HomeMy WebLinkAboutWRIGHT DRAWINGSABBREVIATIONS AC ALTERNATING CURRENT MTS MANUAL TRANSFER SWITCH A/C AIR CONDITIONING MSB MAIN SWITCHBOARD AFG ABOVE FINISHED GRADE MLO MAIN LUGS ONLY AL ALUMINUM (CONDUCTOR) NEC NATIONAL ELECTRICAL CODE AHU AIR HANDLING UNIT NTS NOT TO SCALE ATS AUTOMATIC TRANSFER SWITCH NEW NATIONAL ELECTRICAL MANUFACTURERS AMP AMPERE Estimated ASSOCIATION AFCI ARC FAULT CIRCUIT INTERRUPTER NFPA NATIONAL FIRE PROTECTION ASSOCIATION ANSI AMERICAN NATIONAL STANDARDS INSTITUTE NON -SE NON SERVICE ENTRANCE RATED C CONDUIT PLCS PLACES(QUANNI ) CU COPPER (CONDUCTOR) PNL PANEL COVE CITY OF VERO BEACH PVC POLYVINYL CHLORIDE CONDUIT DC DIRECT CURRENT RMC RIGID METAL CONDUIT DISC DISCONNECT RTU ROOFTOP UNIT EXIST EXISTING BE SERVICE ENTRANCE RATED FPL FLORIDA POWER & LIGHT TYP TYPICAL G GROUND TEMP TEMPORARY GFCI GROUND FAULT CIRCUIT INTERRUPTER TRANS, TX TRANSFORMER IRC INDIAN RIVER COUNTY UG UNDERGROUND RNA KILOVOLTAMPERE UL UNDERWRITERS LABORATORY KW KILOWATT JOIN UNLESS OTHERWISE NOTED MC METAL CLAD CABLE - V VOLT NICE MAIN CIRCUIT BREAKER VA VOLTAMPERE MCC MOTOR CONTROL CENTER W WATT MDP MAIN DISTRIBUTION PANELBOARD XFMR TRANSFORMER EXTERIOR - EXISTING GENERATOR: AIR COOLED GENERAC 221(W M"EE AREAStR GRADE EXISTING (2)518"X8'--...__ T CU GROUND RODS EXTERIOR SCOPE OF WORK: • INSTALL NEW BATTERY IN EXISTING GENERATOR. • INSTALL NEW CHARGING CIRCUIT TO EXISTING GENERATOR. • ANCHOR EXISTING GENERATOR TO EXISTING CONCRETE PAD FOR GENERATOR. • PROVIDE AND I NSTALL CONDUIT AND CONDUCTORS FROM ATS TO GENERATOR. • INSTALL NEW REGULATOR FOR EXISTING PROPANE SUPPLY. • GENERATOR GAS CONNECTION BY ELITE PLUMBING. • NO NEW BRANCH CIRCUIT LOADS SHALL BE ADDED TO HOUSE PANEL UNDER THIS SCOPE OF WORK. tLtUl INIUAL LtUtNU:(SOME SYMBOLS SHOWN MAY NOT SYMBOL SURFACE MOUNT 12DA240V, 10.3 -WORE PANELBOARD EXISTING O O SURFACE MOUNT 277/48OV, 30,4 -WIRE PANELBOARD 200 AMP EXISTING -�-- UTILITY METER CAN OR METER/MAIN COMBO UNIT SUB -PANEL 20D AMP O POINT OF NEW CONNECTION © ETER/MAIN 0 314"PVC W/WTI #19 THHN CU NOTE. O 120/2401 n _-_- 0.8 EXISTING GENERATOR: AIR COOLED GENERAC 221(W M"EE AREAStR GRADE EXISTING (2)518"X8'--...__ T CU GROUND RODS EXTERIOR SCOPE OF WORK: • INSTALL NEW BATTERY IN EXISTING GENERATOR. • INSTALL NEW CHARGING CIRCUIT TO EXISTING GENERATOR. • ANCHOR EXISTING GENERATOR TO EXISTING CONCRETE PAD FOR GENERATOR. • PROVIDE AND I NSTALL CONDUIT AND CONDUCTORS FROM ATS TO GENERATOR. • INSTALL NEW REGULATOR FOR EXISTING PROPANE SUPPLY. • GENERATOR GAS CONNECTION BY ELITE PLUMBING. • NO NEW BRANCH CIRCUIT LOADS SHALL BE ADDED TO HOUSE PANEL UNDER THIS SCOPE OF WORK. tLtUl INIUAL LtUtNU:(SOME SYMBOLS SHOWN MAY NOT SYMBOL SURFACE MOUNT 12DA240V, 10.3 -WORE PANELBOARD --F-7-- FLUSH MOUNT 120124OV, 10, 3 -WARE PANELBOARD O SURFACE MOUNT 277/48OV, 30,4 -WIRE PANELBOARD O I FLUSH MOUNT 277/480V, 30, 4 -WIRE PANELS 4RD -�-- UTILITY METER CAN OR METER/MAIN COMBO UNIT --®-- SURFACE MOUNT AUTOMATIC TRANSFER SWITCH O POINT OF NEW CONNECTION INTERIOR EXISTING JUNCTION BOX IED FLOOR INTERIOR INTERIOR - EXTERIOR _.... -_ ATTIC EXISTING 100 AMP NON -SE RATED ATS/18 CIRCUIT PANEL. -- EXTERIOR GRADE N TO THIS PROJECT). FRAME SIZE -,JV 3`af HEMARATiNO NON-FUSED DISCONNECT L\-NONFUSEP FRAME SRE mal SRAFaq AcceornNO FUSEDDISCONNECT FUSE SIZE GENERATOR AND GENERATORPAD T=D GAS STORAGE TANK I® NATURAL GAS METER 1 GROUND ROD •� THE ELECTRICAL CONTRACTOR SHALLVERIFY AND COORDINATE ALL ELECTRICAL SERVICE ROUGH IN AND INSTALLATION • THIS ELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE 6TH EDITION (2017), LOCAL ORDINANCE, AND THE NATIONAL ELECTRIC CODE THIRTEENTH EDITION NFPA 70(2014). • ALL ELECTRICAL WORK FOR THE ENTIRE PROJECT SHALL BE PERFORMED IN A NEAT AND CRAFTSMAN LIKE MANNER BY PERSONS SKILLED IN THE ELECTRICAL TRADE, AND SHALL BE DONE UNDER THE SUPERVISION OF A MASTER ELECTRICIAN LICENSED IN THE STATE OF FLORIDA. • THIS ELECTRICAL INSTALLATION SHALL BE PROTECTED FROM PHYSICAL DAMAGE AND SECURELY SUPPORTED AND FASTENED, WITH WORKING SPACE PER NEC 110.26. • PVC SCHEDULE 40 CONDUIT SHALL BE USED UNDERGROUND, I N OR BELOW CONCRETE AND WHERE EXPOSED NOT SUBJECT TO DAMAGE. PVC SCHEDULE 80 CONDUIT SHALL BE USED WHERE EXPOSED, SUBJECT TO DAMAGE. • ALL MATERIAL SHALL BE NEW, FR HE FROM DEFECT AND SHALL BE LISTED AND BEAR THE LABEL OF A RECOGNIZED TESTING LABORATORY. • GROUNDING PER NEC ARTICLE 250. • STANDBY SYSTEM INSTALLATION PER NEC ARTICLE 702, AND MANUFACTURER INSTALLATION INSTRUCTIONS, LOAD MANAGEMENT "LCM' LOAD SHED LOAD MANAGEMENT TECHNOLOGY ALLOWS THE LOAD CONTROL MODULE TO MONITOR GENERATOR PERFORMANCE AND ONLY SHED LOADS WHEN ABSOLUTELY NECESSARY BY MONITORING GENERATOR CURRENT AND FREQUENCY. BY ONLY SHEDDING THE NONESSENTIAL CIRCUITS, THE ESSENTIAL CIRCUITS ARE ALWAYS POWERED, LOADS ARE SHED THROUGH INTERRUPTION OF INDIVIDUAL CONTROL CIRCUITS (AHU/AC) AND POWER CIRCUITS (RANGE AND WATER HEATER), 1 GENERATOR ADDITION RISER DIAGRAM Nl'S GENERAL NOTES: 1. LIGHT LINE WORK REPRESENTS EXISTING TO REMAIN. 2. DARK AND RED LINE WORK REPRESENT NEW EQUIPMENT, CONDUIT, AND WIRE. CONDUIT AND WIRE SCHEDULE SYMBOL DESCRIPTION Propane __.. EXISTING 2"PVC UNDERGROUND SERVICE FEEDER O EXISTING OVERHEAD SERVICE RISER, WEATHERHEAD, AND UTILITY FEEDERS O EXISTING 1/2"PVC W1(1) #4 BARE CU O EXISTING 2"PVC W/ 13) #4/0 THWN AL O EXISTING 2 -PVC W1(3)#1 THWN AL, (1) N8 THHN CU GROUND O 1414 -PVC SLEEVE WI GENERAC CABLE WI (3) #3 THHN CU, (1) #8 THHN CU GROUND, 151414THHN CU © I-1I4"PVC W1(3)#3 THHN CU, (1)#8 THHN CU GROUND 0 314"PVC W/WTI #19 THHN CU NOTE. O 112"PVC WI(1)#4 BARE CU NOTE: NOTALL CONDUIT AND WIRE SHOWN ON THIS SCHEDULE MAY PERTAIN TO THIS PROJECT. COMPLETE ELECTRIC INC. 637 SEBASTIAN BLVD. SEBASTIAN, FL 32958 (772)388-0533 Sizing Report Rated Nominal Village 240 Generator Fuel Choice Propane Sizing Method! (NEC 220) Peel IV (Pan In requhed lar selected cirwlt Implemourvpry BON velid for hot. house) General Ughling&Rarordacies 109 Scoare Footage Being Covered(d"2) 1916 Small Appliance Circuits (20 amps) NEC Kitchen Circuits 2 Laundry cianits 0 GENERC Load (IAN) 5,754 0 Fuad In Piam Appllanoes& Motors Managed Loads Estimated B" Namepreta (amps) 240V Wad(kI M'.SA largesl Motm§Sam, A., (IRA) 1.3 109 109 1.3 flaingarator NEC 0.8 Summary NEC Load (kW) 0.8 Relrgeretor Genemi Lighting &Receptacles 0.8 0.8 26 Managed Estimated Nameplate 11.6 10.6 Ar CoMOionin &Reg Loads AiAl (amps) 240V. Land h 4.0 Ton Unit 9.6 4.0 Larger of Healing&Coolic, X 4.0 'Managed Estimated Nameplate HAS", & Heat Pumps Leads (kW) (amps) 240 V Land IkRA Heat Pump (4 Ton) 4.0 40 X Be Estimated gctcal Utilized Transiart Requirement (LRA) (LRA) (LRA) largesl Motm§Sam, A., (IRA) 276 109 109 Wad NEC Summary NEC Load (kW) Required Genemi Lighting &Receptacles 8.6 Fixed-ImPlace Appliances& Motors 26 Sum of all General Loads 11.6 10.6 Cooling 00 4.0 Heating("odermad factors) 96 9.6 Larger of Healing&Coolic, 9.6 96 SI,R, based oa requlremenls of NEC Arms 220, Pad IV 20.2 Elevation 0 I Minimum size generale, for motor staging requlremenls 16 BTU loadrequired 355000 22 kW Genese Model Generator Recommended E-1 E-1 ,.-09/1612020 1 QF 2 ro m COC m V a 4L DRILL CLEAN DRI DRILL V4" DEEPER THAN ANCHOR EMBEDMENT DRILL BIT SIZE: 1/2 TIGI NOTE: 1. THE USE OF A CARBIDE DRILL BIT CONFORMING TO ANSI STANDARD 8212,1515 RECOMMENDED, 2. ANCHOR BOLTS TO BE 3/B"DIA.0-314"LONG - UNLESS OTHERWiSE'NOTED. 3-5 X R EMBEDMENT: 2-1 NOTE: 'GENERATOR PAD IS EXISTING TO REMAIN. 'GENERATOR DETAIL IS FOR REFERENCE ONLY 54" /2 32" TOP VIEW V'MIK - 32" LEFT ELEVATION ----2-- 112'pGENERATOR PAD DETAIL 54" FRONT ELEVATION E -2 E-2 SCALE: 1/2—V -B" 09/16/2020 2 OF 2 i (h SCALE: V= IM" 1 I UL 4x— LP VAPOR (LPV) PIPE SIZING (0.5PS1 OR LESS) P11PE SIZE kW 0.75•• 1" L25' I.5� 2" 25" 3" 7-8 165 570 10 70 255 7000 13-14 45 130 690 _- 16-17 25 115 540 20 IS 85 480 --- --- 27 60 365 25 55 275 605 27 40 260 575 30 _ 20 195 435 35-35 IS 125 290 1030 40 107 250 890 45 82 _ 195 725--- 48 -70 165 - 620 50 70 160 610 60 �— 45 -115 445 1095 70 _ 26 60 260 650 80 15 50 230 590 _ _106 30 _ 165 430 1305 130 70 205 650 150 45 150 490 1.E: TpRtE VpWES ME ANXIMVM PIPE RUN IN FEET. 20' 10' (MAX) .._. (MAX) REGULATORCOLUMN ]" WATER COLUMN EXISTING GENERATOR GENERAL FULL LOADAD : EXISTING 5/e COPPER PIPE 142 F1'/HR 3272 FT'/HR GRADE _--__ -._ GRADE EXISTING 3IRON PIPE LP GAS 39898 FN/HR 10 PSI �. PIPING RISER i EP -1 �. 09/16/2020 SCALE: V=10W"