DELp Manual S Compliance Report Job: Lot 34Block 1 Watersto...
—AIF2. Date: Dec 16, 2008
NHAi1NG • AIR CONDMONDIG Entire House By: SND
DEL -AIR HEATING AND AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665
Project• •
For: ADAMS HOMES-
8616 Merano Avenue, Fort Pierce, FL 34951
Cooling Equipment
Design Conditions
Outdoor design DB:
90.4°F
Sensible gain: 27304 Btuh
Outdoor design WB:
77.4°F
Latent gain: 4437 Btuh
Indoor design DB:
75.0°F
Total gain: 31740 Btuh
Indoor RH:
50%
Estimated airflow: 1167 cfm
Manufacturer's Performance
Data at Actual Design Conditions
Equipment type: SpIitASHP
Manufacturer: Carrier
Model: 25HBC537A0030+FX4DNF037L
Actual airflow:
1167 cfm
Sensible capacity:
28735 Btuh
105% of load
Latent capacity:
4764 Btuh
107% of load
Total capacity:
33499 Btuh
106% of load SHR: 86%
Heating Equipment
Design Conditions
Outdoor design DB: 41.0°F Heat loss: 30011 Btuh
Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: SpIitASHP
Manufacturer: Carrier
Model: 25HBC537A0030+FX4DNF037L
Actual airflow: 1167
cfm
Output capacity: 31763
Btuh
106% of load
Supplemental heat required:
0 Btuh
Backup equipment type:
Elec strip
Manufacturer:
Model:
Actual airflow: 1167
cfm
Output capacity: 6.4
kW
72% of load Temp. rise: 17 OF
Meets all requirements of ACCA Manual S.
Entering coil DB: 77.2°F
Entering coil WB: 63.5°F
Entering coil DB: 69.0°F
Capacity balance: 37 OF
Economic balance: -99 OF
V:ILE COPY
- wrigl7tsoftm 2020-Jun-09 14:02:05
�N •�• o�w�-��m-m Right- Suite® Universal 2019 19.0.12 RSU23828 Page 1
ACCK ..aterstone2000BGR\Lot34BIk1 Waterstone2000BGR.rup Calc = MJ8 Front Door faces: S
Component Constructions Job: Lot 34 Block 1 Watersto...
MDEL-AIR p Date: Dec 16, 2008
HEATING^AIHC•NOMONING Entire House By: SND
DEL -AIR HEATING AND AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665
•i�ect intormation
For: ADAMS HOMES
8616 Merano Avenue, Fort Pierce, FL 34951
Design
Conditions
Location:
Indoor:
Heating
Cooling
St Lucie Co Intl, FL, US
Indoor temperature (OF)
70
75
Elevation: 26 ft
Design TD (OF)
29
15
Latitude: 280N
Relative humidity (%)
30
50
Outdoor: Heating
Cooling
Moisture difference (gr/lb)
2.4
56.9
Dry bulb (OF) 41
90
Infiltration:
Daily range (OF) -
15 (L
) Method
Simplified
Wet bulb ff) -
77
Construction quality
Average
Wind speed (mph) 15.0
7.5
Fireplaces
0
Construction descriptions Or Area U-value Insul R Htg HTM Loss CIg HTM Gain
ft� Btuh/fF T ft? °F/Btuh BtuhM Btu BtuhfiF Btu
Walls
Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 3/8" wood shth, 1/2" gypsum
board i nt fns h
12C-Osw: Frm wall, stucco ext, r-13 cav ins, 2"x4" wood frm, 16" o.c.
stud
Partitions
12C-Osw: Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board
int fnsh, 2"x4" wood frm, 16" o.c. stud
n
265
0.201
4.1
5.83
1546
4.98
1322
e
484
0.201
4.1
5.83
2820
4.98
2411
s
128
0.201
4.1
5.83
745
4.98
637
w
364
0.201
4.1
5.83
2122
4.98
1814
all
1241
0.201
4.1
5.83
7234
4.98
6184
w
192
0.091
13.0
2.64
506
2.21
424
272
0.091
13.0
2.64
717
1.31
356
Windows
10C-v: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap, n
1/8" thk; NFRC rated (SHGC=0.70); foreground = asphalt (0.10); 11.67
ft overhang (6.67 ft window ht, 1 ft sep.); 6.67 ft head ht
18 0.550 0 15.9 284 16.2 288
2A-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap,
n
32
0.330
0
9.57
310
9.90
321
1/8" thk; NFRC rated (SHGC=0.23); foreground = asphalt (0.10); 1.42
a
16
0.330
0
9.57
155
17.8
288
ft overhang (5.25 ft window ht, 0.75 ft sep.); 6.67 ft head ht
w
32
0.330
0
9.57
310
17.8
576
all
81
0.330
0
9.57
775
14.6
1184
2A-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap,
n
49
0.330
0
9.57
465
9.90
481
1/8" thk; NFRC rated (SHGC=0.23); foreground = asphalt (0.10); 11.67
ft overhang (5.25 ft window ht, 0.75 ft sep.); 6.67 ft head ht
2B-2fv: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap,
a
13
0.330
0
9.57
128
24.4
325
1/8" thk; NFRC rated (SHGC=0.31); foreground = asphalt (0.10); 1.42
ft overhang (4 ft window ht, 0.75 ft sep.); 6.67 ft head ht
2A-2ov: 2 glazing, clr outr, air gas, vnl frm mat, cir low-e innr, 1/4" gap, s 39 0.330 0 9.57 369 1.85 71
1/8" thk; NFRC rated (SHGC=0.21); foreground = asphalt (0.10); 1.42
ft overhang (6.25 ft window ht, 4 ft sep.); 6.67 ft head ht
% �- wrightsoft 2020-Jun-09 14:02:05
Ali ...,c.mp.m Right -Suite® Universal 2019 19.0.12 RSU23828 Page 1
...aterstone2000BGR%Lot34BIkI Waterstone200OBGR.rup Calc = MJ8 Front Door faces: S
Doors
11JO: Door, mtl fbrgl type
11 DO: Door, wd sc type
Ceilings
16B-30ad:Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2"
gypsum board intfnsh
Floors
19C-19cscp: Flr floor, frm flr, 6" thkns, carpet flr fnsh, r-2 ext ins, r-19
cav ins, tight crwl ovr, r-11 wall insul
22A-tpl: Bg floor, light dry soil, on grade depth
s 20
0.600
6.3
17.4
352
17.6
356
n 18
0.390
0
11.3
201
11.4
203
2173
0.032
30.0
0.93
2016
1.69
3671
360
0.049
30.0
0.49
177
0.26
94
153
0.989
0
28.7
4388
0
0
wrightsoft- 2020-Jun-09 14:02:05
Right-Suite® Universal 2019 19.0.12 RSU23828 Page 2
... aterstone2000BGR\Lot34BIk1 Waterstone2000BGR.rup Calc = MJ8 Front Door faces: S
V c /� p Project SummaryJob: Lot 34 Block 1 Watersto...
�/®GL�HIR Date: Dec 16, 2008
'6.HEGi1AG•AIACONDRIGNING Entire House By: SND
DEL -AIR HEATING AND AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665
Proaect Information
For: ADAMS HOMES
8616 Merano Avenue, Fort Pierce, FL 34951
Notes: DaytonaBch12.10.10VMT
RVSD 12-29-10 DCS
8-19-15 JA
L. S. 6-9-20 VWK
DesicIn Information
Weather: St Lucie Co Intl, FL, US
Winter Design Conditions
Summer Design Conditions
Outside db 41 OF
Outside db 90 OF
Inside db 70 OF
Inside db 75 OF
Design TD 29 OF
Design TD 15 OF
Daily range L
Relative humidity 50 %
Moisture difference 57 gr/lb
Heating Summary
Structure 20826 Btuh
Ducts 9184 Btuh
Central vent (0 cfm) 0 Btuh
(none)
Humidification 0 Btuh
Piping 0 Btuh
Equipment load 30011 Btuh
Infiltration
Method
Construction quality
Fireplaces
Simplified
Average
0
Heating
Cooling
Area (ft2
2004
2004
Volume ()ft3)
18921
18921
Air changes/hour
0.32
0.16
Equiv. AVF (cfm)
101
50
Heating Equipment Summary
Make Carrier
Trade CARRIER
Model 25H BC537AO030
AHRI ref 10487322
Efficiency
Heating input
Heating output
Temperature rise
Actual air flow
Air flow factor
Static pressure
Space thermostat
Capacity balance point = 37 OF
8.5 HSPF
34600
Btuh Ca) 470F
27
OF
1167
cfm
0.039
cfm/Btuh
0.30
in H2O
Backup:
Input = 6 kW, Output = 21677 Btuh, 100 AFUE
Sensible Cooling Equipment Load Sizing
Structure
17741
Btuh
Ducts
9562
Btuh
Central vent (0 cfm)
0
Btuh
(none)
Blower
0
Btuh
Use manufacturer's data
Rate/swing multiplier
y
1.00
Equipment sensible load
27304
Btuh
Latent Cooling Equipment Load Sizing
Structure
2950
Btuh
Ducts
1487
Btuh
Central vent (0 cfm)
0
Btuh
(none)
Equipment latent load
4437
Btuh
Equipment Total Load (Sen+Lat)
31740
Btuh
Req. total capacity at 0.75 SHR
3.0
ton
Cooling Equipment Summary
Make Carrier
Trade CARRIER
Cond 25HBC537AO030
Coil FX4DNF037L
AHRI ref 10487322
Efficiency 12.5 EER, 15.5
SEER
Sensible cooling
26250
Btuh
Latent cooling
8750
Btuh
Total cooling
35000
Btuh
Actual air flow
1167
cfm
Air flow factor
0.043
cfm/Btuh
Static pressure
0.30
in H2O
Load sensible heat ratio
0.86
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
t -:- wrgtittsoft® 2020-Jun-0914:02:05
.� •°" ^^-+ -� Right -Suite® Universal 2019 19.0.12 RSU23828 Page 1
gyp` ... aterstone2000BGR\Lot34B]kl Waterstone2000BGR.rup Calc = MJ8 Front Door faces: S
DEL AIR Right-JO Worksheet
rannxc • am cosamatm+c Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665
Job: Lot 34 Block 1 Waterstone 2...
Date: Dec 16, 2008
By: SND
1
Room name
Entire House
BR4
2
Exposed wall
180.9 It
13.9 ft
3
Room height
9.4 It d
8.9 ft heat/cool
4
5
Room dimensions
'Room area
2005.0 ft2
1.0 x 177.5 ft
177.5 ft2
Ty
Construction
U-value
Or
HTM
Area (ft2)
Load
Area (ft2)
Load
number
(Btuh/ftZ°F)
(Btuh/ftz)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
Blk wall stucco ezt _
10C v
2A 2ov
0 201
0 550
0 330
- n
n
n
589
15 95
9.57
498
16.20
9:90
364
18
32
265
0
0
1546
`„ 284
310
" 1322
, 288
321
O
0
,. 0
„'_ O
0
0
0
0
0
_ 0
-- 0
0
11
Blk wall, stucco ext
0.201
a
5.83
4.98
513
484
2820
2411
_-0
.______0
_---_
0
0
0
0
2A-2ov
2132fv _ _
Blk wall stucco ext
0.330
�- 0.330
0 201
a
e_•
s '
9.57
9.57
S 83
17.78
2439
4 98
16
_ 13
187
1
1
155
128
288
325
637
0
0
0
0
0
0
0
0
0
0
0
0
128
745
vIJ
t-G
2A 2ov
12C-0sw
2A 2ov
0.330,
_____w 0 600
0.091
_ , 0.330
„ s
.__s ..
w
w
9 b7
-_ _17 40.
2.64
9.57
1 85,
- - 17 58..
2.21
17.78
`39
__._ -20
224
_ , - .._32
64
23
.0 20
192
_ 3
_
369
352
506
310
2122
71
_:356
424
576
-_,__, 1814
0
_ 0
112
16
' , 0
0
x_.--0
96
_ - - -1
0
-- Q'
v253
-,_ _- 155
0
_ _ '._-__2
212
- _ 288
I-D
C _
12C-Osw
11DO _
J6B 30a_d__._
0.091
-0.390
. 0 032
_._0 049
n
„ -
_
2.64
11.31
__-
0.93
_. 0.49
1.31
11.43
, _ 169
-,- _0.26
0,00
289
18
_
_ •„__2173
..._- 360
__..: _164.6
__364
272
18
2173
_ ._360
.. ,153
-_._
717
201
_-�_201.6
_,..__.. 177
., `4388
356
203
_ 3671
94
..__ _ _0
__0
0
0
. -„_ 200
178
._ ._.._ _. 0
0
0
_ 185
87_
.r. _ ._..._ 0
0
0
- ---_-.
_337
.___-...46
0
0
�,_ ,_.200
178
.. _.'.:...;0
6
c) AED excursion
0
210
Envelope loss/gain
17610
136371
680
1093
12
a) Infiltration
3216
854
218
58
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
5
1150
0
0
Appliances/other
2100
0
Subtotal (lines 6 to 13)
20826
17741
899
1151
Less external load
0
0
0
0
14
Less transfer
Redistribution
Subtotal
0
0
20826
0
0
17741
0
0
899
0
0
1151
151
Duct loads
44%
54%
9184
9562
44%
54%
396
621
Total room load
Air required (cfm) 111671
30011
27304
1167
150
1295
1772
76
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
-Fk- wrightsortt 2020-Jun-0914:02:05
Right -Suite® Universal 2019 19.0.12 RSU23828 Page 1
... aterstone2000BGR\Lot34BIkl Waterstone2000BGR.rup Calc = MJ8 Front Door faces: S
',( DEL. AIR Right-M Worksheet
xF "'MM •nmcaxumowNc Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665
Job: Lot 34 Block 1 Waterstone 2...
Date: Dec 16, 2008
By: SND
1
Room name
BR 2
BATH 2
2
Exposed wall
14.0 ft
5.0 ft
3
Room height
8.9 ft heat/cool
10.2 ft heat/cool
4
5
Room dimensions
Room area
13.0 x 14.0 ft
182.0 ft2
8.0 x 5.0 ft
40.0 ft2
Ty
Construction
U-value
Or
HTM
Area (ft2)
Load
Area (W)
Load
number
(Btuh/ft2-OF)
(Btuh/ft2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
W
Blk wall stucco ext.
10C v
2A 2ov ..
2A_2ov ,w.__ ,_
Blk wall, stucco ext
'0 201
0 550
0.330
- 0.201
n`'
n •..
n
a
5 83
15 9$
9 57
5.83
4 98
16 20
9 90
90
4.98
�0
0
0
. 0
M� �0
0
0
0
y0
0-
0
0
0
0
0
0
0
W 0
0
0
0
- 0
0
0
0
D
0
0
0
0
0
0
0
—(�
2A-2ov
2B-2fv
Blk wall stucco exY'
2A 2ov -
0.330
0.330
0 201
-0 330
a
a
s .'
s"
9.57
9.57
S 83
9 57
17.78
24.39
4'9
1 85
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0;
0
0
0
o`
0
0
0
0
0
0
0
, 0
_O600a_S._
...174.Q
_ 1_" 8
. 0_._0
0
Vj/
�--G
12C-0sw
2A-2ov
0.091
0.330
w
w
2.64
9.57
2.21
17.78
112
16
96
1
253
155
212
288
0
0
._.____47____�4?_
0
0
0
0
0
0
q—D
12C-Osw
0.091
2.64
1.31
0
0
0
0
0
0
0
0
C <w _
F , .._
11DO
16B,30ad — -
_19C-19cscp _
0.390
- _9 032
00499
_O 989
_,-to-
n
- -
n_
-
11.31
0�93.
.. .x _49026
.__.- 28,58.
11.43
_wi. 69
O:OQ
0
_ 205
182
_ ,:0
0
_ u2Q5
... _,..182
._
0
._. _ l90
.._._,._. _9Q...__._
w. .; _ 0
0
_ 346
._.�.
0
0
w -_ ..._ 45
..._0
.___. _ 40.
0
_.,.. ... 0
�,_ .: _5
0
0
- 0
t
�_.w.._v
C
6
c) AED excursion
209
-13
Envelope loss/gain
687
1103
457
295
12
a) Infiltration
218
58
91
24
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
0
0
Appliances/other
0
0
Subtotal (lines 6 to 13)
905
1161
548
319
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
905
1161
548
319
15
Duct loads
44%
54%
399
626
44%
54%
242
172
Total room load
1305
1786
789
491
Air required (cfm)
51
76
31
21
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
-�+ wtrigFstsoTt^ 2020-Jun-0914:02:05
.4IEUK ._' "' Right -Suite® Universal 2019 19.0.12 RSU23828 Page 2
...aterstone2000BGR\Lot34BIkl Waterstone2000BGR.rup Calc = MJ8 Front Door faces: S
SDEL AIR Right-JO Worksheet
Mmnm • am caenmaMG Entire House,
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665
Job: Lot 34 Block 1 Waterstone 2...
Date: Dec 16, 2008
By: SND
1
Room name
BR 3
UTIL
2
Exposed wall
36.0 ft
0 ft
3
Room height
9.3 ft heat/cool
9.3 ft heat/cool
4
5
Room dimensions
Room area
1.0 x 145.0 ft
145.0 .ftz
1.0 x 67.0 ft
67.0 ftz
Ty
Construction
U-value
Or
HTM
Area (ft)
Load
Area (ftz)
Load
number
(Btuh/ftZ°F)
(Btuh/ftz)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
I-G
_
Bli< wall stucco ext -
10C v _
0.201
0.550
. n
° rt
5.83'
15.95
+ 4.06
16.20
0
0
P 0
0
_
.0
,0
__
' 0
0
0
0
0
0
u .0
0
'- 0
0.
11
2A 2ov
Blk wall, stucco ext
0.330
-- 0.330
0.201
.
n
_n
a
9.57
_ 9.57_.�_
5.83
9.90
9.90
4.98
0
. __
103
0
103
0
598
0
512
0
0
0
0
0
0
0
0
�
2A-2ov
213-2fv
Blk wall stucco ext
2A 2ov
12C-0sw
2A-2ov
_ ..
Blk wall., stucco ext.__:
0.330
0.330
0.201
0 no
0.091
0.330
__,._,_, 0.201
a
a
s
s•
w
w
__.
•_w
9.57
9.57
5 83
9 57
2.64
9.57
_._
^._583
17.78
24.39
4 98
F 1 `85
1758
2.21
17.78
_.�
___ 4:96
0
0
103
39
0
0
_
_- - __ _731
0
0
64
23
0
0
._ _,___131.
0
0
374
369
0
_ _ 0
_ __- w762
0
0
_ 320
71
0
_ _ 0
-.� 651:.____.�0
0
_ 0
0
0
0
0
0
0
0
0
" 0
0
0
0
-� ___ Q
0
_0
0
0
0
0
�.,
_ __._�0
�IJ
T-G
0
. 0
0
0
__� 0
Fj
12C-Osw
0.091
2.64
1.31
0
0
0
0
131
113
298
148
L.-D
F
,F _....:
11D0
166.30ad.-..__
19C 19cscp
22A tpl_-®:':-.._�.�:�_.m_
0.390
n
11.31
_ (.
0.49
____28 6$;
11.43
__ __1.-69
0.26
__., _0,00
0
_ :'._i_145
0
_, __...145
0
_-- _..:145
0
__._.._ `.•36
0
__. 135
- 0
_t.,..�_1033
0
�___. 245
0
-_.m_w __._0
18
_' •: 9Z
0
.._.:.: �� . 67,
18
201
62
0
.,____ .0.
203
0
__.:_ _ ._e_0
_ ._ Q032
0.049
__. __;; Q 989
__ 67
0
_�,___,_0
. __:::..
-
-
-
6
c) AED excursion
60
-43
Envelope loss/gain
3270
1858
561
422
12
a) Infiltration
654
174
0
0
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
0
0
Appliances/other
0
600
Subtotal (lines 6 to 13)
3924
2032
561
1022
Less external load
0
0
0
0
Less transfer
Redistribution
0
0
0
0
0
0
0
0
14
Subtotal
3924
2032
561
1022
15
Duct loads
441%
54%
1730
1095
449/6
54%
2471
551
Total room load
5654
3127
809
1572
Air required (cfm)
220
134
31
67
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
-*- wrigFstsoffi- 2020-Jun-09 14:02:05
A&A " ' ^ Right -Suite® Universal 2019 19.0.12 RSU23828 Page 3
... aterstone2000BGR\Lot34BIkl Waterstone2000BGR.rup Calc = MJ8 Front Door faces: S
DEL AIR. Right-JO Worksheet
"`"'°'G' AM'o"°""°"'"'G Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL32771 Phone: 407-333-2665
Job: Lot 34 Block 1 Waterstone 2...
Date: Dec 16, 2008
By: SND
1
Room name
M BATH
LIVING/DIN/FOY
2
Exposed wall
12.0 ft
13.0 ft
3
Room height
9.6 ft heat/cool
9.3 ft heat/cool
4
Room dimensions
10.0 x 12.0 ft
1.0 x 345.0 ft
5
Room area
120.0 ft2
345.0 ftz
Ty
Construction
U-value
Or
HTM
Area (ft2)
Load
Area (ft2)
Load
number
(Btuh/ft2-OF)
(Btuh/ft2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
COD]
6
.131k wall stucco exY :
10C v
0.201
0 550
n.a
n
6{'83
15 95
4 98
16 20
, 0
; 0
0
0
0
0
0
0
;, 0
0
0
0
0
2A 2ov
0 330
n
9 57
MO
0
0
0
0
0
0
0
0
- ~
0
U
_ 0
_
...J
11
Blk wall, stuccoaext
0.201
e
5.83
4.98
112
99
575
492
37
37
218
- 186
2A-2ov
0.330
a
9.57
17.78
0
0
0
0
0
0
0
0
2B-2fv
0.330
a
9.57
24.39
13
1
128
325
0
0
0
0
Blk wall stucco ext
0:201
s.
5 83
4,98
0
= 0
0
0
84
'� 64
0
372
" 0
318'
.'D
„
17,85
20
.�,�,_2Q
�- _ _ _ 352
t—G
12C-Osw
0.091
w
2.64
2.21
0
0
0
0
0
0
0
0
2A-2ov
0.330
w
9.57
17.78
0
0
0
0
0_
0_
0
0
!1,.,_..e'_Blkwall�stuccoezt:�'
y
_.._
.,
q—D
12C-Osw
0.091
2.64
1.31
93
93
246
122
65
65
172
86
11DO
0.390
n
11.31
11.43
0
0
0
0
0
0
0
0
_
_
_�,_: -. 127„
F
19C 19cscp
0.049
0.49
0.26
0
0
0
0
0
0,
0
_22A_tpl-__ w r _
_70,989
_
w
,373.._
_0
7,
7>,
v
E ,
�_..
..,.w....9..s._,,.y.�....,
,w+.....�,s
6
c) AED excursion
29
-73
Envelope loss/gain
1420
1199
1808
1456
12
a) Infiltration
218
58
236
63
b) . Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
1
230
Appliances/other
0
0
Subtotal (lines 6 to 13)
1638
1257
1 2044
1749
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
1638
1257
2044
1749
15
Duct loads
44%
549/6
722
678
441%
541/6
901
943
Total room load
2361
19351
2945
2692
Air required (cfm)
92
831
115 1
115
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Jun-0914:02:05
" 'a ^ ^ Right -Suite® Universal 2019 19.0.12 RSU23828 Page 4
... aterstone2000BGR\Lot34BIkl Waterstone2000BGR.rup Calc = MJ8 Front Door faces: S
DEL -AIR Right-M Worksheet
HWMG'Ga1 GGNDMOMG. Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665
Job: Lot 34 Block 1 Waterstone 2...
Date: Dec 16, 2008
By: SND
1
Room name
WIC 2
WIC 1
2
Exposed wall
10.0 ft
0 ft
3
Room height
9.6 It heat/cool
9.6 ft heat/cool
4
Room dimensions
4.0 x 10.0 ft
6.0 x 6.0 ft
5
Room area
40.0 .ft2
36.0 ft2
Ty
Construction
U-value
Or
HTM
Area (ft2)
Load
Area (ft2)
Load
number
(Btuh/ft2-OF)
(Btuh/ft2)
or perimeter (ft)
(Btuh)
or perimeter. (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
BIk wall stucco ext
106 v
2A
0 201
0 550
n }'
n
5 83;
15 95
4 98
16 20
0
0
0
0
0
n 0
0
0
0
0
D
0
0
0
0
0
2ov
0,330
n
9 57
9 90
0
0
0
0
0
0
0
0
2q 2ov
_ _Q_330
upu
, 9 57
.w.9.9Q
_..1 u
. _10
_ w 2 ,0
1 1
Blk wall, stucco ext
0.201
a
5.83
4.98
93
93
544
465
0
0
0
0
2A-2ov
0.330
a
9.57
17.78
0
0
0
0
0
0
0
.0
2B 2fv
0 330
e
9.57
24 39
0
0
0
0
0
0
0
0
BIk wall stucco ext
2A 2ov
D.201
0.330
s r1_1
s
5 83;
9 57:
1 85
0
0%
u 0
0
0
0
0.=
0
0
0
0
0
_
0
' D
0
0
0:600
s_.
_ _17 40
17@8
0
m_ t0
0
_ _. A
_r� _ 0
^ .
_ _ u0
0
y/
t---G
12C-0sw
0.091
w
2.64
2.21
0
0
0
0
0~
0
0
0
.W
2A 2ov
BIk wall,stucco ex4:'
0.330
_ 01
w"
w_
9.57
_" 5 $3
17.78
a 4'98
0
_ ,._. �0
0
�,
0
0
..�.
0
0
0
0
_0
Q
�12C-Osw
0.091
2.64
1.31
0
0
0
0
0
0
0
0
D
11 DO
0.390
n
11.31
11.43
0
0
0
42
0
' _ 7?�.�m_
0
.v- 0.1.
0
- �4?
0
s _38
0
_69
F
19C 19cscp
0.049
0,49
0 26
0
0
0
0
0
0-
0
0
22A.tpl a, .rW _ _
_ :0.989
_
28'88,000
_
7, _.....°_
7-7-77
_.
...._..__s ..,u_
Le.ua+.,v_._�:.,.."..
.,.u_,.r.i,_..
_.._...::_._.�",. r..
�....... ,..�.w.._
_......�.,._......u....s
.... �.... ..._v...
.kM1 . n _..........«
-... __....a..�_..._
....-.v... �.�.�.
_.
_..emu.
,...., ,....f ,.�....-....,.
,
�.,....V...-w_.-.-a".....«.w....___av
... _.: .�'....._.
...
T.
wc...�.__
... .. ....a.si,.
...._...iov._._,�—'+
_.«.,.. x..:....'..w
_.&,....yar.:..�..._..-:..r.,4
_.«SJ_
,.-_....,t .3_n_... ..
..,-.._....
ter....
,
-..:..._
...._..« _
o.....-.., .F ....,... ._w...._«.....,F
_„�....._....-
._
....--..a
,..-w.,.�
.,.,tw_M._u_.
._A.......s,. .
«.....J�.........
..�.,.._,.u_
...- ..mow,
..._,_..
_..___ _..
.. _s.. _.
6
c) AED excursion
-24
-3
Envelope loss/gain
873
518
38
67
12
a) Infiltration
182
48
0
0
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
0
0
Appliances/other
0
0
Subtotal (lines 6 to 13)
1055
567
38
67
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
1055
587
38
67
Ductloads
44%
54%
465
305
44%
54%
17
36
ff
Total room load
1520
872
55
102
Air required (cfm)
59
37
2
4
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
-Pld- 2020-Jun-09 14:02:05
A& r ` '""'•`` ' Right -Suite® Universal 2019 19.0.12 RSU23828 Page 5
... aterstone2000BGR\Lot34B]kl Waterstone2000BGR.rup Calc = MJ8 Front Door faces: S
jWDEL-AIR
Right-M Worksheet
Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665
Job: Lot 34 Block 1 Waterstone 2...
Date: Dec 16, 2008
By: SND
1
Room name
M BR
KIT
2
Exposed wall
32.0 ft
0 ft
3
Room height
9.6 It heat/cool
9.3 It heat/cool
4
5
Room dimensions
Room area
1.0 x 300.0 It
300.0 ftz
1.0 x 126.5 ft
126.5 ftz
Ty
Construction
number
U-value
(BtufditZ°F)
Or
HTM
(Btuh/ftz)
Area (ftz)
or perimeter (ft)
Load
(Btuh)
Area x
or perimeter (ft)
Load
(Bt h)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
Blk wall;stucco ext.,
10C v
2A 2ov
0 201
0 550
'0 330
n
n
n
5;83
15.95
9.57
4%98
16.20
9.90
931
0
32
98
0
0
573
0
_ 310
490
0
321
s' 0
0
0
,$
0
0
; 0
0
0
' 0
0
0
•
11
u..._.._ .
2A 2ov,_�_..__._.___>
wall, stucco ext
._, a0330
0.201
_n:_
a
__.9.57
5.83
_, 9.90
4.98
________._ 0
168
...._.__.;_._Q
152
___�. Q-_._-..�0
885
757
._.__-_--0.--_�__
0
0
0
___._.__ 0
0
�._.__:�Q
0
tlBlk
2A-2ov
28 2fv
Blk wall stucco ext
2A 2ov
0.330
0.330
0 201
-0 330
600
a
a
s7
's
._"sv
9.57
9.57
17.78
24.39
4 98
1.85
17:58
16
0
:0
_ .__ 0
1
0
0
_.__w..=0
155
0
0
._0
288
0
0
0
0
0
0
0
0
0
0
0
0
0
0.
5783
9.57
1.7.4Q.
VN
12C-Osw
2A-2ov _ _. _.-----
Blk.wall,stucco ext,---
0.091
------ 0.330
----.YO 201.
w
-_w----,.
w_
2.64
_ 9.57
_
5.83
2.21
17.78
_
,<. _q.9B
0
0
__ 0
0
-__ 0
0
0
0
_ _ 0
0
o
0
_ o
0
_ ---D
0
. _ _4
q-D
12C-Osw
0.091
2.64
1.31
0
0
0
0
0
0
0
0
F
F_' _:_
11 DO
_16B_30ad.,
19C 19cscp
22A tpl_;_; - _... ,,:�
0.390
0 049
. 0 989
n
_
.._ :_
11.31
Q_93
0.49
_. 28;68,
11.43
,, 1_,69
0.26
a u. 0.00
0
�_ 340
0
, _ _. ,300
0
_n T 340
r 0
_. ..32
0
_ ._. 318
- e 0
L _918
0
_ __ . 575.
0
. .:_ M _0
0
"_ __127
0
_ _..__ 127
0
_. _ _127
0
_.,...._._ 0
0
;; _ _ 117
0
. e 0
0
�___,214
0
_ ._.Q
6
c) AED excursion
-125
-57
Envelope loss/gain
3156
2304
117
157
12
a) Infiltration
581
154
0
0
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
1
230
0
0
Appliances/other
300
1200
Subtotal (lines 6 to 13)
3737
2989
117
1357
Less external load
0
0
0
0
14
Less transfer
Redistribution
Subtotal
0
0
3737
0
0
2989
0
0
117
0
0
1357
15
Duct loads
44%
54%
1648
1611
441/6
54%
52
731
Total room load
Air required (cfm)
5386
209
4600
197
169
7
2088
89
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
-➢'}�➢- wr➢gtitsoft� AcA Right -Suite® Universal 2019 19.0.12 RSU23826 2020-Jun-0914:02:05
Page 6
... aterstone2000BGR\Lot34BIk1 Waterstone2000BGR.rup Calc = MJ8 Front Door faces: S
' DELAIR Right-JO Worksheet
'E°'°'°'"'n'O"°"'°'@'° Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665
Job: Lot 34 Block 1 Waterstone 2...
Date: Dec 16, 2008
By: SND
1
Room name
NOOK
GREAT RM
2
Exposed wall
10.0 ft
35.0 ft
3
Room height
9.8 It heat/cool
9.8 ft heat/cool
4
5
Room dimensions
Room area
10.0 x 10.0 ft
100.0 ftz
1.0 x 326.0 ft
326.0 ft2
Ty
Construction
U-value
Or
HTM
Area (ft2)
Load
Area (ft)
Load
number
(Btuh/ftZ°F)
(Btuh/ftz)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
W�- G
I--G
Blk wall, stucco,exf
10C v
2A 2ov
�- 0 201.
0.550
0.330
ri
n
n
5.83
15.95
9.57
4.98
16.20
9 '90
'^93
0
D
"' v 77
0
0
,; _._._ 450
'0
0
"-384
0
0
-rt 140
18
0
-- �A90
0
0
_ -524
284
10
Zff
288
0
1 1
2A 2ov _ _
Blk wall stucco ext
_0 330
0 201
h
e
9 57
5.83
9 90
4.98
_--�- •J 8
0
_ 0
0
._ 155
0
. 160.
0
,. _ 32
0
-_ 0
0
_310
0
�321.
0
C
G-
2A 2ov
2132fv _. _
Blk wall,'stucco ext'^
0.330
_._ 0.330
e
_?_.
9.57
9.57
9.83
17.76
24.39
4.98
0
_ -_ 0
0
0
_ 0
0
. .. ._0
0
. 0
0
.. 0
0
__.0
_ 0
0
3
ri �0
0
_ _. 0
0
ViJ
I--G
q-D
2A 2ov
12C-0sw
2A 2ov _
12C-Osw
1DO
0.330
0.091
0 330
0.091
0.390
s
w
w ,
n
9 57
2.64
9.57
2.64
11 31
1.85
2.21
17.78
4-98
1.31
11 43
0
0
0
---- .-_ 0
0
0
0
0
0
_ _w.._ y..0
0
0
0
0
0
._ ,; 0
0
0
0
0
0
--.. _. _
0
0
0
0
0
_ 0
187
0
0
0
0
_. _. 0
-- 187
0
0
0
0
0
_. _ 0
0
0
0
_ __. 0
_ 1088
0
0
00,032
_F.
_.
_..._
0049
9
_._z_
_..,_.
_r
__ O.A,
0.49
__28;68.0.00'_____100.___.--_._10.'------_287__-_-
1:69
026
.._._ _ _
•-=__312
_ 0
_ ..._ ..
�_ -112
._..___ 0
_
_ 4
., ._.,__.0
4
189._
__. ..__Q_
_0
_
. __364
------- 326___.
__
__ 364
.___35__,_._100.4
__- _ _ --
_�--338
---
_ ____615
0
__..__0.
--
6
c) AED excursion
-31
-139
Envelope loss/gain
995
702
3547
2463
12
a) Infiltration
182
48
636
169
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
3
690
Appliances/other
0
0
Subtotal (lines 6 to 13)
1177
750
4183
332-2
Less external load
0
0
0
0
14
Less transfer
Redistribution
Subtotal
0
0
1177
0
0
750
0
0
4183
0
0
3322
15
Duct loads
440/6
541%
519
404
44%
541%
1845
1790
Total room load
Air required (cfm)
1696
66
1155
49
6027
234
5112
218
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
-*^ wrigl�tsort^ 2020-Jun-0914:02:05
Right-Suite® Universal 2019 19.0.12 RSU23828 Page 7
...aterstone2000BGR\Lot34BIklWaterstone2000BGR.rup Calc,= MJ8 Front Door faces: S
4 CDEL /� Duct System Summary Job: Lot 34 Block 1 Watersto...
-AIR Date: Dec 16, 2008
'AWNEUnNG Entire House By: SND
DEL -AIR HEATING AND AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665
Project• •
For: ADAMS HOMES
8616 Merano Avenue, Fort Pierce, FL 34951
External static pressure
Pressure losses
Available static pressure
Supply / return available pressure
Lowest friction rate
Actual air flow
Total effective length (TEL)
Heating
0.30
in H2O
0.06
in H2O
0.24
in H2O
0.120 / 0.120
in H2O
0.205
in/100ft
1167
cfm
117 ft
Cooling
0.30 in H2O
0.06 in H2O
0.24 in H2O
0.120 / 0.120 in H 20
0.205 in/100ft
1167 cfm
Supply Branch Detail Table
Name
Design
(Btuh)
Htg
(cfm)
Clg
(cfm)
Design
FR
Diam
(in)
H x W
(in)
Duct
Matl
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
BATH 2
h 789
31
21
0.221
4.0
Ox 0
VIFx
23.7
85.0
st3
BR2
c 1786
51
76
0.225
6.0
Ox0
VIFx
21.5
85.0
st3
BR 3
h 5654
220
134
0.213
8.0
Ox 0
VIFx
27.9
85.0
st3
BR4
c 1772
50
76
0.214
6.0
Ox 0
VIFx
27.1
85.0
sti
GREAT RIM
h 6027
234
218
0.212
9.0
Ox 0
VIFx
28.4
85.0
st1
KIT
c 2088
7
89
0.217
6.0
Ox0
VIFx
25.7
85.0
st1
LIVING/DIN/FOY
c 2692
115
115
0.309
6.0
Ox 0
VIFx
7.6
70.0
MBATH
h 2361
92
83
0.230
6.0
Ox0
VIFx
19.4
85.0
st2
M BR
h 5386
209
197
0.219
8.0
Ox 0
VIFx
24.7
85.0
st2
NOOK
h 1696
66
49
0.205
6.0
Ox0
VIFx
32.3
85.0
sti
UTIL
c 1572
31
67
0.316
5.0
Ox 0
VIFx
6.0
70.0
wic 1
c 102
2
4
0.235
4.0
Ox 0
VIFx
17.0
85.0
st2
WIC 2
h 1520
59
37
0.228
5.0
Ox 0
VIFx
20.1
85.0
'st2
Trunk
Htg
Clg
Design
Veloc
Diam
H x W
Duct
Name
Type
(cfm)
(cfm)
FR
(fpm)
(in)
(in)
Material
Trunk
sti
Peak AVF
357
433
0.205
551
12.0
0 x 0
VinlFlx
st2
Peak AVF
362
321
0.219
665
10.0
0 x 0
VinlFlx
st3
Peak AVF
301
231
0.213
552
10.0
0 x 0
VinlFlx
- wrightsoft, 2020-Jun-0914:02:06
ACCA �M.,..•,o. .. a...,�m, , Right -Suite® Universal 2019 19.0.12 RSU23828 Page 1
... aterstone2000BGR\Lot3481kl Waterstone2000BGR.rup Calc = MJ8 Front Door faces: S
Return Branch Detail Table
Name
Grille
Size (in)
Htg
(cfm)
Clg
(cfm)
TEL
(ft)
Design
FIR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Stud/Joist
Opening (in)
Duct
Matl
Trunk
rb2
Ox 0
1167
1167
0
0
0
0
Ox 0
VIFx
t " wright5Oft® 2020-Jun-09 14:02:06
�M •t• - �m Right -Suite® Universal 2019 19.0.12 RSU23828 Page 2
... aterstone2000BGR\Lot34BIkl Waterstone2000BGR.rup Cale = MJ8 Front Door faces: S
" !
2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Lot 34 Block 1 Waterstone 2000 BGR Builder Name: ADAMS HOMES
Street: 8616 Merano Avenue Permit Office:
City, State, Zip: Fort Pierce, FL, 34951 Permit Number:
U
Owner: Jurisdiction: 661000
W
Design Location: FL, ST_LUCIE_CO_INTL
U
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
requirements
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
Breaks or joints in the air barrier shall be sealed.
Ceiling/attic
The air barrier in any dropped ceiling/soffit shall be aligned with
The insulation in any dropped ceiling/soffit
the insulation and any gaps in the air barrier shall be sealed.
shall be aligned with the air barrier.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed.
Cavities within comers and headers of frame walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity
sealed.
with a material having a thermal resistance of R-3
Knee walls shall be sealed.
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/doorjambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of
Floor framing cavity insulation shall be installed to
(including
insulation.
maintain permanent contact with the underside of
above -garage
subfloor decking,or floor framing cavity
g insulation
and cantilevered
shall be permitted to be in contact with the top side
floors)
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
Narrow cavities
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spac
as.
Recessed lighting
Recessed lightfixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the drywall.
thermal envelope shall be airtight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
Shower/tub
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
on exterior wall
tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC register boots that penetrate building thermal envelope shall
be sealed to the sub -floor or drywall.
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sprinklers
sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
between fire snrinkler co ver plates and walls or ciallends-
a. u 1 auwuun, inbpecuun o! iog wallb bnaii be in accordance with fne provisions of iuu-4UU.
6/9/2020 2:32 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
FOR14 R405-2017
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2017 Florida Building Code, Energy Conservation via the
residential Simulated Performance Method shall include:
❑ This checklist
❑ A Form R405 report that documents that the Proposed Design complies with Section
R405.3 of the Florida Energy Code. This form shall include a summary page
indicating home address, a -ratio and the pass or fail status along with summary
areas and types of components, whether the home was simulated as a worst -case
orientation, name and version of the compliance software tool, name of individual
completing the compliance report (one page) and an input summary checklist that can
be used for field verification (usually four pages/may be greater).
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO for the Performance Method:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 -
one page)
❑ A completed Envelope Leakage Test Report (usually one page)
❑ If Form R405 duct leakage type indicates anything other than "default leakage" then a completed
Form R405 Duct Leakage Test Report (usually one page)
6/9/2020 2:31:07 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
4 }
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2017 Florida Building Code, Energy Conservation, 6th Edition
Jurisdiction: 661000
Permit #:
J,ob Information
Builder: ADAMS HOMES Community: Lot: NA
Address: 8616 Merano Avenue
City: Fort Pierce State: FL Zip: 34951
:.Air Leakage, Test Results Passing results'm`ust.meet either the Performance, Prescriptive, or ERI Method .
`0 PRESCRIPTIVE METHOD -The building or dwelling unit?shall be'tested and verified as having an -air leakage rate of not exceeding 7 air
changes pet hour at apressure of 0.2 inch w.g,: ( Oascals) in Climate Zones 1;and 2.. •,
PERFORMANCE or ERI: METHOD -The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding
theselected ACH(50),value, as'shown on Form R405.-201T(Performance). or R406-2017 (ERI)', section labeled as infiltration; sub -section ACH50.
ACH(50) specified on Form R4052o17?Energy,•Galc (Performance).orR40¢ 2017 (ERI): 7.000
x 60 _ 18838 — Method for calculating buildinq volume:
CFM(50) Building Volume ACH(50) O Retrieved from architectural plans
F1PASS 0 Code software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation Q Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Companyp
Company Name: Phone:
hereby verify that the above Air Leakage results are in accordance with the 2017 6th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
6/9/2020 2:32:09 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
4 }
Florida Building Code, Energy Conservation, 6th Edition (2017)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
FADDRESS: 8616 Merano Avenue Permit Number:
Fort Pierce , FL, 34951
MANDATORY REQUIREMENTS See individual code sections for full details.
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
(Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
El R402.4.1 Building thermal enveld'� building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.
The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
Fi R402.4.1.1 Installation The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
Fi R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
El R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
R402.4.3 Fenestration air IeakageWindows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per
square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
6/9/2020 2:31 PM EnergyGaugeO USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 5
0 J l
MANDATORY REQUIREMENTS - (Continued)
❑ R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
11402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
SECTION R403 SYSTEMS
R403.1 Controls.
❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
El R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the
manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test.
2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the
entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the
test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
❑11403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
❑ R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41 °C)
or below 55°F (1 YC) shall be insulated to a minimum of R-3.
R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory)Heated water circulation systems shall be in
accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2.
Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return
pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited.
Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the
occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and
when there is no demand for hot water.
R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems
shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance
with the times when heated water is used in the occupancy.
6/9/2020 2:31 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 2 of 5
I j)
MANDATORY REQUIREMENTS - (Continued)
R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3 Y2 inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
Fi R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100°F to 140°F (38°C to 60°C).
Fi R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main bumer(s) of
combustion types of service water -heating systems to be turned off.
R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
EJ R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where whole -house mechanical ventilation fans are integral to tested and listed HVAC equipment, they shall be
powered by an electronically commutated motor.
❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10
otherwise.
R403.7 Heating and cooling equipment (Mandatory).
El R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the
equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies,
based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and
indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions
described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that
affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such
as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency
rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed.
TABLE 111403.6.1
WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIRFLOW RATE MINIMUM
(CFM)
MINIMUM EFFICACY a
(CFM/WATT)
AIRFLOW RATE MAXIMU
(CFM)
Range hoods
Any
2.8 cfm/watt
Any
In -line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1.4 cfm/watt
<90
Bathroom, utility room
90
2.8 cfm/watt
Any
For SI: 1 cfm = 28.3 Umin. a. When tested in accordance with HVI Standard 916
6/9/2020 2:31 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS . (Continued)
❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section 403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
FI requirements calculated according to the procedure selected in Section R403.7.1.
❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
C403 and C404 of the IECC—Commercial Provisions in lieu of Section R403.
❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at
❑ the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
6/9/2020 2:31 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 5
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
❑ R403.11 Portable spas (Mandatory�e energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.-
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment (Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be
high -efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high -efficacy lamps.
Exception: Low -voltage lighting.
R404.1.1 Lighting equipment (Mandatory)Fuel gas lighting systems shall not have continuously burning pilot lights.
6/9/2020 2:31 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 5 of 5