florida
Stuart. FL
34996 #AACOO0032
°
INN
SECOND
ry 13EDROOM
8'-0" A.F.F.
Flat Ceding
1-1/2" OVE
HANG 1 Flat Ceiling
-------<IfiCHEN
°
-
o
Upper cabinets to
cy
extend over Ref
ON -VENT
(�
EF
391
OP
NING
Cr
r+
J
m
W.H 22' x 54"
1
r�
iu
erR-II
Atuth
Batts/
lighttic
I
00
I
i
4'0
Steel Ballard
Provide
closer
auto
1
I
I
See detail
on
this sheet
V(J
Uhl
¶
III
�Q
V
1�.
H 22"Lq
GARAGE
O
W-4" A.F.F. OIL J
i ?
a
Flat Ceiling
®
r----------------- ,
®
jBlock
al O MT 0
0
wall in --------- t--
I garage to be
°
struck block i
G
M EGRE SSY
I I
I I
I
I
I I
c.c.u. `�
11-a-01
3'-61, I
MODEL: Date Drawn Revisions
G3-21-20
GARAGE
RIGHT Drawn by:
C.C.U.
Checked by:
D.R.B.
12
3'-4"
REVIEWED FOR
CODE COMPLIANCE
ST. LUCIE COUNTY
N
A/C c
I
Sheet
2.
OF 5
Comm tt
12-101
B
.7 I f\U�
1. ALL FOOTING ARE DESIGNED FOR A MINIMUM OF 2,500 PSF SOIL
BEARING CAPACITY. IF ANY SUB -SOIL, MUCK OR NON -UNIFORM
CONDITIONS EXIST, REPORT TO ARCHITECT AND OBTAIN
PROPER ENGINEERING DATA FOR DESIGN.
2• ALL SLABS AND FOOTINGS TO BE A MINIMUM 2,600 PSi AT 28 DAYS
ALL COLUMNS, FILLED CELLS, AND BEAMS SHALL BE MIN. 3000 PSI
BE 3000 PSI OR 4,000 PSI GROUT MIX AT 28 DAYS
3. POISON SOIL AND COVER W/ 6 MIL. VISQUEEN WITHIN 24 HOURS. NO
SOIL POISONING TO BE ACCOMPLISHED OUTSIDE OF FOUNDATION.
4 GROUND FLOOR SLAB TO BE A MINIMUM 4" THICK W/ 6X6 10/10
WELDED WIRE MESH REINFORCING ON 6 MIL. POLYETHYLENE VAPOR
BARRIER ON TERMITE TREATED, CLEAN MACHINE COMPACTED FiLL
(MINIMUM 95% DENSITY). LAP POLYETHYLENE 12" MINIMUM. FIBERMESH
MIX MAY BE SUBSTITUTED FOR WELDED WIRE MESH.
5• LOT TO BE CLEARED OF ALL SMALL PLANT GROWTH AND DEBRIS
BEFORE FILL IS BROUGHT IN. FILL MATERIAL SHALL CONSIST OF
CLEAN GRANULAR SAND CONTAINING LESS THAN 10% MATERIAL
PASSING THE US STANDARD NO. 200 MESH SIEVE. PLACE
STRUCTURAL FILL IN LOOSE LAYERS OF 12" IN THICKNESS AND
COMPACT EACH LIFT TO AT LEAST 95% OF ITS MODIFIED DRY
PROCTOR VALUE.
6• GENERAL CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND
DIMENSIONS. BRING ANY DISCREPANCIES OR OMISSIONS TO THE
ATTENTION OF THE ARCHITECT.
GARAGE FLOORS TO BE SMOOTH TROWEL FINISH (SLOPPED PER
FOUNDATION PLAN). PROVIDE 1-1/2" RECESS FOR OVERHEAD DOOR
FOUND,470N FLAN
8. SLOPE ALL PORCH SLABS, COVERED WALK, ETC. AWAY
FROM HOUSE TO DRAINS (IF PROVIDED) PER PLANS
9. DESIGN LOADS ARE AS FOLLOWS:
ROOF (DL+LL) = 41 PSF
WIND VELOCITY = PER PERMIT INFO BOX ON SHEET #1
EXPOSURE ="C"
10. ALL REINFORCING STEEL SHALL BE GRADE 60, MEETING ASTM A-16, 6
A-35 SPECIFICATIONS. ALL ANCHOR TO BE A - 301 STEEL.
iI. ALL DOWELS, SLEEVES, CONDUITS, INSERTS, BLOCKOUTS, ANCHOR
BOLTS AND FRAMES SHALL BE IN PLACE PRIOR TO POURING CONCRETE.
FOR OPENINGS AND SPECIAL FEATURES OMITTED ON THESE PLANS,
SEE ARCHITECTURAL OR MECHANICAL PLANS WHERE APPLICABLE,
12. MINIMUM CONCRETE PROTECTION FOR REINFORCING BARS:
FOOTING: 3"
BEAMS: 1-1/2"
13• LAP ALL REINFORCING STEEL A MINIMUM OF 48 BAR DIAMETERS.
14. USE STRUCTURAL GRADE WOOD WITH A MINIMUM Fb OF 1600 PSI
IS. ALL STANDARD LUMBER SHALL BE SYP WITH A MINIMUM Fb OF 1000
PSI OF NO.2 SOUTHERN PINE, UNLESS NOTED OTHERWISE.
16. ALL LUMBER IN CONTACT WiTH ANY CONCRETE OR MASONRY SHALL BE
PRESSURE TREATED. FASTENERS TO HAVE MIN. G185 RATING.
I. Any changes to plans must be submitted to the architect
for approval before proceeding with construction.
2. Contractor shall be responsible for verification of all
notation and dimensions before starting construction.
3. Soil conditions assumed to be 2500 psf. Should any other conditions be
encountered, the architect shall be notified in writing for revision
4. Verify all recess thickness at showers, tile, etc....
S. Contractor to provide filled cell with concrete and 1 45 bar Vert. at 48"
o.c. max. Provide (1) filled cell on each side of openings upp to 5'-11" wide.
Provide (2) filled cells on each side of openings from 6'-O" to 9'-11"
and Provide (3) filled cells on each Side of openings from 10'-0" and up
Contractor to see plans for any other condition used. Foundation walls
shall have filled cells at 24" o.c. unless otherwise noted (see section)
6. Contractor to provide for Form Board Survey — Form Board Survey
to be provided to Truss Company prior to truss construction
1• Contractor to provide for soil test prior to construction and provide
a copy of soil test to architect for review prior to construction
S. ALL Reinforcing steel shall be grade 60, meeting ASTM A-I6 and
A-35 specifications. ALL Anchors to be A-301 steel.
9. Provide a minimum of 3" concrete protection at footings and
1-1/2" concrete protection at beams for ALL reinforcing bars.
#5 bar vert. w/
30' overlap Fill cell with concrete and
11 (1) #5 bar vert. (t ical). Thicken edge to 8"x8"
at each filled c Max. spacing shall not exceed with concrete and 4" concrete slab with fibermesh OR
Wood 48" unless otherwise noted one #5 bar continuous 6"xC' #10/10 WWM on Io mil Visqueen over
Base see foundation plan notes for clean compacted termite treated fill
spacing at openings
GRADE
4' concrete slab with fibermesh OR
b"xg" #10/10 WWM on 6 and Visqueen over <''(
clean compacted termite treated fill �y —
Grade 124-I — —
-111i
14% x 18"d Concrete footing
with (2) #5 bars Cont. and #5
transverse bars at 48" o.c.
TYPICAL FOOTING DETAIL
SCALE 1/2" = 1'-0"
4" concrete slab with fibermesh OR
6"x4" 410/10 WWM on 10 mil Visqueen over
clean compacted termite treated fill
#5 bar Cont.
Step per
a:. foundation plan
�
(2) #5 bars cont. bottom steel
1/ DETAIL AT GARAGE STEPDOWN
SCALE 1/2" = 1'-
12" x 12' concrete column
block filled with concrete
and (2) #1 bars vert. bed
into lintels above
Top of Tooter
14" below finished floor
3O'
OLUMN FOOTING DETAIL
Grade
30"x30"xl6" concrete
column footing with (4)
#5 bars each wag
\� �/ PORCH SLAB EDGE DETAIL
SCALE 1/21, = 1'-01,
#5 bar vert. w/
30" overlap
at each filled cell
#5 bar cont. in curb Fill cell with concrete and
(l) #5 bar vert. (typical).
Max, spacing shall not exceed
Curb height 48' unless otherwise noted
Wood
see foundation plan notes For
Yerifg based on Base
foundation plan spacing at openings
4" concrete slab with fibermesh OR
t 77 6"xV #10/10 WWM on 6 mil Visqueen over
:s clean compacted termite treated fill
r
V
.� I11II11I�I��II�I1=I
1 I I I 111 1=1
—11I1—I II I —I I II II II II I— 14"w x IS"d Concrete footing
with (2) #5 bars cont. and 45
3' transverse bars at 48" o.c.
14"
9 GARAGE CURB DETAIL
SCALE 1/2" = 1'-0'
91
2" x V PT wood secured with
1/2"dia. x 0 expansion anchors
with 2" sq. washer at 18" o.c. overhead door track secured to wood
jamb per manufacturer's product approval
Garage Door Jamb Detail
GARAGE DOOR TO WITHSTAND PRESSURES STATED �TrJ
IN PERMIT INFO BOX ON SHEET #I. SEE PRODUCT
APPROVAL FORM FOR MANUFACTURER MAKE AND MODEL.
SCALE: 1/4" = 1'-0"
POOTING
SCHEDULE
Mark
size
Description
I
14"W
x 18"D
MONOLITHIC FOOTING
WITH 2 #5 BARS CONTINUOUS
12"W
X 12"D
MONOLITHIC FOOTING
WITH (2) #5 BARS CONTINUOUS
©
30"
x 30" x le"D
COLUMN FOOTING WITH (4) #5 BARS EACH WAY
®
8"W
x 8"D
THICKEN SLAB EDGE
WITH I tt5 BAR CONTINUOUS
©
t
WithCurb
With
x 18"D
at Garag]MONOLITHIC
FOOTING
WITH 2 #5 BARS CONTINUOUS - CURB 9 0'-0"
Termite Protection for New
Construction.
Soil treatment used for subterranean termite prevention
inside the foundation perimeter shall be done after all
excavation, backfilling and compaction is complete.
If soil area is disturbed after initial chemical soil treatment
area shall be re -treated with a chemical soil treatment
including spaces boxed or framed.
Treatment must be in accordance with the rules and laws
established by the Florida Department of Agriculture and
consumer services.
Protective sleeves around metallic piping penetrating
concrete slab on grade floors shall not be of cellulose
containing materials and shall receive application of
termicide in annular space between sleeve and pipe.
Filled Cell Masonry Column With One
#5 From Footing To Tie Beam
Conc. Fill To Be 3000 PSI
See Floor Plan For Location
•7
Single Filled Cell Column
NTS
Filled Cell Masonry Column With One
#5 From Footing To Beam Each.
Conc. Fill To Be 3000 PSI
See Floor Plan For Location
Contractor to proti
(i1 roper foundation c
for proper steel in
zr-o°
12" x 12" Concrete column Opt. PATIO/SLA
block filled with concrete and p
(2) #1 bars vert. tied Inca I u 1
lintels above rl to
1
jEl 1 103 i i i i i i f
T I � I
Filled cell under Q
girder above I FI
p I Rear Porch Slab to
I� LU be poured separately
0 from House Slab. L 1
� - I
Thicken Footing to
I r u 24% x 14"d x 24"L
r---- FI �•-- e
Rear Patio/Slab to
be flush with bottom of
sliding door recess.
_a Slope I"
II-i
II-i
i l
I
_i
°ll I
D'
under filled cell
under girder bearing.
J I
FI I
I
I
I
I
I
I
I
I
F-
1
f-
II
r-
I
0
I
ull
I°
I
FI I
I
°
o I 0 0 2 u
I 1 A/C o
r W vi I I Q # I
>/ I
O X I I 1 ��-4'p Steel Ballard
I- aJ
See detail on this sheet
I I I
1 4" concrete slab with fibermesh OR
1 14"xV #10/10 WWM on 6 mil Visqueen cver
H.B. 1 1 clean compacted termite treated f)OII I °
I FI 1 1 a I i=
N II-
° I°
I FI 1 1 iv I o
Ior O LI CD
U U I I W I
I I 1
c `t
•r F vN �;, O I Recess for I
Garage Door—
E0 ISE
I Fl I
I I
I I
°I Ip
s I I
la I ion D ) °
- -T-T T-T-T-T-
in rl 1 1 1 1 1 1 i-.l n
I 4" concrete slab with fibermesh OR /
6"xC 1*10/10 WWM on 6 mil Visqueen over
e-clean compacted termite treated fill
a
D.
:�1
30" min.
Double Filled Cell Column Corner Steel Lap
NTS ntS
,7 Braden t Braden AIA, PA Wynne Building Corp.
Architects - Planners
411 S.E. Coconut Avenue
Tel M2) 28-7-8258
Fax (112) 281-8283
E-mail: bradenaia®comcast.net
Stuart_ FL 34996 #AACOO0032
THE ROYALF.
Spanish Lakes
St. Lucie County Florida
00
s
fJ
0
0
r
2'-g" 9,_0 3,_b„ „
MODEL: Date Drawn Revisions Sheet Comm
GARAGE �-27-20
RIGHT Drawn by: � I 12_101
C.C.U. REVIEWED FOR
Checked bg: CODE COMPLIANCE
D.R.B. tr OF 5
ROCC
ROOF SHEETING
ATTACHMENT DETAIL
I. Minimum Nail Size = 8d ring shank (min. 2.5" long)
2. Minimum Screw Size = 48 x 2"
3. Minimum Sheathing Thickness 19/32" CDX PI Wood
4. Use nails or screws based on pressure for rooT stated
in permit info box on these plans for zone 3
Ke
Area
Ede
Field
Fastener
Pressu re
Zone 1
61,
61,
8d ring shank
45 psf
Zone 2
41,
4"
8d ring shank
74 psf
Zone 3
411
4"
8d ring shank
84 psf
** Zone 3a
611
L11
#8 wood screw
,112.5 psf
** Use nails
or screws based on
pressure
for
roof stated
in permit
info box on these plans
for
zone
3
Verify with Plan
Concrete
/ Lintel
Provide #5 bars with min. 48 bar Provide #5 bar set in re —cast
diameters overla into beam Tie p
RCCf= FLAN
Scale : 1/2" = I'-C"
filled call steel into continuous lintel into beam where length of
beam block steel. the opening calls for it.
— Overhangs at
1'-0"
unless
Otherwise
noted on this sheet
— Roof pitch at
4:12
unless
otherwise
noted on this sheet
Provide Cast -Crete
-
— Truss sop drawings
to be
provided
by manufacturer
SUB-OB/OT precast
lintel set in mortar
=
— Any changes
to this plan
shall be submitted to the
`.T
;�
Min. 8" Bearing
12"x 12"
Column Block
1 Rebar
Rebar 48 Bar Dia.
Min. Overlap
Column to Lintel Attachment
NTS
Provide PT Buck
attached per jamb
letads into filled ci
4" Pre -cast
Still
architect for approval in writing prior to starting construction.
— ALL TRUSS TO TRUSS CONNECTIONS BY
TRUSS MANUFACTURER
— Architect to review Truss Shop Drawings Prior
to construction for layout and uplift verification
Poured Filled Call — Contractor to provide for Form Board Survey and to provide
Form Board Survey to Truss Company prior to truss construction
Trusses at 24" o.c.
see shop drawings by others
Provide 45 bars with min. 48 bar
diameters overlap in filled cell. Tie
filled Cell steel into continuous
Tooter steel.
I I Concrete Footing
footer schedule
— for exact sizes)
DETAIL AT WINDOW OPENING IN
CBS WALL Scale: 1/2" = 1'-0"
SINGLE PLY REAR GIRDER TRUSS
Nail 2' x 4' blocking to vert. leg of
truss with IOd x 1.5 nails at 4' c.c.
v Install Simpson MGT into wall using
r+ 5/8" dia. threaded rod set min. 12'
y/"\ into wet beam and (22) IOd nails into truss
TRUSS BLOCKING DETAIL
AT GIRDER STRAPPING
AT CENTER BEARING POINT
1/8' thick light textured stucco installed per
ASTM C 92L over ASTM D type 2 papper backed
wire lath nailed to substrate through one Isyer of
ASTM D Type 2 felt paper using ed nails. substrate
to be 19/32" CDX Plywood nailed at 6" o-c. in field
and edges with IOd ring shank nails into studs.
Gulf Coast Supply and MFG 5v Crimp Metal roofing FL #11451.12
26 wood'
5v crimp metal roofing attached to plywood deck using #9 x 1.5'"
wood screws with self sealing washer at 12" o.c. max spacing over ASTM D
(type 2) 30 lb felt underlayment installed with min. 4' side laps and 6" end
laps fastened with corrosion resistant tin caps and with 1.25" ring shank nails
spaced L o.c. at all laps and two staggered rows 12" o.c. in field. Attach
deck to trusses using attachment detail on this sheet
Additional Precast Lintel " " "
tt5 bars ;n� Lintel Bar Clear A B
F't';; ti '1 s � =k':, of C AR Length Length Span Bars Bars
2'-101, 2'-8" 1'-6" 2,43 none
1 "' I 1`•'J 1 1 f'` 1
'L----y 's•---- y I* ---- y
3'-6" 3'-4" 2'-2" 2,43 none
8FB-OB/IT 6PS-13AT 8F8-IB/2T
Addtional 4'-O" 3'-0" 2'-8" 2,#3 none
#5 bars
cLeA �;+. 4'-6" 4'-4" 3'-2" 2 #3 none
one Row of "H' ..:
lock Above
5'-4" 5'-2" 4'-01, 2 u3 none
,,Precast LintelFr` 5'-10" 5'-S" 4'-6" 2A4 none
r
1 Additi6'-6" 6'-4" 5'-4" 2,#4 none
onal
#5 bar. _y
1'-6" 1'-O" 6'-2" 2,#5 none
BFIL-IB/IT 81"I6-I15/2T 8'-4" 1'-10" 1'-0" 2 #5 none
NOTES:
I. min. coverage of steel=1.5"
2. min. bearing required a ea. end=8" ALL reinforcing steel is grade 40.
3. standard for remr. steel=ASTM A415
TYPICAL LINTEL SECTION
( PRECAST CONCRETE )
LINTEL SCHEDULE
Mark
Window
or D
Unit
Width
Lintel
Sim
Coat -Greta
Specification
Rows of
"H" Block
Above
"
Bottom
Steel
Size
Top
Steel
Size
Max
Graving
Load
(PLF)
Max.
Uplift
Load
(PLF)
Max
Lateral
Load
(PLF)
L22
2'-2'
3'-6"
8F8-015AT
1
85
3069
15L9
1024
L31
Z'_g+
3'-1'
4'-O'
8F8-OBAT
1
#5
2561
1363
143
L45
4'-5"
5'-10'
8F8-OBAT
1
#5
1105
909
339
L50
W-O'
6'-6"
BF8-OBAT
1
#5
1238
835
121
LLO
V-8'
T-L'
8F8-OBAT
1
#5
1011
121
534
LBO
8'-0'
9'-4"
8F8-I13/2T
1
95
2
#5
152
691
1 512
L90
9'-O"
10'-6"
8F8-8/2T
I
#5
2
#5
1.43
530
401
L905
9'-0"
10'-L'
BF16-I15/2T
ONE
1
#5
2
#5
1533
1183
401
LI00
10'-0"
Il'-4"
8F8-0/2T
1
#5
2
#5
582
494
452
LIOOB
10'-0'
ll'-4"
8FI6-IB/2T
ONE
I
#5
2
85
1366
1028
452
L120
12'-0"
13'-4"
8F8-I15/2'r
1
U5
2
#5
411
428
324
L120B
12'-O"
13'-4'
BFIL-IB/2T
ONE
I
U5
2
#5
1015
110
324
L140
14'-0"
15'-4'
BFIL-I15/2T
ONE
I
#5
2
#5
1250
409
259
LILO
IL'-O"
n'-4'
BF8-113/2'r
1
#5
2
#5
300 1
192
194
L160B
IL'-O"
n'-4'
BFI4-IB/2T I
ONE
I
U5 1
2 1
#5 1
950 1
500
194
- ALL LINTELS SHALL BE MADE BY CAST-CRETE.
- LINTELS SHALL BE FILLED SOLID WITH 3000 PSI CONCRETE
- REFER TO CAST-CRETE CATALOG FOR ALL INFORMATION REGARDING
LINTEL CONSTRUCTION, HANDLING INFORMATION, AND SAFE LOAD REQ.
REQUIREMENTS
- LINTELS OVER 14'-0" LONG ARE TO BE PRESTRESSED.
12
1
Simpson HETA 20 or equal 4
hurricane anchor at each truss
with (10) 10
d x 1 1/2" nails
( 24" o.c.) supporting Max.
I8101ba. uplift
R-11 b
Aluminum Drip �
Edge t Fascia
Flash and Counter
f lash
Nail ledger to
gable and truss
with (2) Iod da
at each web
Aluminum Drip
Edge t Fascia
1/2' thic stucco on 3/8' hi —rib lath
12"
attached to horizontal and vertical wood
framing with nails or staples to provide
2'" X 6" Sub—FBaGI
no law than I-3/4" penetration into
horizontal wood framing and 3/4' penetration
into vertical wood Prammg members
Kagcan full a vent vingl safit installed
using 1/8" die shank x IS' long gals.
roaring nails with 3/8" dia. head per
product approval - we chart sheet #1
5/8" thick light textured
stucco on typical concrete
12' x 12' concrete column
block construction
block filled with concrete
and (2) #1 bar* vert. tied
Varies - see plan
into lintels above
#5 bar vert. w/
thicken edge to 8"x8"
SO" overlap
with concrete and
at each filled cell
one #5 bar continuous
BEYOND
Rear Patio/Slab to
be flush with bottom of
sliding door recess.
Top of factor
14" below finished floor
Step per foundation plan
uSlope
per foundation plan ®T—
R-30 Batts
•R-II batts
ceiling transition
ded using metal studs
nitrify exact configuration
:es Drywall ceding
see typical section
Ceiling transition Insulation Detall
nts
Brace Gable end
with 2" x 4" SYP #2
8ft back nailed to bottom
of top chords using (2) IOd
nails at each tr as
PRE-ENGINEER,E.D WOOD TRUSS
e 24"o.c. TYPICAL
( shop drawings by manufacturer )
"\R-30 blown fiberglass
in bottom chord of trusses
I/2" drywall with smooth finish
Two rows of beam block filled with concrete
and (1) #5 bar coot. in each row. Substitute
precast lintel filled with concrete and (1) #5
bar cont. for bottom row over openings
1/2" drgwall over 1" x furringg
strips at IL" o.c. with R, ?1-foil
insulation on typical 8" Block walls
All drywall to be installed per FBC R102.3.1
i and shall meet all pertaining ASTM codes.
no Mortar to be Type "M" only proportioned er FBC R601.1
and Mortar joints shall comply with FBC �401.2.1.
Provide Our-O-Rock at all wet areas (ex. showers, tubs etc...)
Fill cell with concrete and
(I) #5 bar vert. (typical).
Max. spacing shall not exceed
Wood 48" unless otherwise noted
Base see foundation plan notes for
J spacing at openings
4" concrete slab with fibermesh OR
6"x4" #10/10 WWM on 6 mil Visqueen over
/ clean compacted termite treated fill
to
N
x
O� m
N
o a
a
� L a
a7 W
o to "O
w a—
E_ r x
� u N
4
II
Strap truss to wall using Simpson MGT with
5/8" dia. threaded rod with min 12" embedment
into beam either wet set or in epoxy with
(22) IOd nails into truss. Add blocking to
truss leg per detail on this sheet
a lti
L90B
L90B
Simpson HETA 20
hurricane anchor at each truss
( 24" o.c.) s%portin Max.
ETA 20 1810 lbs. uplift
L45
q Bi
(L o BI B1
N
I-
L45 B
02
I I I VAOA WAF_ WA A I FAA WA JA
ON
v N
Q� Q1
N �
as
L
LL _a
Z a Bj L31
L45 BI
71
Gulf Coast Supply and MFG 5v Crimp Metal roofin FL #11651.12 12
24 ga. 5v crimp metal roofing attached to plywood ack using #9 x 1.5"
wood screws with self sealing washer at 12" o.c. max a acing over ASTM D SLOPE 4
laps fastened with corrosion resistant tin caps and th 1.25" ring shank nails
spaced L" o.c. at all laps and two staggered rows 1 o.c. in field. Attach BI
deck to trusses using attachment detail on this she
"l-1" x 51- 1
r LU J� Il Attic Accessht
1
9
1 I
\I
z
1
T I
III
I I
I \
as 1
77
O
BI I /TR7-A
48"
8' "MAX
I 13I
Q
I ngi I
I \
I^
\
BI
i
L31
LU
IL
c
BI
BI
�
T-
o
in
`r
.41 SLOPE
BI
OB
BI
L90B
N
BI
w
.n
ETA 20
Simpson HETA 20
BI
hurricane anchor at each truss
( 24" o.c.) supporting Max.
I
S45
18K110 lbs. uplift
BI
>
LBI
1-2-19
PANEL
"A"
Pak*
BR
Load
Wee
Description
circa
cec#
Description
Wire
Lead
SR
Pole*
1
20
1.2 kw
#12
Refrigerator
I
Rene
#L
12.0 km
50
2
1
20
1.2 kw
#12
Clothas Washer
3
1
20
1.5 kw
#12
Kitchen S.A.C.
5
L
Dr er
#10
5.0 kw
30
2
1
20
1.5 kw
#12
Kitchen S.A.C.
I
a
1
20
-
#12
Bathroom Racepts
9
10
Am Condenser
#10
5.0 ke
30
2
1
20
1.2 kw
#12
Dishwasher
II
12
1
20
1.2 ku
#12
Miarceave
13
14
Am Hendl
#10
5.0 kw
30
2
I
15
-
#N
General Lighting
IS
It.
I
15
-
#14
General Lighting
11
is
WH
#10
9.0 kw
25
2
I
IS
-
#I4
General Lighting
19
20
1
IS
-
#14
General Lighting
21
22
GDO
#12
0.81 K
20
I
I
15
-
#14
General Lighting
23
24
Spare
Spare
25
1 24
Spare
Spare
21
1 28
Spare
Spare
29
1 30
1 Spare
PANEL "A" LOAD CALCULATION SHEET
Load Description
Qtii.
Watts
Total(Watts)
General Lighting (3, watts aq. ft.)
Small, Appliance, Circlat(s).,,,,, ,,,,,,,,, ,,,,,,,,,,,,,,,,
,Range ...... ......... ......... ......... .................
.Refrigerator..................................................
.Micr.qwave...................................... I..............
Dish .Washer ...................................................
. Clothes, ,Washer ...............................................
Clothes„ Dryer,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
Water Heater
Garage,Door,Opener,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
1135
3
5,205
2
1,500
3.000
1
12,000
12,000
1
1200
1200
1
1,500
1.500
1
1.200
1.200
1
1,200
1200
I
5,000
5 000
I
1 4 500
1 4,500
1
810
810
Total Watts
351.15
First 10000 Watts 9100%
1
10,000
10,000
Remainder 25,415 e40%
1
O
10,24L
Electric Heat or A/C 10.000 965%
1
10,000
10,000
Calculated Load
Watts
30,2414
Voltage
240
Calculated Wattage Divided by Voltage = Total Amps 126.02
Panel Size Required = 150 Amps
Electrical S mbol Legend
$
Single Pole Switch
®
Recessed Can Light
Sa
Double Pole Switch
®
Eyeball Recessed
F6
Push Button Switch
Exhaust Fan
Duplex Outlet
Ceiling Mounted Light
Special Receptacle
♦
Well Mounted Light
aterproo ground fault circuit
ro
Light with Pull Chain (attic)
®
Floor Duplex Outlet
©
Computer Connection Jack
cM 1
Carbon Monoxide Detector
412
Flood Light
TO
Thermostat
m
Electrical Panel
®
Central Vac
8
Electrical Meter
®
Smoke Detector
Ceding fan
®
Television Jack
®
Telephone Jack
DISC
A/C Disconnect
®
I x 4 Florescent Light
®
2 x 4 Florescent Light
®
Speaker Hook -Up
FB = JUNCTION BOX TO SUPPORT A FAN
O = THERMOSTAT LOCATION
B/A = BALANCED AIR
I FIELD VERIFY SERVICE LOCATION RESPECIVE TO PANEL LOCATION AND USE APPROPRIATE RISER BELOW
disc.
(3) #1 THHN Copper
2" PVC Schedule
40 conduit A B
IC
PANEL
200a rated
meter can
Intersystem banding
2" PVC ( FPL Termination point
schedule 80
2" ricid service FPL
#2/0 AL SER Cable
With #1 Grind
2' PVC Schedule
40 conduit sleeve
into attic
200a rated
meter can r
2" PVC ( FPL)-
schedule 80
2" riaid service PPL
A/C^disc.
L I
ISO
AMP
MCB
PANEL
bonding
pant
GEC B# e #�, PeGr iuu•e GEC Bar(5A' cg�pe`r aura
tJ, alvanzied to 8 rJ, alvansied
ground rods ground rods
ELECTRICAL RISER ALTERNATE SERVICE ELECT. RISER
- Contractor shall use AL-CU Landing lugs. NTs - Contractor shall use AL-CU Landing lugs. NTs
- Contractor shall torque lugs I.A.W. - Contractor shall torque lugs I.A.W.
manufacturers recommendations which manufacturers recommendations which
shall be verified prior to construction shall be verified prior to construction
- Verify AIC/KIC Rating prior to ordering equipment - Verify AIC/KIC Rating prior to ordering equipment
ELECTRIC NOTES:
Vent h�rli
143 CFM
IOx1Ox1
Opt. PATIO/SLAB
PORCH
I
I
I
1
Centerl Registers
- on Iceding fan
I
I
I
r4REAT
i OM
DINING
ROOM
THIRD
BEDROOM
84 CFM
IOx6x6
12)d2xa
B/A
r-/I
r
215 CFM
ICJ
12x6x1
12x12x9
B/A
SECOND
BEDROOM
MEC
143 CFM
IOxlOx1
139 CFM
IOXIOxl
M #3TE12
B ROOM
139 CFM
IOXIOxl
ra
r ICJ
1 12)d2x10
B/A
a
r I
F -T
I 1
o
° ITCHEN
12m 1
I
144 CFM
12xLx1
41 CFM
22" x 54"
Attic Accen
with tight I
\-4'0 Steel Ballard
See detail on this sheet
150 Amp
Panel
GARAGE
(-----------------1
I I
I I
I I
I 1
I I
I I
I I
I I
I I
I i
I I
I I
l- ANICAL LAYOUT
SCALE: 1/4" = 1'-0"
1.
Use copper wire only from panel to devices
"21
15,
Contractor shall guarantee all materials and workmanship
20.
All equipment and panel sizes shall be verified before
2.
Provide and wireI required smoke E Carbon
free of defects for a period of not less than two years from
ordering. The contractor shall provide circuit routings to
Monoxide detectors.
the date of acceptance or certificate of occupancy, or one
suit the Job conditions.
3.
Contractor to verify location of electrical
year from closing sale of house.
service and provider.
Correction of defects shall be completed without additional
21.
Furnish and install all fixtures as called for on the plans
4.
ALL bath and kitchen receptacles to be GFCI protected.
charge and shall include replacements or repair of any
or as selected by others.
S.
ALL exterior outlets to be WP/GFCI protected.
other phase of installation that may have been damaged.
6.
Recessed cans to be installed per NFPA requirements.
I6.
It is not the intent of these plans to show every minor detail
22.
All raceways and pipes placed in or through any concrete
1.
Tamper resistant AFCI receptacles are required in
of construction. The contractor shall furnish and install
slab shall be spaced a minimum of three diameters of the
ALL rooms.
all items for a complete electrical system and provide all
largest conduit or pipe from any other service.
8.
A/C Return Air Balance Must comp) w/ FBC R111602
the requirements necessary for the equipment to be placed in
9.
A(C Refr1 nt lines that are run thru slabs must be
proper working order.
23.
All exposed wire below 9'-1" shall be installed in metal EMT
sleeved ini�c�C
ALL A/C Equipment shall comply With energy calculation
IT
All work shall be done in accordance with the N.E.C. and
local
condwt.
Braden It
FA10.
Braden
11.
All work shall be performed by a licensed electrical
shall comply with all codes and ordinances, and shall
meet all standard requirements of the local electric utility
24
Dryer Vents to be installed per
F.BC RMI502
,41,4
12.
contractor, the completed st� stem shall be fully operative,
Contractor for
and telephone company.
Architects
- Planners
shall pay all lees, permits, testing, and
41'1
S.E. Coconut Avenue
13.
inspections including blower testing where required.
All work be coordinated with trades to
18_
The electrical system shall be completely and effective)
Tel
(�Z2) 28Z-8258
shall other avoid
grounded as required by the latest edition of the N.E.C.
interference with the progress of construction.
Fax
: (112) 281-8283
14.
All required insurance shell be provided for protection
19.
All material shall be new and shall bear underwriters'
E-mail:
bradenalaa comca5t.net
against the public liability and property damage for the
labels where applicable.
duration of the work.
Stuart. FL
34996 #AAC000032
Vent thru
Soffit
A#C
SEE MANUAL
"J" and Energy
1 Calculation
I I for Unit info
Exhaust Duct
Thru Soffit
Wire For
Front Post
Light
Opt. PATIO/SLAB
®\ WP GFCI
YY7 \ 777\I ^
PORC� t {�L�'
0 /
V �
I
I
GREAT
ROOM
MASTER
BEDROOM
Smoke / Carbon
Manowds Detector
Combo
I
I v I m ----
I
LO;SET
I` 1
DINING I I GFCI
ROOM `-_--_ I
' % G C~ / �GIfCIGFCI
° - c
` 1 i IT -I E�P\
-------^3�2" 3'-2" ,IE4''
THIRD - -®
BEDROOM W /
c 1
s -
2"h GFCI -
22•- x s4•
\ - 1 Attie Aeees 1
\ W ;y 11 with light I
�0ptelBhtSdetail oaee/
/ 1
Pull chain
1 PO fight In attic
0 1 \ 1 OPTIONAL PANEL Ij Amp
LOCATION /PPanal
/
Smoke /Carbon ` 42"h GFCI
FA Manowde De etaator I I 1 GARAGE/ /
.� Combo d AHU 11
50 M ®Q
Opener
(-----------------1
4J Z I I
I I
I I
I I
JE'C qND
I I
BEDRIC0M I I
i
WP
Center Post Light on
This corner
UJynne Building Corp.
THE ROYALS
Spanish Lakes
St. Lucie County Florida
O
a0
? m Post Light with
v Photo cell
N Exhaust Duct
-,T'hro Soffit
0" Exhaust
Duct Thru
Wall
WP GFCI
Install owlet
'n under disc.
not shown for
n clarity
U
A#/C
ELECTRICAL PL,4N
SCALE: 114" = 1'-0il
FBC 2309.1 Attic Ventinci Calculations
Total Attic Space = 248-1 sq. ft.
Venting Ratio 1/150 = IL.58 sq. ft. required
Provide A Continuous Vented Soffit
wo J
MODEL:
Date Drawn
Revisions
3-21-20
GARAGE
Drawn by:
RIGHT
G.C.U.
Checked bg:
D.R.B.
Sheet
REVIEWED FOR F -
CODE COMPLIANCE
ST. LUCIE COUNTY OF 5
Comm #
12-101
B