HomeMy WebLinkAboutnew plansSTRUCTURAL-GENERAL NOTES: DESIGN CRITERIA AND LOADS 1.WIND DESIGN: WIND SPEED (MPH) V(ADJ)=127 V(ULT)=160 RISK CATEGORY II EXPOSURE CATEGORY D ENCLOSURE CLASSIFICATION ENCLOSED INTERNAL PRESSURE COEFFICIENT CPI =+/- 0.55 TOPOGRAPHIC FACTOR KZT =1.0 2.DESIGN LIVE LOADS: a.ROOF LIVE LOAD 20 PSF 3.DESIGN DEAD LOADS : a.ROOF DEAD LOADS 17 PSF 4.CONTRACTOR HAS THE RESPONSIBILITY TO NOTIFY THE SER OF ANY ARCHITECTURAL, MECHANICAL, ELECTRICAL, OR PLUMBING LOAD IMPOSED ONTO THE STRUCTURE THAT DIFFERS FROM, OR THAT IS NOT DOCUMENTED ON THE ORIGINAL CONTRACT DOCUMENTS (ARCHITECTURAL/ STRUCTURAL/ MECHANICAL/ ELECTRICAL OR PLUMBING DRAWINGS). PROVIDE DOCUMENTATION OF LOCATION, LOAD, SIZE AND ANCHORAGE OF ALL UNDOCUMENTED LOADS IN EXCESS OF 400 POUNDS. PROVIDE MARKED-UP STRUCTURAL PLAN INDICATING LOCATIONS OF ANY NEW EQUIPMENT OR LOADS. SUBMIT PLANS TO THE ENGINEER FOR REVIEW PRIOR TO INSTALLATION. GENERAL REQUIREMENTS 1.THE DESIGN AND CONSTRUCTION OF THIS PROJECT IS GOVERNED BY THE "FLORIDA BUILDING CODE (FBC)", SIXTH EDITION, HEREAFTER REFERRED TO AS THE FBC, AS ADOPTED AND MODIFIED BY THE AUTHORITY HAVING JURISDICTION (AHJ). 2.WHERE OTHER STANDARDS ARE NOTED IN THE DRAWINGS, USE THE LATEST EDITION OF THE STANDARD UNLESS A SPECIFIC DATE IS INDICATED. REFERENCE TO A SPECIFIC SECTION IN A CODE DOES NOT RELIEVE THE CONTRACTOR FROM COMPLIANCE WITH THE ENTIRE STANDARD. 3.REFER TO THE ARCHITECTURAL, MECHANICAL, ELECTRICAL, CIVIL AND PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION INCLUDING BUT NOT LIMITED TO: DIMENSIONS, ELEVATIONS, SLOPES, DOOR AND WINDOW OPENINGS, NON-BEARING WALLS, STAIRS, FINISHES, DRAINS, WATERPROOFING, RAILINGS, CURTAIN WALLS, DEPRESSIONS, MECHANICAL UNIT LOCATIONS, AND OTHER NONSTRUCTURAL ITEMS. 4.THE CONTRACTOR IS RESPONSIBLE FOR THE MEANS AND METHODS OF CONSTRUCTION AND ALL JOB RELATED SAFETY STANDARDS SUCH AS OSHA AND DOSH (DEPARTMENT OF OCCUPATIONAL SAFETY AND HEALTH). 5.THE STRUCTURAL DRAWINGS ARE INTENDED TO SHOW THE GENERAL CHARACTER AND EXTENT OF THE PROJECT AND ARE NOT INTENDED TO SHOW ALL DETAILS OF THE WORK. ARCHITECTURAL DRAWINGS SHALL GOVERN THE WORK FOR ALL DIMENSIONS. 6.PLAN AND DETAIL NOTES AND SPECIFIC LOADING DATA PROVIDED ON INDIVIDUAL PLANS AND DETAIL DRAWINGS SUPPLEMENTS INFORMATION IN THE STRUCTURAL GENERAL NOTES. 7.ALTERNATE PRODUCTS OF SIMILAR STRENGTH, NATURE AND FORM FOR SPECIFIED ITEMS MAY BE SUBMITTED WITH ADEQUATE TECHNICAL DOCUMENTATION TO THE ENGINEER FOR REVIEW. ALTERNATE MATERIALS THAT ARE SUBMITTED WITHOUT ADEQUATE TECHNICAL DOCUMENTATION OR THAT SIGNIFICANTLY DEVIATE FROM THE DESIGN INTENT OF MATERIALS SPECIFIED MAY BE RETURNED WITHOUT REVIEW. ALTERNATES THAT REQUIRE SUBSTANTIAL EFFORT TO REVIEW WILL NOT BE REVIEWED UNLESS AUTHORIZED BY THE OWNER. 8.ALL STANDARD NOTES AND DETAILS CONTAINED HEREIN ARE TYPICAL UNLESS NOTED OTHERWISE. CONTRACTOR'S COORDINATION 1.THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING DETAILS AND ACCURACY OF THE WORK WITH ENGINEER AND OTHER TRADES; FOR CONFIRMING AND CORRELATING ALL QUANTITIES AND DIMENSIONS; FOR SELECTING FABRICATION PROCESSES; FOR TECHNIQUES OF ASSEMBLY; AND FOR PERFORMING WORK IN A SAFE AND SECURE MANNER. 2.DISCREPANCIES, OMISSIONS, OR INCONSISTENCIES WITH APPLICABLE CODE REQUIREMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE PROCEEDING WITH THE WORK. 3.THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AT THE SITE. CONFLICTS BETWEEN THE DRAWINGS AND ACTUAL SITE CONDITIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE PROCEEDING WITH THE WORK. STRUCTURAL CERTIFICATION 1.I CERTIFY THAT THE PLANS AND SPECIFICATIONS COMPLY WITH THE STRUCTURAL PORTION OF THE FLORIDA BUILDING CODE SIXTH EDITION. 2.I ALSO CERTIFY THAT STRUCTURAL ELEMENTS DEPICTED ON THESE PLANS PROVIDE ADEQUATE RESISTANCE TO THE WIND LOADS SPECIFIED IN SECTION 1609 IN THE FBC AND CHAPTER 3 IN THE FBC-RESIDENTIAL. FOUNDATION AND SLABS ON GRADE 1.FOUNDATION IS DESIGNED BASED ON PRESUMPTIVE SAFE ALLOWABLE BEARING PRESSURE OF 1,500 PSF. CONTRACTOR SHALL VERIFY THAT THE MINIMUM BEARING PRESSURE IS OBTAINED PRIOR TO FOOTING PLACEMENT. 2.THE ARCHITECT /ENGINEER ASSUMES NO RESPONSIBILITY FOR ANY INTERPRETATION THAT THE SUBSURFACE CONDITIONS DESCRIBED IN THE TEST BORING LOGS OCCUR CONSISTENTLY THROUGHOUT THE JOB SITE. TEST BORINGS ARE INCLUDED ONLY TO ASSIST THE CONTRACTOR DURING BIDDING AND SUBSEQUENT CONSTRUCTION AND REPRESENT SOIL CONDITIONS ONLY AT THE SPECIFIC LOCATIONS AND AT THE PARTICULAR TIMES THEY WERE TAKEN. 3.REINFORCED FOUNDATION REQUIREMENTS USED IN THE DESIGN: a.MINIMUM DEPTH BELOW FINISHED GRADE......................1'-0" b.MAXIMUM ALLOWABLE BEARING CAPACITY.....................1,500 PSF c.MODULUS OF SUBGRADE REACTION.............................. 200 PCI d.PASSIVE LATERAL PRESSURE........................................... 250 PSF e.ACTIVE LATERAL PRESSURE (UNRESTRAINED) ............55 PSF f.ACTIVE LATERAL PRESSURE (RESTRAINED)……………35 PSF g.COEFFICIENT OF SLIDING FRICTION………………………0.4 4.ALL FOUNDATION CONCRETE SHALL BE CAST IN THE DRY. DEWATERING OPERATION SHALL BE DONE IN SUCH A WAY THAT GROUND WATER LEVELS OUTSIDE THE SITE WILL BE MAINTAINED TO AVOID SETTLEMENT AND DAMAGE TO NEARBY BUILDINGS AND STRUCTURES. 5.SYNTHETIC FIBER REINFORCEMENT SHALL COMPLY WITH ASTM-C-1116, AND THE DOSAGE AMOUNT SHALL BE IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATION BUT NOT LESS THAN 1.2 LBS/CY 6.WELDED WIRE FABRIC SHALL CONFORM TO A.S.T.M. A185 (LATEST EDITION), AND BE SUPPORTED ON SLAB CHAIRS SPACED AT 3' -0 O.C.. MAXIMUM. 7.THE CONCRETE STRENGTHS SHOWN IN THE FOLLOWING TABLE ARE THE MINIMUM COMPRESSIVE STRENGTHS AT 28 DAYS AND THE WATER/CEMENT RATIO IS THE MAXIMUM. THE SPECIFIED SLUMP IS THE MAXIMUM PRIOR TO THE ADDITION OF ADMIXTURES. CONCRETE SHALL BE STANDARD WEIGHT CONCRETE (145 PCF). ITEM OF STRENGTH AGG SLUMP WATER/CEMENT CONSTRUCTION (PSI) (IN) (IN) (LB/LB) FOUNDATION / SLAB ON GRADE 2,500 3/4 4-6 0.50 8.REMOVE AND REPLACE MINIMUM 1 FEET OF EXISTING SOIL BELOW FOUNDATION WITH COMPACTED, MOISTURE-TREATED, NON-EXPANSIVE FILL MATERIAL. FILL AREA SHALL EXTEND 1 FOOT BEYOND FOUNDATION FOOTPRINT. 9.FOR SITE PREPARATION, REMOVE DELETERIOUS MATERIAL SUCH AS VEGETATION, ORGANIC SOILS AND ROOT ZONES, EXISTING FILL, OR LOOSE, SOFT FROZEN, OR OTHERWISE UNSUITABLE MATERIALS FROM BELOW THE PROPOSED FOUNDATION AREAS. 10.SOIL BENEATH SLABS AND FOOTINGS SHALL BE EXCAVATED AS REQUIRED TO REMOVE ALL ORGANIC AND DELETERIOUS MATERIALS. PLACE CLEAN SAND FILL IN MAXIMUM OF 12 INCH LIFTS. SUBGRADE AND EACH LIFT SHALL BE COMPACTED TO A MINIMUM OF 95 PERCENT OF ITS MODIFIED PROCTOR VALUE IN ACCORDANCE WITH ASTM D 1557. 11.SUBGRADE SHALL BE UNIFORM OVER THE ENTIRE FOUNDATION AREA. DEPRESS SLABS ON GRADE FOR FLOOR FINISHES PER ARCHITECTURAL DRAWINGS. 12.FOUNDATIONS SHALL BEAR ON EITHER COMPETENT NATIVE SOIL OR COMPACTED STRUCTURAL FILL AS PER THE GEOTECHNICAL REPORT. EXTERIOR PERIMETER FOOTINGS SHALL BEAR NOT LESS THAN 24 INCHES BELOW FINISH GRADE, UNLESS OTHERWISE SPECIFIED BY THE GEOTECHNICAL ENGINEER AND/OR THE BUILDING OFFICIAL. 13.PROVIDE 6 MIL 'VISQUEEN' VAPOR BARRIER UNDER ALL SLABS ON FILL (UNLESS OTHERWISE NOTED ON PLANS). 14.COLUMNS, BEAMS, WALLS OR ANY OTHER STRUCTURAL MEMBER PENETRATING SLABS ON FILL SHALL BE ISOLATED BY PRE-MOLDED JOINT FILLER (1/2" THICK) COMPLYING WITH ASTM D1752, TYPE 1. 15.TOPS OF FOOTINGS AND SLABS ON GRADE SHALL BE AS SHOWN ON PLANS WITH VERTICAL CHANGES AS INDICATED WITH STEPS IN THE FOOTINGS; LOCATIONS OF STEPS SHOWN AS APPROXIMATE AND SHALL BE COORDINATED WITH THE CIVIL GRADING PLANS TO ENSURE THAT THE EXTERIOR PERIMETER FOOTINGS BEAR NO LESS THAN 24 INCHES BELOW FINISH GRADE, OR AS OTHERWISE INDICATED BY THE GEOTECHNICAL ENGINEER OR BUILDING OFFICIAL. AB - ANCHOR BOLT AFF - ABOVE FINISHED FLOOR AHJ - AUTHORITY HAVING JURISDICTION ALT - ALTERNATE APPROX - APPROXIMATELY ARCH - ARCHITECT BOTT - BOTTOM BRG - BEARING CCCL - COASTAL CONST. CONTROL LINE CFS - COLD FORMED STEEL CMU - CONCRETE MASONRY UNIT COL - COLUMN CONC - CONCRETE CONT - CONTINUOUS D&E - DRILLED AND EPOXY DBL - DOUBLE DIA - DIAMETER DIM - DIMENSION DN - DOWN EA - EACH ELEV - ELEVATION/ELEVATOR ENGR - ENGINEER EW - EACH WAY E - EXISTING EXP - EXPANSION EXT - EXTERIOR FBC - FLORIDA BUILDING CODE FF - FINISH FLOOR FND - FOUNDATION FT - FEET/FOOT FTG - FOOTING ABBREVIATIONS HORIZ - HORIZONTAL IN - INCH/INCHES INT - INTERIOR MAS - MASONRY MAX - MAXIMUM MFR - MANUFACTURER MIN - MINIMUM MISC - MISCELLANEOUS MPH - MILES PER HOUR N - NEW NTS - NOT TO SCALE OC - ON CENTER PSF - POUNDS PER SQUARE FOOT PT - PRESSURE TREATED REV - REVISION/REVISED SPECS - SPECIFICATIONS SCHED - SCHEDULE SYP - SOUTHERN YELLOW PINE TYP - TYPICAL UNO - UNLESS NOTED OTHERWISE VERT - VERTICAL VIF - VERIFY IN FIELD W/- WITH W/O - WITHOUT WRB -WEATHER RESISTANT BARRIER WWF - WELDED WIRE FABRIC WWM - WELDED WIRE MESH #5 - STEEL REINFORCING BAR (REBAR) #5 (5/8") NOTE: THE ENGINEER HAS REVIEWED THE ABOVE COMPONENTS OR CLADDING AND HAS APPROVED THEIR USE IN THIS STRUCTURE. THESE PRODUCTS PROVIDE ADEQUATE RESISTANCE TO THE WIND LOADS AND FORCES SPECIFIED BY CURRENT CODE PROVISIONS. PRODUCT APPROVAL AFFIDAVIT FORM CATEGORY / SUBCATEGORY APPROVAL NUMBER(S)MANUFACTURER MODEL NUMBER BUILDING DESIGN PRESSURES (+PSF)(-PSF) PRODUCT DESIGN PRESSURES (+PSF)(-PSF) A. ROOFING PRODUCTS 1. METAL ROOF FL# 11651.13 2. UNDERLAYMENT FL# 5259-R28 N/A GULF COAST SUPPLY & MANUFACTURING, LLC.26 Ga. 5V CRIMP POLY GLASS USA, INC.POLYGLASS ROOF UNDERLAYMENTS N/A PER SCHEDULE -131 PER TABLE "A" 16.CONCRETE COVER FOR REINFORCING STEEL SHALL BE AS FOLLOWS: a.CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3” b.EXPOSED TO EARTH OR WEATHER: NO.5 AND SMALLER BARS 1 1/2” NO. 6 AND LARGER BARS 2” 17.NON-EXPANSIVE BACKFILL SHALL BE PLACED IN CONTROLLED LIFTS NOT TO EXCEED 12 INCHES AND SHALL BE COMPACTED TO AT LEAST 95% OF LABORATORY MAXIMUM DENSITY (ASTM D 1557). 18.AREA DRAINAGE SHALL BE DIRECTED AWAY FROM THE FOUNDATION. 19.GENERAL CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR SHORING, SHEETING AND BRACING OF EXCAVATIONS. 20.GENERAL CONTRACTOR SHALL INSTALL ALL PIPE SLEEVES, BOXED OPENINGS, ANCHOR BOLTS, ETC., AS REQUIRED FOR THE VARIOUS TRADES. WALL POCKETS TO RECEIVE BEAMS AND SLABS SHALL BE PROVIDED AS REQUIRED FOR THE SUPER-STRUCTURE. SHOP DRAWINGS SHOWING THE POSITION OF OPENINGS SHALL BE SUBMITTED TO THE CONTRACTING OFFICER PRIOR TO PLACEMENT OF CONCRETE. 21.LOCATE SAWCUTS PER PLAN OR IF NOT SHOWN ON PLANS COMPLY WITH ACI 224.3. 22.IN NO CASE SHALL TRUCKS, BULLDOZERS OR OTHER HEAVY EQUIPMENT BE PERMITTED CLOSER THAN 8'-0" FROM ANY FOUNDATION WALL UNLESS APPROVED BY ENGINEER. CONCRETE MASONRY 1.CONCRETE MASONRY WORK SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE REQUIREMENTS FOR MASONRY, AND REQUIREMENTS AND SPECIFICATIONS FOR MASONRY STRUCTURES ACI 530 / ASCE 6 (LATEST EDITION). 2.ALL MASONRY WORK SHALL CONFORM TO ACI 530/ASCE 6 STANDARDS, LATEST EDITION. 3.MOISTURE CONTENT OF BLOCKS SHALL NOT EXCEED 35% OF TOTAL ABSORPTION AT THE TIME OF PLACEMENT. 4.BLOCK UNITS SHALL CONFORM TO FLORIDA CONCRETE AND PRODUCTS ASSOCIATION SPECIFICATION "CM-1" . 5.MAXIMUM LINEAR SHRINKAGE FOR BLOCK UNITS USED FOR EXTERIOR WALL SHALL NOT EXCEED .04%. 6.CONCRETE MASONRY UNITS SHALL BE IN CONFORMANCE WITH ASTM C 90, GRADE N, TYPE II. MASONRY UNITS SHALL BE TESTED IN ACCORDANCE WITH ASTM C 140 AND SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 1900 PSI MINIMUM BASED ON THE NET CROSS SECTIONAL AREA. 7.TESTING TO BE DONE FOLLOWING ASTM C 140 "SAMPLING AND TESTING OF CONCRETE MASONRY UNITS". 8.USE ALL GROUT CONFORMING TO ASTM C 476 WITH A MIN. COMPRESSIVE STRENGTH OF 3000 PSI IN 28 DAYS, TESTED IN ACCORDANCE WITH ASTM C 39, COARSE TYPE WITH MAX. AGGREGATE SIZE OF 3/8" AND SLUMP OF 8" TO 11". TEST SAMPLES FOR COMPRESSIVE STRENGTH EVERY 30 YARDS OR EA DAY OF GROUTING. 2,800 PSI PUMP MIX READY MIX CONCRETE MADE WITH MAX. 3/8" AGGREGATE AND MAX. 9" SLUMP IS ACCEPTED ALTERNATE. NO ADMIXTURES WILL BE PERMITTED IN MORTAR. 9.GROUT FOR POURING SHALL BE A FLUID CONSISTENCY. 10.USE TYPE "M" MORTAR IN CONFORMANCE WITH ASTM C 270, AND ASTM C 780, TYPES (DO NOT USE MASONRY CEMENT). MORTAR SHALL BE FRESHLY PREPARED AND UNIFORMLY MIXED. 11.REMOVE MORTAR PROTRUDING INTO CELL CAVITIES THAT ARE TO BE REINFORCED AND GROUTED. ALLOW A MIN. OF 24 HOURS FOR MORTAR TO CURE BEFORE PLACING GROUT. 12.REINFORCING STEEL SHALL CONFORM TO ASTM A 615 GRADE 60, FY = 60,000 PSI. ALL SPLICES (LAPS) AND CORNER BARS SHALL BE MINIMUM 30 INCHES OR AS SHOWN ON DRAWINGS. EPOXY COATED BARS SHALL HAVE THEIR LAP LENGTHS 50% GREATER THAN THOSE SPECIFIED ABOVE. 13.USE PRESSURE-TREATED WOOD FOR ALL WOOD IN CONTACT WITH MASONRY. 14.DO NOT STACK MASONRY UNITS MORE THAN 2' -8" HIGH AND IN PALLETS OF 4'x4' MAXIMUM SURFACE AREA AND NO LESS THAN 8 FT. AWAY FROM EACH OTHER. 15.ALL UNITS TO BE LAID UP IN RUNNING BOND WITH CONCAVE COMPRESSED JOINTS UNLESS NOTED OTHERWISE. 16.HEAD AND BED JOINTS SHALL BE 3/8" THICK EXCEPT STARTING JOINT AT FOUNDATION WHICH SHALL BE 1/4" MINIMUM AND 3/4" MAXIMUM. ALL UNITS SHALL BE LAID WITH FULL MORTAR COVERAGE OF THE FACE SHELLS IN BOTH HORIZONTAL AND VERTICAL OR TRUSS. 17.INTERSECTING WALLS SHALL BE INTERLOCKED WITH RUNNING BOND. 18.18 GAUGE DOVETAIL ANCHORS (5~8" LONG) AND INSERTS SHALL BE USED EVERY 2ND BLOCK COURSE AT BLOCK-COLUMN INTERSECTIONS. 19.WHERE VERTICAL REINFORCEMENT IS REQUIRED PROVIDE ONE PIECE, NO SPLICES, CENTERED IN THE WALL UNLESS SPECIFICALLY DETAILED. OTHERWISE.PROVIDE VERTICAL SUPPORT SPACERS AT 200 REINFORCEMENT DIAMETERS MAXIMUM BUT NOT EXCEEDING 10 FEET. THE CONTRACTOR HAS THE OPTION TO USE ADDITIONAL LAP SPLICES FOR THE PLACEMENT OF THE VERTICAL REINFORCING. 20.VERTICAL CELLS TO BE FILLED SHALL HAVE VERTICAL ALIGNMENT SUFFICIENT TO MAINTAIN A CLEAR, UNOBSTRUCTED, CONTINUOUS VERTICAL CELL MEASURING NOT LESS THAN 3" AND HAVING A CLEAR AREA OF 10 SQUARE INCHES. 21.REINFORCING BARS REQUIRE A MINIMUM CLEAR DISTANCE OF 1/4" FOR FINE GROUT OR 1/2" FOR COURSE GROUT BETWEEN ANY MASONRY FACE. A MINIMUM 2" COVER FROM THE EXTERIOR FACE OF THE BLOCK TO THE REINFORCING INCLUDING GROUT SHALL ALSO BE OBSERVED. 22.FOR REINFORCING CONGESTION KNOCK OUT BLOCKS TO BE USED TO FACILITATE CONSTRUCTION. 23.ALL REINFORCING TERMINATING AT BOND BEAMS REQUIRE A STANDARD HOOK WITH AN EMBEDMENT OF 6" MIN. 24.USE MINIMUM 1 #5 IN FILLED CELL AT WALL INTERSECTIONS, EACH SIDE OF OPENINGS IN THE WALL AND AT THE ENDS OF WALLS UNLESS NOTED IN PLANS TO BE DIFFERENT. 25.ALL CELLS CONTAINING REINFORCING OR EMBEDDED ITEMS SHALL BE SOLID GROUTED. 26.CLEANOUT OPENINGS SHALL BE PROVIDED AT THE BOTTOM OF ALL CELLS TO BE FILLED IN EACH POUR OF GROUT WHERE SUCH GROUT POUR IS IN EXCESS OF 4 FEET IN HEIGHT. ANY OVERHANGING MORTAR OR OTHER OBSTRUCTION OR DEBRIS SHALL BE REMOVED FROM THE INSIDES OF SUCH CELL WALLS. THE CLEANOUTS SHALL BE SEALED BEFORE GROUTING, AFTER INSPECTION. 27.GROUT SHALL BE A CONTINUOUS OPERATION POURED IN LIFTS OF 8 FEET MAXIMUM HEIGHT. ALL GROUT SHALL BE CONSOLIDATED AT TIME OF POURING BY PUDDLING OR VIBRATION AND THEN RECONSOLIDATED AGAIN BY PUDDLING LATER, BEFORE PLASTICITY IS LOST. 28.WHEN TOTAL GROUT POUR EXCEEDS 8 FEET IN HEIGHT, THE GROUT SHALL BE PLACED IN FOUR FOOT LIFTS WITH NOT LESS THAN 30 MINUTES NOR MORE THAN ONE HOUR BETWEEN LIFTS. VIBRATE EACH LIFT AND RECONSOLIDATE PREVIOUS LIFT AFTER PLACING NEXT. 29.WHEN THE GROUTING IS STOPPED FOR ONE HOUR OR LONGER, HORIZONTAL CONSTRUCTION JOINTS SHALL BE FORMED BY STOPPING THE POUR OF GROUT NOT LESS THAN 1/2 INCH BELOW THE TOP OF THE UPPERMOST UNIT GROUTED. 30.UNITS WHICH ARE DISTURBED AFTER INITIAL BOND IS ACHIEVED MUST BE REMOVED AND RELAID WITH FRESH MORTAR TO ENSURE ADEQUATE BOND STRENGTH AND MINIMIZE THE LIKELIHOOD OF WATER PENETRATION INTO AN UNBONDED JOINT 31.CHASES AND RECESSES SHALL BE CONSTRUCTED AS MASONRY UNITS ARE LAID. MASONRY DIRECTLY ABOVE CHASES OR RECESSES WIDER THAN 12 INCHES SHALL BE SUPPORTED ON PRECAST GROUTED LINTELS. 32.PROVIDE PRECAST LINTELS OVER ALL OPENINGS IN MASONRY CONSTRUCTION UNLESS NOTED OTHERWISE IN PLAN. PROVIDE #5 BAR IN ALL LINTELS GROUTED SOLID AND SHALL HAVE 4" MINIMUM BEARING AT EACH END. FOR RECESSED LINTELS THE MINIMUM BEARING SHALL BE 8". 33.FOR SPECIAL INSPECTIONS THE ARCHITECT/ENGINEER SHALL BE GIVEN A MINIMUM 72 HOURS NOTICE PRIOR TO EACH REINFORCED BLOCK GROUTING OR CONCRETING OPERATION. 34.LINTELS MAY BE USED IN MASONRY OPENINGS UP TO 6' -6" CLEAR. THESE MAY BE PRE CAST OR CAST IN PLACE. THE LATTER SHALL BE 8" X 12" MINIMUM WITH 2 # 5 TOP AND BOTTOM, #3 TIES AT 12" AND SHALL BEAR 8” AT EACH SIDE OF OPENINGS. 35.ALL BEAMS NOT SCHEDULED ARE TIE BEAMS AND SHALL BE 8" X 12" MIN. WITH 2#5 LONGITUDINAL BARS TOP AND BOTTOM AND #3 TIES AT 24". AT CORNERS USE 2#5 TOP AND BOTTOM CORNERS BARS WITH 30" LEGS AND 4 #3 TIES AT 12" EACH SIDE. 36.ALL COLUMNS NOT SCHEDULED ARE TIE COLUMNS AND SHALL BE 8"X12" MIN. WITH 4 #5 VERTICAL BARS AND # 3 TIES AT 12" O.C. TIMBER AND PRE-ENGINEERED WOOD TRUSSES TIMBER AND PRE-ENGINEERED WOOD TRUSSES 1.ALL LUMBER SHALL MEET THE STANDARD OF QUALITY AS STATED IN FBC 2303. 2.ALL PRESERVATIVE TREATED WOOD REQUIRED TO BE TREATED PER CODE OR DRAWINGS SHALL BE IDENTIFIED BY THE QUALITY MARK OF AN INSPECTION AGENCY WHICH HAS BEEN APPROVED BY AN ACCREDITATION BODY WHICH COMPLIES WITH THE REQUIREMENTS OF THE AMERICAN LUMBER STANDARD COMMITTEE TREATED WOOD PROGRAM, OR EQUIVALENT. 3.ALL LUMBER SIZES NOTED AND SPECIFIED ON PLANS ARE NOMINAL SIZES UNLESS SPECIFICALLY INDICATED AS NET SIZE. 4.WOOD IN CONTACT WITH THE GROUND OR BELOW GROUND LEVEL SHALL BE NATURALLY DURABLE OR PRESERVATIVE-TREATED WOOD. 5.WOOD IN CONTACT WITH CONCRETE OR MASONRY SHALL BE NATURALLY DURABLE OR PRESERVATIVE-TREATED WOOD. 6.SUBMIT TRUSS SHOP DRAWINGS SIGNED AND SEALED BY AN ENGINEER REGISTERED IN THE STATE OF FLORIDA FOR REVIEW PRIOR TO FABRICATION. SHOP DRAWINGS SHALL INCLUDE TRUSS LAYOUT, DESIGN LOADS, TRUSS REACTIONS (DL & LL AND DL & WL) AND ALL OTHER INFORMATION REQUIRED FOR PROPER TRUSS INSTALLATION. DESIGN OF TRUSSES SHALL INCLUDE THE UPLIFT EFFECTS OF THE APPROPRIATE DESIGN WIND LOAD UTILIZING SHAPE FACTORS FROM THE FLORIDA BUILDING CODE. 7.TRUSS MEMBERS AND COMPONENTS SHALL NOT BE CUT, NOTCHED, DRILLED, SPLICED, OR OTHERWISE ALTERED IN ANY WAY WITHOUT THE WRITTEN APPROVAL OF THE S.E.R. ALTERATIONS RESULTING IN THE ADDITION OF LOADS TO ANY MEMBER (E.G. HVAC EQUIPMENT, WATER HEATER) SHALL NOT BE PERMITTED WITHOUT VERIFICATION THAT THE TRUSS IS CAPABLE OF SUPPORTING SUCH ADDITIONAL LOADING. 8.BORED HOLES NOT GREATER THAN 60 PERCENT OF THE WIDTH OF THE STUD ARE PERMITTED IN NONBEARING PARTITIONS OR IN ANY WALL WHERE EACH BORED STUD IS DOUBLED, PROVIDING NOT MORE THAN TWO SUCH SUCCESSIVE DOUBLE STUDS ARE BORED. IN NO CASE SHALL THE EDGE OF THE BORED HOLE BE NEARER THAN 5/8 INCH TO THE EDGE OF THE STUD. BORED HOLES SHALL NOT BE LOCATED AT THE SAME SECTION OF STUD AS A CUT OR NOTCH. 9.DESIGN CALCULATIONS FOR TRUSSES SHALL CLEARLY SHOW THE DESIGN LOADS FOR BOTH GRAVITY AND UPLIFT CONDITIONS. 10.ROOF PLYWOOD SHALL BE SPAN RATED STRUCTURAL SHEATHING, ATTACHED TO ROOF FRAMING WITH GALVANIZED RINGSHANK NAILS PER DRAWINGS. PROVIDE 1/8" SPACING AT PANEL EDGES AND END JOINTS UNLESS OTHERWISE NOTED. 11.PROVIDE TRUSS ANCHORS AT ALL RAFTER/TRUSS TO BEARING CONNECTIONS. ALL TRUSS TO TRUSS CONNECTORS AND TIE DOWNS ARE RESPONSIBILITY OF THE TRUSS MANUFACTURER. 12.ALL WOOD TRUSS TO MASONRY OR CONCRETE SHALL HAVE A MOISTURE BARRIER. 13.CHECK SCHEDULE AND/OR SECTIONS FOR VARIATIONS IN STRAPS. PROVIDE MULTIPLE OR SPECIFIC STRAPS AT TRUSS GIRDERS AND GABLE ENDS AS SHOWN ON PLANS. 14.ALL NAILS AND METAL HARDWARE EXPOSED TO THE WEATHER SHALL BE GALVANIZED OR COATED WITH AN APPROVED MATERIAL. ALL NAILS SHALL BE COMMON WIRE NAILS UNLESS NOTED OTHERWISE. SPACE NAILS IN STRAPS SO AS NOT TO SPLIT WOOD. 15.ALL STRUCTURAL ELEMENTS MUST BE S.P.F. GRADE 1, S. PINE GRADE 2 OR BETTER. SCOPE OF WORK: 1.ADD NEW SLAB AND ADDITION PER PLAN. 2.ADD FILLED CELLS TO EXISTING WALLS PER DETAIL. 3.ADD NEW WALLS PER PLAN. 4.ADD NEW TRUSSES PER PLAN & OVER FRAMING DETAIL. 5.NEW ROOFING TO BE INSTALLED PER PRODUCT APPROVAL. LOCATION PLAN SCALE: 3/32" = 1'-0" (E) GARAGE (E) OPEN PORCH (E) HOUSE PROPOSED ADDITION (E) PATIO AREA OF WORK 4'-0"2'-0"4'-0"2'-6"2'-0"4'-0"Rodolfo Villamizar, State of Florida Professional Engineer, License No. 61000 This item has been digitally signed and sealed by Rodolfo Villamizar, P.E. on the date adjacent to the seal using a SHA authentication code. Printed copies of this document are not considered signed and sealed and the SHA authentication code must be verified on any electronic copies.20-0128SHEET OF AS NOTED123456DATE: 20-0128 3HEERMANCE RESIDENCE122 Queen Catherina CourtRVAERRK20-01281835 - 20TH STREETVERO BEACH, FL 32960PH. (772) 569-0035FX. (772) 778-36177MAR 2020RODOLFO VILLAMIZAR FL. P.E.#61000 FT. PIERCEFLORIDAMELBOURNE, FL - PH (321) 253-1510FT. PIERCE, FL - PH (772) 468-9055MOIA BOWLES VILLAMIZAR & ASSOCIATESCONSULTING ENGINEERING CA #3728REVISIONSDATE06-16-202010-13-2020ODOLFVLIL No. 61000 STATE OF ROFL ADI RF O RP ISSE ANO INEEE N GL ENSECILROAM Z I A R PERMIT SETBLDG DEPT COMMENTS10-09-20LOCATION PLAN, ANDSTRUCTURAL NOTESS1 1 (E) HOUSE(N) GARBAGE AREA PROPOSED FOUNDATION PLAN SCALE: 1/4" = 1'-0" 6" THICK 3,000 PSI CONC. SLAB W/ #4 @ 18" O.C. E.W. ON TREATED COMPACTED SOIL S.O.G. EXISTING CMU WALL FILLED CELL W/ #5 VERT. 30" LAP SPLICE TYP. S.O.G. F-1 F-1F-1F-13 8" 24'-1" A 15'-0"8"1'-4"6'-10"6'-2"15'-0"1'-4"1'-4"8"5'-10"5'-10"B C D 8"8"6'-1"6'-4"(E) LOW WALL TO REMAIN VERIFY IN FIELD OR INSTALL PER DETAIL SEE WALL ANCHOR DETAIL, TYP. VERIFY IN FIELD OR INSTALL PER DETAIL SEE WALL ANCHOR DETAIL, TYP. SEE WALL ANCHOR DETAIL, TYP. VERIFY IN FIELD OR INSTALL PER DETAIL 41 7'-6"7'-9"7'-6"8"3'-0" 2 7'-7" 10'-7" (N) PATIO SEE LINTEL TO (E) COLUMN DETAIL 4" F-1 F-1 FOUNDATION SCHEDULE MARK F-1 W x D x L REINFORCEMENT (2) #5 BARS CONT. W/ #4 TIES @ 18" O.C. NOTES 18" X 16" X CONT. NORTH ELEVATION SCALE: 1/4" = 1'-0" 12 4 ELEV: 0'-0" FINISHED FLOOR ELEV: 8'-6" TOP OF (N) BEAM ELEV: 8'-0" TOP OF (E) WALL (N) METAL ROOF (E) STUCCO FINISH(N) STUCCO FINISH 5'-10"1'-4" 15'-0" 8"5'-10"1'-4"8"8"6'-1"6'-4" 2'-6" O/H 4'-0" O/H (N) CHIMNEY EAST ELEVATION SCALE: 1/4" = 1'-0" 12 4 ELEV: 8'-0" TOP OF (E) WALL ELEV: 0'-0" FINISHED FLOOR ELEV: 8'-6" TOP OF (N) BEAM (N) METAL ROOF (N) CHIMNEY (N) STUCCO FINISH (N) STUCCO FINISH (E) STUCCO FINISH(E) STUCCO FINISH 6'-6"1'-4" 24'-1" 8"7'-1"8"6'-6"1'-4"1'-4"6'-3"3'-0" 4'-0" O/H 4'-0" O/H SOUTH ELEVATION SCALE: 1/4" = 1'-0" 12 4 ELEV: 0'-0" FINISHED FLOOR ELEV: 8'-6" TOP OF (N) BEAM ELEV: 8'-0" TOP OF (E) WALL (N) CHIMNEY (N) METAL ROOF (N) STUCCO FINISH (E) STUCCO FINISH (E) STUCCO FINISH 5'-10"1'-4" 15'-0" 8"5'-10"1'-4" 2'-6" O/H #5 BAR VERT IN GROUTED CELL NEW EXIST CMU WALL EXISTING WALL ANCHOR DETAIL SCALE: 3/4" = 1'-0" #3 x 1'-0" DOWEL W/ STD. HOOK @ 16" O.C. VERT. IN MORTAR JOINTS, EPOXY ANCHOR 5" INTO EXISTING CMU VERIFY EXISTING FILLED CELL OR SAWCUT & REMOVE CMU FACE AND GROUT MONOLITHICALLY W/ NEW CELL TYPICAL FOOTING INTERSECTION DETAIL SCALE: 3/4" = 1'-0" CORNER PLAN AT PAD PERPENDICULAR SCALE: 3/4" = 1'-0" LINTEL DESIGNATION TYPICAL COLUMN TO FOUNDATION SECTION SCALE: 1/2" = 1'-0" FILLED CELL ON EXISTING WALL DETAIL SCALE: 1/2" = 1'-0" Rodolfo Villamizar, State of Florida Professional Engineer, License No. 61000 This item has been digitally signed and sealed by Rodolfo Villamizar, P.E. on the date adjacent to the seal using a SHA authentication code. Printed copies of this document are not considered signed and sealed and the SHA authentication code must be verified on any electronic copies.20-0128SHEET OF AS NOTED123456DATE: 20-0128 3HEERMANCE RESIDENCE122 Queen Catherina CourtRVAERRK20-01281835 - 20TH STREETVERO BEACH, FL 32960PH. (772) 569-0035FX. (772) 778-36177MAR 2020RODOLFO VILLAMIZAR FL. P.E.#61000 FT. PIERCEFLORIDAMELBOURNE, FL - PH (321) 253-1510FT. PIERCE, FL - PH (772) 468-9055MOIA BOWLES VILLAMIZAR & ASSOCIATESCONSULTING ENGINEERING CA #3728REVISIONSDATE06-16-202010-13-2020ODOLFVLIL No. 61000 STATE OF ROFL ADI RF O RP ISSE ANO INEEE N GL ENSECILROAM Z I A R PERMIT SETBLDG DEPT COMMENTS10-09-20PROPOSED FOUNDATIONPLAN, AND ELEVATIONSS2 1 1 BUILDING ROOF SHEATHING FASTENING SCHEDULE WITH 19/32" PLYWOOD SPACING REQUIRED FOR 8d GALV. RINGSHANK NAILS ZONE 1 ZONE 2 ZONE 3 ENCLOSED DESIGN PRESSURE ALLOWABLE DESIGN PRESSURE ULTIMATE * a = 4.0 FEET EDGE DISTANCE 6" O.C. @ EDGES 6" O.C. @ FIELD 3" O.C. @ EDGES 6" O.C. @ FIELD -36 PSF -60 PSF 3" O.C. @ EDGES 3" O.C. @ FIELD -83 PSF -137 PSF -113 PSF -188 PSF PROPOSED FRAMING PLAN SCALE: 1/4" = 1'-0" 3 A B 41 BM-1BM-1 BM-1 BM-1BM-1BM-1BM-1(E) ROOF P.E. TRUSSES @ 24" O.C. TYP. OVERFRAMING OVER (E) ROOF PER DETAIL ROOF SHEATHING PER FASTENING SCHEDULE BM-1 BM-1AA 4'-0" 4'-0"2'-6"2'-0" C SEE WALL STEP UP DETAIL D ROOF ZONES SCALE: 1/8" = 1'-0" 3 2 2 2 2 2 1 1 22 2 2 4.0 FTa = ENCLOSED 3 22 3 2 2 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 22 2 2 2 2 2 2 3 3 3 3 BEAM/LINTEL SCHEDULE MARK REINFORCEMENT / CONNECTIONTYPE NOTES BM-1 8F20 CMU LINTEL(1) #7 BAR @ TOP & (1) #5 BAR @ BOTTOM NOTES: 1.PROVIDE TRUSS CONNECTOR AT ENDS OF ALL TRUSSES. 2.TRUSSES WITH MULTIPLE STRAPS, CONNECTORS SHALL BE STAGGERED EACH SIDE OF TRUSS TO AVOID SPLITTING MEMBER. 3.TRUSS CONNECTORS AND CLIPS NOTED ON THIS LAYOUT ARE MODEL No.'S OF "SIMPSON STRONG-TIE", CONTRACTOR MAY SUBSTITUTE EQUAL STRAPS FROM ANOTHER MANUFACTURER. 4.TRUSS TO TRUSS CONNECTIONS ARE THE RESPONSIBILITY OF THE TRUSS MANUFACTURER. 5.PROVIDE TRUSS CONNECTORS IN ACCORDANCE WITH TRUSS LAYOUT FROM TRUSS MANUFACTURER. 6.STRAPS WERE SIZED TO SAFELY RESIST THE WIND REACTIONS SHOWN IN THE PRE-ENGINEERED TRUSS PROFILE AND PLACEMENT PLAN DWGS. CONNECTOR SCHEDULE TRUSS STRAP UP. MAX (LBS)FASTENERS NOTES MASONRY WALL TYPICAL HETA 20 1,810 (14) 10d x 11 2" TO TRUSS SP1 555 PER FIREPLACE DETAIL(6) 10d x 3" TO STUD & (4) 10d x 3" TO PLATE VGT 4,940 (16) 1 4" x 3" SDS TO GIRDER & (1) 5 8" ANCHOR W/ 3" MIN. EMBED.A VTCR 370 (4) 10d TO SUPPORTING FRAMING &(6) 10d x 11 2" TO TRUSS/RAFTER PER OVERFRAMING DETAIL MTS16 990 (14) 10d x 11 2"PER FIREPLACE DETAIL ELEVATION OF A TYPICAL MASONRY WALL SCALE: 1/2" = 1'-0" TYPICAL MASONRY ARCH OPENING SCALE: 1/2" = 1'-0" SCALE: 1/2" = 1'-0" OVERFRAMING TRUSSES DETAIL EXISTING CMU WALL TO TOP CHORD OF (E) TRUSSES PROVIDE ONE 2x6 P.T. W/ (2) 1/4"x4" LAG SCREWS SPACED @ 16" O.C. @ VALLEYS AND EVERY 4'-O" MAX. AND @ 8' O.C. MAX. VTCR AT EA END @ 24" O.C. MAX. OVERFRAME TRUSSES METAL FLASHING2x4 P.T. @ 24" O.C. MAX. STRUCTURAL SHEATHING PER SCHEDULE ROOF PER FLORIDA PRODUCT APPROVAL FIREPLACE DETAIL SCALE: 3/4" = 1'-0" SIMPSON SP1 @ EA. STUD STRUCTURAL SHEATHING TYPICAL ALL SIDES MTS16 @ EA/ CORNER CONNECT TO TOP CHORD GALV. FLASHING TRUSS PER PLAN 2x4's @ 16" O.C. 2x4 BLOCKING (3) 10d NAILS AS SHOWN TYP. STORM COLLAR GALV. FLASHING (E) ROOF RAFTER - TO REMAIN 2x6 P.T. ABOVE 2x4 P.T. TOP PLATE, TYP. P.E. WOOD TRUSSES @ 24" O.C. CHIMNEY PIPE TERMINATION CAP P.E. TRUSSES @ 24" O.C. STRUCTURAL SHEATHING PER SCHEDULE ROOF PER FLORIDA PRODUCT APPROVAL STRAP PER SCHEDULE FASCIA/DRIP EDGE TO MATCH SOFFIT 1/2" CDX PLYWOOD SOFFIT W/ 8d RINGSHANK NAILS @ 6" O.C. WALL STEP UP DETAIL SCALE: 1/2" = 1'-0" (E) 2x10's (E) CMU WALL (N) 1 2" THREADED ROD @ 12" O.C. MAX. THRU (2) 2x6 P.T. OVER (E) 2x10's & 6" MIN. EPOXY INTO (E) CMU WALL ELEV: 9'-0" ELEV: 8'-0" Rodolfo Villamizar, State of Florida Professional Engineer, License No. 61000 This item has been digitally signed and sealed by Rodolfo Villamizar, P.E. on the date adjacent to the seal using a SHA authentication code. Printed copies of this document are not considered signed and sealed and the SHA authentication code must be verified on any electronic copies.20-0128SHEET OF AS NOTED123456DATE: 20-0128 3HEERMANCE RESIDENCE122 Queen Catherina CourtRVAERRK20-01281835 - 20TH STREETVERO BEACH, FL 32960PH. (772) 569-0035FX. (772) 778-36177MAR 2020RODOLFO VILLAMIZAR FL. P.E.#61000 FT. PIERCEFLORIDAMELBOURNE, FL - PH (321) 253-1510FT. PIERCE, FL - PH (772) 468-9055MOIA BOWLES VILLAMIZAR & ASSOCIATESCONSULTING ENGINEERING CA #3728REVISIONSDATE06-16-202010-13-2020ODOLFVLIL No. 61000 STATE OF ROFL ADI RF O RP ISSE ANO INEEE N GL ENSECILROAM Z I A R PERMIT SETBLDG DEPT COMMENTS10-09-20PROPOSED FRAMING PLAN,ROOF ZONES,AND ELEVATIONSS3 1 1 1