HomeMy WebLinkAboutAPPROVED Building 6 STRUCTURALS (2009-0498) PREPARED FOR: Al ROOF TRUSSES 4451 ST LUCIE BLVD ABBREVIATIONS GENERAL NOTES DESIGN PARAMETERS & ASSUMPTIONS FT PIERCE, FL 34946 CODE EDITION: AB ANCHOR BOLT LAV LAVATORY 1. DO NOT SCALE THESE DRAWINGS. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED x❑ FLORIDA BUILDING CODE ABV ABOVE LG. LONG DIMENSIONS. THE CONTRACTOR SHALL REVIEW THESE DRAWINGS IN THEIR ENTIRETY BEFORE x❑ ASCE 7 (EXPOSURE CONDITION) C AFF ABOVE FINISHED FLOOR LIN. LINEN COMMENCING CONSTRUCTION AND SHALL ACCEPT FULL RESPONSIBILITY FOR ANY ERRORS AFI ARC FAULT INTERRUPT LGT LIGHT OR OMISSIONS NOT REPORTED IMMEDIATELY IN WRITING TO THE WHOLE HOUSE ENGINEERING, BUILDING DESIGNED AS: LLC. BACKCHARGES WILL NOT BE ACCEPTED. ❑ PARTIALLY ENCLOSED ❑ ENCLOSED ❑x OPEN ❑ TESTED (WIND TUNNEL) Ki..liyeigne°eyRamaPrana" ALUM ALUMINUM L.T. LAUNDRY TUB rielam BUILDINGHEIGHT: CN"Ra.k,P,,,,, ,.,t,,eetlng.net' AHU AIR HANDLER UNIT MAX. MAXIMUM 2. THE GENERAL CONTRACTOR SHALL VERIFY THE BUILDING POSITION WITHIN THE SETBACK LINES HN...EaP,a°a"LLO,L-F,d House Engineer ng LLC.L=F°n PRIOR TO COMMENCING CONSTRUCTION. x❑ <- 60FT. (ASCE 7) Red..h11111vil�°'"'_ B.F. BI FOLD M.C. MEDICINE CABINET Dale:2020.09.21 08:56:09-04'00' B.P. BI PASS MECH MECHANICAL El > bOFT. (MUST USE ASCE 7) 3. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO BE FAMILIARIZED WITH ALL EXISTING ALLOWABLE BEARING PRESSURE: 2500 PSF PER GFA REPORT 20-8137.01 BLK. BLOCK M.R.H. MEAN ROOF HEIGHT CONDITIONS AS THEY ARE NOT NECESSARILY SHOWN ON THESE DRAWINGS. BRKFST BREAKFAST MTL METAL MEAN ROOF HEIGHT: 21'4' . BLK'G BLOCKING MFR. MANUFACTURER 4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING LOCATIONS OF ALL FLOOR, (FOR LOW RISE BUILDING WITH SLOPED ROOFS) BM BEAM MICRO. MICROWAVE ROOF, AND WALL OPENINGS AND PENETRATIONS. RISK FACTOR: II BRG. BEARING MIN. MINIMUM 5. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING LOCATIONS OF ALL FLOOR, (DETERMINED BY BUILDING USE/OCCUPANCY, BOT. BOTTOM MIR MIRROR ROOF, AND WALL OPENINGS AND PENETRATIONS. REFR TO ASCE 7 TABLE 1.5-1) PREPARED BY: CAB CABINET M.O. MASONRY OPENING CER CERAMIC MONO. MONOLITHIC b. IT IS THE CONTRACTORS SOLE RESPONSIBILITY TO COORDINATE THE WORK OF ALL TRADES, BASIC WIND VELOCITY PRESSURES: CJ CONTROL JOINT DETERMINE ERECTION PROCEDURE, AND SEQUENCE TO INSURE THE SAFETY OF THE BUILDING, APPROPRIATE POSITIVE/ NEGATIVE PRESSURE COEFFICIENTS HAVE BEEN APPLIED TO MTL. METAL ITS COMPONENTS, AND TRADE BASE DURING CONSTRUCTION. MAIN WIND FORCE RESISTING SYSTEM, AND BUILDING ENVELOPE COMPONENTS AND CL CENTER LINE OBSC OBSCURE CLADDING, AS APPLICABLE: CLG. CEILING O.H.D. OVER HEAD DOOR 7. ALL DETAILS AND SECTIONS SHOWN ON THESE DRAWINGS ARE INTENDED TO BE TYPICAL AND WIND SPEED 160 (3-SEC. GUST CLO CLOSET OC ON CENTER SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR CONDITION ELSEWHERE IN THE WORK EXCEPT ) ENGINEERING CLR CLEAR OPP OPPOSITE WHERE A DIFFERENT DETAIL AND OR SECTION IS SHOWN. CMU CONCRETE MASONRY UNITS P.L.F. POUNDS PER LINEAR FOOT 8. BUILDER IS RESPONSIBLE FOR ADEQUATE BRACING OF STRUCTURAL OR NON-STRUCTURAL COL. COLUMN P.S.F. POUNDS PER SQUARE FOOT MEMBERS DURING CONSTRUCTION. PRE FABRICATED BUILDING NOTES CONC. CONCRETE WHOLE HOUSE ENGINEERING P.S.I. POUNDS PER SQUARE INCH 9. IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO PROVIDE ALL NECESSARY SHOP, WINDOWS, DOORS, ETC. TO WHOLE HOUSE ENGINEERING, LLC FOR REVIEW AND 4451 ST. LUCIE BLVD,SUITE 201 CONN CONNECTION P.T. PRESSURE TREATED DRAWINGS THE CONTENTS OF THESE DRAWINGS ARE FOR THE FOUNDATION OF A PRE FABRICATED BUILDING SUPPLIED BY KIRBY BUILDING SYSTEMS WITH KIRBY PROJECT NUMBER K2080080A.THE CSMT. CASEMENT PRE FABRICATED BUILDING MANUFACTURER IS RESPONSIBLE FOR THE GRAVITY AND LATERAL DESIGN OF THE BUILDING. FORT PIERCE,FL 34946 PART'N. PARTITION APPROVAL. CONTACT: 772.409.1003 CTR CENTER PH PHONE THE FOUNDATION DRAWINGS PRODUCED IN THIS DRAWING SET IS BASED ON THE REACTIONS PROVIDED BY KIRBY BUILDING SYSTEMS DATED 08/25/2020 SIGNED BY ROGER.L.HILL WITH ENGINEERING@WHENGINEERING.NET DBL. DOUBLE PKT. POCKET 10. ALL WINDOWS AND DOORS SHALL BE CAULKED AND WEATHER STRIPPED. FLORIDA LICENSE NUMBER 79464.THE REACTIONS PROVIDED BY KIRBY BUILDING SYSTEMS ARE USED FOR DESIGN OF THE FOUNDATION AND ARE LISTED BELOW. DF DRINKING FOUNTAIN PL PROPERTY LINE DIA. DIAMETER 11. THESE DOCUMENTS, AS INSTRUMENTS OF SERVICE, ARE THE PROPERTY WHOLE HOUSE IT IS THE RESPONSIBILITY OF THE PRE FABRICATED BUILDING MANUFACTURER TO ATTEST TO THE ADEQUACY OF LOADING ON THE BUILDING PER APPLICABLE BUILDING CODES AND THE DRAWING NOTICE: PLYWD. PLYWOOD ENGINEERING, LLC, AND SHALL NOT BE USED OR REPRODUCED WITHOUT THEE EXPRESS WRITTEN PROVIDED REACTIONS AT THE FOUNDATION ARE ACCURATE AND COMPLIANT TO ALL APPLICABLE CODES. DISP. DISPOSAL PNL PANEL CONSENT OF WHOLE HOUSE ENGINEERING, LLC. THESE DRAWINGS AND DOCUMENTS ARE DP DESIGN PRESSURE CONFIDENTIAL AND ARE THE SOLE DR. DOOR R RADIUS 12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL REQUIRED BUILDING AND PROPERTY OF WHOLE HOUSE ENGINEERING, REF REFIGERATOR LLC. AND MAY NOT BE REPRODUCED, DW DISH WASHER TRADE PERMITS AND FOR THEIR RESPECTIVE COSTS.REINF REINFORCE, REINFORCED ����■�w���w����a����wwo������smma��mre��a�r��,��-��________________________________ EA EACH DISSEMINATED OR REDISTRIBUTED WITHOUT REQ REQUIRED 13. THESE DRAWINGS ARE DIAGRAMATIC AND ARE INTENDED TO SHOW THE DESIGN INTENT ONLY. K208008:2AR2 Additional ► Racoons Report : 8/ 25/ G 1 • 54pm THE EXPRESS WRITTEN CONSENT OF E.E. EACH END RM ROOM THEY DO NOT SHOW EVERY MINOR DETAIL OF CONSTRUCTION. ALL TRADES ARE RESPONSIBLE WHOLE HOUSE ENGINEERING, LLC. EJ EXPANSION JOINT FOR FURNISHING COMPLETE BUILDING SYSTEMS AND ALL ITEMS THAT WOULD NORMALLY BE _===��s�=¢__________________________=���*RR�� s�'a�4=`=i`=`"""_'_`- �_________________= WARNING: DO NOT SCALE DRAWINGS. R.O. ROUGH OPENING CONSIDERED INCIDENTAL TO THEIR INSTALLATION. PLEASE CONTACT DESIGNER WITH ANY ELEC. ELECTRICAL S.C. SOLID CORE ELEV. ELEVATION QUESTIONS REGARDING DIMENSIONS. SCHED SCHEDULE 14. THE STRUCTURAL SYSTEM FOR THIS BUILDING HAS BEEN DESIGNED IN ACCORDANCE WITH THE ARCHITECTURAL SYMBOLS CONTAINED EMER EMERGENCY S.G.D. SLIDING GLASS DOOR FLORIDA BUILDING CODE, 2017 EDITION. WITHIN THESE DOCUMENTS ARE FOR ENCL ENCLOSURE SF SQUARE FOOT GRAPHIC PURPOSES ONLY. SIZE AND EQ EQUAL 15. ALL CONTRACTOR RFI SHALL STATE CONTRACTOR'S SUGGESTION(S) FOR RESOLUTION AND LOCATION MAY VARY IN ORDER TO MEET SH SINGLE HUNG COST IMPLICATIONS FOR SUGGESTION(S). FOR IS NOT RESPONSIBLE FOR DETERMINING COST- �. ' rCll � �.L]1�1t1 �aGt 1�I3 [ THE MANUFACTURER'S SPECIFICATIONS. E.S. EACH SIDE SH SHELF OR COST EFFECTIVENESS OF RFI RESPONSES. ESPELECTO STATIC PAINT --a"---"`--'--""""-""'"'"__' SHWR SHOWER EW EACH WAY EXT. EXTERIOR SPEC SPECIFICATION FOUNDATION PLAN NOTES. ENGINEER'S SIGNATURE&SEAL: SMS SHEET METAL SCREWS Frame I� }1 -Dead Collateral ----Live--- Win Leftl Wind Rk htl EXT'G EXISTING EXP EXPANSION SQ SQUARE 1. SLAB ON GRADE SHALL BE 5"THICK 3000 PSI CONCRETE SLAB WITH 6"x6"/W 1.4 X W 1.4 I1 ne Li ate liorz Vert Ho r z Vert Hear z Vert Rio r z Vert H o r z Vert RAMA P RA N AV K R ISTA IV F.B.C. FLORIDA BUILDING CODE SS STAINLESS STEEL WELDED WIRE MESH LOCATED IN THE MIDDLE TO UPPER 1/3 OF SLAB,SUPPORTED 3'-0"ON ST. STIRRUPS CENTER MAX., ON 6-MIL. VAPOR BARRIER, ON CLEAN 95%COMPACTED TERMITE TREATED FILL. �---' ---"! -- `---' -"�- _'- - ----- --___ _____ FL PE #88906 FDN FOUNDATION STD STANDARD DESIGN SOIL BEARING CAPACITY IS 2000 PSF. ACTUAL BEARING CAPACITY MUST BE CERTIFIED FIN. FL. FINISH FLOOR 6 C 0 . 0 1 . 0 0 . 0 0 . 7 10 . 1 2 . 6 .r 0 T 3 -9 ' 9 . 8 4 '$TL. STEEL TO MEET 2000 PSF MIN. BY AN ARCHITECT OR A PROFESSIONAL ENGINEER. FLUOR FLUORESCENT 6 A -0 F 1 2 . 6 _0 . 1 1 . 7 -0 . 4 4 . 9 1 . 5 -1 7 • 4 7 . 4 -2 2 , 6 FO FLOOR OUTLET SW SWITCH 2. ALL BARS OF FOUNDATION STEEL SHALL BE CONTINUOUS AROUND CORNERS USING CORNER F.R. FIRE RATED SYM SYMMETRICAL BARS W/A MINIMUM LAP SPLICE OF 30" (48 BAR DIAMETERS). ANA V FR. DR. FRENCH DOOR TEMP. TEMPERED ��� • •. / �, T.B. THROUGH BOLT 3. AT ALL INTERSECTING BLOCK WALLS, INTERWEAVE CONCRETE BLOCK OR BREAK OUT A 5"x 5" �Q;••��C E NSA •.;S� FRAM'G FRAMING HOLE BETWEEN WALLS @ 24" O.C. VERTICALLY TO ALLOW CONCRETE TO FILL BOTH CELLS. Q' 9 FT FOOT OR FEET T.BM TIE BEAM ,�; No. 88906 FURR FURRING THK THICK 4. PLUMBING SLEEVE MINIMUM SPACING SHALL BE THREE DIAMETERS CENTER TO CENTER OF THE CONTINUED ON PAGE S-2.0 _ * _ G.T. GIRDER TRUSS T &G TONGUE &GROOVE LARGER SLEEVE, OR b"CLEAR BETWEEN SLEEVES, WHICHEVER IS GREATER. SLEEVES OR TOB TOP OF BEAM GROUPS OF SLEEVES 16 INCH IN DIAMETER AND LARGER SHALL BE TREATED AS A SLAB = �O . STATE OF GA. GAUGE •'•, �v GALV. GALVANIZED T.O.B.B. TOP OF BOND BEAM OPENING AND REINFORCED PER TYPICAL OPENING REINFORCING DETAILS. � �� ' F4 0 R 10 F AL ECG GFI GROUND FAULT INTERRUPT T. .PL. TOP OF W %D PLATE ,�S SION GL. GLASS T.O.T.B. TOP OF TIE BEAM CONCRETE NOTES - /0011111111W GND. GROUND TPH TOILET PAPER HOLDER GYP GYPSUM TYP. TYPICAL 1. ALL CONCRETE SHALL BE PER AN APPROVED MIX DESIGN PROPORTIONED TO ACHIEVE A GYP. BD. GYPSUM WALLBOARD U.N.O. UNLESS NOTED OTHERWISE STRENGTH AT 28 DAYS AS LISTED BELOW WITH A PLASTIC AND WORKABLE MIX: REVISION DATE BY REV HB HOSE BIBB UL UNDERWRITERS LABORATORIES 1.1. 3,000 PSI FOR FOUNDATIONS AND SLABS ON GRADE. HC HOLLOW CORE VERT VERTICAL 1.2. 4,000 PSI FOR OTHER STRUCTURAL CONCRETE. PERMIT 09/17/2020 RK HGT. HEIGHT V.I.F. VERIFY IN FIELD 2. CONCRETE SHALL BE PLACED AND CURED ACCORDING TO ACI STANDARDS AND HORZ. HORIZONTAL W.A. WEDGE ANCHORS SPECIFICATIONS.AGGREGATES TO BE CLEAN AND WELL GRADED, 1-1/4"MAXIMUM SIZE. HM HOLLOW METAL W/ WITH CONCRETE SLUMP IS TO BE 5"MINIMUM TO 6"MAXIMUM. 2,500 PSI FOR SLABS ON GRADE & HPS. HOOPS WC WATER CLOSET FOUNDATIONS. HR HOUR WD. WOOD 3. MINIMUM CONCRETE COVER FOR REINFORCING BARS: HVAC HEATING VENTILATION AIR COND. WH WATERHEATER STRUCTURAL PART MINIMUM COVER FOOTINGS (CAST AGAINST SOIL) HVHZ HIGH VELOCITY HURRICANE ZONE WM WASHING MACHINE STRUCTURAL PART MINIMUM COVER ID INSIDE DIMENSION W/O WITHOUT FOOTINGS (CAST AGAINST SOIL) 3" . WP WATERPROOF SLABS (CAST AGAINST SOIL W/VAPOR BARRIER) 1-1/2" INSUL INSULATION SLABS (ABOVE GRADE LEVEL) 3/4". INT. INTERIOR WPH WALL PHONE BEAMS AND COLUMNS 1-1/2" LAM. LAMINATE WSCT WAINSCOT WT WEIGHT 4. REINFORCING BARS, UNLESS OTHERWISE SPECIFIED, SHALL BE NEW BILLET STEEL MEETING A.S.T.M. A615, GRADE 60. REINFORCING BARS SHALL BE DETAILED, FABRICATED,SUPPORTED IN FORMS AND SPACED WITH ACCESSORIES FOLLOWING THE REQUIREMENTS OF THE"MANUAL OF STANDARD PRACTICES FOR DETAILING REINFORCED CONCRETE STRUCTURES. (A.C.I. 318)". PROJECT NUMBER, NAME &ADDRESS: 5. LAP ALL REINFORCING BAR SPLICES 48 BAR DIAMETERS (UNLESS OTHERWISE NOTED).ALL REINFORCING BARS SHALL BE SECURELY WIRED TOGETHER IN THE FORMS.TWO-WAY MATS OF STEEL SHALL BE TIED AT ALTERNATE INTERSECTIONS BOTH WAYS. PROVIDE CORNER BARS AT ALL BUILDING 6 STRUCTURAL DESIGN STATEMENT CORNERS FOR ALL CONTINUOUS REINFORCING IN UNIT MASONRY #5 X 5-0" (30" EACH WAY) UNLESS OTHERWISE NOTED. 4451 ST LUCIE BLVD 1. I CERTIFY THAT, TO THE BEST OF MY KNOWLEDGE AND BELIEF,THESE PLANS AND 6. AT ALL POURED CONCRETE BEAM AND BOND BEAM INTERSECTIONS, EXTEND BOND BEAM SPECIFICATIONS HAVE BEEN DESIGNED TO COMPLY WITH THE APPLICABLE STEEL 30" INTO POURED BEAMS. FT PIERCE, FL 34946 STRUCTURAL PORTIONS OF THE BUILDING CODES. 2. I ALSO CERTIFY THAT THE STRUCTURAL COMPONENTS,SYSTEMS, & RELATED 7. ANY OF THE SPECIFICALLY NOTED BEAMS MAY BE BUILT UP TO 1"SMALLER OR 2"LARGER ELEMENTS PROVIDE ADEQUATE RESISTANCE TO WIND LOADS AND FORCES WITHOUT ANY CHANGE OF REQUIRED STEEL. SPECIFIED BY THE CODES LISTED IN THESE NOTES. 8. BEAMS WITH THE PREFIX"TB#"SHALL BE OF CONCRETE, POURED AFTER THE BLOCK WALLS BELOW ARE IN PLACE. REINFORCING SHALL BE CONTINUOUS THROUGH TIE BEAMS WITH MINIMUM LAP SPLICES OF 48 BAR DIAMETERS AND BENT BARS AT CORNERS. USE METAL LATH, MORTAR, OR SPECIAL UNITS TO CONFINE CONCRETE TO REQUIRED AREAS, IN ACCORDANCE DRAWN BY: WITH ACI 530.1 (SOLID METAL OR FELT CAVITY CAPS ARE PROHIBITED). RK 9. NO STRUCTURAL CONCRETE SHALL BE STRIPPED UNTIL IT HAS REACHED AT LEAST TWO THIRDS OF THE 28 DAY DESIGN STRENGTH. DESIGN, ERECTION, AND REMOVAL OF ALL FORMWORK, SHORES, AND RESHORES SHALL MEET THE REQUIREMENTS SET FORTH IN ACI STANDARDS 347 AND 301. SHEET TITLE: 10. EMBEDDED CONDUITS WITHIN SLABS, BEAMS, OR WALLS,SHALL OCCUPY ONLY THE MIDDLE STRCUTU RAL NOTES ONE THIRD OF THE MEMBER DEPTH OR THICKNESS. MAXIMUM CONDUIT O.D. FOR SINGLE CONDUITS OR SUM OF O.D.'S FOR MULTIPLE CONDUITS THAT CROSS SHALL BE NO LARGER THAN ONE THIRD THE MEMBER DEPTH. PARALLEL CONDUITS SHALL BE SPACED WITH A MINIMUM OF 3 DIAMETERS CLEAR. CONDUITS SHALL BE A MINIMUM OF 1 DIAMETER AWAY SHEET NO.: FROM AND SHALL NOT INTERFERE WITH OR DISPLACE ANY TENDONS OR REINFORCING. CONDUIT SHALL NOT BE TIED TO REINFORCING OR TENDONS. CONDUITS SHALL NOT OCCUR WITHIN COLUMN ZONES OF SLABS AND/OR TRANSFER GIRDERS. CONDUIT PLACEMENT SHALL NOT IMPAIR THE STRENGTH OF THE CONSTRUCTION AS JUDGED BY THE ENGINEER. S 00 PREPARED FOR: Al ROOF TRUSSES 4451 ST LUCIE BLVD FT PIERCE, FL 34946 PREPARED BY: Frame Col Wired-Left2 Wind-Right2 Wind-Longl Wind_Long2 -Seis_Left- Frame Cal ----Dead- Collateral --Live-re- Wind.,'Leftl Wind,Rightl kH Line Lute Horz Vert Harz Vert Horz Vert Harz alert Horz Vert Line Line Horz Vert Nora Vert Rorz Vert Harz alert Horz Vert ENGINEERING - -6 C -10 .0 -10.7 0. 2 2. 9 11 . 8 4 . 9 11 . 6 4 . 9 0 . 0 -0.1 3 C 0 .1 1 .2 0 . 1 1 . 3 0 . 3 3. 5 -3.2 -17 . 9 9. 5 -3 . 6 6 A --5.1 4 . 6 0 . 8 -0. 9 9. 6 -3 0 . 8 9 . 6 -30. 8 0 ,.0 0.1 3 A -0 .1 1 .2 -0. 1 1 .3 -0 . 3 3 . 6 -7 . 7 -9. 1 3. 6 --16 , 4 WHOLE HOUSE ENGINEERING 4451 ST. LUCIE BLVD,SUITE 201 Frame Col �lind_Lef t2: Wind_Right2 Wind-Longl igznd_Long2 -Seis_Left- FORT PIERCE,FL 34946 Frame Col -Seis Right F1PAT_LL_l CONTACT: 772.409.1003 Dine Lime Harz Vert Horz Vert Line Line Harz Vert Harz Vert Horz Vert Horz alert Horz Vert ENGINEERING@WHENGINEERING.NET ----- ------ ----- ----- ----- ----- _ - - ? , S -11 . 0 .0 -�0 . 1 3 C 10 2 5 9 2 .5 8.3 5 . 1 19 9 6 � � Q 0 .1 0. 3 2 . 9 DRAWING NOTICE: 6 A 0 .0 -0 . 1 -0. 3 3.0 3 A -0 . 8 2 . 9 10. 5 -4 .4 --6 . 9 --12 . 1 -4 . 9 -15 . 8 0 .0 0 . 1 THESE DRAWINGS AND DOCUMENTS ARE Frame Cal -SeisRight -Seis_Lon - F4PAT_LL_1 CONFIDENTIAL AND ARE THE SOLE PROPERTY OF WHOLE HOUSE ENGINEERING, Line Line Horz alert Horz *pert Horz Vertu LLC. AND MAY NOT BE REPRODUCED, _:____ _____ ----- ----- _____ _____ DISSEMINATED OR REDISTRIBUTED WITHOUT Frame Col ----Dead--- Collateral ----Live--- Wind_Leftl Wind_Right1 � � � + � 0 . 1 0 . 0 -0 . 1 �� � �; � THE EXPRESS WRITTEN CONSENT OF Line Line Harz Vert Horz Vert Horz Vert Horz alert Harz Vert WHOLE HOUSE ENGINEERING, LLC. 3 R 0 , 0 -0 . 1 0 , 0 0 .1 -0. 3 3, 6 WARNING: DO NOT SCALE DRAWINGS. ----- ------ ----- ----- ----- ----- ----- ----- ----- ----- ----- ----- PLEASE CONTACT DESIGNER WITH ANY 5 C 0 . 2 1 .4 0.2 1 .8 0 . 6 4 . 4 -1 . 5 --19 . 8 .7 , 4 -15 . 6 QUESTIONS REGARDING DIMENSIONS. ------------------------------------------------------------------------------ ARCHITECTURAL SYMBOLS CONTAINED 5 A -0 . 2 0 . 9 -0.2 1 .3 =Q . 6 3..2 -2 . 2 --12 . 8 12 . 1 -8 . 6 WITHIN THESE DOCUMENTS ARE FOR Frame Cal ----Dead--- Collateral ----Lice--- Wind_Leftl Wi nd_ltightl GRAPHIC PURPOSES ONLY. SIZE AND Frame Col Gain Left2 Wind--H ght i 2 thin Lon 2 -Seis eft- LOCATION MAY VARY IN ORDER TO MEET -Lon 1$ Wind g Line Line Horz Vert Horz Vert Horz Vert Harz Vert Horz Vert THE MANUFACTURER'S SPECIFICATIONS. Line Une iiorz Vert Horz Vert Horz Vert Horz Vert Harz Vert --__.. ------ ----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ------ ----- ----- ----- ----- ----- ----- ----- ----- ----- ----- 2 C 0 . 1 1. .2 0 . 1 1 . 3 0 . 3 3. 4 -3 . 3 -18 .2 9 . 8 -3 . 7 5 C -8 . 3 -0 . 4 -1 . 5 3 . 8 6 . 2 -20.7 6 . 2 -20 . 7 0 .0 0 . 0 2 A -0 . 1 1 .2 -0 . 1 114 -0 . 3 3 .5 -7 . 8 -9. 3 3 . 5 -16. 6 ENGINEER'S SIGNATURE&SEAL: s A -7 . 8 -3 . 3 s.s 0 ' 9 16' 9 --11 . 9 16 . 9 -11 . 9 -o . l 0 . 0 RAMA PRANAV KRISTA Frame Col Wind_Left2 Wind_Right2 Wind-Longl Winci_I.ang2 -3eis,Left- Frame Cal --Seis_Right F2PAT_LL_l Line Line Horz Vert Horz Vert Horz Vert Horz Vert Horz Vert FL PE #88906 Line Line Harz Vert Horz Vert ___ ----- ----- ----- ----- ----- ----- ----- ----- ----- ----- _---_ ---_- ------ ----- ----- ----- ------ 2 C -10 .4 -6 !0 2 . 7 8 . 4 5.2 -1 5. 1 7 . 6 -11. 5 0 . 0 -0. 1 5 C 0. 0 0 . 0 0 . 6 4 . 4 2 A -0 .7 2. 9 10 . 6 -4 . 5 -6. 9 -12 .3 -5 . 0 -16. 0 0 . 0 0. 1 5 A 0 . 1 0 . 0 -0 . 6 3 . 2 •``00R pN A V Frame Col -Seis_Right -Seis_Long- F5PAT_LL_1 ��`•�`QQ • "" "•�GQs;%% -------------------------------- ----------------------------------------- ---- Line Line Horz Vert Horz Vert _9Qrz Vert = -__-_ --- -- ----- ----- ----- ----- ----- ----- ' * No. 88906 Frame Col -----Dead----- Collateral ----Live--- Wind_Leftl Wind_Rightl 2 C 0. 0 0 . 1 0 . 0 -0 . 1 0. 3 3 . 4 Line Line Horz Vert Harz Vert Horz alert Harz Vert Horz Vert 2 A 0 . 0 -0 . 1 0 . 0 0 . 1 -0 . 3 :3 . 5 �:, STATE of ----- -��--- - -- -____ ----- ----- ----- ----- ----- ----- ----- ----- '•,�•�`�.'•:`� ORIOP SS/•..... j\\\,\\��, 4 C 0 . 0 1.5 0 . 0 1 . �4 0 . 1 3.4 1 . 7 -13 . 2 14 . 4 3 . 0 ----------------------------------------------------------------------------- ,,,,,,,��ONAL\\����� 4 A -0 . 1 3 .0 -0 . 2 2 . 4 -0 . 4 5.7 2 . 9 -25 . 1 10 . 4 -31 . 1 Frame Cal ----Dead--- Collateral ----Life--- Wind--eftl Wind_R.ightl Frame Cal Wind-Left2 Wind_Right2 Kind„„Longl Wind_Long2 -Seis_Left- Line Line Horz ;.Pert. Harz Vert Horz Vert Harz Vert Harz Vert REVISION DATE BY REV Line Line Horz Vert Horz Vert iiorz Vert Horz Vert Harz Vertu ----- ------ ----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ------ ----- ----- ----- ----- ----- ----- --- ----- --- ----- 1 C 0 . 1 0 . 9 0 . 1 0 . 8 0 .3 2 . 9 0 . 1 -8 . 1 6 . 3 -1 , 6 PERMIT 09/17/2020 RK -- 4 C -14 .7 -13. 5 -2 . 0 2 . i 16 . 8 1 .4 18 , 8 5 . 1 -0 - -0 . 1 1 A -0. 1 1 .3 -0 . 1 0 . 9 -0 .3 3 . 0 2 . 2 -11 . 9 4 . 8 -12 . 4 4 A -7 . 9 6 .3 -0 . 5 2 . 4 12 . 1 -39.3 14 . 4 -43 . 0 -0 . ! 0. 1 Frame Cal Wind_Left2 WindRight2 Wind_Longl Winc_Long2 -Seis_Left- Frame Col -Seis_Right -Seis_Long- F3PAT_LL_l Line Line Horz Vert Horz alert Kurz Vert Horz Vert Harz Vert Line Line Horz Vert, Horz Vert Horz alert ----- -�-�-_ ----- ----- ----- ----- ----- ----- ----- ----- ----- --_-- 1 C -7 . 6 -6. 8 -1 . 4 -0 - 3 6. 1 -5 . 3 7 . 9 -1 . 7 0 .0 0. 0 4 c 0 . 1 0 . 1 �0 . 0� O-0 . 1 0.2 3.7 1 A -3.5 2 .4 -0 . 9 1 . 9 4 . 5 -14 .5 7 . 0 -18.2 0 . 0 0 . 0 K 0 + 1 -0 V . 1 aV a1 l0 . 3, 3p� Frame Cal -8eis_Right --Seis_Long- F6PAT_LL_l ------------------------------------------------------------------------------- Lire Line Rorz Vert uor2 Vert Aorz Vert •--.- ------ ---,-- ----- ----- ----- ----- --is- 1 c 0 . 0 0 . 0 0 . 0 -0 . 1 0 . 3 2 . 9 PROJECT NUMBER, NAME &ADDRESS: I A 0 . 0 0 . 0 0 , 0 0 . 1 -0 . 3 3 . 0 BUILDING 6 4451 ST LUCIE BLVD FT PIERCE, FL 34946 DRAWN BY: RK SHEET TITLE: STRUCTURAL NOTES II SHEET NO.: S = 2 * 0 PREPARED FOR: Al ROOF TRUSSES 3 2 4451 ST LUCIE BLVD FT PIERCE, FL 34946 26-0" 26-0" 24'-0" 16-0" 26-0" F6 Fb I Fb F6 F3 F4 F1 F5 F5 F3 B-D B-E B-F B-F B-F B-D PREPARED BY: kH ENGINEERING 5"CONC.SLAB 2500 PSI W/ 6X6 #10 W.W.M. OR FIBERMESH REINFORCING ON 6-MIL. VIS-QUEEN MOISTURE BARRIER ON CLEAN TERMITE TREATED SOIL, WHOLE HOUSE ENGINEERING COMPACTED TO 95%MODIFIED PROCTOR. 4451 ST. LUCIE BLVD,SUITE 201 PROVIDE CONTROL JOINTS PER 4/S3.0 FORT PIERCE,FL 34946 CONTACT: 772.409.1003 ENGINEERING@ WHENGINEERING.NET DRAWING NOTICE: THESE DRAWINGS AND DOCUMENTS ARE CONFIDENTIAL AND ARE THE SOLE PROPERTY OF WHOLE HOUSE ENGINEERING, LLC. AND MAY NOT BE REPRODUCED, DISSEMINATED OR REDISTRIBUTED WITHOUT F3 F2 F5 F5 F3 THE EXPRESS WRITTEN CONSENT OF WHOLE HOUSE ENGINEERING, LLC. B-A B-C B-B B-B B-A WARNING: DO NOT SCALE DRAWINGS. PLEASE CONTACT DESIGNER WITH ANY QUESTIONS REGARDING DIMENSIONS. ARCHITECTURAL SYMBOLS CONTAINED AA, WITHIN THESE DOCUMENTS ARE FOR Fb F6 F6 Fb GRAPHIC PURPOSES ONLY. SIZE AND LOCATION MAY VARY IN ORDER TO MEET THE MANUFACTURER'S SPECIFICATIONS. TOP OF FOOTING FOR ALL FOUNDATIONS TO BE 12" BELOW GRADE AND CENTERED ON THE COLUMNS ENGINEER'S SIGNATURE &SEAL: EMBED. DEPTH PER SCOHEEDULE. REEFER TO OF ANCHORS DKIRBYDRAW DRAWINGS FOR ANTHONY TOMBO FOOTING AND BASE PLATE SCHEDULE ANCHOR LAYOUT AND BASE PLATE NO OF CAST IN PLACE EMBED. DEPTH OF ANCHOR LAYOUT SPECIFICATIONS FL, PE #80083 MARK SIZE DEPTH REINFORCING ANCHORS ANCHORS AND BASE PLATE PROVIDE FOOTING TOP REINFORCEMENT AS #5 AT 8" O.0 EACH WAY 12'-6" WIDTH BY F� 12'-b" LENGTH 18 PER 2/S3.0 (6)-3/4" DIA ANCHORS 16" PER KIRBY DRAWING El \111111111//,,�/ 13'-6" WIDTH BY RQNA.V F2 13'-6" LENGTH 18 PER 2/S3.0 (4)-3/4" DIA ANCHORS 16" PER KIRBY DRAWING El \�`��1.Q;.• E E NSF•.. -,, PROVIDE FOOTING BOTTOM REINFORCEMENT 1 1'-O" WIDTH BY AS #5 AT 8"O.0 EACH WAY No. 88906 _ F3 1 1'-0" LENGTH 18 PER 2/S3.0 (4)-3/4" DIA ANCHORS 16" PER KIRBY DRAWING El _ - _ * : * _ M 00 F4 9'-0" WIDTH BY 18" PER 2/S3.0 (4)-3/4" DIA ANCHORS 16" PER KIRBY DRAWING El = = -o•. STATE OF 9'-0" LENGTH ,.-5 i G, F v ' 10'-6" WIDTH BY �•. . '.��.�F' . ( p R 10 P.G�\\�` F5 18" PER 2/S3.0 (4)-3/4" DIA ANCHORS 16" PER KIRBY DRAWING El - — .' is .' - -. SS/•• A �� 10'-6" LENGTH ON L NOTES 1. BASE PLATE CALLOUTS 'B-X' REFER TO BASE PLATE PROFILES OF KIRBY DRAWING El. FOLLOW KIRBY SHEET E1 FOR ANCHOR LAYOUT AND BASE PLATE DIMENSIONS 2. REFER TO DETAIL 3/S3.0 FOR F6 SLAB TURNDOWN DETAIL REVISION DATE BY REV 3. TOP OF FOOTING FOR ALL FOUNDATIONS TO BE 12"BELOW GRADE FOOTING DETAIL AT PERMIT 09/17/2020 RK (-2-� BUILDING 6 S-3.0 SCALE: 3/811 = 11-011 PROVIDE CONTROL JOINTS AT EVERY 1 OFT REFER TO PLAN FOR REINFORCEMENT DETAIL 1/8"SAWCUT X 1/4 SLAB THICKNESS WHERE SHOWN ON 5"CONC., REINF. W/ 6"x6"W 1.4xW 1.4 WWF ON FOUNDATION PLAN 6-MIL POLY ETHYLENE VAPOR BARRIER ON PROJECT NUMBER, NAME &ADDRESS: WELL-COMPACTED CLEAN TERMITE TREATED FILL. ° a.a. a ° ° ° a as ---- BUILDING 6 a _a-la-------------- SEE PLAN 4451 ST LUCIE BLVD #5 CONT. BOTTOM REINFORCEMENT a a a FT PIERCE, FL 34946 DRAWN BY: (---3 1`6 - SLAB TURNDOWN 4 TYP. CONTROL JOINT RK S-3'0 SCALE: 1 11 = 1 1-011 S-3.0 SCALE: 1 -1 /211 — 1 -011 SHEET TITLE: FOUNDATION PLAN AND DETAILS SHEET NO.: S = 3 .0