HomeMy WebLinkAboutAPPROVED Building 6 ELECTRICAL (E0-1) (2009-0498) LIGHTING FIXTURE SCHEDULE ELECTRICAL SPECIFICATIONS ELECTRICAL SHEET INDEX LAMPS BALLAST SYMBOL TYPE DESCRIPTION NO. TYPE WATT TYPE VOLTAGE MOUNTING REMARKS F2.1 ELECTRICAL NOTES, LEGEND & INDEX 4' LINEAR LED FIXTURE 1 LED 253 — 277 BOTTOM OF PART 1 — GENERAL 0 OA H.E. WILLIAMS MODEL GL-4-L300 SERIES 40001C - TRUSS 1 2 A. THE CONTRACTOR SHALL SUPPLY AND INSTALL ALL NEW ELECTRICAL WORK INDICATED. ELECTRICAL PLAN OLED SECURITY LIGHT 1 LED 93 _ 277 WALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH DRAWINGS AND APPLICABLE SPECIFICATIONS. B H.E. WILLIAMS MODEL WPCL SERIES. 4000'K MOUNTED O IF A PROBLEM IS ENCOUNTERED IN COMPLYING WITH THIS REQUIREMENT, CONTRACTOR SHALL NOTIFY ELECTRICAL RISER DIAGRAM THE ARCHITECT/ENGINEER AS SOON AS POSSIBLE AFTER DISCOVERY OF THE PROBLEM AND o SHALL NOT PROCEED WITH THAT PORTION OF THE WORK UNTIL ARCHITECT/ENGINEER HAS DIRECTED NOTES: GENEREAL NOTE: CORRECTIVE ACTION TO BE TAKEN. OVERIFY CEILING TYPES PRIOR TO ORDERING FIXTURES. NO SUBSTITUTIONS TO THE LIGHT FIXTURE SCHEDULE CONTAINED B. THE CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO BID AND FAMILIARIZE HIMSELF WITH ALL IN THESE DOCUMENTS WILL BE CONSIDERED WITHOUT PRIOR REVIEW CONDITIONS AFFECTING ELECTRICAL AND COMMUNICATIONS INSTALLATION AND MAKE PROVISIONS AS TO O PROVIDE FIXTURE WITH ACCESSORY WIRE GUARD. AND/OR APPROVAL BY THE ARCHITECT AND ELECTRICAL ENGINEER. THE COST THEREOF. C. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC ELECTRICAL LEGEND CODE (AS ADOPTED BY THE AUTHORITY HAVING JURISDICTION) AND ALL CODES AND ORDINANCES OF THE AUTHORITY HAVING JURISDICTION. THE SPECIFICATION, CODES AND STANDARDS LISTED BELOW ARE UTILIZED IN THIS PROJECT. 1. NATIONAL ELECTRICAL CODE (NFPA-70) TELEPHONE OUTLET WITH 3/4" CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING. a 2. CODE FOR SAFETY TO LIFE (NFPA-101) MOUNT 18" A.F.F. TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED. 3. STANDARD FOR THE INSTALLATION, MAINTENANCE AND USE OF LOCAL PROTECTIVE SIGNALING SYSTEMS (NFPA-72) DATA OUTLET WITH 3/4" CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING. 4. UNDERWRITERS' LABORATORIES (UL) MOUNT 18" A.F.F. TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED. 5. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA) 6. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) TELEPHONE/DATA OUTLET WITH 3/4" CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING. 7. FEDERAL SPECIFICATION (FED. SPEC.) MOUNTED ABOVE COUNTER, SEE ARCHITECTURAL DRAWING FOR SPECIFIC REQUIREMENTS. 8. INSULATED POWER CABLE ENGINEERS ASSOCIATION (IPCEA) 9. FLORIDA BUILDING CODE. 2017 EDITION 0 TELEPHONE/DATA OUTLET WITH 3/4" CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING. 10. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE) MOUNT 18" A.F.F. TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED. 11. CITY OF FORT PIERCE BUILDING CODE. (AMMENDMENTS TO FLORIDA BUILDING CODE 2017) Digitally 12. ADDITIONALLY, DESIGNS, WORK PRACTICES AND CONDITIONS MUST CONFORM WITH THE ❑0 TELEPHONE/DATA OUTLET WITH 3/4" CONDUIT RUN TO THE NEAREST STUD WALL AND °u°";`o""ice::.. signed b OCCUPATIONAL SAFETY AND HEALTH ACT OF 1970 (OSHA) STUBBED OUT FROM WALL 6" ABOVE CEILING. PROVIDE BRASS COVER PLATE AND Bradly Bi own D. DO NOT SCALE THE ELECTRICAL DRAWINGS. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS CARPET FLANGE. `0eo,,,,,,,, Date: :E s - FOR EXACT LOCATION OF ALL EQUIPMENT. CONFIRM WITH OWNER'S REPRESENTATIVE. TELEVISION OUTLET WITH 3/4 CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING. 0,f s...EOP` ' 2d� 0.09. 3 E. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE MOUNT AT 18" A.F.F. TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED. 9ey ';, q. 0$: �:35 04'00' CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM 20 AMP DUPLEX RECEPTACLE (NEMA 5-20R) MOUNTED AT 18" A.F.F. TO CENTER LINE OF AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER. OUTLET UNLESS NOTED OTHERWISE. F. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FROM A g PERIOD OF NOT LESS THAN ONE YEAR FROM DATE OF ACCEPTANCE. lf� 20 AMP QUADRUPLEX RECEPTACLE (NEMA 5-20R) MOUNTED AT 18" A.F.F. TO CENTER LINE ¢o E¢ G. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE OF OUTLET UNLESS NOTED OTHERWISE. B , REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED aiv t IS THERE BY. tmGFI 20 AMP DUPLEX RECEPTACLE (NEMA 5-20R) WITH GROUND FAULT CIRCUIT INTERRUPTER, I Ul_Jz MOUNT AT 18" A.F.F. TO CENTER LINE OF OUTLET. UNLESS NOTED OTHERWISE. H. ALL REQUIRED INSURANCE SHALL BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY AND a ° 3w PROPERTY DAMAGE FOR THE DURATION OF THE WORK. } 20 AMP DUPLEX RECEPTACLE (NEMA 5-20R) MOUNTED ABOVE COUNTER ° N I. CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTIONS AND TESTING. CONTRACTOR SEE ARCHITECTUAL DRAWINGS FOR SPECIFIC REQUIREMENTS. � TO OBTAIN PERMIT AND APPROVED SUBMITTALS PRIOR TO BEGINNING WORK OR ORDERING EQUIPMENT. 20 AMP DUPLEX RECEPTACLE (NEMA 5-20R) WITH ISOLATED GROUND, MOUNT AT 18" A.F.F. y J. THE TERM "PROVIDE" USED IN THE CONSTRUCTION DOCUMENTS AND SPECIFICATIONS SHALL MEAN THAT TO CENTERLINE OF OUTLET UNLESS OTHERWISE NOTED. THE CONTRACTOR IS TO FURNISH, INSTALL AND CONNECT COMPLETE. 20 AMP QUADRUPLEX RECEPTACLE (NEMA 5-20R) WITH ISOLATED GROUND, MOUNT AT 18" PART 2 — PRODUCTS A.F.F. TO CENTERLINE OF OUTLET UNLESS OTHERWISE NOTED. 2 's V w A. MINIMUM WIRE SIZE SHALL BE #12 A.W.G. (EXCEPT AS NOTED OTHERWISE FOR CONTROL WIRING). ALL 20 AMP DUPLEX RECEPTACLE (NEMA 5-20R), RECESS FLOOR MOUNTED. PROVIDE BRASS CONDUCTORS SHALL BE 98% CONDUCTIVITY, COPPER WITH "THHN—THWN" INSULATION UNLESS OTHERWISE COVER PLATE AND CARPET FLANGE. B. ELO CTRICAL METALLIC TUBING (EMT) SHALL BE OF BEST QUALITY STEEL, SMOOTH INSIDE AND OUT ON 20 AMP DUPLEX RECEPTACLE (NEMA 5-20R), CEILING MOUNTED. AND SHALL BE HOT—DIPPED GALVANIZED. a C. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS SPECIAL—PURPOSE RECEPTACLE IN WET OR DAMP LOCATIONS AND SPECIAL ENCLOSURES FOR OTHER CLASSIFIED AREAS. z D. RIGID NONMETALIC CONDUIT SHALL BE SCHEDULE 40 PVC. QQ JUNCTION BOX E. ALL MATERIALS SHALL BE NEW AND BEAR UNDERWRITERS' LABELS WHERE APPLICABLE. F. PANELBOARDS: 0P SINGLE GANG JUNCTION BOX FOR POWER CONNECTION TO MODULAR FURNITURE SYSTEM 1. CURRENT CARRYING BUSES SHALL BE COPPER. GROUND BUS BARS SHALL BE COPPER. INSTALL IN EXACT MANNER AS DIRECTED BY FURNITURE SUPPLIER. 2. ALL CIRCUIT BREAKERS SHALL BE BOLT ON. PLUG—IN BREAKERS ARE NOT ACCEPTABLE. 3. CIRCUIT BREAKERS USED AS SWITCHES IN FLUORESCENT OR HID LIGHTING CIRCUITS SHALL O DOUBLE GANG JUNCTION BOX FOR TELEPHONE/DATA CONNECTION TO MODULAR FURNITURE BE LISTED AND MARKED "SWD" 7�0 SYSTEM. INSTALL IN EXACT MANNER AND LOCATION AS DIRECTED BY FURNITURE 4. ALL CIRCUIT BREAKERS FEEDING MECHANICAL EQUIPMENT SHALL BE HACR TYPE. SUPPLIER. EXTEND (2) 3/4" EMPTY CONDUITS FROM JUNCTION BOX TO ABOVE 5. A.I.C. RATINGS SHALL BE AS INDICATED ON PANELBOARD SCHEDULES. CEILING AND TERMINATE WITH INSWLATING BUSHING 6" FROM WALL. 6. ALL PANELBOARDS SHALL BE FURNISHED WITH PLASTIC LAMINATE NAMEPLATES WITH 1/4" TELE/POWER POLE FOR TELEPHONE/DATA/POWER CONNECTION TO MODULAR FURNITURE ENGRAVED LETTERING FOR PANEL IDENTIFICATION. 8 WIRE SYSTEM (SEE DETAIL THIS SHEET). INSTALL IN EXACT MANNER AND LOCATION 7. ALL PANELBOARDS SHALL BE PROVIDED WITH TYPE—WRITTEN DIRECTORY OF BRANCH CIRCUIT AS DIRECTED BY FURNITURE SUPPLIER, WIREMOLD CATALOG # 25DTP-4D W/IVORY FINISH. DESIGNATIONS. FF71 G. DISCONNECT SWITCHES SHALL BE H.P. RATED, HEAVY DUTY, QUICK—MAKE, QUICK—BREAK. ENCLOSURES SHALL BE NEMA-1 FOR INDOOR LOCATIONS, NEMA 3R FOR OUTDOOR LOCATIONSOR AS OTHERWISE NOTED. SPECIAL PURPOSE RECEPTACLE MOUNTED BELOW RAISE FLOOR. H. MOTOR STARTERS SHALL BE MANUAL OR MAGNETIC AS INDICATED ON THE ELECTRICAL DRAWINGS, WITH OVERLOAD RELAYS IN EACH PHASE. I. WIRING DEVICES (GENERAL PURPOSE RECEPTACLES AND WALL SWITCHES) COLOR SHALL BE COORDINATED EF EXHAUST FAN. SEE MECHANICAL DRAWINGS FOR SPECIFICATIONS. WITH CLIENT. PART 3 — EXECUTION $ SINGLE POLE, 20 AMP, SWITCH. MOUNT 42" A.F.F. TO CENTERLINE OF SWITCH UNLESS A. COLOR CODING OF CONDUCTORS SHALL BE AS FOLLOWS: OTHERWISE NOTED. 1. 208/120 VOLTS, 3 PHASE, 4—WIRE SYSTEM: UNGROUNDED CONDUCTORS: 1 BLACK, 1 RED AND 13 3—WAY, 20 AMP, SWITCH. MOUNT 42" A.F.F. TO CENTERLINE OF SWITCH UNLESS BLUE. GROUNDED (NEUTRAL) CONDUCTOR; WHITE. GROUNDING CONDUCTORS SHALL BE GREEN. OTHERWISE NOTED. 2. 480/277 VOLT, 3—PHASE, 4—WIRE SYSTEM: UNGROUNDED CONDUCTORS: 1 BROWN, 1 YELLOW, AND 1110 1 PURPLE. GROUNDED (NEUTRAL) CONDUCTORS; GREY. GROUNDING CONDUCTORS SHALL BE GREEN. $D SINGLE POLE, 20 AMP, SWITCH WITH DIMMER. MOUNT 42" A.F.F. TO CENTERLINE OF SWITCH ��yy Un 3. BRANCH CIRCUIT WIRING (#6 AND SMALLER) SHALL BE COLOR CODED BY CONTINUOUS INSULATION UNLESS OTHERWISE NOTED. COLOR AND FEEDERS AND SERVICES (#4 AND LARGER) SHALL BE CODED AT ALL JUNCTION OR W PULL POINTS (EXCEPT LB'S OR LBD'S) USING COLOR MARKERS OR PLASTIC TAPE MANUFACTURED $M MOTOR RATED SWITCH FOR THE PURPOSE. B. WIRING METHODS $p MOTION DETECTOR SWITCH, OSW—DT-0601—MV—X, COOPER CONTROLS. r� w 1. ALL CONDUCTORS SHALL BE INSTALLED IN ELECTRICAL METALLIC TUBING (EMT) UNLESS OTHERWISE NOTED, SPECIFIED OR AS SPECIFICALLY PROHIBITED BY THE AUTHORITY HAVING TWO POLE 30 AMP SWITCH. MOUNT ADJACENT EQUIPMENT TO BE CONTROLLED. W JURISDICTION. ALL FITTINGS AND COUPLINGS FOR EMT CONDUIT SHALL BE ALL STEEL RAIN TIGHT COMPRESSION TYPE OR ALL STEEL CONCRETE TIGHT SET SCREW TYPE. 2. SCHEDULE 40 PVC CONDUIT, WITH FITTINGS AND COUPLINGS APPROPRIATE FOR THE USE, SHALL ® FACTORY MOUNTED DISCONNECT/STARTER (SEE MECHANICAL SCHEDULE) BE INSTALLED UNDERGROUND OR BELOW SLABS ON GRADE. g a/ 3. TYPE MC CABLE WITH ALUMINUM ARMOR AND INTERNAL GROUND IS ACCEPTABLE FOR AB FUSIBLE DISCONNECT SWITCH A = POLES, 6= FRAME SIZE, C= FUSE RATING w0 USE AS GENERAL BRANCH CIRCUIT WIRING FOR CIRCUITS 20 AMPERES OR LESS AND CONCEALED C IN WALLS OR ABOVE SUSPENDED CEILING AND AS APPROVED BY THE AUTHORITY HAVING JURISDICTION. t2KI A� FUSIBLE MOTOR STARTER DISCONNECT SWITCH A = POLES, B= NEMA SIZE, C= FUSE RATING � w C. ELECTRICAL SYSTEM SHALL BE COMPLETE AND EFFECTIVELY GROUNDED AS REQUIRED BY THE LATEST EDITION OF THE N.E.C. AND LOCAL CODES. W D. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS — GROUNDING ELECTRODE & CONDUCTOR SYSTEM WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE AND ACCEPTED BY ENGINEER/ARCHITECT. Ti TRANSFORMER E. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS OF CONSTRUCTION. p ELECTRICAL PANELBOARD F. THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF POWER AND TELEPHONE COMPANIES, AND SHALL BE FULLY COORDINATED WITH THEM PRIOR TO COMMENCEMENT OF WORK. G. PROVIDE AND INSTALL CONDUIT, CONDUCTORS, PULL WIRES, BOXES, COVER PLATES, AND WIRING TELEPHONE WOOD BACKBOARD DEVICES, FOR ALL OUTLETS AS INDICATED. H. MATERIALS, PRODUCTS, AND EQUIPMENT, INCLUDING ALL COMPONENTS THEREOF, SHALL BE NEW WP WEATHERPROOF AND SUCH AS APPEAR ON THE UL LIST OF APPROVED ITEMS AND SHALL MEET OR EXCEED THE T C TIME CLOCK REQUIREMENTS OF NEC, NEMA, AND IECE. / I. CONTRACTOR SHALL SUBMIT AT LEAST FIVE (5) SETS OF SHOP DRAWINGS OR CUT SHEETS OF LIGHTING RE RELOCATED w °' FIXTURES, SWITCHES, AND OTHER ELECTRICAL ITEMS FOR APPROVAL BY ENGINEER/ARCHITECT. J. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED OF HIS WORK. K. ALL LAY—IN LIGHTING FIXTURES SHALL BE SECURED TO THE SUSPENDED CEILING GRID AT EACH CORNER. E EXISTING TO REMAIN Q.., L. CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS AND PROVIDE ALL NECESSARY CONTROL A.F.F. ABOVE FINISH FLOOR LL WIRING. M. ALL ELECTRICAL POWER WIRING FOR THE HVAC SYSTEM INCLUDING WIRING THRU LINE VOLTAGE CONTROL DEVICES SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. Oi CEILING MOUNTED DUAL TECHNOLOGY MOTION SENSOR BY WATTSTOPPER. N. CONDUCTORS FOR BRANCH CIRCUITS SHALL BE INCREASED FROM SIZES INDICATED ON PANEL SCHEDULES TO PREVENT VOLTAGE DROP EXCEEDING 3% AT THE FARTHEST DEVICE. LOADS FOR DETERMINING CONDUCTOR O CEILING MOUNTED LOW VOLTAGE DUAL TECHNOLOGY MOTION SENSOR BY WATTSTOPPER. projt.no.: 2020-0527 SIZE SHALL BE BASED ON ACTUAL CONNECTED LOAD OR 80% OF BREAKER SIZE, WHICHEVER IS GREATER. CONTACT ENGINEER OF RECORD FOR ALL RUNS IN EXCESS OF 100 FT. FOR DETERMINATION OF WIRE SIZE. LV FOR BID PURPOSES, INCREASE WIRE BY ONE (1) WIRE SIZE FOR RUNS 100 FT. TO 200 FT. AND TWO (2) project manager: DM WIRE SIZES FOR RUNS OVER 200 FT. 0. FEEDER CONDUCTORS SHALL BE INCREASED FROM SIZES INDICATED ON RISER DIAGRAM TO PREVENT checked by: BB VOLTAGE DROP EXCEEDING 2%. LOADS FOR DETERMINING CONDUCTOR SIZE SHALL BE BASED ON ACTUAL CONNECTED LOAD OR 80% OF BREAKER SIZE, WHICHEVER IS GREATER. P. THE CONTRACTOR SHALL CONFIRM WITH THE ELECTRICAL UTILITY COMPANY ANY AND ALL REQUIREMENTS scale: AS NOTED SUCH AS: METERING EQUIPMENT REQUIREMENTS AND METERING EQUIPMENT LOCATION, TRANSFORMER SIZE AND LOCATION OR SERVICE POINT, CONDUIT ENTRY AND LUG SIZE RESTRICTIONS. THE CONTRACTOR date: 09/15/20 SHALL SCHEDULE ALL REQUIRED DOWN TIME FOR THE OWNERS CONFIRMATION. Q. ANY CONFLICTS AND DESCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE PROCEEDING WITH ANY WORK. R. PER NEC 210.8(B)(3) ALL 15— AND 20—AMPERE, 125—VOLT RECEPTACLES IN NONDWELLING—TYPE KITCHENS TO BE GFCI PROTECTED. sheet EO . I PERMIT ISSUED CONSTRUCTION ISSUED project