jB's A/C & Electrical, Inc.
2090 N.W.Federal Highway Stuart,FL 3499.4 1 772.634.6315 1 jbrowningac@gmail.com
September 27,2020 �O1
In reference to:
Sancho Residence Mini-Split Addition to Master Suite
Saint Lucie-County RECEIVED
433 SE Gasparilla Avenue OCT 0.1 2020
Port St.Lucie,FL 34983 permitting Department
St. Lucie County
Included within this document:
• HVAC Mini-Split installation location layout
Floor plan layout including location of existing system and new system
Heating&Cooling load schedule
New HVAC system specifications
2017 FBC,Energy Conservation Code conformance statement
• ACCA Manual J,heating&cooling load requirements prior to installation of Mini-Split .
• ACCA Manual J;Heating&Cooling load calculations after installation of Mini-Split
• AHRI Certificate 6,000.(nominal) Btuh Mitsubishi Mini-Split
• ERI Comparison Report for Sancho residence prior to Mini-Split installation
• ERI Comparison Report for Sancho residence after addition of Mini-Split S��E COUNT*
REVIEW
8LDG:
WE:
ELEC:
DAB;
PLUMB;
DAB
. RIEEH: D
DATE:
r
Yee.Y..m.Ha1..rnwruM•�rv.rM+•lam.
uA
'H :;M r
IA
\ I
33'-0!
I
1 V ul�
V • � A CO
LINE OF ROOF OVERHANG (ABOVE 4-J V s 3 M
C "d- CV
dam' r-
1EVIATIONS
COVERED PATIO (LINE FINISHED WALL SURFACE O� 'l I� m
ENING I.D. v 00
MANUAL J CALCULATIONS u z V)
ZING I.D., REF. MANUAL J "*s co
)ING GLASS DOORS TO Q N rn
FRED WINDOWS) N
// z ER I.D. REFERENCE MANUAL J v n
W2 5 ULATIONS M
i I.1.1
LOAD SCHEDULE
o 4 ( ROOM
HEATING COOLING
DINING ROOM SgREft.) (Btuh) (Btuh)
±919 24,354 SENSIBLE:
27,565
LATENT:
3 D2 2,402
TOTAL:
L 29,967 Z
±386 6,996 SENSIBLE: C
7,231 F
LATENT:
665
TOTAL: W O cp co
i 2 7,896 Z a V =
(STEM IS A 36,000 BTUH SYSTEM W Z cc v
0I "D FOR THE HOME WHICH REQUIRES '�_ j
io 00 BTUH, MULTIPLE FAN SPEED y Z y •� J
ILED IN MASTER SUITE WILL W Q •L LL
i ;TING EXCESS LOAD REQUIREMENT. �.. Z c0 t
'STEM WILL REMAIN AS-IS. J G
00. o
OVATION SPECIFICATIONS y W *%
SYSTEM:
Z Z t= cN U
OARA6E )0 BTU/H WALL-MOUNTED HEAT PUMP y V d
IA; OUTDOOR UNIT: MUZ-FH06NA
E NUMBER: 201754426 a
r(-D
. , 1,700 (MIN) - 9,000 (MAX)
—I) (@47'F): 1,600 (MIN), 14,000 (MAX)
i
:ONSERVATION
ING, SECTION 701.2 CONFORMANCE:
tTION THEREOF SHALL NOT BE ALTERED
TOMES LESS SAFE OR ENERGY EFFICIENT
i
IOMPARISON REPORT CALCULATED BY PREPARED BY:
I BC 6TH EDITION CODE COMPLIANCE Kathleen Connolly
13'-0" rION OF THE SANCHO RESIDENCE PRIOR DATE:
HVAC SYSTEM RENCS MINI-SPLIT = 13,432 kWh, ENERGY September 27, 2020
TION OF MINI-SPLIT = 12,392 kWh. SCALE:
OVIDED WITH PERMIT DOCUMENTATION. 3 16" = 1'-O"
SHEET:
NOTE: FLOOR PLAN IS DIAGRAMMORE ENERGY EFFICIENT WITH THE ADDITION 1 OF 1
HEATING & COOLING LOADS DUCTLESS SYSTEMS IN THE MASTER SUITE JOB NO.:
AMONGST DIMENSIONS WILL B200910
I
��osr 3
Residential System .Sizing Calculation
Su-mmary
JESUS AND DANIA SANCHO Project Title:
433 SE Gasparilla Ave SANCHO RESIDENCE EXISTING
Port St. Lucie, FL 34983
9/27/2020
Location for weather data: Fort Pierce, FL -Defaults: Latitude(27.48) Altitude(25 ft.) Temp Range(L)
Humidity data: Interior RH 50% Outdoor wet bulb 78F Humidity difference 62 r.
Winter design temperature(TMY3 99%) 40 F Summer design temperature(TMY3 99%). 91 F
Winter setpoint 70 F Summer setpoint 75 F
Winter ternizierature difference 30` F Summer temperature difference 16 F
Total heating load calculation 31419 Btuh Total cooling load calculation 38066 Btuh
Submitted heating capacity %of calc Btuh Submitted cooling capacity % of calc Btuh
Total (Electric Strip Heat) 114.6 36000 Sensible(SHR=0.75) 68.6 24000
Latent 261.0 8000
Total 84.1 32000
WINTER_ CALCULATIONS
Winter Heating Load for 1305 sqft)
Load component Load
Window total 231 sqft 7815 Btuh ceirngs(1o.o%> .
Wall total. 1248 sqft 9211 Btuh WMows(2a.I%)
Door total 38 sqft 521 Btuh
Ceiling total 1305. sqft 3157 Btuh
Floor total See detail report 6443 Btuh weiis(2s.3%)
Infiltration 26 cfm 868 Btuh
Duct loss 3404 Btuh
Subtotal 31419 Btuh
Ventilation 0 cfm 0 Btuh
TOTAL HEAT LOSS 31419 Btuh CDo (1.7%)
SUMMER CALCULATIONS �100f5(20�5' 'nei.(2.e%'
Summer Cooling Load for 1305 sqft)
Load component Load
Window total 231 sqft 10394 Btuh
Wall total 1248 sqft 6746 Btuh
Door total 38 sqft 539 Btuh Ceilings(12.4%) iNindo is(27.3°,5)
Ceiling total 1305 sqft 4736 Btuh
Floor total 0 Btuh
Infiltration 20 cfm 347 Btuh
Internal gain 8950 Btuh
Duct gain. 3290 Btuh Walls(17:7%}
Sens.Ventilation 0 cfrn 0 Btuh
Blower Load .0 Btuh Latentint(3.4%)
Total sensible gain 35001 Btuh
Latent gain(ducts) 934 Btuh
Latent gain(infiltration) 832 Btuh
Latent gain(ventilation) 0 Btuh Infil.(3.1%) Int.Gain(23.5%)
Latent-gain(internal/occupants/other) 1300 Btuh Ducts(11.1%)
Total latent gain 3065 Btuh
TOTAL HEAT GAIN 38066 Btuh
EnergyGauge®Sy a i,
8th Edition PREPARED BY:
DATE: 2v
EnergyGauge®/USRCZB v6.1.04
i
�,
,.
System Sizing Calculations- - Winter
Residential Load - Whole House Component Details
JESUS AND DANIA SANCHO Project Title:
433 SE Gasparilla Ave SANCHO RESIDENCE EXISTING
Port St. Lucie, FL 34983 Building Type: User
9/27/2020
Reference City: Fort Pierce, FL (Defaults) Winter Temperature Difference: 30.0 F (TMY3 99%)
Component Loads for Whole House
Window Panes/Type Frame U Orientation Area s ft X HTM= Load
1 1, Clear Metal 1.13 SE 66.7 33.9 2260 Btuh
2 1, Clear Metal 1.13 NW 40.0 33.9 1356 Btuh
3 1, Clear Metal 1.13 NW 18.0 33.9 610 Btuh
4 1, Clear Metal 1.13 NW 40.0 33.9 1356 Btuh
5 1, Clear Metal 1.13 NE 12.5 33.9 424 Btuh
6 1, Clear Metal 1.13 NE 6.0 33.9 203 Btuh
7 1, Clear Metal 1.13 NE 6.0 33.9 203 Btuh
8 1, Clear Metal 1.13 NE 12.5 33.9 424 Btuh
9 1, Clear Metal 1.13 SE 16.4 33.9 555-13tuh.
10 1, Clear Metal 1.13 SW 12.5 33.9 424 Btuh
Window Total 230.5 s ft 7815 Btuh
Walls Type Omt. Ueff.. R-Value Area X HTM= Load
(Cav/Sh)
1 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 89 8.33 744 Btuh
2 Frame -Wood -Adj (0.095) 11.0/0.0 133 2.85 379 Btuh
3 Frame - Wood -Adj (0.095) 11.0/0.0 84 2.85 238 Btuh
4 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 80 8.33 666 Btuh
5 Conc BIk,Hollow - Ext (0.278) 1.0/0.0 232 8.33 1933 Btuh
6 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 88 8.33 733 Btuh
7 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 120 8.33 1000 Btuh
8 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 190 8.33 1584 Btuh
9 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 117 8.33 973 Btuh
10 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 88 8.33 730 Btuh
11 Conc BIk,Hollow - Ext (0.278) 1.0/0.0 28 8.33 229 Btuh
Wall Total 1248 s ft 9211 Btuh
Doors Type Storm Ueff. Area X HTM= Load
1 Insulated-Exterior, n (0.460) 20 13.8 276 Btuh
2 Wood -Garage, n (0.460) 18 13.8 245 Btuh
Door Total 38 s ft 521 Btuh
Ceilings Type/Color/Surface Ueff. R-Value Area.X HTM= Load
1 Vented Attic/L/Shing (0.081) 11.0/0.0 919 2.4 2223 Btuh
2 Vented Attic/L/Shirig (0-.081) 11.0/0.0 386 2.4 934 Btuh
Ceiling Total 1305 s ft 315713tuh
Floors Type Ueff. R-Value Size X HTM= Load
1 Slab On Grade (1.180) 0.0 130.0 ft(perim.) 35.4 4602 Btuh
2 Slab On Grade (1.180) 0.0 52.0 ft(perim.) 35.4 1841 Btuh
Floor Total 1305 s ft 6443 Btuh
Envelope Subtotal: 27147 Btuh
EnergyGauge®/USRCZB v6.1.04 Page 1
i .
Manual J WinterCalculations
Residential Load Component Details (continued)
JESUS AND DANIA SANCHO Project Title:
433 SE Gasparilla Ave SANCHO RESIDENCE EXISTING
Port St. Lucie, FL 34983 Building Type: User
9/27/2020
Infiltration Type Wholehouse ACH Volume(cuft) Wall Ratio CFM=
Natural 0.15 10440 1.00 26.3 868 Btuh
Duct load Average sealed, R6.0, Supply(Att), Retum(Att) (DLM of 0.122)_ 3404 Btuh
All Zones Sensible Subtotal All Zones 31419 Btuh
HOLE HOUSE TOTALS
Subtotal Sensible Heat Loss 31419 Btuh
Totals for Heating Ventilation Sensible Heat Loss 0 Btuh
Total Heat Loss 31419 Btuh
EQUIPMENT
1. Electric Strip Heat 36000 Btuh
Key:Window types-NFRC(Requires U-Factor and Shading coefficient(SHGC)of glass as numerical values)
or-Glass as'Clear'.or Tint'(Uses U-Factor and SHGC defaults)
U-(Window U-Factor)
HTM-(ManualJ Heat Transfer Multiplier)
Version 8
EnergyGauge®/USRCZB v6.1.04 Page 2
System Sizing Calculations - Summer
Residential Load - Whole House Component Details
JESUS AND DANIA SANCHO Project Title:
433 SE Gasparilla Ave SANCHO RESIDENCE EXISTING
Port St. Lucie, FL 34983
9/27/2020
Reference City: Fort Pierce, FL Temperature Difference: 16.OF(TMY3 99%) Humidity difference: 62gr.
Component Loads for Whole House
Type` Overhang Window Area(sqft) HTM Load
Window Panes SHGC U InSh IS Omt Len H t Gross Shaded Unshaded Shaded Unshaded
1 1 Clear 0.74,1.13 B-L No SE 10.Of 2.Oft 66.7 66.7 0.0 24 44 1588 Btuh
2 1 Clear 0.74,1.13 B-L No NW 10.Of 2.Oft 40.0 0.0 40.0 24 42 1692 Btuh
3 1 Clear 0.74,1.13 B-L No NW 10.01' 2.Oft 18.0 0.0 18.0 24 42 761 Btuh
4 1 Clear 0.74,1.13 _B-L No NW 10.01' 2.Oft 40.0 0.0 40.0 24 42 1692 Btuh
5 1 Clear 0.74,1.13 B-L No NE 2.Oft 2.0ft 12.5 0.0 12.5 24 42 529 Btuh
6 1 Clear 0.74,1.13 B-L No NE 2.Oft 2.Oft 6.0 0.0 6.0 24 42 254 Btuh
7 1 Clear 0.74,1.13 B-L No NE 2.Oft 2.Oft 6.0 0.0 6.0 24 42 254 Btuh
8 1 Clear 0.74,1.13 B-L No NE 2.Oft 2.Oft 12.5 0.0 12.5 24 42 529 Btuh
9 1 Clear 0.74,1.13 B-L No SE 2.Oft 2.Oft 16.4 4.8 11.5 24 44 622 Btuh
10 1 Clear 0.74,1.13 B-L No SW 10.Of 2.Oft 12.5 12.5 0.0 24 44 298 Btuh
Excursion 2177 Btuh
Window Total 231 (sqft) 10394 Btuh
Walls Type U-Value R-Value Area(sqft) HTM Load
Cav/Sheath
1 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 89.3 6.2 556 Btuh
2 Frame-Wood-Adj 0.09 11.0/0.0 133.3 1.5 202 Btuh
3 Frame-Wood-Adj 0.09 11.0/0.0 83.6 1.5 127 Btuh
4 Concrete Blk,Hollow-Ext 0.28 1.0/0.0. 80.0 6.2 498 Btuh
5 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 232.0 6.2 .1443 Btuh
6 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 88.0 6.2 547 Btuh
7 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 120.0 6.2 746 Btuh
8 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 190.2 6.2 1183 Btuh
9 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 116.8 6.2 727 Btuh
10 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 87.6 6.2 545 Btuh
11 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 27.5 6.2 171 Btuh
Wall Total 1248 (sqft) 6746 Btuh
Doors Type Area (sqft) HTM Load
1 Insulated-Exterior 20.0 14.3 285 Btuh
2 Wood-Garage 17.8 14.3 254 Btuh
Door Total 38(sqft) 539 Btuh
Ceilings_ Type/Color/Surface U-Value R-Value Area(sqft) HTM Load
1 Vented Attic/Light/Shingle 0.081 11.0/0.0 919.0 3.63 3335 Btuh
2 Vented Attic/Light/Shingle 0.081 11.0/0.0 386.0 3.63 1401 Btuh
Ceiling Total 1305 (sqft) 4736 Btuh
Floors Type R-Value Size HTM Load
1 Slab On Grade 0.0 919(ft-perimeter) 0.0 0 Btuh
2 Slab On Grade 0.0 386(ft-perimeter) 0.0 0 Btuh
Floor Total 1305.0 (sqft) 0 Btuh
Envelope Subtotal: 22415 Btuh
EnergyGauge®/USRCZB v6.1.04 Page 1
1
Manual J Summer Calculations
Residential Load -Component Details (continued)
JESUS AND DANIA SANCHO Project Title: Climate:FL VERO_BEACH_MUNICIPAL A
433 SE Gasparilla Ave SANCHO RESIDENCE EXISTING
Port St. Lucie, FL 34983
9/27/2020
Infiltration Type Average ACH Volume(cuft)Wall Ratio CFM= Load
Natural 0.11 10440 1 19.7 347 Btuh
Internal Occupants Btuh/occupant Appliance Load
gain 5 X 230 + 7800 . 8950 Btuh
Sensible Envelope.Load: 31712 Btuh
Duct load. Average sealed,Supply(R6.0-Attic),Retum(RU-Attic) (DGM of 0.104) 3290 Btuh
Sensible Load All Zones 35001 Btuh
0
EnergyGauge®/USRCZB v6.1.04 Page 2
Manual J Summer Calculations
Residential Load - Component Details (continued)
JESUS AND DANIA SANCHO Project Title: Climate:FL VERO_BEACH_MUNICIPAL_A
433 SE Gasparilla Ave SANCHO RESIDENCE EXISTING
Port St. Lucie, FL 34983
9/27/2020
WHOLE HOUSE TOTALS
Sensible Envelope Load All Zones 31712 Btuh
Sensible Duct Load 3290 Btuh
Total Sensible Zone Loads 35001 Btuh
Sensible ventilation 0 Btuh
Blower 0 Btuh
Whole House Total sensible gain 35001 Btuh
Totals for Cooling Latent infiltration gain (for 62 gr. humidity difference) 832 Btuh
Latent ventilation gain 0 Btuh
Latent duct gain 934 Btuh
Latent occupant gain (5.0 people @ 200 Btuh per person) 1000 Btuh
Latent other gain 300 Btuh
Latent total gain 3065 Btuh
TOTAL GAIN 38066 Btuh
EQUIPMENT
1-Central Unit TGoodman# 32000 Btuh
'Key: Window types(Panes-Number and type of panes of glass)
(SHGC-Shading coefficient of glass as SHGC numerical value)
(U-Window U-Factor)
(InSh-Interior shading device:norie(No),Blinds(B),Draperies(D)or Roller Shades(R))
- For Blinds:Assume medium color,half closed
For Draperies:Assume medium weave,half closed
For Roller shades:Assume translucent,half closed
(IS-Insect screen:none(N),Full(F)or Half(%:))
(Ornt-compass orientation)
Version 8
EnergyGauge®/USRCZB v6.1.04 Page 3
System Sizing Calculations Winter.
Residential Load - Room by Room Component Details
JESUS AND DANIA SANCHO Project Title:
433 SE Gasparilla Ave SANCHO RESIDENCE EXISTING
Port St. Lucie, FL 34983 Building Type: User
9/27/2020
Reference City: Fort Pierce, FL (Defaults) Winter Temperature Difference: 30.0. F(TMY3 99%)
Comm-ponent,Loads4or'ft rn 41: Main
Window Panes/Type Frame U Orientation Area s ft X HTM= Load
1 1, Clear Metal 1.13 SE 66.7 33.9 2260 Btuh
2 1, Clear Metal 1.13 NW 40.0 33.9 1356 Btuh
3 1, Clear Metal 1.13 NW 18.0 33.9 610 Btuh
4 1, Clear Metal 1.13 NW 40.0 33.9 1,356 Btuh
7 1, Clear Metal 1.13. NE . 6.0 33.9 .203 Btuh
8 1, Clear Metal 1.13 NE . 12.5 33.9 424 Btuh
9 1, Clear Metal 1.13 SE 16.4 33.9 555 Btuh
10 1, Clear Metal 1.13 SW, 12.5 33.9 424 Btuh
Window Total 212.0 s ft 7188 Btuh
Walls Type Omt. Ueff. R-Value Area X HTM= Load
(Cav/Sh)
1 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 89 8.33 744 Btuh
2 Frame -Wood, -Adj (0.095) 11.0/0.0 133 2.85 379 Btuh
3 Frame-Wood -Adj (0.095) 11.0%0.0 84 2.85 238 Btuh
4 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 80 8.33 666 Btuh
5 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 232 8.33 1933 Btuh "
9 . Conc Blk,Hollow - Ext (0.278) 1.0/0.0 117 .8.33 973 Btuh
10 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 88 8.33 730 Btuh
11 Conc Blk,H0116W - Ext (0.278) 1.0/0.0 28 8.33 229 Btuh
Wall Total 850 s ft 5894 Btuh
Doors Type Storm Ueff. Area X- HTM= Load
1 Insulated-Exterior, n (0.460) 20 13.8 276 Btuh
2 'Wood - Garage, n , (0.460) 18 13.8 245 Btuh
Door Total 38(s ft 521 Btuh
Ceilings Type/Color/Surface Ueff. R-Value Area X HTM= Load
1 Vented Attic/L/Shing (0.081) 11.0/0.0 919 2.4 2223 Btuh
Ceilin Total 919 s ft 222313tuh
Floors Type . Ueff. R-Value Size X HTM= Load
1 Slab On Grade (1.180) 0.0 130.0 ft(perim.) 35.4 4602 Btuh
Floor Total 919 s ft 4602 Btuh
Room Envelope Subtotal: 20428 Btuh
Infiltration Type Wholehouse ACH Room Volume Wall Ratio CFM=
Natural 0.15 7352 0.68 11.9 591 Btuh
Duct load Average sealed,Supply(R6.0-Attic),Retum(R6.0-Attic) (DLM of 0.122). 2554 Btuh
Room#1 Sensible Room Subtotal 23573 Btuh
/ EnergyGauge®/USRCZB v6.1.04 Page 1
Manual J Winter Calculations
Residential Load - Component Details (continued)
JESUS AND DANIA SANCHO Project Title: .
433 SE Gasparilla Ave SANCHO RESIDENCE EXISTING
Port St. Lucie, FL 34983 Building Type: User
9/27/2020
Component Loads for Room#2: MASTER SUITE
Window Panes/Type Frame U Orientation Area s ft X HTM= Load
5 1, Clear Metal 1.13 NE 12.5 33.9 424 Btuh
6 1, Clear Metal 1.13. NE 6.0 33.9 203 Btuh
Window Total 18.5 s ft .627 Btuh
Walls Type Omt. Ueff. R-Value . Area X HTM= Load
(Cav/Sh)
6 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 88 8.33 733 Btuh
7 Conc Blk,Hollow -Ext (0.278) 1.0/0.0 120 8.33 1000 Btuh
8 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 190 8.33 1584 Btuh
Wall Total 398 s ft 3317 Btuh
Ceilings Type/Color/Surface Ueff. R-Value Area X HTM= Load
2 Vented Attic/UShing (0.081) 11.0/0.0 386 2.4 934 Btuh
Ceiling Total 386 s ft 93413tuh
Floors Type Ueff. R-Value Size X HTM= Load
2 Slab On Grade (1.180) 0.0 52.0 ft(perim.) 35.4 1841 Btuh
Floor Total 386 s ft 1841 Btuh
Room Envelope Subtotal: 6719 Btuh
Infiltration Type Wholehouse ACH Room Volume Wall Ratio CFM=
Natural 0.15 3088 0.32 8.4 277 Btuh
Duct load .Average sealed,Supply(R6.0-Attic),Retum(R6.0-Attic) (DLM of 0.122) 850 Btuh
Room#2 Sensible Room Subtotal 7846 Btuh
HOLE HOUSE TOTALS
Subtotal Sensible Heat Loss 31419 Btuh
Totals for Heating Ventilation Sensible Heat Loss 0 Btuh
Total Heat Loss 31419 Btuh
EnergyGauge®/USRCZB v6.1.04 Page 2
Manual J Winter Calculations
Residential Load - Component Details (continued)
JESUS AND DANIA SANCHO Project Title:
433 SE Gasparilla Ave SANCHO RESIDENCE EXISTING
Port St. Lucie, FL 34983 Building Type: User
9/27/2020
- EQUIPMENT
1. Electric Strip Heat 36000 Btuh
Key:Window types-NFRC(Requires U-Factor and Shading coefficient(SHGC)of glass as numerical values)
or-Glass as'Clear or Tint'(Uses U-Factor and SHGC defaults)
U-(Window U-Factor)
HTM-(ManualJ Heat Transfer Multiplier)
Version 8
• '1
EnergyGauge®/USRCZB v6.1.04 t Page 3
System Sizing Calculations - Summer
Residential Load - Room by Room Component Details
JESUS AND DANIA SANCHO Project Title:
433 SE Gasparilla Ave SANCHO RESIDENCE EXISTING
Port St. Lucie, FL 34983
9/27/2020
Reference City: Fort Pierce, FL Temperature Difference: 16.OF(TMY3 99%) Humidity difference: 62gr.
Component_Loads for Room#1: Main•
Type* Overhang Window Area(sqft) HTM Load
'Window Panes SHGC U InSh IS Omt Len H t Gross Shaded Unshaded Shaded Unshaded .
1 1 Clear 0.74,1.13 B-L No SE 10.0f 2.Oft 66.7 66.7 0.0 24 44 1588 Btuh
2 1 Clear 0.74, 1.13 B-L No NW 10.0f 2.Oft 40.0 0.0 40.0 24 42 1692 Btuh
3 1 Clear 0.74,1.13 B-L No NW 10.0f 2.Oft 18.0 0.0 18.0 24 42 761 Btuh
4 1 Clear 0.74,1.13 .B-L No NW 1.0.0f 2.Oft 40.0 0.0 40.0 24 42 1692 Btuh
7 1 Clear 0.74,1.13 B-L No NE 2.Oft 2.Oft 6.0 0.0 6.0 24 42 254 Btuh
8 1 Clear 0.74, 1.13 B-L No NE 2.Oft 2.Oft 12.5 0.0 12.5 24 42 529 Btuh
9 1 Clear 0.74,1.13 B-L No SE 2.Oft 2.Oft 16A 4.8 11.5 24 44 622 Btuh
10 1-Clear 0.74,1.13 B-L No SW 10.0f 2.Oft 12.5 12.5 0.0 24 44 298 Btuh
Window Total 212(sqft) 7435 Btuh
Walls Type U-Value R-Value Area(sqft) HTM Load
Cav/Sheath
1 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 89.3 6.2 556 Btuh
2 •Frame-Wood-Adj 0.09 11.0/0.0 133.3 1.5 202 Btuh
3 Frame-Wood-Adj 0.09 11.0/0.0 83.6 1.5 127 Btuh
4 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 80.0 6.2 498 Btuh
5 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 232.0 6.2 1443 Btuh
9 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 116.8 6.2 727 Btuh
10 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 87.6 6.2 545 Btuh
11 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 27.5 6.2 171 Btuh
Wall Total 850 (sqft) 4269 Btuh
Doors Type Area (sqft) HTM Load
1 Insulated-Exterior 20.0 14.3 285 Btuh
2 Wood-Garage 17.8 14.3 254 Btuh
Door Total 38 (sqft) 539 Btuh
Ceilings_ Type/Color/Surface U-Value R-Value Area(sqft) HTM Load
1 Vented Attic/Light/Shingle 0.081 11.0/0.0 919.0 3.63 3335 Btuh
Ceiling Total 919 (sqft) 3335 Btuh
Floors Type R-Value Size HTM Load
1 Slab On Grade 0.0 919(ft-perimeter) 0.0 0 Btuh
Floor.Total 919.0 (sqft) 0 Btuh
Zone Envelope Subtotal: 15577 Btuh
Infiltration Type Wholehouse ACH Volume(cuft)Wall Ratio CFM= Load
Natural 0.11 . 7352 0.68 13.4 236 Btuh
Internal Occupants Btuh/occupant Appliance Load
gain 3 X 230 + 5800 6490 Btuh
Sensible Envelope Load: 22304 Btuh
Duct load Average sealed,Supply(R6.0-Attic),Retum(R6.0-Attic) (DGM of 0.104) 2314 Btuh
Sensible Zone Load 24617 Btuh
EnergyGauge®/USRCZB v6.1.04 Page 1
Manual J Summer Calculations
Residential Load - Component Details (continued)
JESUS AND DANIA SANCHO Project Title: Climate:FL_VERO_BEACH_MUNICIPAL_A
433 SE Gasparilla Ave SANCHO RESIDENCE EXISTING
Port St. Lucie, FL 34983
9/27/2020
Component Loads for Room#2: MASTER SUITE
Type" Overhang Window Area(sgft) HTM Load
Window Panes SHGC U InSh IS Omt Len H t Gross Shaded Unshaded Shaded Unshaded
5 1 Clear 0.74, 1.13 B-L No NE 2.Oft 2.Oft 12.5 0.0 12.5 24 42 529 Btuh-
6 1 Clear 0.74,1.13 B-L No NE 2.Oft 2.Oft 6.0 0.0 6.0 24 A2 254 Btuh
Window Total 19 (sqft) 782 Btuh
Walls Type U-Value R-Value Area(sqft) HTM Load
Cav/Sheath
6 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 88.0 6.2 547 Btuh
7 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 120.0 6.2 746 Btuh
8 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 190.2 6.2 1183 Btuh
Wall Total 398 (sqft) 2477 Btuh
Ceilings Type/Color/Surface U-Value R-Value Area(sqft) HTM Load
2 Vented Attic/Light/Shingle 0.081 11.0/0.0 386.0 3.63 1401 Btuh
Ceiling Total 386 (sqft) 1401 Btuh
Floors Type R-Value Size HTM Load
2 Slab On Grade 0.0 386(ft-perimeter) 0.0 0 Btuh
Floor Total 386.0 (sqft) 0 Btuh
Zone Envelope Subtotal: 4660 Btuh
Infiltration Type Wholehouse ACH Volume(cuft) Wall Ratio CFM= Load
Natural 0.11 3088 0.32 6.3 111 Btuh
Internal Occupants Btuh/occupant Appliance Load
gain 2 X 230 + 2000 2460 Btuh
Sensible Envelope Load: 7231 Btuh
Duct load Average sealed,Supply(R6.0-Attic),Retum(R6.0-Attic) (DGM of 0.104) 750 Btuh
Sensible Zone Load 7981 Btuh
The following window Excursion will be assigned to the system loads.
Windows July excursion for System 1 2177 Btuh
Excursion Subtotal: 2177 Btuh
EnergyGauge®/USRCZB v6.1.04 Page 2
Manual J Summer Calculations
Residential Load - Component Details (continued)
JESUS AND DANIA SANCHO Project Title: Climate:FL_VERO_BEACH_MUNICIPAL A
433 SE Gasparilla Ave SANCHO RESIDENCE EXISTING
Port St. Lucie, FL 34983
9/27/2020
Duct load 226 Btuh
Sensible Excursion Load 2403 Btuh
EnergyGauge®/USRCZB v6.1.04 Page 3
..k
Manual J Summer Calculations .
Residential Load - Component Details (continued)
JESUS AND DANIA SANCHO Project Title: Climate:FL VERO_BEACH_MUNICIPAL_A
433 SE Gasparilla Ave SANCHO RESIDENCE EXISTING
Port St. Lucie, FL 34983
9/27/2020
F
WHOLE HOUSE TOTALS
Sensible Envelope Load AII.Zones 31712 Btuh
Sensible•Duct Load 3290 Btuh
Total Sensible Zone Loads 35001 Btuh
Sensible ventilation 0 Btuh
Blower 0 Btuh
Whole House Total sensible gain 35001 Btuh
Totals for Cooling Latent infiltration gain (for 62 gr. humidity difference) 832 Btuh
Latent ventilation gain 0 Btuh
Latent duct gain 934 Btuh
Latent occupant gain (5.0 people @ 200 Btuh per person) 1000 Btuh
Latent other gain 300 Btuh
Latent total gain 3065 Btuh
TOTAL GAIN 38066 Btuh
a
EQUIPMENT
1-Central Unit Goodman# 32000 Btuh
`Key: Window types(Panes-Number and type of panes of glass)
(SHGC-Shading coefficient of glass as SHGC numerical value)
(U-Window U-Factor)
(InSh-Interior shading device:none(No),Blinds(B),Draperies(D)or Roller Shades(R))
- For Blinds:Assume medium color,half closed
For Draperies:Assume medium weave,.half closed
For Roller shades:Assume translucent,half closed
(IS-Insect screen:none(N),Full(F)or Half(%))
(Omt-compass orientation)
Version 8
EnergyGauge®/USRCZB v6.1.04 Page 4
Residential System Sizing Calculation
Summary
JESUS AND DANIA SANCHO Project Title: -
433 SE Gasparilla Ave SANCHO RESIDENCE MINISPLIT
Port St. Lucie, FL 34983
9/27/2020
Location for weather data: Fort.Pierce, FL -Defaults: Latitude(27.48) Altitude(25 ft.) Temp Range(L)
Humidity data: Interior RH 50% Outdoor wet bulb 78F Humidity difference 62 r.
Winter design temperature(TMY3 99%) 40 .F Summer design temperature(TMY3 99%) 91 F
Winter setpoint 70. F Summer setpoint 75 F
Winter tem erature difference 30 F Summer temperature difference 16 F
Total heating load calculation 31349 Btuh Total cooling load calculation 37863 Btuh
Submitted heating capacity % of talc Btuh Submitted cooling capacity %of talc Btuh
Total (Electric Strip Heat) 134.0 42000 Sensible(SHR=0.75) 81.9 28500
Latent 309.7 9500
Total 100.4 38000
WINTER CALCULATIONS
Winter HeatingLoad for 1305 sqft) '
Load component Load
Window total 231 sqft 7815 Btuh caings(to.1%)
Wall total 1248 sqft 9211 Btuh windo�
Door total 38 sqft 521 Btuh
Ceiling total 1305 sqft 3157 Btuh
Floor total See detail report 6443 Btuh Walls(29.455)
Infiltration 26 cfm 868 Btuh
Duct loss 3335 Btuh
Subtotal 31349, Btuh ou�cs(to.s%)
Ventilation 0 cfm 0 Btuh
TOTAL HEAT LOSS 31349 Btuh
C000rs(t.7%)
SUMMER CALCULATIONS Floors(2D.s%) Infil.(2.8%)
Summer Cooling Load for 1305 sqft)
Load component Load
Window total 231 sqft 10148 Btuh
Wall total 1248 sqft 6746 Btuh
Door total 38 sqft 539 Btuh ceilings(12b%)
Ceiling total 1305 sqft 4736 Btuh Windaris(26.8%)
Floor total 0 Btuh
Infiltration 20 cfm 347 Btuh
Internal gain 8950 Btuh
Duct gain 3330 Btuh Walls(17.8 )
Sens.Ventilation 0 cfm 0. Btuh
Blower Load 0 Btuh LLA Latentint(3.4°5)
Total sensible gain 34795 Btuh
Latent gain.(ducts) 936 Btuh Doors(1.4%)
Latent gain(infiltration)" 832 Btuh
Latent gain(ventilation) 0 Btuh Infil.(3.1%)
Int.Gain(23.6%)
Latent ain intemal/occu ants/other 1300
9 Btuh
( P ) Ducts 11.3
Total latent gain 3067 Btuh
TOTAL HEAT GAIN 1 37863 Btuh
EnergyGauge®Sy to
8th Edition PREPARE
DATE:
EnergyGauge®/USRCZB v6.1.04
i
System Sizing Calculations - Winter
Residential Load - Whole House Component Details
JESUS AND DANIA SANCHO Project Title:
433 SE Gasparilla Ave SANCHO RESIDENCE MINISPLIT
Port St. Lucie, FL 34983. Building Type: User
9/27/2020
Reference City: Fort Pierce, FL (Defaults) Winter Temperature Difference: 30.0 F (TMY3 99%)
Component Loads for Whole House
Window Panes/Type Frame U Orientation Area s ft X HTM= Load
1 1, Clear Metal 1.13 SE 66.7 33.9 2260 Btuh
2 1, Clear Metal 1.13 NW 40.0 33.9 1356 Btuh
3 1, Clear Metal 1.13 NW 18.0 33.9 610 Btuh
4 1, Clear Metal 1.13 NW 40.0 33.9 1356 Btuh
5 1, Clear Metal 1.13 NE 12.5 33.9 424 Btuh
6 1, Clear Metal 1.13 NE 6.0 33.9 203 Btuh
7 1, Clear . Metal 1.13 NE 6.0 33.9 203 Btuh
8 1, Clear Metal 1.13 NE 12.5 33.9 424 Btuh
9 1, Clear Metal 1.13 SE 16.4 33.9 555 Btuh
10 1, Clear Metal 1.13 SW 12.5 33.9 424 Btuh
Window Total 230.5 s ft 7815 Btuh
Walls Type Omt. Ueff. R-Value Area X HTM= Load
(Cav/Sh)
1 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 89 8.33 744 Btuh
2 Frame -Wood -Adj (0.095) 11.0/0.0 133 2.85 379 Btuh
3 Frame -Wood -Adj (0.095) 11.0/0.0 84 2.85 238 Btuh
4 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 80 8.33 666 Btuh
5 Conc BIk,Hollow - Ext (0.278) 1.0/0.0 232 8.33 1933 Btuh
6 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 88 8.33 733 Btuh
7 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 120 8.33 1000 Btuh
8 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 190 8.33 1584 Btuh
9 Conc Blk,Hollow -Ext (0.278) 1.0/0.0 117 8.33 973 Btuh
10 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 88 8.33 _ 730 Btuh
11 Conc Blk,Hollow - Ext, (0.278) 1.0/0.0 28 8.33 229 Btuh
Wall Total 1248 s ft 9211 Btuh
Doors Type Storm Ueff. Area X HTM= Load
1 Insulated- Exterior, n (0.460) 20 13.8 276 Btuh
2 Wood - Garage, n (0.460) 18 13.8 245 Btuh
Door Total 38 s ft 521 Btuh
Ceilings Type/Color/Surface Ueff. R-Value Area X HTM= Load
1 Vented Attic/L/Shing (0.081) 11.0/0.0 919 2.4 2223 Btuh
2 Vented Attic/L/Shing (0.081) 11.0/0.0 386 2.4 934 Btuh
Ceiling Total 1305 s ft 315713tuh
Floors Type Ueff. R-Value Size X HTM= Load
1 Slab On Grade (1.180) 0.0 130.0 ft(perim.) 35.4 4602 Btuh
2 Slab On Grade (1.180) 0.0 52.0 ft(perim.) 35.4 1841 Btuh
Floor Total 1305 s ft 6443 Btuh
Envelope Subtotal: 27147 Btuh
EnergyGauge®/USRCZB v6.1.04 Page 1
Manual J Winter Calculations
Residential Load - Component Details (continued)
JESUS AND DANIA SANCHO I Project Title:
433 SE Gasparilla Ave SANCHO RESIDENCE MINISPLIT
Port St. Lucie, FL 34983 Building Type: User
9/27/2020
Infiltration Type Wholehouse ACH Volume(cuft) Wall Ratio CFM=
Natural 0.15 10440 1.00 26.3 868 Btuh.
Duct load Average sealed, R6.0, Supply(Att), Retum(Att) (DLM of 0.159) .3335 Btuh
All Zones Sensible Subtotal All Zones 31349 Btuh
HOLE HOUSE TOTALS "
Subtotal Sensible Heat Loss 31349 Btuh
Totals for Heating Ventilation Sensible Heat Loss 0 Btuh
Total Heat Loss 31349 Btuh
EQUIPMENT
1. Electric Strip Heat 36000 Btuh
2. Electric Heat Pump MITSUBISHI#MUZ-FH06NA 6000 Btuh
Key:Window types-NFRC(Requires U-Factor and Shading coefficient(SHGC)of glass as numerical values)
or-Glass as'Clear'or Tint'(Uses U-Factor and SHGC defaults)
U-(Window U-Factor)
HTM-(ManualJ Heat Transfer Multiplier)
Version 8
EnergyGauge®/USRCZB v6.1.04 Page 2
i
System, Sizing Calculations - Summer
Residential Load - Whole House Component Details
JESUS AND DANIA SANCHO Project Title:
433 SE Gasparilla Ave SANCHO RESIDENCE MINISPLIT
Port St. Lucie, FL 34983
9/27/2020
Reference City: Fort Pierce, FL Temperature Difference: 16.OF(TMY3 99%) Humidity difference: 62gr.
Component Loads for Whole House
Type* Overhang Window Area(sqft) HTM Load
Window Panes SHGC U InSh IS Omt Len H t Gross ShadedUnshadet Shaded Unshaded
1 1 Clear 0.74,1.13 B-L No SE 10.Of 2.Oft 66.7 66.7 0.0 24 44 1588 Btuh
2 1 Clear 0.74,1.13 B-L No NW 10.Of 2.Oft 40.0 0.0 40.0 24 42. 1692 Stuh
3 . 1 Clear 0.74,1.13 B-L No NW 10.Of 2.Oft 18.0 0.0 18.0 24 42 761 Btuh
4 1 Clear 0.74,1.13 B-L No NW 10.Of 2.Oft 40.0 0.0 40.0 24 42 1692. Btuh
5 1 Clear 0.74, 1.13 B-L No NE 2.Oft 2.Oft 12.5 0.0 12.5 24 42 529 Btuh
6 1 Clear 0.74,1.13 B-L No NE 2.Oft 2.Oft 6.0 0.0 6.0 24 42 254 Btuh
7 . 1 Clear 0.74,1.13 B-L No NE 2.Oft 2.Oft 6.0 0.0 6.0 24 42 254 Btuh
8 1 Clear 0.74,1.13 B-L No NE 2.Oft 2.Oft 12.5 0.0 12.5 24 42 529 Btuh
9 1 Clear 0.74,1.13 B-L No SE 2.Oft 2.Oft 16.4 4.8 11.5 24 44 622 Btuh
10 1 Clear 0.74,1.13 B-L No SW 10.0f 2.Oft 12.5 12.5 0.0 24 44 298 Btuh
Excursion 1931 Btuh
Window Total 231 (sqft) 10148 Btuh
Walls Type U-Value R-Value Area(sqft) HTM Load
Cav/Sheath
1 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 89.3 6.2 556 Btuh
2 Frame-Wood-Adj 0.09 11.0/0.0 133.3 1.5 202 Btuh
3 Frame-Wood-Adj 0.09 11.0/0.0 83.6 1.5 127 Btuh
4 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 80.0 6.2 498 Btuh
5 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 232.0 6.2 1443 Btuh
6 Concrete Blk,Hollow-'Ext 0.28 1.0/0.0 88.0 6.2 547 Btuh
7 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 120.0 6.2 746 Btuh
8 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 190.2 6.2 1183 Btuh
9 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 116.8 6.2 727 Btuh
10 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 87.6 6.2 545 Btuh
11 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 27.5 6.2 171 Btuh
Wall Total 1248 (sqft) 6746 Btuh
Doors Type Area (sqft) HTM Load
1 Insulated-Exterior 20.0 14.3 285 Btuh
2 Wood-Garage 17.8 14.3 254 Btuh
Door Total 38 (sqft) 539 Btuh
Ceilings Type/Color/Surface U-Value R-Value Area(sqft) HTM Load
1 Vented Attic/Light/Shingle 0.081 11.0/0.0 919.0 3.63 3335 Btuh
2 Vented Attic/Light/Shingle 0.081 11.0/0.0 386.0 3.63 1401 Btuh
Ceiling Total 1305 (sqft) 4736 Btuh
Floors Type R-Value Size HTM Load
1 Slab On Grade 0.0 919(ft-perimeter) 0.0 0 Btuh
2 Slab On Grade 0.0 386(ft-perimeter) 0.0 0 Btuh
Floor Total 1305.0 (sqft) 0 Btuh
Envelope Subtotal: 22169 Btuh
EnergyGauge®/USRCZB v6.1.04 Page 1
Manual J Summer Calculations
Residential Load - Component Details (continued)
JESUS AND DANIA SANCHO Project Title: Climate:FL VERO_BEACH_MUNICIPAL A
433 SE Gasparilla Ave SANCHO RESIDENCE MINISPLIT
Port St. Lucie, FL 34983
9/27/2020
Infiltration Type Average ACH Volume(cuft)Wall Ratio CFM= Load
Natural 0.11 10440 1 19.7 347 Btuh
Internal Occupants Btuh/occupant Appliance Load
gain 5 X 230 + 7800 8950 Btuh
Sensible Envelope Load: 31466 Btuh
Duct load Average sealed,Supply(R6.0-Attic),Retum(R&O-Attic) (DGM of 0.137) 3330 Btuh
Sensible Load All Zones 34795 Btuh
EnergyGauge®/USRCZB v6.1.04 Page 2
Manual J Summer Calculations
Residential Load - Component Details (continued)
JESUS AND DANIA SANCHO Project Title: Climate:FL_VERO_BEACH_MUNICIPAL_A
433 SE Gasparilla Ave SANCHO RESIDENCE MINISPLIT
Port St. Lucie, FL 34983
9/27/2020
WHOLE HOUSETOTALS
Sensible Envelope Load All Zones 31466 Btuh
Sensible Duct Load 3330 Btuh
Total Sensible Zone Loads 34795 Btuh
Sensible ventilation 0 Btuh
Blower 0 Btuh
Whole House Total sensible gain 34795 Btuh
Totals for Cooling Latent infiltration gain (for 62 gr. humidity difference) 832 Btuh
Latent ventilation gain 0 Btuh
Latent duct gain 936 Btuh
Latent occupant gain (5.0 people @ 200 Btuh per person) 1000 Btuh
Latent other gain 300 Btuh
Latent total gain 3067 Btuh
TOTAL GAIN 37863 Btuh
EQUIPMENT
1. Central Unit Goodman# 32000 Btuh
2.Central Unit MITSUBISHI#MUZ-FH06NA 6000 Btuh
'Key: Window types(Panes-Number and type of panes of glass)
(SHGC-Shading coefficient of glass as SHGC numerical value)
(U-Window U-Factor).
(InSh-Interior shading device:none(No),Blinds(B),Draperies(D)or Roller Shades(R))
- For Blinds:Assume medium color,half closed
For Draperies:Assume medium weave,half closed
For Roller shades:Assume translucent,half closed
(IS-Insect screen:none(N),Full(F)or Half(%))
(Omt-compass orientation)
Version 8
1 '
EnergyGauge®/USRCZB v6.1.04 Page 3
1
System Sizing Calculations - Winter
Residential Load - Room by Room Component Details
JESUS AND DANIA SANCHO Project Title:
433 SE Gasparilla Ave SANCHO RESIDENCE MINISPLIT
Port St. Lucie, FL 34983 Building Type: User
9/27/2020
Reference City: Fort Pierce, FL (Defaults) Winter Temperature Difference: 30.0 F (TMY3 99%)
Component Loads for Room#1: Main
Window Panes/Type Frame U Orientation Area s ft X HTM= Load
1 1, Clear Metal 1.13 SE 66.7 33.9 2260 Btuh
2 1, Clear Metal 1.13 NW 40.0 33.9 1356 Btuh
3 1, Clear Metal 1.13 NW 18.0 33.9 610 Btuh
4 1, Clear Metal 1.13 NW 40:0 33.9 1356 Btuh
7 1, Clear Metal 1.13 NE 6.0 33.9 203 Btuh
8 1, Clear Metal 1.13 NE 12.5 33.9 424 Btuh
9 1, Clear Metal 1.13 SE 16.4 33.9 555 Btuh
10 1, Clear Metal 1.13 SW 12.5 33.9 424 Btuh
Window Total 212.0 s ft 7188 Btuh
Walls Type Omt. Ueff. R-Value Area X HTM= Load
(Cav/Sh)
1 Conc Blk,Hollow - Ext. (0.278) 1.0/0.0 89 8.33 744 Btuh
2 Frame -Wood -Adj (0.095) 11.0/0.0 .133 2.85 379 Btuh
3 Frame -Wood -Adj (0.095) 11.0/0.0 84 2.85 238 Btuh
4 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 80 8.33 666 Btuh
5 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 232 8.33 1933 Btuh
9 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 117 8.33 973 Btuh
10 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 88 8.33 730 Btuh
11 Conc Blk,Hollow -Ext (0.278) 1.0/0.0 28 8.33 229 Btuh
Wall Total 850 s ft 5894 Btuh
Doors Type Storm Ueff. Area X HTM= Load
1 Insulated- Exterior, n. (0.460) 20 13.8 276 Btuh
2 Wood - Garage, n (0.460) 18 13.8 245 Btuh
Door Total 38 s ft 521 Btuh
Ceilings Type/Color/Surface Ueff. R-Value Area X HTM= Load
1 Vented Attic/L/Shing (0.081). 11.0/0.0 919 2.4 2223 Btuh
Ceiling Total 919 s ft 222313tuh
Floors Type Ueff. R-Value Size X HTM= Load
1 Slab On Grade (1.180) 0.0 130.0 ft(perim.) 35.4 4602 Btuh
Floor Total 919 s ft 4602 Btuh
Room Envelope Subtotal: 20428 Btuh
Infiltration Type Wholehouse ACH Room Volume, Wall Ratio CFM=
Natural 0.15 7352 0.68 17.9 591 Btuh
Duct load Average sealed,Supply(R6.0-Attic),Retum(R6.0-Attic) (DLM of,0.159) 3335 Btuh
Room#1 Sensible Room Subtotal 2435413tuh
EnergyGauge®/USRCZB v6.1.04 Page 1
r
Manual J Winter Calculations
Residential Load - Component Details (continued)
JESUS AND DANIA SANCHO Project Title:
433 SE Gasparilla Ave SANCHO RESIDENCE MINISPLIT
Port St. Lucie, FL 34983 Building Type: User
9/27/2020
Component toads for Room#2: MASTER SUITE
Window Panes/Type Frame U Orientation Area s ft X HTM= Load
5 1, Clear Metal 1.13 NE 12.5 33.9 424 Btuh
6 1, Clear Metal 1.13 NE 6.6 33.9 203 Btuh
Window Total 18.5 s ft 627 Btuh
Walls Type Omt. Ueff. R-Value Area X HTM= Load
(Cav/Sh)
6 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 88 8.33 733 Btuh
7 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 120 8.33 1000 Btuh
8 Conc Blk,Hollow - Ext (0.278) 1.0/0.0 190 8.33 1584 Btuh
Wall Total 398 s ft 3317 Btuh
Ceilings Type/Color/Surface Ueff. R-Value Area X HTM= Load
2 Vented Attic/L/Shing (0.081) 11.0/0.0 386 2.4 934 Btuh
Ceiling Total 386(soft) 9346tuh
Floors Type Ueff. . R-Value Size X HTM= Load
2. Slab On Grade (1.180) 0.0 52.0 ft(perim.) 35.4 1841 Btuh
Floor Total 386 s ft 1841 Btuh
Room Envelope Subtotal: 6719 Btuh
Infiltration Type Wholehouse ACH Room Volume Wall Ratio CFM=
Natural 0.15. 3088 0.32 8.4 277 Btuh
Duct load No ducts assigned to this zone. (DLM of 0.000) 0 Btuh
Room#2 Sensible Room Subtotal 6996 Btuh
SYSTEM GROUPS(BLOCK LOADS)
Heating Loads
For System(s):1 Block load .24354 Btuh
Serving Rooms: 1
EnergyGauge®/USRCZB v6.1.04 Page 2
Manual J Winter Calculations
Residential Load - Component Details (continued)
JESUS AND DANIA SANCHO Project Title:
433 SE Gasparilla Ave SANCHO RESIDENCE MINISPLIT
Port St. Lucie, FL 34983 Building Type: User
9/21/2020
Heating Loads .
For System(s):2 Block load 6996 Btuh
Serving Rooms:2
�1-16LE HOUSET'OTALS
Subtotal Sensible Heat Loss 31349 Btuh
Totals for Heating Ventilation Sensible Heat Loss 0 Btuh
Total Heat Loss 31349 Btuh
EQUIPMENT
1. Electric Strip Heat 36000 Btuh
2. Electric Heat Pump MITSUBISHI#MUZ-FH06NA 6000 Btuh
Key:Window types-NFRC(Requires U-Factor and Shading coefficlent(SHGC)of glass as numerical values)
or-Glass as'Clear'or Tint'(Uses U-Factor and SHGC defaults)
U-(Window U-Factor)
HTM-(ManualJ Heat Transfer Multiplier)
Version 8
EnergyGauge®/USRCZB v6.1.04 Page 3
System Sizing Calculations - Summer .
Residential Load - Room by Room Component Details
JESUS AND DANIA SANCHO Project Title:
433 SE Gasparilla Ave SANCHO RESIDENCE MINISPLIT
Port St. Lucie, FL 34983
9/27/2020
Reference City: Fort Pierce, FL - Temperature Difference: 16.OF(TMY3 99%) Humidity difference: 62gr.
Component Loads for Room#1: Main
Type" Overhang Window Area(sqft) HTM Load
Window Panes SHGC U InSh IS Omt Len H t Gross Shadedl-Inshaded Shaded Unshaded
1 1 Clear 0.74,1.13 B-L No SE 10.Of 2.Oft 66.7 66.7 0.0 24 44 1588 Btuh
2 1 Clear 0.74, 1.13 B-L No NW 10.Of 2.Oft 40.0 0.0 40.0 24 42 1692 Btuh
3 1 Clear 0.74, 1.13 B-L No NW 10.Of 2.Oft 18.0 0.0 18.0 24 42 761 Btuh
4 1 Clear 0.74,1.13 B-L No NW 10.Of 2.Oft 40.0 0.0 40.0 24 42 1692 Btuh
7 1 Clear 0.74, 1.13 B-L No NE 2.Oft 2.Oft 6.0 0.0 6.0 24 42 254 Btuh
8 1 Clear 0.74,1.13 B-L No NE 2.Oft 2.Oft 12.5 0.0 12.5 24 42 529 Btuh
9 1 Clear 0.74, 1.13 B-L No SE 2.Oft 2.Oft 16.4 4.8 11.5 24 44 622 Btuh
10 1 Clear 0.74, 1.13 B-L No SW 10.Of 2.Oft 12.5 12.5 0.0 24 44 298 Btuh
Window Total 212 (sqft) 7435 Btuh
Walls Type U-Value R-Value Area(sqft) HTM Load
Cav/Sheath
1 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 89.3 6.2 556 Btuh
2 Frame-Wood-Adj 0.09 11.0/0.0 133.3 1.5 202 Btuh
3 Frame-Wood-Adj 0.09 11.0/0.0 83.6 1.5 127 Btuh
4 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 80.0 6.2 498 Btuh
5 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 232.0 6.2 1443 Btuh
9 Concrete BIk,Hollow-Ext 0.28 1.0/0.0 116.8 6.2 727 Btuh
10 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 87.6 6.2 545 Btuh
11 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 27.5 6.2 171 Btuh
Wall Total 850 (sqft) 4269 Btuh
Doors Type Area (sqft) HTM Load
1 Insulated-Exterior 20.0 14.3 285 Btuh
2 Wood-Garage 17.8 14.3 254 Btuh
Door Total 38 (sqft) 539 Btuh
Ceilings Type/Color/Surface U-Value R-Value Area(sqft) HTM Load
1 Vented Attic/Light/Shingle 0.081 11.0/0.0 919.0 3.63 3335 Btuh
Ceiling Total 919 (sqft) 3335 Btuh
Floors Type R-Value Size HTM Load
1 Slab On Grade 0.0 919(ft-perimeter) 0.0. 0 Btuh
Floor Total 919.0(sqft) 0 Btuh
Zone Envelope Subtotal: 15577 Btuh
Infiltration _Type Wholehouse ACH Volume(cuft) Wall Ratio CFM= Load
Natural .0.11 7352 0.68 13.4 236 Btuh
Internal Occupants Btuh/occupant Appliance Load
gain 3 X 230 + 5800 6490 Btuh
Sensible Envelope Load: 22304 Btuh
Duct load Average sealed,Supply(R6.0-Attic),Retum(R6.0-Attic) (DGM of 0.137) 3064 Btuh
Sensible Zone Load 25368 Btuh
-EnergyGauge®/USRCZB v6.1.04 Page 1
Manual J Summer Calculations
Residential Load - Component Details (continued)
JESUS AND DANIA SANCHO Project Title: Climate:FL VERO_BEACH_MUNICIPAL_A
433 SE Gasparilla Ave SANCHO RESIDENCE MINISPLIT
Port St. Lucie, FL 34983
9/27/2020
Comporent Loads for Room#2: MASTER SUITE
Type* Overhang Window Area(sqft) HTM Load
Windo'W. Panes SHGC U InSh IS Omt Len H t Gross Shaded Unshaded Shaded Unshaded
5 1 Clear 0.74,1.13 B-L No NE 2.Oft 2.Oft 12.5 0.0 12.5 24 42 529 Btuh
6 1 Clear 0.74,1.13 B-L No NE 2.0ft 2.Oft 6.0 0.0 6.0 24 42 254 Btuh
Window Total 19(s ft) 782 Btuh
Walls Type U-Value R-Value Area(sqft) HTM Load
Cav/Sheath
6 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 88.0 6.2 547 Btuh
7 Concrete Blk,Hollow-Ext 0.28 1.0/0.0 120.0 6.2 746 Btuh
8 Concrete Blk,Hollow-Ext. 0.28 1.0/0.0 190.2 6.2 1183 Btuh
Wall Total 398 (sqft) 2477 Btuh
Ceilings. Type/Color/Surface U-Value R-Value Area(sqft) HTM Load
2 Vented Attic/Light/Shingle 0.081 11.0/0.0 386.0 .3.63 1401 Btuh
Ceiling Total 386 (sgft) 1401 Btuh
Floors Type R-Value Size HTM Load
2 Slab On Grade' 0.0 386(ft-perimeter). 0.0 0. Btuh
Floor Total 386.0 (sqft) 0 Btuh
Zone Envelope Subtotal: 4660 Btuh
Infiltration Type Wholehouse ACH Volume(cuft)Wall Ratio CFM= Load
Natural 0.11 3088 .0.32 6.3 111 Btuh
Internal Occupants Btuh/occupant Appliance Load
gain 2 X 230 + 2000 2460 Btuh
Sensible Envelope Load: 7231 Btuh
Duct load No ducts assigned to this zone. (DGM of 0.000) 0 Btuh
Sensible Zone Load 7231 Btuh
The folloi signtl toth " ysf loado rsiowle ms.wngw
Windows July excursion for System. 1 1931 Btuh
July excursion for System 2 0 Btuh
Excursion Subtotal: .1931 Btuh
EnergyGauge®/USRCZB v6.1.04 Page 2
Manual J Summer Calculations
Residential Load - Component Details (continued)
JESUS AND DANIA SANCHO Project Title: * Climate:FL VERO_BEACH_MUNICIPAL A
433 SE Gasparilla Ave SANCHO RESIDENCE MINISPLIT
Port St. Lucie, FL 34983
9/27/2020
Duct load 265' Btuh
Sensible Excursion-Load 2197 Btuh
EnergyGauge®/USRCZB v6.1.04 Page 3
Manual J Summer .Calculations
Residential Load Component Details (continued)
JESUS AND DANIA SANGHO Project Title: Climate:FL_VERO_BEACH_MUNICIPAL_A
433 SE Gasparilla Ave SANGHO RESIDENCE MINISPLIT
Port St. Lucie, FL 34983
9/27/2020
SYSTEM GROUPS(BLOCK LOADS)
Sensible Envelope Load 22304 Btuh
Window Excursion 1931 Btuh
Cooling'Loads Sensible Duct Load (duct gain multiplier of 0.137) 3330 Btuh
(Includes 265 Btuh due to window excursion)
Sensible ventilation 0 Btuh
For System(s): Zone Sensible gain 27565 Btuh
1 Latent infiltration/ventilation gain 566 Btuh
Serving Zones: Latent duct gain 936 Btuh
1 Latent occupant gain 600 Btuh
Latent other gain 300 Btuh
Total block load 29967 Btuh
Sensible Envelope Load 7231 Btuh
Window Excursion 0 Btuh
Cooling Loads Sensible Duct Load (duct gain multiplier of 0.000) 0 Btuh
Sensible ventilation 0 Btuh
For System(s): Zone Sensible gain 7231 Btuh
2 Latent infiltration/ventilation gain 265 Btuh
Serving Zones: Latent duct gain 0 Btuh
2 Latent occupant gain 400 Btuh
Latent other gain 0 Btuh
Total block load 7896 Btuh
EnergyGauge®/USRCZB v6.1.04 Page 4
Manual J Summer Calculations
Residential Load - Component Details (continued)
JESUS AND DANIA SANCHO Project Title: Climate:FL VERO_BEACH_MUNICIPAL A
433 SE Gasparilla Ave SANCHO RESIDENCE MINISPLIT
Port St. Lucie, FL•34983
9/27/2020
WHOLE HOUSE TOTALS
Sensible Envelope Load All Zones 31466 Btuh
Sensible Duct Load 3330 Btuh
Total Sensible Zone Loads 34795 Btuh
Sensible ventilation 0 Btuh
Blower 0 Btuh
Whole House Total sensible gain 34795 Btuh
Totals for Cooling Latent infiltration gain (for 62 gr. humidity difference) 832 Btuh
Latent ventilation gain 0 Btuh
Latent duct gain 936 Btuh
Latent occupant gain (5.0 people @ 200 Btuh per person) 1000 Btuh
Latent other gain 300 Btuh
Latent total gain 3067 Btuh
TOTAL GAIN 37863 Btuh
EQUIPMENTS
1. Central Unit Goodman# 32000 Btuh
2.Central Unit MITSUBISHI#MUZ-FH06NA 6000 Btuh
"Key: Window types(Panes-Number and type of panes of glass)
(SHGC-Shading coefficient of glass as SHGC numerical value)
(U-.Window U-Factor)
(InSh-Interior shading device:none(No),Blinds(B),Draperies(D)or Roller Shades(R))
- For Blinds:Assume medium color,half closed
For Draperies:Assume medium weave,half closed
For Roller shades:Assume translucent,half dosed
(IS-Insect screen:none(N),Full(F)or Half(%))
(Omt-compass orientation)
Version 8
EnergyGauge®/USRCZB v6.1.04 Page 6
This combination qualifies for a Federal Energy Efficiency Tax Credit when
A "IMPo placed in service between 1/1/2015 and 12/31/2020.
rusual CERTIFIED
Certificate of Product Ratings
AHRI Certified Reference Number:201754426 Date:09-27-2020 Model Status:Active
AHRI Type:HRCU-A-CB-O(Mini-Split Heat Pump,with Remote Outdoor Unit Air-Source,Free Delivery)
Series Name:M-Series
Outdoor Unit Brand Name:Mitsubishi Electric
Outdoor Unit Model Number:MUZ-FH06NA
Indoor Type:Mini-Splits(Non-Ducted)
Indoor Model Number(s):MSZ-FH06NA**
Rated as follows in accordance with the latest edition of AHRI 210/240 with Addendum 1,Performance Rating of Unitary
Air-Conditioning&Air-Source Heat Pump Equipment and subject to rating accuracy by AHRI-sponsored,independent,third party testing:
Cooling Capacity(95F):6000
EER(95F):19.00
SEER:33.10
High Heat(47F):8700
Low Heat(17F):5900
HSPF:13.50
Sold in?:USA
t°Active"Model Status are those that an AHRI Certification Program Participant is currently producing AND selling or offering for sale;OR new models that are being
marketed but are not yet being produced"Production Stopped"Model Status are those that an AHRI Certification Program Participant is no longer producing BUT is still
selling or offering for sale.
Ratings that are accompanied by WAS indicate an involuntary re-rate. The new published ratino is shown along with the previous(i.e.WAS)rating.
DISCLAIMER
AHRI does not endorse the product(s)listed on this Certificate and makes no representations,warranties or guarantees as to,and assumes no responsibility for,
the product(s)listed on this Certificate.AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s),or the
unauthorized alteration of data listed on this Certificate.Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS ��12�
This Certificate and its contents are proprietary products of AHRI.This Certificate shall only be used for Individual,personal and
confidential reference purposes.The contents of this Certificate may not,In whole or in part,be reproduced;copied;disseminated; 0%0- 1A
entered into a computer database;or otherwise utilized,in any form or manner or by any means,except for the user's individual,
personal and confidential reference. AIR-CONDITIONING,HEATING,
CERTIFICATE VERIFICATION &REFRIGERATION INSTITUTE
The Information for the model cited on this certificate can be verified at www.ahridirectory.org,click on"Verify Certificate"link we make life better-
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above,and the Certificate No.,which is listed at bottom right.
©2020Air-Conditioning, Heating,and Refrigeration Institute CERTIFICATE NO.: 132457194561718197
ERI Comparison report
Wholehouse Summary
JESUS AND DANIA SANCHO Project Title: TMY_City:FL_VERO BEACH_MUNICI
433 SE Gasparilla Ave SANCHO RESIDENCE EXISTING Elec UlR Florida Average
Port St. Lucie, FL 34983 Building Type: Rating13 Gas Util: Florida Average ,
9/27/2020
End-Use Energy Consumption Annual Cost
Rated Reference Rated Reference
Cooling Electric 4093 kWh 3079 kWh $475 $357
Cooling Fan 919 kWh 667 kWh $107 $77
Mechanical Vent Fan 0 kWh 0 kWh . ' $0 $0
Total Cooling 5012 kWh 3746 kWh $582 $435
Heating Electric 490 kWh 124 kWh $57 $14
Heating Fan/Pump 28 kWh 18 kWh $3 $2
Mechanical Vent Fan 0 kWh 0 kWh $0 $0
Total Heating 518 kWh 142 kWh $60 $16
Hot Water 1981 kWh 1982 kWh $230 $230 J
Hot Water Pump 0 kWh 0 kWh $0 $0
Total Hot Water 1981 kWh 1982 kWh $230 $230
Ceiling Fans 0 kWh 0 kWh $0 $0
Clothes Washer 69 kWh 69 kWh $8 $8
Dehumidifier 0 kWh 0 kWh $0 $0
Dishwasher 171 kWh 171 kWh $20 $20
Dryer Electric 970 kWh 970 kWh $113 $113
Lighting 1764 kWh 1764 kWh $205 $205
Miscellaneous 1188 kWh 1188 kWh $138 $138
Pool Pump 0 kWh 0 kWh $0 $0
Range Electric 448 kWh 448 kWh $52 $52
Refrigerator .691 kWh 691 kWh $80 $80
Television 620 kWh 620 kWh $72 $72
Total (kWh) 13432 kWh 11790 kWh $1559 $1369
Total (Therms) 0 Therms 0 Therms $0 $0
Total (Oil Gallons) 0 Gallons 0 Gallons $0 $0
Total (Propane Gallons) 0 Gallons 0 Gallons $0 $0
PV Produced (kWh) 0 kWh 0 kWh $0 $0
Assumes net metering
Total Cost $1559 $1369
Rated Emissions (Calculated as Total - PV Produced)
S02 = 29.47 Lbs NOX = 13.74 Lbs CO2 = 8.01 Tons
Reference Emissions (Calculated as Total - PV Produced)
S02 = 25.87 Lbs NOX = 12.06 Lbs CO2 = 7.03 Tons
EnergyGauge®/USRCZB v6.1.04
ERI Comparison report
Wholehouse Summary_
JESUS AND DANIA SANCHO Project Title: TMY_City:FL VERO BEACH MUNICI
433 SE Gasparilla Ave SANCHO RESIDENCE MINISPLIT Elec Util. Florida_Average
Port St. Lucie, FL 34983 Building Type: Rating13 Gas Util: Florida Average
9/27/2020
End-Use Energy Consumption Annual Cost
Rated Reference Rated Reference
Cooling Electric 3496 kWh 3049 kWh $406 $354
Cooling Fan 855 kWh 657 kWh $99 $76
Mechanical Vent Fan 0 kWh 0 kWh $0 $0
Total Cooling 4351 kWh 3706 kWh $505 $430
Heating Electric 400 kWh 146 kWh $46 $17
Heating Fan/Pump 25 kWh 20 kWh $3 $2
Mechanical Vent Fan 0 kWh 0 kWh $0 $0
Total Heating 425 kWh 166 kWh $49 $19
Hot Water 1695 kWh . 1982 kWh $197 $230
Hot Water Pump 0 kWh 0 kWh $0 $0
Total Hot Water 1695 kWh 1982 kWh $197 $230
Ceiling Fans 0 kWh 0 kWh $0 $0
Clothes Washer 69 kWh 69 kWh $8 $8
Dehumidifier 0 kWh 0 kWh $0. $0
Dishwasher 171 kWh 171 kWh $20 $20
Dryer Electric 970 kWh 970 kWh $113 $113
Lighting 1764 kWh 1764 kWh $205 $205
Miscellaneous 1188 kWh 1188 kWh $138 $138
Pool Pump 0 kWh 0 kWh $0 $0
Range Electric 448 kWh 448 kWh $52 $52
Refrigerator . 691 kWh 691 kWh $80 $80
Television 620 kWh 620 kWh $72 $72
Total (kWh) 12392 kWh 11774 kWh $1439 $1367 .
Total (Therms) 0 Therms 0 Therms $0 $0
Total (Oil Gallons) 0 Gallons 0 Gallons $0 $0
Total (Propane Gallons) 0 Gallons 0 Gallons $0 $0
PV Produced (kWh) 0 kWh 0 kWh $0 $0
Assumes net metering
Total Cost $1439 $1367
Rated Emissions (Calculated as Total - PV Produced)
S02 = 27.19 Lbs NOX = 12.68 Lbs CO2 = 7.39 Tons
Reference Emissions (Calculated as Total - PV Produced)
S02 = 25.83 Lbs NOX= 12.04 Lbs CO2 = 7.02 Tons
EnergyGauge®/USRCZB v6.1.04