REPORT OF STEM WALL BACKFILL COMPACTION LvL;`r-count
Client: G.W. Purucker Homes
5608 PGA Boulevard, Suite 208
Palm Beach Gardens, Florida 33410
Site: Lot 42, Watersong
St. Lucie County, Florida
Stem Wall Backfill (Slab Area)
Report Date:
May 7, 2008
Project No:
337
Lab No:
323
Permit No:
0802W0181,_-
Technician:
W. Hissong
Density tests and Hand Cone Penetrometer (HCP) readings were made in the stem wall backfill (slab area)
to a depth of three feet at a minimum of three locations. Density tests were performed in the upper one foot
of fill. HCP readings were taken in hand auger boreholes at one foot intervals from slab grade through the
depth of fill. At the time of our testing no information was available regarding the foundation setbacks.
The density tests were performed in general compliance with ASTM D 2922. The HCP test, in conjunction
with information about the soil type, is empirically correlated to the relative density of subsurface soils.
Density
Test No.
Date
Tested
Location
Elevation
(feet)
Dry Density( stJ
Percent
Compaction
In Place
Proctor
1
5/7/08
Center, North Side
0-1
115.8
119.4
97.0
2
Center, East Side
0-1
115.5
119.4
96.7
3
Center, South Side
0-1
1 115.3
119.4
96.6
4
Center, West Side
0-1
118.8
1 119.4
99.5
5
Center, Elevator Pit
0-1
115.5
1 119.4
96.7
* All elevations are below slab grade.
In the locations and depths that were tested, the stem wall backfill (slab area) has been compacted to a
minimum of 95 percent of the modified Proctor maximum dry density (ASTM D 1557).
Distribution:
Client - 3
SsLWhi . D.e"
PC1VUjs
Submitted by:
A. M. ENGINEERING AND TESTING, INC.
5/71' 0e
Paul C. Martin
Florida Registration No. 65051
F: t-
F. W,f DataIG. GV. Purucker Homes - Various - 3371323 - Lot 42, Watersong, SLC - Stem wall backfill.doc