Roofing Systems
See General Information for Roofing Systems
JOHNS MANVILLE R10167
717 17TH ST
DENVER,CO 80202-3330 USA
A minimum 1/4 in.thick layer of"Invinsa® FR"can be used in lieu of"Invinsa®"in any existing non-combustible roof deck Classification.This can be
above or below additional insulation layers described in the Certified roofing system.The resulting roofing assembly can be used over a combustible roof
deck(minimum 15/32-in.thick plywood).All insulation joints must be staggered a minimum of 6-in.from the roof deckjoints and from the insulation
joints directly below.The maximum incline shall be in accordance with the Certification established for the original roofing system as published on UL's
Product iQ'"database for the Classifications published under the product category of Roofing Systems(TGFU);however the incline cannot exceed 3:12.
A minimum 1-in.thick layer of"ENRGY 30 FR"can be used in lieu of"ENRGY 30"in any existing non-combustible roof deck Classification.This can be
above or below additional insulation layers described in the Certified roofing system.The resulting roofing assembly can be used over a combustible roof
deck(minimum 15/32-in.thick plywood).All insulation joints must be staggered a minimum of 6-in.from the roof deckjoints and from the insulation
joints directly below.The maximum incline shall be in accordance with the Certification established for the original roof system as listed in UL's Product
iQT"database for the Classifications published under the product category of Roofing Systems(TGFU);however the incline cannot exceed 3:12.
A minimum 1-in.thick layer of"ENRGY 3®CGF"can be used in lieu of"ENRGY 30"in any existing non-combustible deck Classification.This can be above
or below additional insulation layers described in the Certified roofing system.The resulting roofing assembly can be used over a combustible roof deck
(minimum 15/32-in.plywood).All insulation joints must be staggered a minimum of 12-in.from the deckjoints and from the insulation joints directly
below.The maximum incline shall be in accordance with the Certification established for the original roof system as listed in UL's Roofing Materials&
Systems Directory,however the incline cannot exceed 1/2:12.
A minimum 1/2 in.thick layer of"SeparatoRT"CGF"can be used in lieu of"ENRGY 30"in any existing non-combustible deck Classification.This can be
above or below additional insulation layers described in the Certified roofing system.The resulting roofing assembly can be used over a combustible roof
deck(minimum 15/32 in.plywood).All insulation joints must be staggered a minimum of 12 in.from the deckjoints and from the insulation joints directly
below.The maximum incline shall be in accordance with the Certification established for the original roof system as published on UL Product iQT"'
databaseUL's,however the incline cannot exceed 1/2:12.
A minimum 1/2 in.thick layer of"ProtectoRTm HD"can be used in lieu of"Invinsa®"in any existing non-combustible deck Classification.This can be above
or below additional insulation layers described in the Certified roofing system.The resulting roofing assembly can be used over a combustible roof deck
(minimum 15/32 in.plywood).All insulation joints must be staggered a minimum of 12 in.from the deckjoints and from the insulation joints directly
below.The maximum incline shall be in accordance with the Certification established for the original roof system as published on UL Product iQT"'
databaseUL's,however the incline cannot exceed 1/2:12.
Minimum 1/2 in.thick thick avpsum board or minimum 1/4 in.thick Georgia-Pacific Gypsum LLC"DensDeck® Roofboard"or"DensDeck Prime®
Roofboard"or"DensDeck DuraGuardT"Roofboard"or minimum 1/4 in.thick United States Gypsum Co.SECUROCKT"Glass-Mat Roof Board(Type SGMRX)
or minimum 1/4 in.thick National Gypsum Co."DEXcell Glass Mat Roof Board"or minimum 1/4 in.thick National Gypsum Co."DEXcell FA Glass Mat Roof
Board"may be used in any existing noncombustible roof deck Classification.When this is done,the resulting roofing system is acceptable for use over
combustible(15/32 in.thick minimum)roof decks.Thejoints in the board or overlayment board are offset 6 in.with thejoints in the deck.If polystyrene
insulation is used in the existing noncombustible roof deck Classification,it must be placed beneath the gypsum board or"DensDeck® Roofboard"or
"DensDeck Prime® Roofboard"or"DensDeck DuraGuardTm Roofboard".
Minimum 2-in.thick unfaced structural cement fiber units,formed into slabs or boards and covered under Structural Cement-Fiber Units(CIYT),are
suitable alternates as roof decks for all certified roofing systems intended for use over noncombustible decks.
"DuraFoam"may be used in lieu of"Fesco-Foam"applicable Classifications.
"Fesco HD"is a suitable alternate to"Duraboard"in any applicable Classification.
"RetroPlus"is an acceptable alternate to"Retro-Fit"or"ENRGY 38"in any applicable Classification."RetroPlus"may be placed over"ENRGY 30"in any
applicable Classification.
https://iq.ulprospector.com/en/profile?e=148903 1/93
10/9/2020 TGFU.R10167-Roofing Systems I UL Product iQ
"Tapered Fesco-Foam"and"Tapered DuraFoam"are acceptable alternates to"Fesco-Foam"and"DuraFoam",respectively,in any applicable Classification.
"JM TopGard 5001",is an acceptable alternate to"JM TopGard 4001"in all applicable Classifications.
Any of the following insulations may be used in lieu of"ENRGY 30"in any applicable Classification:"Tapered ENRGY 30","ENRGY 30 AGF","Tapered
ENRGY 30 AGF","ENRGY 30 CGF","Tapered ENRGY 30 CGF","ENRGY 30 Foil Faced","Tapered ENRGY 38 Foil Faced","ENRGY 30 25 PSI","Tapered
ENRGY 30 25 PSI","ENRGY 30 25 PSI AGF","Tapered ENRGY 38 25 PSI AGF","ENRGY 38 25 PSI CGF","Tapered ENRGY 30 25 PSI CGF","ENRGY 30 25
PSI Foil Faced","Tapered ENRGY 38 25 PSI Foil Faced","ValuTherm'"","Tapered ValuTherm'"","ValuThermT°"AGF","Tapered ValuTherm'"AGF",
"ValuTherm'"CGF","Tapered ValuTherm-CGF","ValuTherrn" 25 PSI","Tapered ValuTherm-25 PSI","ValuTherm-25 PSI AGF","Tapered ValuTherm'"25
PSI AGF","ValuTherm'°"25 PSI CGF","Tapered ValuThermTm 25 PSI CGF","APTM' Foil Faced Sheathing","Tapered APTM' Foil Faced Sheathing","DiamondBacke
Pre-Cut Crickets","Diamond Back® Pre-Cut Miters","R-PanelT"","Tapered R-Panel'""","R-PanelT""25 PSI","Tapered R-PanelT""25 PSI","SeparatoRTM"',
"SeparatoRTM'CGF","SeparatoRM FR".
"ENRGY 3.E"is a suitable alternate to"ENRGY 30"in any applicable Classification.Any of the following insulations may be used in lieu of"ENRGY 3.E"in
any applicable Classification:"Tapered ENRGY 3.E","ENRGY 3.E 25 PSI","Tapered ENRGY 3.E 25 PSI".
"ENRGY 38 C1"is a suitable alternate to"ENRGY 30"in any applicable Classification.Any of the following insulations may be used in lieu of"ENRGY 30
C1"in any applicable Classification:"Tapered ENRGY 30 C1","ENRGY 30 C1 CGF","Tapered ENRGY 38 C1 CGF".
"Invinsa®Foam"or"Tapered Invinsa®Foam"may be used in lieu of the combination of"Invinsa®"and"ENRGY 30"in any Classified system where
"Invinsa®"is directly over"ENRGY 38".
"ENRGY 30 FR"is a suitable alternate to"ENRGY 30"in any applicable Classification.Any of the following insulations may be used in lieu of"ENRGY 30
FR"in any applicable Classification:"Tapered ENRGY 30 FR","ENRGY 30 25 PSI FR","Tapered ENRGY 30 25 PSI FR".
"Invinsa® FR"is a suitable alternate to"Invinsa®"in any applicable Classification.
"Invinsa®Foam FR"may be used in lieu of the combination of"ENRGY 30 FR"and"Invinsa®"in any Classified system where"ENRGY 30 FR"is directly
over"Invinsa®".
"Invinsa®Foam FR"is a suitable alternate to"Invinsa®Foam"in any applicable Classification.Any of the following insulations may be used in lieu of
"Invinsa®Foam FR"in any applicable Classification:"Tapered Invinsa®Foam FR".
Any of the following insulations may be used in lieu of"Invinsa®"in any applicable Classification:"Invinsa®Plus","ProtectoR"HD","ProtectoR'"HD FR".
"ProtectoRTM' HD FR"is a suitable alternate to"Protectolk' HY in any applicable Classification.
"ProtectoR Foam®"may be used in lieu of"Invinsa®Foam",or in lieu of the combination of"ProtectoR- HY directly over"ENRGY 30",in any Classified
system.
"Urethane Insulation Adhesive"or"JM 2 Part Urethane Insulation Adhesive Canister"or"JM 2 Part Urethane Insulation Adhesive"and"JM Two-Part UTA"
or"JM Two Part Urethane Insulation Adhesive"and"JM Two Part Urethane Insulation Adhesive Canister"or"JM Two-Part UTA Canister"may be used to
adhere insulation or cover boards in any of the following Classifications.
"JM Vapor Barrier SA"or"JM Vapor Barrier SAR"can be used beneath insulation in any of the following applicable Classifications.
Unless otherwise indicated,"JM PVC SD Plus"may be used in lieu of"JM PVC"in any applicable Classification.
Base sheets and ply sheets may be adhered with hot asphalt(15 to 25-Ibs/100-ft.2)or"BUR Adhesive",applied at 1 to 2-gal/100-ft.Z unless otherwise
specified adhesive may be applied by brush,roller,notched squeegee or spray equipment.
Vapor barriers or ply sheets are optional beneath roof insulation on all systems.
Unless otherwise indicated,minimum 7/16-in.thick non-veneer APA rated oriented strand board may be substituted for wood fiberboard in the following
systems.
Unless otherwise indicated,wood fiberboard or"RetroPlus"may be substituted for polyisocyanu rate insulation in any of the following non-combustible
systems.
Two plies of any Type G1 base sheet is an acceptable alternate to one ply of Type G2 ply sheet in any Classification.
"GlasPly IV"or"GlasPly Premier"may be used in any applicable roofing system when a Type G1 base/ply sheet is referenced.
"GlasBase XT"is an acceptable alternate to"GlasBase"in all applicable Classifications.
"JM Coating Acrylic CR",are acceptable alternates to"JM Coating Acrylic"in all applicable Classifications.
Base/Ply Sheet Listed: Acceptable Alternative
'DynaBase" "DynaBasePR`
"DynaMopGL 2.2 P/S`
"DynaMop GL 2.2 P/S QL"*
https://iq.ulprospector.com/en/profile?e=148903 2/93
10/9/2020 TGFU.R10167-Roofing Systems I UL Product iQ
"DynaWeld Base"
"DynaWeld GL 2.2 P/P"
"DynaWeld Base" "DynaWeld GL 2.2 P/P"
"DynaBase PR" "DynaBase HP"
"DynaWeld Base XT'
"DynaGrip Base" "DynaGrip Base SD/SA"
"DynaGrip Base SA/SA"
"Dibiten SAS Base"
"DynaGrip Cap" "Dibiten SAS Cap"
"DynaWeld GL 2.2 P/P" "DynaBase HW"
"DynaPly T1" "DynaPly T1 HW"
"DynaPly" "DynaPly HW"
"DynaFast 180 HW" "DynaFast HP HW"
*Limited to noncombustible roof deck
Membrane Listed: Acceptable Alternative
"DynaLastic 180 S" "DynaLastic 180"
"DynaBase PR"
"DynaWeld PR 3.0 P/P"
"DynaWeld 180S"
"DynaMopGL 2.2 P/S"
"DynaMop GL 2.2 P/S QL"
"DynaLastic HP"
"DynaFast 180S"*
"DynaLastic 180" "DynaWeld Cap 180"
"DynaLastic HP Cap"
"DynaWeld 180 S" "DynaFast 180 HW`
"DynaWeld HP"
"DynaWeld Cap 180" "DynaWeld HP Cap"
"DynaLastic 180 FR" "DynaWeld Cap 180 FR"
"DynaLastic 250 FR" "DynaWeld Cap 250 FR"
"DynaLastic 250" "DynaWeld Cap 250"
"DynaLastic 250 S" "DynaWeld 250 S"
https://iq.ulprospector.com/en/profile?e=148903 3/93
10/9/2020 TGFU.R10167-Roofing Systems I UL Product iQ
4.Deck:NC Incline:3
Insulation(Optional):—Any thickness,one or more layers"Fesco"or"DuraBoard","Fesco-Foam", "Fiber Glass Roof Insulation", "ENRGY
30"or any UL Classified polyisocya n u rate insulation,mechanically fastened or hot mopped in combination(optional)with 1/2 in.thick
"Retro-Fit"cover board or 3/4 in.thick"Fesco"or"DuraBoard"over polystyrene.
Ply Sheet:—One or more plies Type G1 or"GlasPly IV","GlasPly Premier";or Type G2"GlasBase"or"Ventsulation";or"PermaPly 28";or
"DynaPly T1", "DynaPly", "DynaBase"or"DynaLastic 180 S" (SBS modified bitumen);mechanically fastened or hot mopped.
Ply Sheet:—"DynaLastic 180 S", "DynaLastic 250 S","DynaLastic 250", "DynaKap T1","DynaKap","DynaPly T1", "DynaPly", "DynaGlas",
"DynaMax FR", "DynaLastic 250FR","Roof Defender SBS Cap Sheet"or"DynaBase" (SBS modified bitumen),hot mopped.
Surfacing:—Gravel and hot roofing asphalt.
5.Deck:C-15/32 Incline: 1
Insulation(Optional):—Any thickness,one or more layers, "Fesco"or"DuraBoard","Fesco-Foam","Fiber Glass Roof Insulation", "ENRGY
30"or any UL Classified polyisocya n u rate insulation,mechanically fastened or hot mopped in combination(optional)with 1/2 in.thick
"Retro-Fit"cover board,or 3/4 in.thick"Fesco"or"DuraBoard"over polystyrene.
Ply Sheet:—Two or more plies Type G1 or"GlasPly IV", "GlasPly Premier";or Type G2"GlasBase"or"Ventsulation";or"PermaPly 28";or
"DynaPly T1", "DynaPly'or"DynaBase" (SBS modified bitumen);mechanically fastened or hot mopped.
Ply Sheet:—"DynaLastic 180 S", "DynaLastic 250 S","DynaLastic 250", "DynaKap T1","DynaKap","DynaPly T1", "DynaPly", "DynaGlas",
"DynaMax FR", "DynaLastic 250FR","Roof Defender SBS Cap Sheet"or"DynaBase"(SBS modified bitumen),hot mopped.
Surfacing:—Gravel and hot roofing asphalt.
6.Deck:C-15/32 Incline:2
Insulation(Optional):—Any thickness,one or more layers, "Fesco"or"DuraBoard","Fesco Foam", "Fiber Glass Roof Insulation","ENRGY
30"or any UL Classified polyisocya n u rate insulation,mechanically fastened or hot mopped in combination(optional)with 1/2 in.thick
"Retro-Fit"cover board,or 3/4 in.thick"Fesco"or"DuraBoard"over polystyrene.
Ply Sheet:—Three or more plies Type G1 or"GlasPly IV", "GlasPly Premier";or Type G2"GlasBase"or"Ventsulation";or"PermaPly 28";or
"DynaPly T1","DynaPly'or"DynaBase" (SBS modified bitumen);mechanically fastened or hot mopped.
Ply Sheet:—"DynaLastic 180 S", "DynaLastic 250 S","DynaLastic 250", "DynaKap T1","DynaKap","DynaPly T1", "DynaPly", "DynaGlas",
"DynaMax FR", "DynaLastic 250FR","Roof Defender SBS Cap Sheet"or"DynaBase"(SBS modified bitumen),hot mopped.
Surfacing:—Gravel and hot roofing asphalt.
7.Deck:NC Incline:2
Insulation(Optional):—Any UL Classified(except polystyrene),any thickness.
Base Sheet:—One ply"DynaBase".
Ply Sheet:—Two or more plies"DynaBase"(SBS modified bitumen),hot mopped.
Surface Coating:—Gravel,embedded in hot roofing asphalt or any UL Classified emulsion applied at the rate of 4-5 gal/sq.
8.Deck:C-15/32 Incline: 1/2
Insulation(Optional):—Any thickness,one or more layers, 1/2 in.thick"Retro-Fit","Fesco"or"DuraBoard","Fesco-Foam", "DuraBoard",
"ENRGY 38",hot mopped or mechanically fastened.All insulation joints offset from plywood deckjoints,6 in.minimum.
Base Sheet:—One or more plies Type G1 or"GlasPly IV"or"GlasPly Premier;or Type G2"GlasBase"or"Ventsulation";or"PermaPly 28";or
"DynaPly T1","DynaPly"or"DynaBase" (SBS modified bitumen);hot mopped;or"DynaWeld Base", heat welded.
Membrane:—"DynaKap FR T1", "DynaKap FR","DynaGlas 30 FR","DynaLastic 180FR", "DynaMax FR", "DynaLastic 250FR" or"DynaGlas FR"
(SBS modified bitumen),hot mopped,or"DynaWeld Cap FR", heat welded.
9.Deck:NC Incline: 1/2
Insulation(Optional):—One or more layers,any thickness, "Fesco"or"DuraBoard","Fesco-Foam", "DuraBoard", "ENRGY "or any UL
Classified polyisocya n u rate insulation,mechanically fastened or hot mopped in combination (optional)with 1/2 in.thick"Retro-Fit"cover
board or 3/4 in.thick"Fesco"or"DuraBoard"over polystyrene, mechanically fastened or hot mopped.
Base Sheet:—One or more plies Type G1 or"GlasPly Premier", "GlasPly IV";or Type G2"GlasBase"or"Ventsulation";or"PermaPly 28";or
"DynaPly T1","DynaPly', "DynaBase","DynaLastic 180 S"or"DynaFast 1805" (SBS modified bitumen);mechanically fastened or hot mopped;
or"DynaWeld Base", heat welded;or"DynaFast 180 HW",mechanically fastened or heat welded.
Membrane:—"DynaKap FR T1", "DynaKap FR","DynaGlas 30 FR","DynaGlas FR","DynaMax FR"or"DynaLastic 250FR" (SBS modified
bitumen), hot mopped,or"DynaWeld Cap FR",heat welded.
10.Deck:NC Incline: 1/2
Insulation(Optional):—Any thickness,one or more layers, "Fesco"or"DuraBoard","Fesco-Foam","ENRGY 3®"or any UL Classified
polyisocya n u rate insulation,hot mopped or mechanically fastened in combination (optional)with 1/2 in.thick"Retro-Fit"cover board or 3/4
in.thick"Fesco"or"DuraBoard"over polystyrene.