HomeMy WebLinkAboutStructural Analysis tnxTower Report - version 8.0.7.4 Date: August 10, 2020 Angela Harris Paul J. Ford and Company Crown Castle 250 E. Broad St., Ste 600 8000 Avalon Blvd Columbus, OH 43215 Alpharetta, GA 30009 614-221-6679 Subject: Structural Analysis Report Carrier Designation: T-Mobile Co-Locate Carrier Site Number: A2P0090A Carrier Site Name: Crown 800642 FL W Midway Crown Castle Designation: Crown Castle BU Number: 800642 Crown Castle Site Name: FL WEST MIDWAY CCI 800642 Crown Castle JDE Job Number: 617106 Crown Castle Work Order Number: 1872769 Crown Castle Order Number: 526773 Rev. 0 Engineering Firm Designation: Paul J. Ford and Company Project Number: 37520-1608.001.8700 Site Data: 16800 Okeechobee Road, FORT PIERCE, St. Lucie County, FL Latitude 27° 22' 53.3'', Longitude -80° 29' 48.4'' 245 Foot - Self Support Tower Dear Angela Harris, Paul J. Ford and Company is pleased to submit this “Structural Analysis Report” to determine the structural integrity of the above mentioned tower. The purpose of the analysis is to determine acceptability of the tower stress level. Based on our analysis we have determined the tower stress level for the structure and foundation, under the following load case, to be: LC5: Proposed Equipment Configuration Sufficient Capacity This analysis utilizes an ultimate 3-second gust wind speed of 155 mph as required by the 2017 Florida Building Code, 6th Edition. Applicable Standard references and design criteria are listed in Section 2 - Analysis Criteria. Respectfully submitted by: Christina Hedges, PE Project Manager chedges@pauljford.com August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 2 tnxTower Report - version 8.0.7.4 TABLE OF CONTENTS 1) INTRODUCTION 2) ANALYSIS CRITERIA Table 1 - Proposed Equipment Configuration Table 2 - Other Considered Equipment 3) ANALYSIS PROCEDURE Table 3 - Documents Provided 3.1) Analysis Method 3.2) Assumptions 4) ANALYSIS RESULTS Table 4 - Section Capacity (Summary) Table 5 – Tower Component Stresses vs. Capacity – LC5 4.1) Recommendations 5) APPENDIX A tnxTower Output 6) APPENDIX B Base Level Drawing 7) APPENDIX C Additional Calculations August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 3 tnxTower Report - version 8.0.7.4 1) INTRODUCTION This tower is a 245 ft Self Support tower designed by Trylon in January 2001. 2) ANALYSIS CRITERIA TIA-222 Revision: TIA-222-H Risk Category: II Wind Speed: 155 mph Exposure Category: C Topographic Factor: 1 Service Wind Speed: 60 mph Table 1 - Proposed Equipment Configuration Mounting Level (ft) Center Line Elevation (ft) Number of Antennas Antenna Manufacturer Antenna Model Number of Feed Lines Feed Line Size (in) 220.0 223.0 3 andrew ADFD1820-3333B-XDM w/ Mount Pipe 3 1 1 1/4 1 1/2 3 commscope FFHH-65C-R3 w/ Mount Pipe 1 commscope HCS 2.0 3 nokia AEHC w/ Mount Pipe 6 nokia AHFIG 3 nokia AHLOA 220.0 3 raycap ASU9338TYP01 3 tower mounts Site Pro 1 VFA12-HD Table 2 - Other Considered Equipment Mounting Level (ft) Center Line Elevation (ft) Number of Antennas Antenna Manufacturer Antenna Model Number of Feed Lines Feed Line Size (in) 249.0 250.0 1 antel BSA-185025/12 w/ Mount Pipe 12 1-5/8 2 antel BSA-185065/12x2 w/ Mount Pipe 6 jma wireless DBC-67C-U-2SF 2 jma wireless X7CQAP-665-VR0 w/ Mount Pipe 4 jma wireless X7CQAP-FRO-645-VR0 w/ Mount Pipe 249.0 1 tower mounts Platform Mount [LP 603-1] August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 4 tnxTower Report - version 8.0.7.4 Mounting Level (ft) Center Line Elevation (ft) Number of Antennas Antenna Manufacturer Antenna Model Number of Feed Lines Feed Line Size (in) 200.0 203.0 4 cci antennas HPA-33R-BUU-H6-K w/ Mount Pipe 3 3 6 12 5/16 3/8 3/4 1 5/8 6 commscope E15Z01P19 3 commscope SBNHH-1D85C w/ Mount Pipe 5 ericsson RRUS 32 3 ericsson RRUS 4415 B25 1 ericsson RRUS 4426 B66 3 ericsson RRUS-11 3 kathrein 800 10723 w/ Mount Pipe 1 kathrein 800 10865 w/ Mount Pipe 5 kmw communications KFTDR00110030 2 raycap DC6-48-60-18-8C 1 raycap DC6-48-60-18-8F 6 triasx TBC0020F1V1 200.0 1 tower mounts Sector Mount [SM 502-3] 128.0 129.0 3 commscope TTTT65AP-1XR w/ Mount Pipe 3 7/8 3 ericsson 800MHZ SMR FILTER 3 ericsson RRUS 31 B25 3 ericsson RRUS 82 W/SOLAR SHIELD 3 ericsson RRUS-11 800MHz 3 rfs celwave APXVSPP18-C w/ Mount Pipe 128.0 1 tower mounts (3) Connect-It V-Frame P/N: PVFM(fw)-3-n-mh-2 3) ANALYSIS PROCEDURE Table 3 - Documents Provided Document Remarks Reference Source 4-TOWER FOUNDATION DRAWINGS/DESIGN/SPECS Morrison Hershfield Corp. (Mapping), 7/31/08 2293716 CCISITES 4-TOWER MANUFACTURER DRAWINGS Trylon, 112940.330, 1/22/01 366603 CCISITES 3.1) Analysis Method tnxTower (version 8.0.7.4), a commercially available analysis software package, was used to create a three-dimensional model of the tower and calculate member stresses for various loading cases. Selected output from the analysis is included in Appendix A. When applicable, Crown Castle has calculated and provided the effective area for panel antennas using approved methods following the intent of the TIA-222 Standard. August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 5 tnxTower Report - version 8.0.7.4 3.2) Assumptions 1) Tower and structures were maintained in accordance with the TIA-222 Standard. 2) The configuration of antennas, transmission cables, mounts and other appurtenances are as specified in Tables 1 and 2 and the referenced drawings. This analysis may be affected if any assumptions are not valid or have been made in error. Paul J. Ford and Company should be notified to determine the effect on the structural integrity of the tower. 4) ANALYSIS RESULTS Table 4 - Section Capacity (Summary) Section No. Elevation (ft) Component Type Size Critical Element P (K) SF*P_allow (K) % Capacity Pass / Fail T1 245 - 240 Leg 2 1/2" solid 3 -11.84 118.23 10.0 Pass T2 240 - 220 Leg 2 1/2" solid 15 -56.32 118.23 47.6 Pass T3 220 - 210 Leg 15TL1.5x1/2x5/8 44 -74.92 222.84 45.2 Pass T4 210 - 200 Leg 15TL1.5x1/2x5/8 57 -109.25 222.84 49.0 Pass T5 200 - 180 Leg 15TL1.75x1/2x5/8 66 -182.98 312.87 58.5 Pass T6 180 - 160 Leg 15TL1.75x1/2x5/8 81 -254.01 312.87 81.2 Pass T7 160 - 140 Leg Trylon 2.00 (18x15) 96 -291.96 417.74 69.9 Pass T8 140 - 120 Leg Trylon 2.25 (18x15) 105 -367.95 528.76 69.6 Pass T9 120 - 100 Leg Trylon 2.25 (18x15) 114 -431.82 528.76 81.7 Pass T10 100 - 80 Leg Trylon 2.5 (18x24) 123 -503.71 633.19 79.6 Pass T11 80 - 60 Leg Trylon 2.75 (18x24) 132 -571.06 780.85 73.1 Pass T12 60 - 40 Leg Trylon 2.75 (18x24) 141 -636.87 780.85 81.6 Pass T13 40 - 20 Leg Trylon 2.75 (18x24) 150 -704.24 780.85 90.2 Pass T14 20 - 0 Leg Trylon 3.00 (18x24) 159 -763.15 940.35 81.2 Pass T1 245 - 240 Diagonal L2 1/2x2 1/2x1/4 11 -3.92 35.08 11.2 27.0 (b) Pass T2 240 - 220 Diagonal L2 1/2x2 1/2x1/4 23 -6.11 35.08 17.4 42.2 (b) Pass T3 220 - 210 Diagonal L3x3x1/4 53 -10.40 37.17 28.0 37.2 (b) Pass T4 210 - 200 Diagonal L3x3x1/4 62 -10.90 34.25 31.8 41.2 (b) Pass T5 200 - 180 Diagonal L3x3x1/4 71 -14.44 28.40 50.8 54.4 (b) Pass T6 180 - 160 Diagonal L3 1/2x3 1/2x1/4 87 -15.24 35.49 43.0 56.6 (b) Pass T7 160 - 140 Diagonal L5x5x3/8 101 -27.81 61.93 44.9 66.6 (b) Pass T8 140 - 120 Diagonal L5x5x3/8 111 -25.40 56.94 44.6 61.5 (b) Pass T9 120 - 100 Diagonal L5x5x3/8 119 -29.55 52.26 56.5 70.8 (b) Pass T10 100 - 80 Diagonal L5x5x3/8 128 -28.66 47.92 59.8 68.7 (b) Pass T11 80 - 60 Diagonal L5x5x3/8 137 -29.59 43.93 67.4 70.9 (b) Pass T12 60 - 40 Diagonal L5x5x3/8 146 -31.48 40.28 78.1 Pass T13 40 - 20 Diagonal L5x5x3/8 156 -29.25 36.97 79.1 Pass August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 6 tnxTower Report - version 8.0.7.4 Section No. Elevation (ft) Component Type Size Critical Element P (K) SF*P_allow (K) % Capacity Pass / Fail T14 20 - 0 Diagonal L6x6x7/16 164 -36.78 64.55 57.0 88.1 (b) Pass T1 245 - 240 Top Girt L6x6x7/16 4 -1.17 163.39 0.7 8.3 (b) Pass T2 240 - 220 Top Girt L6x6x7/16 17 0.30 182.41 0.2 2.1 (b) Pass T3 220 - 210 Top Girt L3x3x1/4 46 -0.14 38.84 0.4 0.5 (b) Pass Summary Leg (T13) 90.2 Pass Diagonal (T14) 88.1 Pass Top Girt (T1) 8.3 Pass Bolt Checks 88.1 Pass Rating = 90.2 Pass Table 5 - Tower Component Stresses vs. Capacity – LC5 Notes Component Elevation (ft) % Capacity Pass / Fail 1 Anchor Rods 0 35.0 Pass 2 Base Foundation (Compared w/ Design Loads) 0 87.3 Pass Structure Rating (max from all components) = 90.2% Notes: • All structural ratings are per TIA-222-H Section 15.5 1) See additional documentation in “Appendix C – Additional Calculations” for calculations supporting the % capacity consumed. 2) Foundation capacity determined by comparing analysis reactions to original design reactions. 4.1) Recommendations The tower and its foundation have sufficient capacity to carry the proposed load configuration. No modifications are required at this time. August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 7 tnxTower Report - version 8.0.7.4 APPENDIX A TNXTOWER OUTPUT Paul J. Ford and Company 250 E. Broad St., Ste 600 Columbus, OH 43215 Phone: 614-221-6679 FAX: Job: 245' s/s tower Fort Pierce, FL Project: (PJF37520-1608) 800642 FL West Midway Client: Crown Castle Drawn by: Chrissy Hedges App'd: Code: TIA-222-H Date: 08/10/20 Scale: NTS Path: G:\TOWER\375_Crown_Castle\2020\37520-1608_800642_FL WEST MIDWAY CCI 8006\37520-1608.001.8700_SA_1872769\37520-1608.001.eri Dwg No. E-1 245.0 ft 240.0 ft 220.0 ft 210.0 ft 200.0 ft 180.0 ft 160.0 ft 140.0 ft 120.0 ft 100.0 ft 80.0 ft 60.0 ft 40.0 ft 20.0 ft 0.0 ft REACTIONS - 155 mph WIND TORQUE 247 kip-ft 136 K SHEAR 18504 kip-ft MOMENT 109 K AXIAL SHEAR: 78 K UPLIFT: -705 K SHEAR: 87 K DOWN: 800 K MAX. CORNER REACTIONS AT BASE: ARE FACTORED ALL REACTIONS S e c t i o n T1 T2 T3 T4 T5 T6 T7 T8 T9 T1 0 T1 1 T1 2 T1 3 T1 4 L e g s SR 2 1 / 2 " s o l i d 15 T L 1 . 5 x 1 / 2 x 5 / 8 15 T L 1 . 7 5 x 1 / 2 x 5 / 8 Tr y l o n 2 . 0 0 ( 1 8 x 1 5 ) Tr y l o n 2 . 2 5 ( 1 8 x 1 5 ) Tr y l o n 2 . 5 ( 1 8 x 2 4 ) Tr y l o n 2 . 7 5 ( 1 8 x 2 4 ) Tr y l o n 3 . 0 0 ( 1 8 x 2 4 ) L e g G r a d e A5 7 2 - 5 0 35 0 W D i a g o n a l s L2 1 / 2 x 2 1 / 2 x 1 / 4 L3 x 3 x 1 / 4 L3 1 / 2 x 3 1 / 2 x 1 / 4 L5 x 5 x 3 / 8 L6 x 6 x 7 / 1 6 D i a g o n a l G r a d e 30 0 W T o p G i r t s L6 x 6 x 7 / 1 6 L3 x 3 x 1 / 4 N. A . F a c e W i d t h ( f t ) 6 7 8 10 12 14 16 18 20 22 24 26 28 # P a n e l s @ ( f t ) 5 @ 5 6 @ 1 0 8 @ 2 0 W e i g h t ( K ) 0. 8 2. 1 1. 6 1. 5 3. 5 3. 7 4. 7 5. 2 5. 3 6. 3 7. 0 7. 1 7. 2 9. 2 65 . 2 MATERIAL STRENGTH GRADE GRADEFy FyFu Fu A572-50 50 ksi 65 ksi 300W 44 ksi 65 ksi 350W 51 ksi 65 ksi TOWER DESIGN NOTES 1. Tower is located in Autauga County, Alabama. 2. Tower designed for Exposure C to the TIA-222-H Standard. 3. Tower designed for a 155 mph basic wind in accordance with the TIA-222-H Standard. 4. Deflections are based upon a 60 mph wind. 5. Tower Risk Category II. 6. Topographic Category 1 with Crest Height of 0.00 ft 7. TIA-222-H Annex S 8. TOWER RATING: 90.2% August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 8 tnxTower Report - version 8.0.7.4 Tower Input Data The main tower is a 3x free standing tower with an overall height of 245.00 ft above the ground line. The base of the tower is set at an elevation of 0.00 ft above the ground line. The face width of the tower is 6.00 ft at the top and 28.00 ft at the base. This tower is designed using the TIA-222-H standard. The following design criteria apply: 1) Tower is located in Autauga County, Alabama. 2) Tower base elevation above sea level: 18.00 ft. 3) Basic wind speed of 155 mph. 4) Risk Category II. 5) Exposure Category C. 6) Simplified Topographic Factor Procedure for wind speed-up calculations is used. 7) Topographic Category: 1. 8) Crest Height: 0.00 ft. 9) Deflections calculated using a wind speed of 60 mph. 10) TIA-222-H Annex S. 11) A non-linear (P-delta) analysis was used. 12) Pressures are calculated at each section. 13) Tower analysis based on target reliabilities in accordance with Annex S. 14) Load Modification Factors used: Kes(Fw) = 0.95. 15) Stress ratio used in tower member design is 1.05. 16) Local bending stresses due to climbing loads, feed line supports, and appurtenance mounts are not considered. Options Consider Moments - Legs Distribute Leg Loads As Uniform Use ASCE 10 X-Brace Ly Rules Consider Moments - Horizontals Assume Legs Pinned √ Calculate Redundant Bracing Forces Consider Moments - Diagonals √ Assume Rigid Index Plate Ignore Redundant Members in FEA Use Moment Magnification √ Use Clear Spans For Wind Area √ SR Leg Bolts Resist Compression Use Code Stress Ratios √ Use Clear Spans For KL/r All Leg Panels Have Same Allowable √ Use Code Safety Factors - Guys Retension Guys To Initial Tension Offset Girt At Foundation Escalate Ice √ Bypass Mast Stability Checks √ Consider Feed Line Torque Always Use Max Kz √ Use Azimuth Dish Coefficients √ Include Angle Block Shear Check Use Special Wind Profile √ Project Wind Area of Appurt. √ Use TIA-222-H Bracing Resist. Exemption √ Include Bolts In Member Capacity Autocalc Torque Arm Areas Use TIA-222-H Tension Splice Exemption Leg Bolts Are At Top Of Section Add IBC .6D+W Combination Poles √ Secondary Horizontal Braces Leg √ Sort Capacity Reports By Component Include Shear-Torsion Interaction Use Diamond Inner Bracing (4 Sided) Triangulate Diamond Inner Bracing Always Use Sub-Critical Flow SR Members Have Cut Ends Treat Feed Line Bundles As Cylinder Use Top Mounted Sockets SR Members Are Concentric Ignore KL/ry For 60 Deg. Angle Legs Pole Without Linear Attachments Pole With Shroud Or No Appurtenances Outside and Inside Corner Radii Are Known August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 9 tnxTower Report - version 8.0.7.4 Leg B Leg C Leg A F a c e A F a c e B Face C Triangular Tower Wind Normal Wind 90 Wind 180 Z X Tower Section Geometry Tower Section Tower Elevation ft Assembly Database Description Section Width ft Number of Sections Section Length ft T1 245.00-240.00 6.00 1 5.00 T2 240.00-220.00 6.00 1 20.00 T3 220.00-210.00 6.00 1 10.00 T4 210.00-200.00 7.00 1 10.00 T5 200.00-180.00 8.00 1 20.00 T6 180.00-160.00 10.00 1 20.00 T7 160.00-140.00 12.00 1 20.00 T8 140.00-120.00 14.00 1 20.00 T9 120.00-100.00 16.00 1 20.00 T10 100.00-80.00 18.00 1 20.00 T11 80.00-60.00 20.00 1 20.00 T12 60.00-40.00 22.00 1 20.00 T13 40.00-20.00 24.00 1 20.00 T14 20.00-0.00 26.00 1 20.00 Tower Section Geometry (cont’d) Tower Section Tower Elevation ft Diagonal Spacing ft Bracing Type Has K Brace End Panels Has Horizontals Top Girt Offset in Bottom Girt Offset in T1 245.00-240.00 5.00 X Brace No No 0.0000 0.0000 T2 240.00-220.00 5.00 X Brace No No 0.0000 0.0000 T3 220.00-210.00 10.00 X Brace No No 0.0000 0.0000 T4 210.00-200.00 10.00 X Brace No No 0.0000 0.0000 T5 200.00-180.00 10.00 X Brace No No 0.0000 0.0000 T6 180.00-160.00 10.00 X Brace No No 0.0000 0.0000 T7 160.00-140.00 20.00 X Brace No No 0.0000 0.0000 T8 140.00-120.00 20.00 X Brace No No 0.0000 0.0000 T9 120.00-100.00 20.00 X Brace No No 0.0000 0.0000 August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 10 tnxTower Report - version 8.0.7.4 Tower Section Tower Elevation ft Diagonal Spacing ft Bracing Type Has K Brace End Panels Has Horizontals Top Girt Offset in Bottom Girt Offset in T10 100.00-80.00 20.00 X Brace No No 0.0000 0.0000 T11 80.00-60.00 20.00 X Brace No No 0.0000 0.0000 T12 60.00-40.00 20.00 X Brace No No 0.0000 0.0000 T13 40.00-20.00 20.00 X Brace No No 0.0000 0.0000 T14 20.00-0.00 20.00 X Brace No No 0.0000 0.0000 Tower Section Geometry (cont’d) Tower Elevation ft Leg Type Leg Size Leg Grade Diagonal Type Diagonal Size Diagonal Grade T1 245.00- 240.00 Solid Round 2 1/2'' solid A572-50 (50 ksi) Equal Angle L2 1/2x2 1/2x1/4 300W (44 ksi) T2 240.00- 220.00 Solid Round 2 1/2'' solid A572-50 (50 ksi) Equal Angle L2 1/2x2 1/2x1/4 300W (44 ksi) T3 220.00- 210.00 Truss Leg 15TL1.5x1/2x5/8 A572-50 (50 ksi) Equal Angle L3x3x1/4 300W (44 ksi) T4 210.00- 200.00 Truss Leg 15TL1.5x1/2x5/8 A572-50 (50 ksi) Equal Angle L3x3x1/4 300W (44 ksi) T5 200.00- 180.00 Truss Leg 15TL1.75x1/2x5/8 A572-50 (50 ksi) Equal Angle L3x3x1/4 300W (44 ksi) T6 180.00- 160.00 Truss Leg 15TL1.75x1/2x5/8 A572-50 (50 ksi) Equal Angle L3 1/2x3 1/2x1/4 300W (44 ksi) T7 160.00- 140.00 Truss Leg Trylon 2.00 (18x15) 350W (51 ksi) Equal Angle L5x5x3/8 300W (44 ksi) T8 140.00- 120.00 Truss Leg Trylon 2.25 (18x15) 350W (51 ksi) Equal Angle L5x5x3/8 300W (44 ksi) T9 120.00- 100.00 Truss Leg Trylon 2.25 (18x15) 350W (51 ksi) Equal Angle L5x5x3/8 300W (44 ksi) T10 100.00- 80.00 Truss Leg Trylon 2.5 (18x24) 350W (51 ksi) Equal Angle L5x5x3/8 300W (44 ksi) T11 80.00- 60.00 Truss Leg Trylon 2.75 (18x24) 350W (51 ksi) Equal Angle L5x5x3/8 300W (44 ksi) T12 60.00- 40.00 Truss Leg Trylon 2.75 (18x24) 350W (51 ksi) Equal Angle L5x5x3/8 300W (44 ksi) T13 40.00- 20.00 Truss Leg Trylon 2.75 (18x24) 350W (51 ksi) Equal Angle L5x5x3/8 300W (44 ksi) T14 20.00-0.00 Truss Leg Trylon 3.00 (18x24) 350W (51 ksi) Equal Angle L6x6x7/16 300W (44 ksi) Tower Section Geometry (cont’d) Tower Elevation ft Top Girt Type Top Girt Size Top Girt Grade Bottom Girt Type Bottom Girt Size Bottom Girt Grade T1 245.00- 240.00 Equal Angle L6x6x7/16 300W (44 ksi) Solid Round A36 (36 ksi) T2 240.00- 220.00 Equal Angle L6x6x7/16 300W (44 ksi) Solid Round A36 (36 ksi) T3 220.00- 210.00 Equal Angle L3x3x1/4 300W (44 ksi) Solid Round A36 (36 ksi) Tower Section Geometry (cont’d) August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 11 tnxTower Report - version 8.0.7.4 Tower Elevation ft Gusset Area (per face) ft2 Gusset Thickness in Gusset Grade Adjust. Factor Af Adjust. Factor Ar Weight Mult. Double Angle Stitch Bolt Spacing Diagonals in Double Angle Stitch Bolt Spacing Horizontals in Double Angle Stitch Bolt Spacing Redundants in T1 245.00- 240.00 0.00 0.8750 A36 (36 ksi) 1 1 1 36.0000 36.0000 36.0000 T2 240.00- 220.00 0.00 0.3750 A36 (36 ksi) 1 1 1 36.0000 36.0000 36.0000 T3 220.00- 210.00 0.00 0.3750 A36 (36 ksi) 1 1 1 36.0000 36.0000 36.0000 T4 210.00- 200.00 0.00 0.3750 A36 (36 ksi) 1 1 1 36.0000 36.0000 36.0000 T5 200.00- 180.00 0.00 0.3750 A36 (36 ksi) 1 1 1 36.0000 36.0000 36.0000 T6 180.00- 160.00 0.00 0.3750 A36 (36 ksi) 1 1 1 36.0000 36.0000 36.0000 T7 160.00- 140.00 0.00 0.3750 A36 (36 ksi) 1 1 1 36.0000 36.0000 36.0000 T8 140.00- 120.00 0.00 0.3750 A36 (36 ksi) 1 1 1 36.0000 36.0000 36.0000 T9 120.00- 100.00 0.00 0.3750 A36 (36 ksi) 1 1 1 36.0000 36.0000 36.0000 T10 100.00- 80.00 0.00 0.3750 A36 (36 ksi) 1 1 1 36.0000 36.0000 36.0000 T11 80.00- 60.00 0.00 0.3750 A36 (36 ksi) 1 1 1 36.0000 36.0000 36.0000 T12 60.00- 40.00 0.00 0.3750 A36 (36 ksi) 1 1 1 36.0000 36.0000 36.0000 T13 40.00- 20.00 0.00 0.3750 A36 (36 ksi) 1 1 1 36.0000 36.0000 36.0000 T14 20.00- 0.00 0.00 0.8750 A36 (36 ksi) 1 1 1 36.0000 36.0000 36.0000 Tower Section Geometry (cont’d) K Factors1 Tower Elevation ft Calc K Single Angles Calc K Solid Rounds Legs X Brace Diags X Y K Brace Diags X Y Single Diags X Y Girts X Y Horiz. X Y Sec. Horiz. X Y Inner Brace X Y T1 245.00- 240.00 Yes No 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 T2 240.00- 220.00 Yes No 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 T3 220.00- 210.00 Yes No 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 T4 210.00- 200.00 Yes No 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 T5 200.00- 180.00 Yes No 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 T6 180.00- 160.00 Yes No 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 T7 160.00- 140.00 Yes No 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 T8 140.00- 120.00 Yes No 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 T9 120.00- 100.00 Yes No 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 T10 100.00- 80.00 Yes No 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 T11 80.00- 60.00 Yes No 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 T12 60.00- 40.00 Yes No 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 T13 40.00- 20.00 Yes No 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 12 tnxTower Report - version 8.0.7.4 K Factors1 Tower Elevation ft Calc K Single Angles Calc K Solid Rounds Legs X Brace Diags X Y K Brace Diags X Y Single Diags X Y Girts X Y Horiz. X Y Sec. Horiz. X Y Inner Brace X Y T14 20.00- 0.00 Yes No 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1Note: K factors are applied to member segment lengths. K-braces without inner supporting members will have the K factor in the out-of- plane direction applied to the overall length. Tower Section Geometry (cont’d) Truss-Leg K Factors Truss-Legs Used As Leg Members Truss-Legs Used As Inner Members Tower Elevation ft Leg Panels X Brace Diagonals Z Brace Diagonals Leg Panels X Brace Diagonals Z Brace Diagonals T3 220.00- 210.00 1 0.5 0.7 1 0.5 0.85 T4 210.00- 200.00 1 0.5 0.7 1 0.5 0.85 T5 200.00- 180.00 1 0.5 0.7 1 0.5 0.85 T6 180.00- 160.00 1 0.5 0.7 1 0.5 0.85 T7 160.00- 140.00 1 0.5 0.7 1 0.5 0.85 T8 140.00- 120.00 1 0.5 0.7 1 0.5 0.85 T9 120.00- 100.00 1 0.5 0.7 1 0.5 0.85 T10 100.00- 80.00 1 0.5 0.7 1 0.5 0.85 T11 80.00- 60.00 1 0.5 0.7 1 0.5 0.85 T12 60.00- 40.00 1 0.5 0.7 1 0.5 0.85 T13 40.00- 20.00 1 0.5 0.7 1 0.5 0.85 T14 20.00- 0.00 1 0.5 0.7 1 0.5 0.85 Tower Section Geometry (cont’d) Tower Elevation ft Leg Diagonal Top Girt Bottom Girt Mid Girt Long Horizontal Short Horizontal Net Width Deduct in U Net Width Deduct in U Net Width Deduct in U Net Width Deduct in U Net Width Deduct in U Net Width Deduct in U Net Width Deduct in U T1 245.00- 240.00 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 T2 240.00- 220.00 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 T3 220.00- 210.00 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 T4 210.00- 200.00 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 T5 200.00- 180.00 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 13 tnxTower Report - version 8.0.7.4 Tower Elevation ft Leg Diagonal Top Girt Bottom Girt Mid Girt Long Horizontal Short Horizontal Net Width Deduct in U Net Width Deduct in U Net Width Deduct in U Net Width Deduct in U Net Width Deduct in U Net Width Deduct in U Net Width Deduct in U T6 180.00- 160.00 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 T7 160.00- 140.00 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 T8 140.00- 120.00 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 T9 120.00- 100.00 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 T10 100.00- 80.00 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 T11 80.00- 60.00 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 T12 60.00- 40.00 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 T13 40.00- 20.00 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 T14 20.00- 0.00 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 Tower Section Geometry (cont’d) Tower Elevation ft Leg Connection Type Leg Diagonal Top Girt Bottom Girt Mid Girt Long Horizontal Short Horizontal Bolt Size in No. Bolt Size in No. Bolt Size in No. Bolt Size in No. Bolt Size in No. Bolt Size in No. Bolt Size in No. T1 245.00- 240.00 Flange 0.8750 A325N 6 0.6250 A325N 1 0.6250 A325N 1 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 T2 240.00- 220.00 Flange 0.8750 A325N 6 0.6250 A325N 1 0.6250 A325N 1 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 T3 220.00- 210.00 Flange 0.6250 A325N 18 0.6250 A325N 2 0.6250 A325N 2 0.0000 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 T4 210.00- 200.00 Flange 0.7500 A325N 18 0.6250 A325N 2 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 T5 200.00- 180.00 Flange 0.7500 A325N 18 0.6250 A325N 2 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 T6 180.00- 160.00 Flange 0.8750 A325N 18 0.6250 A325N 2 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 T7 160.00- 140.00 Flange 0.8750 A325N 18 0.7500 A325N 2 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 T8 140.00- 120.00 Flange 0.8750 A325N 18 0.7500 A325N 2 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 T9 120.00- 100.00 Flange 0.8750 A325N 18 0.7500 A325N 2 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 T10 100.00- 80.00 Flange 1.0000 A325N 18 0.7500 A325N 2 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 T11 80.00- 60.00 Flange 1.0000 A325N 18 0.7500 A325N 2 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 T12 60.00- 40.00 Flange 1.0000 A325N 18 0.7500 A325N 2 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 T13 40.00- 20.00 Flange 1.1250 A325N 18 0.7500 A325N 2 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 T14 20.00- 0.00 Flange 1.1250 A325N 18 0.7500 A325N 2 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 0.6250 A325N 0 Feed Line/Linear Appurtenances - Entered As Round Or Flat August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 14 tnxTower Report - version 8.0.7.4 Description Face or Leg Allow Shield Exclude From Torque Calculation Componen t Type Placement ft Face Offset in Lateral Offset (Frac FW) # # Per Row Clear Spacin g in Width or Diameter in Perimete r in Weight plf *** *** Safety Line 3/8 B No No Ar (CaAa) 230.00 - 6.00 0.0000 0.5 1 1 0.3750 0.3750 0.22 **** HCS 2.0 Part 3(1-1/2) A No No Ar (CaAa) 220.00 - 6.00 0.0000 0.4 1 1 2.0000 1.5500 1.5500 1.71 ASU9323TY P01( 1-1/4) A No No Ar (CaAa) 220.00 - 6.00 1.2500 0.4 3 3 2.0000 0.5000 1.2400 1.05 1.5'' flat Cable Ladder Rail A No No Af (CaAa) 220.00 - 6.00 0.0000 0.4 2 2 24.000 0 1.5000 1.5000 1.80 LDF7-50A(1- 5/8) A No No Ar (CaAa) 200.00 - 6.00 0.0000 -0.38 6 4 0.5000 1.9800 0.82 LDF7-50A(1- 5/8) A No No Ar (CaAa) 200.00 - 6.00 0.0000 -0.41 4 4 0.5000 1.9800 0.82 WR- VG86ST- BRD( 3/4) A No No Ar (CaAa) 200.00 - 6.00 0.0000 -0.44 6 3 0.5000 0.7740 0.59 FB-L98B- 034- XXX(3/8) A No No Ar (CaAa) 200.00 - 6.00 1.5000 -0.44 3 2 0.3937 0.3937 0.06 840 10414(5/16) A No No Ar (CaAa) 200.00 - 6.00 1.5000 -0.44 3 2 0.3150 0.3150 0.06 LDF7-50A(1- 5/8) A No No Ar (CaAa) 200.00 - 6.00 0.0000 -0.46 2 2 0.5000 1.9800 0.82 1.5'' flat Cable Ladder Rail A No No Af (CaAa) 200.00 - 6.00 0.0000 -0.41 2 2 24.000 0 1.5000 1.5000 1.80 *** LDF5- 50A(7/8'') C No No Ar (CaAa) 128.00 - 6.00 0.0000 -0.45 3 2 1.5000 2.0000 1.0900 0.33 T-Brackets C No No Af (CaAa) 230.00 - 6.00 0.0000 -0.45 1 1 1.0000 1.0000 8.40 T-Brackets B No No Af (CaAa) 230.00 - 6.00 0.0000 0.45 1 1 1.0000 1.0000 8.40 *** LDF7-50A(1- 5/8) C No No Ar (CaAa) 245.00 - 6.00 0.0000 0.4 12 6 0.5000 1.9800 0.82 1.5'' flat Cable Ladder Rail C No No Af (CaAa) 230.00 - 6.00 0.0000 0.4 2 2 24.000 0 1.5000 1.5000 1.80 *** Feed Line/Linear Appurtenances - Entered As Area Description Face or Leg Allow Shield Exclude From Torque Calculation Componen t Type Placement ft Face Offset in Lateral Offset (Frac FW) # CAAA ft2/ft Weight plf *** *** * 1'' round Climb Ladder Rail B No No CaAa (In Face) 245.00 - 230.00 9.0000 0.1 2 No Ice 0.10 2.67 5/8'' ladder rung (12'' long 12'' oc) B No No CaAa (In Face) 245.00 - 230.00 9.0000 0.1 1 No Ice 0.06 1.04 Safety Line 3/8 B No No CaAa (In Face) 245.00 - 230.00 0.0000 0.1 1 No Ice 0.04 0.22 *** August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 15 tnxTower Report - version 8.0.7.4 Discrete Tower Loads Description Face or Leg Offset Type Offsets: Horz Lateral Vert ft ft ft Azimuth Adjustmen t ° Placement ft CAAA Front ft2 CAAA Side ft2 Weight K *** 5/8'' x 8 ft lightning rod C From Leg 0.00 0.00 4.00 0.0000 249.00 No Ice 0.50 0.50 0.01 Strobe Light B From Leg 0.00 0.00 0.00 0.0000 254.00 No Ice 1.08 1.08 0.05 2 3/8'' OD x 3.5' Mount Pipe B From Leg 0.00 0.00 0.00 0.0000 245.00 No Ice 0.72 0.72 0.01 Obstruction light A From Leg 1.00 0.00 0.00 0.0000 123.00 No Ice 0.50 0.50 0.01 Obstruction light B From Leg 1.00 0.00 0.00 0.0000 123.00 No Ice 0.50 0.50 0.01 Obstruction light C From Leg 1.00 0.00 0.00 0.0000 123.00 No Ice 0.50 0.50 0.01 *** BSA-185025/12 w/ Mount Pipe A From Leg 4.00 0.00 1.00 0.0000 249.00 No Ice 8.76 3.61 0.06 BSA-185065/12x2 w/ Mount Pipe B From Leg 4.00 0.00 1.00 0.0000 249.00 No Ice 5.02 3.61 0.04 BSA-185065/12x2 w/ Mount Pipe C From Leg 4.00 0.00 1.00 0.0000 249.00 No Ice 5.02 3.61 0.04 (2) X7CQAP-FRO-645- VR0 w/ Mount Pipe A From Leg 4.00 0.00 1.00 0.0000 249.00 No Ice 11.63 7.79 0.09 (2) X7CQAP-665-VR0 w/ Mount Pipe B From Leg 4.00 0.00 1.00 0.0000 249.00 No Ice 9.51 6.34 0.08 (2) X7CQAP-FRO-645- VR0 w/ Mount Pipe C From Leg 4.00 0.00 1.00 0.0000 249.00 No Ice 11.63 7.79 0.09 (2) DBC-67C-U-2SF A From Leg 4.00 0.00 1.00 0.0000 249.00 No Ice 0.16 0.11 0.01 (2) DBC-67C-U-2SF B From Leg 4.00 0.00 1.00 0.0000 249.00 No Ice 0.16 0.11 0.01 (2) DBC-67C-U-2SF C From Leg 4.00 0.00 1.00 0.0000 249.00 No Ice 0.16 0.11 0.01 Platform Mount [LP 603-1] C None 0.0000 249.00 No Ice 40.62 40.62 2.06 Empty Mount Pipe A From Leg 4.00 0.00 0.00 0.0000 249.00 No Ice 1.20 1.20 0.02 Empty Mount Pipe B From Leg 4.00 0.00 0.00 0.0000 249.00 No Ice 1.20 1.20 0.02 Empty Mount Pipe C From Leg 4.00 0.00 0.00 0.0000 249.00 No Ice 1.20 1.20 0.02 ***220*** ADFD1820-3333B-XDM w/ Mount Pipe A From Leg 4.00 0.00 3.00 0.0000 220.00 No Ice 11.64 4.06 0.06 August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 16 tnxTower Report - version 8.0.7.4 Description Face or Leg Offset Type Offsets: Horz Lateral Vert ft ft ft Azimuth Adjustmen t ° Placement ft CAAA Front ft2 CAAA Side ft2 Weight K ADFD1820-3333B-XDM w/ Mount Pipe B From Leg 4.00 0.00 3.00 0.0000 220.00 No Ice 11.64 4.06 0.06 ADFD1820-3333B-XDM w/ Mount Pipe C From Leg 4.00 0.00 3.00 0.0000 220.00 No Ice 11.64 4.06 0.06 FFHH-65C-R3 w/ Mount Pipe A From Leg 4.00 0.00 3.00 0.0000 220.00 No Ice 12.97 6.20 0.16 FFHH-65C-R3 w/ Mount Pipe B From Leg 4.00 0.00 3.00 0.0000 220.00 No Ice 12.97 6.20 0.16 FFHH-65C-R3 w/ Mount Pipe C From Leg 4.00 0.00 3.00 0.0000 220.00 No Ice 12.97 6.20 0.16 AHLOA A From Leg 4.00 0.00 3.00 0.0000 220.00 No Ice 2.23 1.39 0.08 AHLOA B From Leg 4.00 0.00 3.00 0.0000 220.00 No Ice 2.23 1.39 0.08 AHLOA C From Leg 4.00 0.00 3.00 0.0000 220.00 No Ice 2.23 1.39 0.08 ASU9338TYP01 A From Leg 4.00 0.00 0.00 0.0000 220.00 No Ice 3.20 1.03 0.02 ASU9338TYP01 B From Leg 4.00 0.00 0.00 0.0000 220.00 No Ice 3.20 1.03 0.02 ASU9338TYP01 C From Leg 4.00 0.00 0.00 0.0000 220.00 No Ice 3.20 1.03 0.02 AEHC w/ Mount Pipe A From Leg 4.00 0.00 3.00 0.0000 220.00 No Ice 6.96 3.45 0.11 AEHC w/ Mount Pipe B From Leg 4.00 0.00 3.00 0.0000 220.00 No Ice 6.96 3.45 0.11 AEHC w/ Mount Pipe C From Leg 4.00 0.00 3.00 0.0000 220.00 No Ice 6.96 3.45 0.11 (2) AHFIG A From Leg 4.00 0.00 3.00 0.0000 220.00 No Ice 3.08 1.40 0.08 (2) AHFIG B From Leg 4.00 0.00 3.00 0.0000 220.00 No Ice 3.08 1.40 0.08 (2) AHFIG C From Leg 4.00 0.00 3.00 0.0000 220.00 No Ice 3.08 1.40 0.08 HCS 2.0 A From Leg 4.00 0.00 3.00 0.0000 220.00 No Ice 0.94 0.70 0.00 Site Pro 1 VFA12-HD A From Leg 2.00 0.00 0.00 0.0000 220.00 No Ice 13.20 9.20 0.66 Site Pro 1 VFA12-HD B From Leg 2.00 0.00 0.00 0.0000 220.00 No Ice 13.20 9.20 0.66 Site Pro 1 VFA12-HD C From Leg 2.00 0.00 0.00 0.0000 220.00 No Ice 13.20 9.20 0.66 *** 800 10723 w/ Mount Pipe A From Leg 4.00 0.0000 200.00 No Ice 6.67 4.76 0.10 August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 17 tnxTower Report - version 8.0.7.4 Description Face or Leg Offset Type Offsets: Horz Lateral Vert ft ft ft Azimuth Adjustmen t ° Placement ft CAAA Front ft2 CAAA Side ft2 Weight K 0.00 3.00 800 10723 w/ Mount Pipe B From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 6.67 4.76 0.10 800 10723 w/ Mount Pipe C From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 6.67 4.76 0.10 (2) HPA-33R-BUU-H6-K w/ Mount Pipe A From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 14.77 7.45 0.11 (2) HPA-33R-BUU-H6-K w/ Mount Pipe C From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 14.77 7.45 0.11 SBNHH-1D85C w/ Mount Pipe A From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 5.56 4.47 0.08 SBNHH-1D85C w/ Mount Pipe B From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 5.56 4.47 0.08 SBNHH-1D85C w/ Mount Pipe C From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 5.56 4.47 0.08 800 10865 w/ Mount Pipe B From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 7.15 4.45 0.10 (2) E15Z01P19 A From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 0.78 0.34 0.01 (4) E15Z01P19 B From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 0.78 0.34 0.01 (2) TBC0020F1V1 B From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 0.51 0.37 0.01 TBC0020F1V1 A From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 0.51 0.37 0.01 (3) TBC0020F1V1 C From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 0.51 0.37 0.01 (5) RRUS 32 A From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 2.86 1.78 0.06 DC6-48-60-18-8C A From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 2.74 2.74 0.03 DC6-48-60-18-8C C From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 2.74 2.74 0.03 KFTDR00110030 A From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 0.91 0.42 0.03 (4) KFTDR00110030 C From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 0.91 0.42 0.03 (2) RRUS 4415 B25 A From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 1.64 0.68 0.04 RRUS 4415 B25 B From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 1.64 0.68 0.04 DC6-48-60-18-8F B From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 1.21 1.21 0.03 August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 18 tnxTower Report - version 8.0.7.4 Description Face or Leg Offset Type Offsets: Horz Lateral Vert ft ft ft Azimuth Adjustmen t ° Placement ft CAAA Front ft2 CAAA Side ft2 Weight K RRUS 4426 B66 B From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 1.64 0.73 0.05 RRUS-11 C From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 2.79 1.19 0.05 (2) RRUS-11 C From Leg 4.00 0.00 3.00 0.0000 200.00 No Ice 2.79 1.19 0.05 Sector Mount [SM 502-3] A None 0.0000 200.00 No Ice 33.02 33.02 1.67 *** APXVSPP18-C w/ Mount Pipe A From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 4.60 4.01 0.09 APXVSPP18-C w/ Mount Pipe B From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 4.60 4.01 0.09 APXVSPP18-C w/ Mount Pipe C From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 4.60 4.01 0.09 TTTT65AP-1XR w/ Mount Pipe A From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 5.30 3.18 0.06 TTTT65AP-1XR w/ Mount Pipe B From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 5.30 3.18 0.06 TTTT65AP-1XR w/ Mount Pipe C From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 5.30 3.18 0.06 RRUS 82 W/SOLAR SHIELD A From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 2.98 1.43 0.06 RRUS 82 W/SOLAR SHIELD B From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 2.98 1.43 0.06 RRUS 82 W/SOLAR SHIELD C From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 2.98 1.43 0.06 RRUS-11 800MHz A From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 2.52 1.30 0.05 RRUS-11 800MHz B From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 2.52 1.30 0.05 RRUS-11 800MHz C From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 2.52 1.30 0.05 RRUS 31 B25 A From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 1.62 1.28 0.06 RRUS 31 B25 B From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 1.62 1.28 0.06 RRUS 31 B25 C From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 1.62 1.28 0.06 800MHZ SMR FILTER A From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 0.65 0.22 0.01 800MHZ SMR FILTER B From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 0.65 0.22 0.01 800MHZ SMR FILTER C From Leg 4.00 0.00 1.00 0.0000 128.00 No Ice 0.65 0.22 0.01 August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 19 tnxTower Report - version 8.0.7.4 Description Face or Leg Offset Type Offsets: Horz Lateral Vert ft ft ft Azimuth Adjustmen t ° Placement ft CAAA Front ft2 CAAA Side ft2 Weight K (2) Empty Mount Pipe A From Leg 4.00 0.00 0.00 0.0000 128.00 No Ice 1.20 1.20 0.02 (2) Empty Mount Pipe B From Leg 4.00 0.00 0.00 0.0000 128.00 No Ice 1.20 1.20 0.02 (2) Empty Mount Pipe C From Leg 4.00 0.00 0.00 0.0000 128.00 No Ice 1.20 1.20 0.02 (3) Connect-It V-Frame P/N: PVFM(fw)-3-n-mh-2 C None 0.0000 128.00 No Ice 33.02 33.02 1.67 *** Truss-Leg Properties Section Designation Area in2 Area Ice in2 Self Weight K Ice Weight K Equiv. Diamete r in Equiv. Diamete r Ice in Leg Area in2 15TL1.5x1/2x5/8 2501.4163 2501.4163 0.76 0.00 8.6855 8.6855 5.3014 15TL1.5x1/2x5/8 2501.4163 2501.4163 0.76 0.00 8.6855 8.6855 5.3014 15TL1.75x1/2x5/8 2628.4298 2628.4298 0.89 0.00 9.1265 9.1265 7.2158 15TL1.75x1/2x5/8 2628.4298 2628.4298 0.89 0.00 9.1265 9.1265 7.2158 Trylon 2.00 (18x15) 2978.4799 2978.4799 0.96 0.00 10.3419 10.3419 9.4248 Trylon 2.25 (18x15) 3106.3441 3106.3441 1.13 0.00 10.7859 10.7859 11.9282 Trylon 2.25 (18x15) 3106.3441 3106.3441 1.13 0.00 10.7859 10.7859 11.9282 Trylon 2.5 (18x24) 3096.4779 3096.4779 1.42 0.00 10.7517 10.7517 14.7262 Trylon 2.75 (18x24) 3227.6991 3227.6991 1.63 0.00 11.2073 11.2073 17.8187 Trylon 2.75 (18x24) 3227.6991 3227.6991 1.63 0.00 11.2073 11.2073 17.8187 Trylon 2.75 (18x24) 3227.6991 3227.6991 1.63 0.00 11.2073 11.2073 17.8187 Trylon 3.00 (18x24) 3421.5531 3421.5531 1.91 0.00 11.8804 11.8804 21.2058 Load Combinations Comb. No. Description 1 Dead Only 2 1.2 Dead+1.0 Wind 0 deg - No Ice 3 0.9 Dead+1.0 Wind 0 deg - No Ice 4 1.2 Dead+1.0 Wind 30 deg - No Ice 5 0.9 Dead+1.0 Wind 30 deg - No Ice 6 1.2 Dead+1.0 Wind 60 deg - No Ice 7 0.9 Dead+1.0 Wind 60 deg - No Ice 8 1.2 Dead+1.0 Wind 90 deg - No Ice 9 0.9 Dead+1.0 Wind 90 deg - No Ice 10 1.2 Dead+1.0 Wind 120 deg - No Ice 11 0.9 Dead+1.0 Wind 120 deg - No Ice 12 1.2 Dead+1.0 Wind 150 deg - No Ice August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 20 tnxTower Report - version 8.0.7.4 Comb. No. Description 13 0.9 Dead+1.0 Wind 150 deg - No Ice 14 1.2 Dead+1.0 Wind 180 deg - No Ice 15 0.9 Dead+1.0 Wind 180 deg - No Ice 16 1.2 Dead+1.0 Wind 210 deg - No Ice 17 0.9 Dead+1.0 Wind 210 deg - No Ice 18 1.2 Dead+1.0 Wind 240 deg - No Ice 19 0.9 Dead+1.0 Wind 240 deg - No Ice 20 1.2 Dead+1.0 Wind 270 deg - No Ice 21 0.9 Dead+1.0 Wind 270 deg - No Ice 22 1.2 Dead+1.0 Wind 300 deg - No Ice 23 0.9 Dead+1.0 Wind 300 deg - No Ice 24 1.2 Dead+1.0 Wind 330 deg - No Ice 25 0.9 Dead+1.0 Wind 330 deg - No Ice 26 Dead+Wind 0 deg - Service 27 Dead+Wind 30 deg - Service 28 Dead+Wind 60 deg - Service 29 Dead+Wind 90 deg - Service 30 Dead+Wind 120 deg - Service 31 Dead+Wind 150 deg - Service 32 Dead+Wind 180 deg - Service 33 Dead+Wind 210 deg - Service 34 Dead+Wind 240 deg - Service 35 Dead+Wind 270 deg - Service 36 Dead+Wind 300 deg - Service 37 Dead+Wind 330 deg - Service Maximum Reactions Location Condition Gov. Load Comb. Vertical K Horizontal, X K Horizontal, Z K Leg C Max. Vert 18 759.23 71.08 -41.84 Max. Hx 18 759.23 71.08 -41.84 Max. Hz 7 -659.93 -62.88 37.15 Min. Vert 7 -659.93 -62.88 37.15 Min. Hx 7 -659.93 -62.88 37.15 Min. Hz 18 759.23 71.08 -41.84 Leg B Max. Vert 10 779.59 -75.87 -39.75 Max. Hx 23 -683.43 67.79 35.04 Max. Hz 23 -683.43 67.79 35.04 Min. Vert 23 -683.43 67.79 35.04 Min. Hx 10 779.59 -75.87 -39.75 Min. Hz 10 779.59 -75.87 -39.75 Leg A Max. Vert 2 799.52 -4.26 87.06 Max. Hx 19 -337.75 6.01 -37.87 Max. Hz 2 799.52 -4.26 87.06 Min. Vert 15 -705.29 4.35 -77.76 Min. Hx 7 374.50 -5.75 40.11 Min. Hz 15 -705.29 4.35 -77.76 Maximum Tower Deflections - Service Wind Section No. Elevation ft Horz. Deflection in Gov. Load Comb. Tilt ° Twist ° T1 245 - 240 5.939 26 0.2379 0.0459 T2 240 - 220 5.688 26 0.2370 0.0457 T3 220 - 210 4.706 26 0.2238 0.0435 T4 210 - 200 4.238 26 0.2126 0.0412 T5 200 - 180 3.798 26 0.1992 0.0392 T6 180 - 160 2.991 26 0.1743 0.0337 T7 160 - 140 2.298 26 0.1444 0.0280 August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 21 tnxTower Report - version 8.0.7.4 Section No. Elevation ft Horz. Deflection in Gov. Load Comb. Tilt ° Twist ° T8 140 - 120 1.726 26 0.1201 0.0234 T9 120 - 100 1.253 26 0.0995 0.0193 T10 100 - 80 0.863 26 0.0780 0.0154 T11 80 - 60 0.558 26 0.0600 0.0119 T12 60 - 40 0.321 26 0.0447 0.0085 T13 40 - 20 0.147 26 0.0292 0.0052 T14 20 - 0 0.036 26 0.0133 0.0021 Critical Deflections and Radius of Curvature - Service Wind Elevation ft Appurtenance Gov. Load Comb. Deflection in Tilt ° Twist ° Radius of Curvature ft 254.00 Strobe Light 26 5.939 0.2379 0.0459 207242 249.00 5/8'' x 8 ft lightning rod 26 5.939 0.2379 0.0459 207242 245.00 2 3/8'' OD x 3.5' Mount Pipe 26 5.939 0.2379 0.0459 207242 220.00 ADFD1820-3333B-XDM w/ Mount Pipe 26 4.706 0.2238 0.0435 70944 200.00 800 10723 w/ Mount Pipe 26 3.798 0.1992 0.0392 55349 128.00 APXVSPP18-C w/ Mount Pipe 26 1.432 0.1078 0.0209 55807 123.00 Obstruction light 26 1.318 0.1027 0.0199 58548 Maximum Tower Deflections - Design Wind Section No. Elevation ft Horz. Deflection in Gov. Load Comb. Tilt ° Twist ° T1 245 - 240 37.880 2 1.5175 0.2915 T2 240 - 220 36.281 2 1.5114 0.2904 T3 220 - 210 30.019 2 1.4268 0.2762 T4 210 - 200 27.039 2 1.3551 0.2621 T5 200 - 180 24.236 2 1.2696 0.2494 T6 180 - 160 19.085 2 1.1118 0.2141 T7 160 - 140 14.670 2 0.9219 0.1779 T8 140 - 120 11.020 2 0.7672 0.1490 T9 120 - 100 7.996 2 0.6359 0.1225 T10 100 - 80 5.509 2 0.4987 0.0982 T11 80 - 60 3.563 2 0.3834 0.0754 T12 60 - 40 2.047 2 0.2858 0.0538 T13 40 - 20 0.936 2 0.1864 0.0331 T14 20 - 0 0.232 2 0.0848 0.0135 Critical Deflections and Radius of Curvature - Design Wind Elevation ft Appurtenance Gov. Load Comb. Deflection in Tilt ° Twist ° Radius of Curvature ft 254.00 Strobe Light 2 37.880 1.5175 0.2915 32561 249.00 5/8'' x 8 ft lightning rod 2 37.880 1.5175 0.2915 32561 245.00 2 3/8'' OD x 3.5' Mount Pipe 2 37.880 1.5175 0.2915 32561 220.00 ADFD1820-3333B-XDM w/ Mount Pipe 2 30.019 1.4268 0.2762 11054 200.00 800 10723 w/ Mount Pipe 2 24.236 1.2696 0.2494 8730 128.00 APXVSPP18-C w/ Mount Pipe 2 9.139 0.6886 0.1329 8745 123.00 Obstruction light 2 8.414 0.6559 0.1263 9149 August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 22 tnxTower Report - version 8.0.7.4 Bolt Design Data Section No. Elevation ft Component Type Bolt Grade Bolt Size in Number Of Bolts Maximum Load per Bolt K Allowable Load per Bolt K Ratio Load Allowable Allowable Ratio Criteria T1 245 Leg A325N 0.8750 6 1.60 41.56 0.039 1.05 Bolt Tension Diagonal A325N 0.6250 1 3.92 13.81 0.284 1.05 Bolt Shear Top Girt A325N 0.6250 1 1.21 13.81 0.088 1.05 Bolt Shear T2 240 Leg A325N 0.8750 6 8.50 41.56 0.204 1.05 Bolt Tension Diagonal A325N 0.6250 1 6.11 13.81 0.443 1.05 Bolt Shear Top Girt A325N 0.6250 1 0.30 13.81 0.022 1.05 Bolt Shear T3 220 Leg A325N 0.6250 18 3.86 20.34 0.190 1.05 Bolt Tension Diagonal A325N 0.6250 2 4.78 12.24 0.390 1.05 Member Block Shear Top Girt A325N 0.6250 2 0.07 12.24 0.005 1.05 Member Block Shear T4 210 Leg A325N 0.7500 18 5.40 30.10 0.179 1.05 Bolt Tension Diagonal A325N 0.6250 2 5.30 12.24 0.433 1.05 Member Block Shear T5 200 Leg A325N 0.7500 18 9.05 30.10 0.301 1.05 Bolt Tension Diagonal A325N 0.6250 2 6.99 12.24 0.571 1.05 Member Block Shear T6 180 Leg A325N 0.8750 18 12.70 41.56 0.306 1.05 Bolt Tension Diagonal A325N 0.6250 2 8.20 13.81 0.594 1.05 Bolt Shear T7 160 Leg A325N 0.8750 18 14.71 41.56 0.354 1.05 Bolt Tension Diagonal A325N 0.7500 2 13.91 19.88 0.700 1.05 Bolt Shear T8 140 Leg A325N 0.8750 18 18.40 41.56 0.443 1.05 Bolt Tension Diagonal A325N 0.7500 2 12.83 19.88 0.646 1.05 Bolt Shear T9 120 Leg A325N 0.8750 18 21.57 41.56 0.519 1.05 Bolt Tension Diagonal A325N 0.7500 2 14.78 19.88 0.743 1.05 Bolt Shear T10 100 Leg A325N 1.0000 18 25.10 54.52 0.460 1.05 Bolt Tension Diagonal A325N 0.7500 2 14.33 19.88 0.721 1.05 Bolt Shear T11 80 Leg A325N 1.0000 18 28.37 54.52 0.520 1.05 Bolt Tension Diagonal A325N 0.7500 2 14.79 19.88 0.744 1.05 Bolt Shear T12 60 Leg A325N 1.0000 18 31.55 54.52 0.579 1.05 Bolt Tension Diagonal A325N 0.7500 2 15.74 19.88 0.792 1.05 Bolt Shear T13 40 Leg A325N 1.1250 18 34.78 68.69 0.506 1.05 Bolt Tension Diagonal A325N 0.7500 2 14.96 19.88 0.752 1.05 Bolt Shear T14 20 Leg A325N 1.1250 18 37.57 68.69 0.547 1.05 Bolt Tension Diagonal A325N 0.7500 2 18.39 19.88 0.925 1.05 Bolt Shear Compression Checks Leg Design Data (Compression) Section No. Elevation ft Size L ft Lu ft Kl/r A in2 Pu K fPn K Ratio Pu fPn T1 245 - 240 2 1/2'' solid 5.00 5.00 96.0 K=1.00 4.9087 -11.84 112.60 0.105 1 T2 240 - 220 2 1/2'' solid 20.00 5.00 96.0 K=1.00 4.9087 -56.32 112.60 0.500 1 T3 220 - 210 15TL1.5x1/2x5/8 10.02 10.02 40.0 K=1.00 5.3014 -78.78 212.23 0.371 1 T4 210 - 200 15TL1.5x1/2x5/8 10.02 10.02 40.0 K=1.00 5.3014 -109.25 212.23 0.515 1 T5 200 - 180 15TL1.75x1/2x5/8 20.03 10.02 34.3 K=1.00 7.2158 -182.98 297.97 0.614 1 T6 180 - 160 15TL1.75x1/2x5/8 20.03 10.02 34.3 7.2158 -254.01 297.97 0.852 1 August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 23 tnxTower Report - version 8.0.7.4 Section No. Elevation ft Size L ft Lu ft Kl/r A in2 Pu K fPn K Ratio Pu fPn K=1.00 T7 160 - 140 Trylon 2.00 (18x15) 20.03 20.03 32.6 K=1.00 9.4248 -291.96 397.85 0.734 1 T8 140 - 120 Trylon 2.25 (18x15) 20.03 20.03 32.6 K=1.00 11.928 2 -367.95 503.58 0.731 1 T9 120 - 100 Trylon 2.25 (18x15) 20.03 20.03 32.6 K=1.00 11.928 2 -431.82 503.58 0.858 1 T10 100 - 80 Trylon 2.5 (18x24) 20.03 20.03 38.4 K=1.00 14.726 2 -503.71 603.04 0.835 1 T11 80 - 60 Trylon 2.75 (18x24) 20.03 20.03 34.9 K=1.00 17.818 7 -571.06 743.67 0.768 1 T12 60 - 40 Trylon 2.75 (18x24) 20.03 20.03 34.9 K=1.00 17.818 7 -636.87 743.67 0.856 1 T13 40 - 20 Trylon 2.75 (18x24) 20.03 20.03 34.9 K=1.00 17.818 7 -704.24 743.67 0.947 1 T14 20 - 0 Trylon 3.00 (18x24) 20.03 20.03 32.5 K=1.00 21.205 7 -763.15 895.57 0.852 1 1 P u / fPn controls Truss-Leg Diagonal Data Section No. Elevation ft Diagonal Size Ld ft Kl/r fPn K A in2 Vu K fVn K Stress Ratio T3 220 - 210 0.5 1.68 113.0 238.57 0.1963 1.98 4.18 0.474 T4 210 - 200 0.5 1.68 113.0 238.57 0.1963 1.11 4.18 0.266 T5 200 - 180 0.5 1.67 112.1 324.71 0.1963 1.05 4.24 0.247 T6 180 - 160 0.5 1.67 112.1 324.71 0.1963 1.93 4.24 0.455 T7 160 - 140 0.625 1.83 98.3 430.59 0.3068 1.41 8.65 0.163 T8 140 - 120 0.625 1.81 97.4 544.96 0.3068 1.99 8.74 0.227 T9 120 - 100 0.625 1.81 97.4 544.96 0.3068 1.36 8.74 0.156 T10 100 - 80 0.625 2.38 128.0 672.79 0.3068 1.35 4.40 0.308 T11 80 - 60 0.625 2.37 127.4 814.08 0.3068 1.31 4.44 0.294 T12 60 - 40 0.625 2.37 127.4 814.08 0.3068 1.46 4.44 0.330 T13 40 - 20 0.625 2.37 127.4 814.08 0.3068 2.29 4.44 0.515 T14 20 - 0 0.75 2.36 105.7 968.83 0.4418 2.66 8.84 0.301 Diagonal Design Data (Compression) Section No. Elevation ft Size L ft Lu ft Kl/r A in2 Pu K fPn K Ratio Pu fPn T1 245 - 240 L2 1/2x2 1/2x1/4 7.81 3.63 96.6 K=1.09 1.1900 -3.92 33.41 0.117 1 T2 240 - 220 L2 1/2x2 1/2x1/4 7.81 3.63 96.6 K=1.09 1.1900 -6.11 33.41 0.183 1 T3 220 - 210 L3x3x1/4 11.93 5.06 107.0 K=1.04 1.4400 -10.40 35.40 0.294 1 T4 210 - 200 L3x3x1/4 12.50 5.41 112.3 K=1.02 1.4400 -10.90 32.62 0.334 1 T5 200 - 180 L3x3x1/4 13.80 6.14 123.4 K=0.99 1.4400 -14.44 27.05 0.534 1 T6 180 - 160 L3 1/2x3 1/2x1/4 15.24 6.91 119.6 K=1.00 1.6900 -15.24 33.80 0.451 1 T7 160 - 140 L5x5x3/8 23.86 11.23 132.4 K=0.97 3.6100 -27.81 58.98 0.472 1 T8 140 - 120 L5x5x3/8 25.01 11.85 138.0 K=0.96 3.6100 -25.40 54.23 0.468 1 T9 120 - 100 L5x5x3/8 26.26 12.50 144.1 K=0.95 3.6100 -29.55 49.77 0.594 1 August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 24 tnxTower Report - version 8.0.7.4 Section No. Elevation ft Size L ft Lu ft Kl/r A in2 Pu K fPn K Ratio Pu fPn T10 100 - 80 L5x5x3/8 27.59 13.19 150.5 K=0.94 3.6100 -28.66 45.64 0.628 1 T11 80 - 60 L5x5x3/8 29.01 13.92 157.2 K=0.93 3.6100 -29.59 41.84 0.707 1 T12 60 - 40 L5x5x3/8 30.49 14.67 164.1 K=0.92 3.6100 -31.48 38.36 0.821 1 T13 40 - 20 L5x5x3/8 32.02 15.45 171.3 K=0.91 3.6100 -29.25 35.21 0.831 1 T14 20 - 0 L6x6x7/16 33.61 16.25 153.5 K=0.94 5.0600 -36.78 61.48 0.598 1 1 P u / fPn controls Top Girt Design Data (Compression) Section No. Elevation ft Size L ft Lu ft Kl/r A in2 Pu K fPn K Ratio Pu fPn T1 245 - 240 L6x6x7/16 6.00 5.52 87.8 K=1.58 5.0600 -1.17 155.61 0.007 1 T2 240 - 220 L6x6x7/16 6.00 5.52 87.8 K=1.58 5.0600 -0.14 155.61 0.001 1 T3 220 - 210 L3x3x1/4 6.00 4.32 103.8 K=1.18 1.4400 -0.14 36.99 0.004 1 1 P u / fPn controls Tension Checks Leg Design Data (Tension) Section No. Elevation ft Size L ft Lu ft Kl/r A in2 Pu K fPn K Ratio Pu fPn T1 245 - 240 2 1/2'' solid 5.00 5.00 96.0 4.9087 9.62 220.89 0.044 1 T2 240 - 220 2 1/2'' solid 20.00 5.00 96.0 4.9087 50.98 220.89 0.231 1 T3 220 - 210 15TL1.5x1/2x5/8 10.02 10.02 40.0 5.3014 69.51 238.57 0.291 1 T4 210 - 200 15TL1.5x1/2x5/8 10.02 10.02 40.0 5.3014 97.16 238.57 0.407 1 T5 200 - 180 15TL1.75x1/2x5/8 20.03 10.02 34.3 7.2158 162.94 324.71 0.502 1 T6 180 - 160 15TL1.75x1/2x5/8 20.03 10.02 34.3 7.2158 228.57 324.71 0.704 1 T7 160 - 140 Trylon 2.00 (18x15) 20.03 20.03 32.6 9.4248 264.74 430.59 0.615 1 T8 140 - 120 Trylon 2.25 (18x15) 20.03 20.03 32.6 11.928 2 331.28 544.96 0.608 1 T9 120 - 100 Trylon 2.25 (18x15) 20.03 20.03 32.6 11.928 2 388.33 544.96 0.713 1 T10 100 - 80 Trylon 2.5 (18x24) 20.03 20.03 38.4 14.726 2 451.87 672.79 0.672 1 T11 80 - 60 Trylon 2.75 (18x24) 20.03 20.03 34.9 17.818 7 510.67 814.08 0.627 1 T12 60 - 40 Trylon 2.75 (18x24) 20.03 20.03 34.9 17.818 7 567.99 814.08 0.698 1 T13 40 - 20 Trylon 2.75 (18x24) 20.03 20.03 34.9 17.818 7 626.01 814.08 0.769 1 T14 20 - 0 Trylon 3.00 (18x24) 20.03 20.03 32.5 21.205 7 676.23 968.83 0.698 1 August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 25 tnxTower Report - version 8.0.7.4 1 P u / fPn controls Truss-Leg Diagonal Data Section No. Elevation ft Diagonal Size Ld ft Kl/r fPn K A in2 Vu K fVn K Stress Ratio T3 220 - 210 0.5 1.68 113.0 238.57 0.1963 1.98 4.18 0.474 T4 210 - 200 0.5 1.68 113.0 238.57 0.1963 1.11 4.18 0.266 T5 200 - 180 0.5 1.67 112.1 324.71 0.1963 1.05 4.24 0.247 T6 180 - 160 0.5 1.67 112.1 324.71 0.1963 1.93 4.24 0.455 T7 160 - 140 0.625 1.83 98.3 430.59 0.3068 1.41 8.65 0.163 T8 140 - 120 0.625 1.81 97.4 544.96 0.3068 1.99 8.74 0.227 T9 120 - 100 0.625 1.81 97.4 544.96 0.3068 1.36 8.74 0.156 T10 100 - 80 0.625 2.38 128.0 672.79 0.3068 1.35 4.40 0.308 T11 80 - 60 0.625 2.37 127.4 814.08 0.3068 1.31 4.44 0.294 T12 60 - 40 0.625 2.37 127.4 814.08 0.3068 1.46 4.44 0.330 T13 40 - 20 0.625 2.37 127.4 814.08 0.3068 2.29 4.44 0.515 T14 20 - 0 0.75 2.36 105.7 968.83 0.4418 2.66 8.84 0.301 Diagonal Design Data (Tension) Section No. Elevation ft Size L ft Lu ft Kl/r A in2 Pu K fPn K Ratio Pu fPn T1 245 - 240 L2 1/2x2 1/2x1/4 7.81 3.63 58.8 0.7519 3.72 36.80 0.101 1 T2 240 - 220 L2 1/2x2 1/2x1/4 7.81 3.63 58.8 0.7519 5.95 36.80 0.162 1 T3 220 - 210 L3x3x1/4 11.93 5.06 68.1 0.9394 9.55 45.98 0.208 1 T4 210 - 200 L3x3x1/4 12.50 5.41 72.6 0.9394 10.60 45.98 0.230 1 T5 200 - 180 L3x3x1/4 13.80 6.14 82.0 0.9394 13.98 45.98 0.304 1 T6 180 - 160 L3 1/2x3 1/2x1/4 15.24 6.91 78.4 1.1269 15.57 55.16 0.282 1 T7 160 - 140 L5x5x3/8 23.86 11.23 88.3 2.4614 25.34 120.49 0.210 1 T8 140 - 120 L5x5x3/8 25.01 11.85 93.0 2.4614 25.67 120.49 0.213 1 T9 120 - 100 L5x5x3/8 26.26 12.50 98.0 2.4614 27.16 120.49 0.225 1 T10 100 - 80 L5x5x3/8 27.59 13.19 103.3 2.4614 27.18 120.49 0.226 1 T11 80 - 60 L5x5x3/8 29.01 13.92 108.9 2.4614 27.47 120.49 0.228 1 T12 60 - 40 L5x5x3/8 30.49 14.67 114.7 2.4614 28.97 120.49 0.240 1 T13 40 - 20 L5x5x3/8 32.02 15.45 120.7 2.4614 29.91 120.49 0.248 1 T14 20 - 0 L6x6x7/16 33.61 16.25 105.8 3.5079 32.91 171.71 0.192 1 1 P u / fPn controls Top Girt Design Data (Tension) Section No. Elevation ft Size L ft Lu ft Kl/r A in2 Pu K fPn K Ratio Pu fPn T1 245 - 240 L6x6x7/16 6.00 5.52 37.2 3.5489 1.21 173.72 0.007 1 T2 240 - 220 L6x6x7/16 6.00 5.52 37.2 3.5489 0.30 173.72 0.002 1 T3 220 - 210 L3x3x1/4 6.00 4.32 61.3 0.9394 0.13 45.98 0.003 1 1 P u / fPn controls Section Capacity Table Section No. Elevation ft Component Type Size Critical Element P K øPallow K % Capacity Pass Fail August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 26 tnxTower Report - version 8.0.7.4 Section No. Elevation ft Component Type Size Critical Element P K øPallow K % Capacity Pass Fail T1 245 - 240 Leg 2 1/2'' solid 3 -11.84 118.23 10.0 Pass T2 240 - 220 Leg 2 1/2'' solid 15 -56.32 118.23 47.6 Pass T3 220 - 210 Leg 15TL1.5x1/2x5/8 44 -74.92 222.84 45.2 Pass T4 210 - 200 Leg 15TL1.5x1/2x5/8 57 -109.25 222.84 49.0 Pass T5 200 - 180 Leg 15TL1.75x1/2x5/8 66 -182.98 312.87 58.5 Pass T6 180 - 160 Leg 15TL1.75x1/2x5/8 81 -254.01 312.87 81.2 Pass T7 160 - 140 Leg Trylon 2.00 (18x15) 96 -291.96 417.74 69.9 Pass T8 140 - 120 Leg Trylon 2.25 (18x15) 105 -367.95 528.76 69.6 Pass T9 120 - 100 Leg Trylon 2.25 (18x15) 114 -431.82 528.76 81.7 Pass T10 100 - 80 Leg Trylon 2.5 (18x24) 123 -503.71 633.19 79.6 Pass T11 80 - 60 Leg Trylon 2.75 (18x24) 132 -571.06 780.85 73.1 Pass T12 60 - 40 Leg Trylon 2.75 (18x24) 141 -636.87 780.85 81.6 Pass T13 40 - 20 Leg Trylon 2.75 (18x24) 150 -704.24 780.85 90.2 Pass T14 20 - 0 Leg Trylon 3.00 (18x24) 159 -763.15 940.35 81.2 Pass T1 245 - 240 Diagonal L2 1/2x2 1/2x1/4 11 -3.92 35.08 11.2 27.0 (b) Pass T2 240 - 220 Diagonal L2 1/2x2 1/2x1/4 23 -6.11 35.08 17.4 42.2 (b) Pass T3 220 - 210 Diagonal L3x3x1/4 53 -10.40 37.17 28.0 37.2 (b) Pass T4 210 - 200 Diagonal L3x3x1/4 62 -10.90 34.25 31.8 41.2 (b) Pass T5 200 - 180 Diagonal L3x3x1/4 71 -14.44 28.40 50.8 54.4 (b) Pass T6 180 - 160 Diagonal L3 1/2x3 1/2x1/4 87 -15.24 35.49 43.0 56.6 (b) Pass T7 160 - 140 Diagonal L5x5x3/8 101 -27.81 61.93 44.9 66.6 (b) Pass T8 140 - 120 Diagonal L5x5x3/8 111 -25.40 56.94 44.6 61.5 (b) Pass T9 120 - 100 Diagonal L5x5x3/8 119 -29.55 52.26 56.5 70.8 (b) Pass T10 100 - 80 Diagonal L5x5x3/8 128 -28.66 47.92 59.8 68.7 (b) Pass T11 80 - 60 Diagonal L5x5x3/8 137 -29.59 43.93 67.4 70.9 (b) Pass T12 60 - 40 Diagonal L5x5x3/8 146 -31.48 40.28 78.1 Pass T13 40 - 20 Diagonal L5x5x3/8 156 -29.25 36.97 79.1 Pass T14 20 - 0 Diagonal L6x6x7/16 164 -36.78 64.55 57.0 88.1 (b) Pass T1 245 - 240 Top Girt L6x6x7/16 4 -1.17 163.39 0.7 8.3 (b) Pass T2 240 - 220 Top Girt L6x6x7/16 17 0.30 182.41 0.2 2.1 (b) Pass T3 220 - 210 Top Girt L3x3x1/4 46 -0.14 38.84 0.4 0.5 (b) Pass Summary Leg (T13) 90.2 Pass Diagonal (T14) 88.1 Pass Top Girt (T1) 8.3 Pass Bolt Checks 88.1 Pass RATING = 90.2 Pass August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 27 tnxTower Report - version 8.0.7.4 APPENDIX B BASE LEVEL DRAWING August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 28 tnxTower Report - version 8.0.7.4 August 10, 2020 245 Ft Self Support Tower Structural Analysis CCI BU No 800642 Project Number 37520-1608.001.8700, Order 526773, Revision 0 Page 29 tnxTower Report - version 8.0.7.4 APPENDIX C ADDITIONAL CALCULATIONS Self Support Anchor Rod Capacity *TIA-222-H Section 15.5 Applied Anchor Rod Data Anchor Rod Summary (units of kips, kip-in) (6) 2" ø bolts (Williams High Tensile UNC Tie-rods N; Fy=81 ksi, Fu=105 ksi) Pu_t = 117.5 φPn_t = 196.88 Stress Rating l ar (in):0.875 Vu = 13 φVn = 123.7 35.0% Mu = n/a φMn = n/a Pass Uplift 705.00 78.00 Total Eccentricity (in) 0.000 Connection Properties Analysis Results Axial Force (kips) 0.00 Shear Force (kips) 0.00 Considered Eccentricity Leg Mod Eccentricity (in) 0.000 *Anchor Rod Eccentricity Applied Anchor Rod N.A Shift (in) 0.000 Comp. Applied Loads Grout Considered:No Site Info BU # 800642 Site Name FL West Midway Order # 526773 Rev 0 Analysis Considerations TIA-222 Revision H Analysis Date: 8/10/2020CCIplate - Version 3.7.0 Job Number:A37520-1608.001.8700 Engineer:CMH Date:8/10/2020 Site Name:FL WEST MIDWAY CCI 800642 Site Number:800642 WO No.:1872769 Order No.:526773 Rev 0 675.00 911.25 800.00 83.61% Sufficient 589.00 795.15 705.00 84.44% Sufficient 63.00 85.05 78.00 87.34% Sufficient Notes: 112940.330.0301 1/22/2001Design Drawing Date: Design Drawing Number: Self-Support Tower TIA-222-H TIA-222-F Trylon Structure Type: Current Analysis Code: Original Design Code: Manufacturer: Adjusted Original Design Current Analysis (kips, kip-ft) Original Design (kips, kip-ft) Monopole and Tower Foundation Comparison Tool (Version v1.5 - Effective Date 04/1/2020 ) 1. Reac<on Ra<o Normalized per TIA-222-H Sec<on 15.5 2. The original tower design was completed in accordance with the TIA-222-F standard. Per section 15.6.2 of the TIA-222-H standard, the reactions from the original design shall be multiplied by 1.35 for comparison to the reac<ons from this analysis. Reactions Ratio ResultBase Reaction Axial Compression Shear Moment Tension (Uplift) Apply Capacity Normalization per Section 15.5 Compare Base Shear Compare Base Axial Compression 37520-1608_Monopole and Tower Foundation Comparison Tool v1.5 ASCE 7 Hazards Report Address: No Address at This Location Standard:ASCE/SEI 7-10 Risk Category:II Soil Class:D - Stiff Soil Elevation:18.55 ft (NAVD 88) Latitude: Longitude: 27.381472 -80.496778 Wind Results: Data Source: Date Accessed: Wind Speed: 154 Vmph 10-year MRI 86 Vmph 25-year MRI 105 Vmph 50-year MRI 116 Vmph 100-year MRI 127 Vmph ASCE/SEI 7-10, Fig. 26.5-1A and Figs. CC-1–CC-4, incorporating errata of March 12, 2014 Thu Jul 23 2020 Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear interpolation between contours. Wind speeds are interpolated in accordance with the 7-10 Standard. Wind speeds correspond to approximately a 7% probability of exceedance in 50 years (annual exceedance probability = 0.00143, MRI = 700 years). Site is in a hurricane-prone region as defined in ASCE/SEI 7-10 Section 26.2. Glazed openings shall be protected against wind-borne debris as specified in Section 26.10.3. Mountainous terrain, gorges, ocean promontories, and special wind regions should be examined for unusual wind conditions. Page 1 of 3https://asce7hazardtool.online/Thu Jul 23 2020 SS : 0.057 S1 : 0.029 F a : 1.6 F v : 2.4 SMS : 0.092 SM1 : 0.07 SDS : 0.061 SD1 : 0.046 T L : 8 PGA : 0.027 PGA M : 0.044 F PGA : 1.6 Ie : 1 Design Response Spectrum S (g) vs T(s)a MCE Response SpectrumR S (g) vs T(s)a Seismic Site Soil Class: Results: Seismic Design Category D - Stiff Soil A Data Accessed: Date Source: Thu Jul 23 2020 USGS Seismic Design Maps based on ASCE/SEI 7-10, incorporating Supplement 1 and errata of March 31, 2013, and ASCE/SEI 7-10 Table 1.5-2. Additional data for site-specific ground motion procedures in accordance with ASCE/SEI 7-10 Ch. 21 are available from USGS. Page 2 of 3https://asce7hazardtool.online/Thu Jul 23 2020 Ice Results: Data Source: Date Accessed: Ice Thickness: 0.00 in. Concurrent Temperature: 25 F Gust Speed: 30 mph Standard ASCE/SEI 7-10, Figs. 10-2 through 10-8 Thu Jul 23 2020 Ice thicknesses on structures in exposed locations at elevations higher than the surrounding terrain and in valleys and gorges may exceed the mapped values. Values provided are equivalent radial ice thicknesses due to freezing rain with concurrent 3-second gust speeds, for a 50-year mean recurrence interval, and temperatures concurrent with ice thicknesses due to freezing rain. Thicknesses for ice accretions caused by other sources shall be obtained from local meteorological studies. Ice thicknesses in exposed locations at elevations higher than the surrounding terrain and in valleys and gorges may exceed the mapped values. The ASCE 7 Hazard Tool is provided for your convenience, for informational purposes only, and is provided “as is” and without warranties of any kind. The location data included herein has been obtained from information developed, produced, and maintained by third party providers; or has been extrapolated from maps incorporated in the ASCE 7 standard. While ASCE has made every effort to use data obtained from reliable sources or methodologies, ASCE does not make any representations or warranties as to the accuracy, completeness, reliability, currency, or quality of any data provided herein. Any third-party links provided by this Tool should not be construed as an endorsement, affiliation, relationship, or sponsorship of such third-party content by or from ASCE. ASCE does not intend, nor should anyone interpret, the results provided by this Tool to replace the sound judgment of a competent professional, having knowledge and experience in the appropriate field(s) of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the contents of this Tool or the ASCE 7 standard. In using this Tool, you expressly assume all risks associated with your use. Under no circumstances shall ASCE or its officers, directors, employees, members, affiliates, or agents be liable to you or any other person for any direct, indirect, special, incidental, or consequential damages arising from or related to your use of, or reliance on, the Tool or any information obtained therein. To the fullest extent permitted by law, you agree to release and hold harmless ASCE from any and all liability of any nature arising out of or resulting from any use of data provided by the ASCE 7 Hazard Tool. Page 3 of 3https://asce7hazardtool.online/Thu Jul 23 2020