Whole Building Performance Method for Commercial Buildings Form 40OA 97
ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Community Affairs
FLA/COM-97 Version 2.2
PROJECT NAME -MARTIN FOWLER PERMITTING OFFICE:
ADDRESS: COMMERCE PARK BLVD.& RESERV _ST. LUCIE COUNTY
.ST. LUCIE CTY., FL. CLIMATE ZONE: _6
OWNER: _MARTIN FOWLER PERMIT NO:
AGENT: JURISDICTION NO: 661000
BUILDING TYPE: Mercantile (Retail)
'CONSTRUCTION CONDITION: New construction
DESIGN COMPLETION: _Finished Building
CONDITIONED FLOOR AREA: _3080 NUMBER OF ZONES: 3
MAX. TONNAGE OF EQUIPMENT PER SYSTEM: 6
COMPLIANCE CALCULATION:
METHOD A DESIGN CRITERIA RESULT
----------------- -------------- ------
A. WHOLE BUILDING 56.59 100.00 PASSES
PRESCRIPTIVE REQUIREMENTS:
LIGHTING
EXTERIOR LIGHTING
400.00
1088.00
PASSES
LIGHTING CONTROL REQUIREMENTS
PASSES
HVAC EQUIPMENT
COOLING EQUIPMENT
1. EER
8.90
8.90
PASSES
IPLV
8.30
8.30
PASSES
2. SEER
12.05
10.00
PASSES
3. EER
8.90
8.90
PASSES
IPLV
8.30
8.30
PASSES
. HEATING EQIUIPMENT
1. Et
20.00
N/A
2. Et
20.00
N/A
3. Et
20.00
N/A
AIR DISTRIBUTION SYSTEM INSULATION
REQUIREMENTS
1. Conditioned Space
6.00
0.00
N/A
2. Conditioned Space
6.00
0.00
N/A
3. Conditioned Space
6.00
0.00
N/A
REHEAT SYSTEM TYPES USED
NO REHEAT SYSTEM is USED
WATER HEATING EQUIPMENT
! 1. EF
20.00
0.89
PASSES
_
PIPING INSULATION REQUIREMENTS
1. Non -Circulating
2.00
0.60
PASSES
----------------------------------------------------------------------------
COMPLIANCE CERTIFICATION:
I hereby certify that the plans and Review of the plans and specifica-
specifications covered by this calcu- tions covered by this calculation
lation are in compliance -with the indicates compliance with the
F'lorid'a Energy ficien Co
PREPARED BY:
DATE: e! --o/
I hereby'certify that this building is
in compliance with the Florida Energy
Efficiency Code.
OWNER/AGENT:
DATE:
I hereby certify(*) that the system design
_Energy Efficiency.Code.
SYSTEM DESIGNER
Florida Energy Efficiency Code.
Before construction is completed,
this building will be inspected
for compliance in accordance with
Section 553.908, Florida Statutes.
BUILDING OFFICIAL:�Zp
DATE:
ST• �DFDRCoI T ON3O0
RE VXD BY BE
i�r c gib S e' Florida
1,�5 A~ ��EECTIOI�
QgSTRATION/STATE
ARCHITECT
MECHANICAL: William Duffey #24433 Florida
'PLUMBING William Duffey #24433 Florida
ELECTRICAL: William Duffey #24433 Florida
LIGHTING .
'(*) Signature is required where Florida law requires design to be performed
by registered design professionals. Typed names and registration numbers may
be used where all relevant information is contained on signed/sealed plans.
BUILDING ENVELOPE SYSTEMS COMPLIANCE
CHECK
401.-- ---- GLAZING --ZONE' 1------------------------------------------------ v-
Elevatioh Type U SC VLT Shading Area(Sgft)
---- 4.------------------ ---- ---- ---- -------------- ----------
Southeast Commercial 1.31 .94 .88 Continuous Ove 12111
Southeast Commercial 1.31 .94 .88 Continuous Ove 8311
Southeast Commercial 1.31 .94 .88 Continuous Ove 9
Total Glass Area in Zone 1 = 213;
401.------GLAZING--ZONE 2------------------------------------------------ v-
Elevation Type U SC VLT Shading Area(Sgft);
------------------------ ---- ---- ---- -------------- ----------
Northwest Commercial 1.31 .94 .88 None oil
Total Glass Area in Zone 2 = oil
'401.------GLAZING--ZONE 3------------------------------------------------ v
Elevation Type U SC VLT Shading Area(Sgft)
------------------------ ---- ---- ---- -------------- ----------
+Southwest Commercial 1.31 .94 .88 None oil
Total Glass Area in Zone 3 = 0;
Total Glass Area = 21311
402------ =WALLS --ZONE 1------------------------------------------------ 1 ---
Elevation Type U Insul R Gross(Sgft);
----------------------------------------- ----- ------- ----------
Northwest cbs/siding/1/2"dw .194 4 1041
Southwest cbs/siding/l/2"dw .194 4 550
Southeast cbs/siding/l/2"dw .194 4 958
Total Wall Area in Zone 1 = 1612
402. -----WALLS--ZONE 2------------------------------------------------ ;---
Elevation Type U Insul R Gross(Sgft)
----------------------------------------- ----- ------- -----------
Northeast interior wall 0 0 135611
Total Wall Area in Zone 2 = 1356;
402. -----WALLS--ZONE 3------------------------------------------------;---
Elevation Type U Insul R Gross(Sgft)
-,---------------------------------------- ----- ------- -----------
Northwest cbs/siding/l/2"dw .194 4 399
Northeast cbs/siding/l/2"dw .194 4 555
Southeast cbs/siding/l/2"dw .194 4 150;
Total Wall Area in Zone 3 = 110311
Total Gross Wall Area = 4071
403.------DOORS--ZONE 1------------------------------------------------ 1---
Elevation Type U Area(Sgft)
----------------------------------------------=---- ---------------�
Southeast 2 DOUBLE GLASS 1.03 42
Southwest 1-3/4 Steel Door -Solid Urethane foam co 0.40 21
Total Door Area in Zone 1 = 63
403.------DOORS--ZONE 2------------------------------------------------ 1---
Elevation Type U Area(Sgft)
--------------------------------------------------- ----- ----------
No doors 0.00 oil
Total Door Area.in Zone 2 = oil
403.. -----DOORS--ZONE 3------------------------------------------------; --
Elevation Type U Area(Sgft)
-------------------------------------------------- ----- ---------
Northwest 1-3/4 Steel Door -Solid Urethane foam co 0.40 21
Total Door Area in Zone 3 = 2111
Total Door.Area = 84
4D4.- ----ROOFS--ZONE 1------------------------------------- V---------- ;---
Type Color U Insul R Area(Sgft)
- - - - - M- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
3"wood/2"insul/st. seam ' Medium .073 10 1476
Total Roof Area in Zone 1 = 147611
404.-3----ROOFS--ZONE 2------------------------------------------------ ;---
Type • Color U Insul R Area(Sgft)
------------------------------------ ------ ----------------------
3"wood/2"insul/st. seam Medium .073 10 72811
Total Roof Area in Zone 2 = 728;
404.------ROOFS--ZONE 3------------------------------------------------ ;---
Type Color U Insul R Area(Sgft)
------------------------------------ -- --- ----------------------
3"wood/2"INSUL/ST. SEAM/CEILING Medium .028 32 66911
Total Roof Area in Zone 3 = 669;
Total Roof Area = 2873;
405.- -----FLOORS-ZONE 1------------------------------------------------;---
TypeInsul R Area(Sgft)
-----------------------------------------------------------------
Slab on Grade/Uninsulated 0 1476
Total Floor Area in Zone 1 = 1476
405.------FLOORS-ZONE 2-------------------------------------------------- ;---
Type Insul R Area(Sgft);
-----------------------------------------------------------------
Slab on Grade/Uninsulated 0 72811
Total Floor Area in Zone 2 = 728;
405.------FLOORS-ZONE 3------------------------------------------------ ;---
Type Insul R Area(Sgft)
-----------------------------------------------------------------;
Floor over Unconditioned Space/Uninsulated 0 669;
Total Floor Area in Zone 3 = 669;
Total Floor Area = 2873;
406.------INFILTRATION -------------------------------------------------- ;---
CHECK
Infiltration Criteria in 406.1.ABCD have been met.
MECHANICAL SYSTEMS
CHECK
:-----------------------------------------------------------------;---- ;---
HVAC load sizing has been performed. (407.1.ABCD)
407.------COOLING SYSTEMS -----------------------------------------------
Type No Efficiency IPLV Tons;
---------------------------- ------------- -------------------
1.. Air Cooled ( >= 65,000 Btu/h 1 8.9 0 6.31;
2. Split System 1 12.05 0 3.44
3. Air Cooled ('>= 65,000 Btu/h 1 8.9 0 6.30
408.------HEATING SYSTEMS ----------------------------------------------- ;
---
Type No Efficiency BTU/hr
-------------------------------- ---------------------------
1.. Electric Resistance 1 20 30000;
�2."Electric Resistance 1 20 3000011
3, Electric Resistance 1 20 30000
409.------VENTILATION ---------------------------------------------------- ;---
CHECK
Ventilation Criteria in 409.1.ABCD have been met.
410.-----AIR DISTRIBUTION SYSTEM----------------------------------------!---
CHECK;
------------------------------------------------------------------;-----i---
Duct sizing and design have been performed. (410.1.ABCD)
AHU Type Duct Location R-value;
-..--------------------------------------------------------------
1. Air Conditioners Conditioned Space 6
2, Air Conditioners` Conditioned Space 6
3. Atr Conditioners Conditioned Space 6
CHECK;
------------------------------------------------------------------;-----;---
Testing and balancing will be performed. (410.1.ABCD)
411.-----PUMPS AND PIPING -ZONE -----------------------------------------'---
Basic prescriptive requirements in 411.1.ABCD have been met. 11
PLUMBING SYSTEMS
411.-----PUMPS AND PIPING -ZONE 1--------------------------------------- 1---
I
. Type R-value/in Diameter Thickness;
---------------------------------------------------�
411.-----PUMPS AND PIPING -ZONE 2--------------------------------------
• Type R-value/in Diameter Thickness;
---------------------------------------------------
411. ----PUMPS AND PIPING -ZONE 3_______________________________________�___
Type R-value/in Diameter Thickness;
---------------------------------------------------
1. Non -Circulating 6 .75 2
412.-----WATER HEATING SYSTEMS -ZONE 1---------------------------------1--_
Type Efficiency StandbyLoss InputRate Gallons;
----------------------------------------------------------------
412.-----WATER HEATING SYSTEMS -ZONE 2__________________________________I___
Type Efficiency StandbyLoss InputRate Gallons;
------------------------ ---------- ------ -----------------------�
412.-----WATER HEATING SYSTEMS -ZONE 3----------------------------------1---
I
Type Efficiency StandbyLoss InputRate Gallons;
---------------------------------------------------------------
�1. <=12 kW 20 0 9000 30
ELECTRICAL SYSTEMS
CHECK;
413.-----ELECTRICAL POWER DISTRIBUTION -----------------------------
Metering criteria in 413.1.ABCD have been met.
414. ----MOTORS-------------------------------------------------- ; ----;---
Motor efficiencies in 414.1.ABCD have been met.
4f5.-----LIGHTING SYSTEMS -ZONE 1-------------------------------------- '---
_ 1
Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)
---------- ----------------- ---------------- --- ------ ----------
Type D(Gen 1 On/Off 2 960 118011
Accounting 2 On/Off 2 192 131
Material H 1 On/Off 2 1440 3301,
Total Watts for Zone 1 = 259211
Total Area for Zone 1 = 1641
415. ----LIGHTING SYSTEMS -ZONE 2 ---------------------------------------
Spa7ce Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)
---------- ----------------- ----------------- --- ----------------�
Type D(Gen 1 On/Off 2 960 728
Total Watts for Zone 2 = 96011
Total Area for Zone 2 = 72811
415.-----LIGHTING SYSTEMS -ZONE 3--------------------------------------- 1-__
Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)
---------- ----------------- ----------------- --- ----------------
Kitchen 1 On/Off 1 On/Off 1 416 495
Toilet and 1 On/Off 2 On/Off 0 128 165
t. Total Watts for Zone 3 544
Total Area for Zone 3 = 660
Total Watts = 409611
r Total Area - 3029
;CHECK;
Lighting criteria in 415.1.ABCD have been met.
------------------------------------------------------------------; --- ;---
16. Operation/maintenance manual will be provided to owner.(102.1)
----------------------------------------------------------------------------