Manual S Compliance Report
Job:
Lot37Block50-7lndian...
—AI R
Date:
12.29.08
7,XHWIMc•AIR CORDMON111G
Entire House
By:
KDAVIS
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM
Project Information
For: ADAMS HOMES APR � 3 2020
5213 Birch Drive, Fort Pierce, FL 34982
Permitting Department
St, Lucie County
♦ • ling Equi •
Design Conditions
Outdoor design DB: 90.4°F
Sensible gain: 26881 Btuh
Outdoor design WB: 77.4°F
Latent gain: 4815 Btuh
Indoor design DB: 75.0°F
Total gain: 31696 Btuh
Indoor RH: 50%
Estimated airflow: 1167 cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: SplitASHP
Manufacturer: Carrier
Model: 25HBC537A0030+FX4DNB037L
Actual airflow: 1167 cfm
Sensible capacity: 28314 Btuh
105% of load
Latent capacity: 5054 Btuh
105% of load
Total capacity: 33368 Btuh
105% of load SHR: 85%
Heating Equipment
Design Conditions
Entering coil DB: 76.7°F
Entering coil WB: 63.3°F
Outdoor design DB: 41.0°F Heat loss: 25070 Btuh Entering coil DB: 69.4°F
,Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split ASHP
Manufacturer: Carrier Model: 25HBC537A0030+FX4DNB037L
Actual airflow: 1167 cfm
Output capacity: 31719 Btuh 127% of load Capacity balance: 33 OF
Supplemental heat required: 0 Btuh Economic balance: -99 OF
Backup equipment type: Elec strip
Manufacturer: Model:
Actual airflow: 1167 cfm
Output capacity: 7.1 kW 96 of load Temp. rise: 19 OF
Meets all requirements of ACCA Manual S. 1'1
4e Co;,y
- wrightsoftm 2020-Feb-1210:23:03
JCCX M •t• o• • A.•�.ry�mwM Right -Suite® Universal 2019 19.0.12 RSU23828 Page 1
...10AGL\Lot37Blk50-7lndianRiverEstates2010AGL.rup Calc = MJ8 Front Door faces: E
DEL-AIR
REA7IRG-MRCONOmOMNG
Component Constructions
Entire House
Job:
Date:
By:
L ot
37.B...
122908 .29.08 ock50-7Indian
M.DAVIS
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM
•Ilect intormation
For: ADAMS HOMES
5213 Birch Drive, Fort Pierce, FL 34982
Design
Condition's
Location:
Indoor:
Heating
Cooling
St Lucie Co Intl, FL, US
Indoor temperature (OF)
70
75
Elevation: 26 ft
Design TD (OF)
29
15
Latitude: 280N
Relative humidity (%)
30
50
Outdoor: Heating
Cooling
Moisture difference (gr/lb)
2.4
56.9
Dry bulb (IF) 41
90
Infiltration:
Daily range (°F) -
15 ( L
) Method
Simplified
Wet bulb (°F) -
77
Construction quality
Average
Wind speed (mph) 15.0
7.5
Fireplaces
0
Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain
ft' Btu h/ft�- °F ft' °F/Btuh BtuhM Btu BluhM Btu
Walls
Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh
Partitions
12C-Osw: Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board
int fnsh, 2"x4" wood frm, 16" o.c. stud
n 283
6.143
4.1
4.15
1175
2.59
733
e 184
0.143
4.1
4.15
765
2.59
477
s 272
0.143
4.1
4.15
1127
2.59
703
w 348
0.143
4.1
4.15
1445
2.59
902
all 1088
0.143
4.1
4.15
4511
2.59
2816
164
0.091
13.0
2.64
433
1.31
215
Windows
2A-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap, n
1/8" thk; NFRC rated (SHGC=0.23);.50% drapes, medium; 1.3 ft
overhang (2.17 ft window ht, 0.9 ft sep.); 6.67 ft head ht
2A-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap, e
1/8" thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1.3 ft
overhang (5.3 ft window ht, 0.9 ft sep.); 6.67 ft head ht
2A-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap, e
1/8" thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 7.33 ft
overhang (5.3 ft window ht, 0.9 ft sep.); 6.67 ft head ht
2A-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap, s
1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.3 ft w
overhang (5.3 ft window ht, 0.9 ft sep.); 6.67 ft head ht all
1013-v: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, w
1/8" thk; NFRC rated (SHGC=0.70); 11.5 ft overhang (6.7 It window ht,
1 ft sep.); 6.67 ft head ht
2A-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low-e innr, 1/4" gap, w
1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 11.5 ft
overhang (5.3 ft window ht, 0.9 ft sep.); 6.67 ft head ht
5
0.330
0
9.57
45
8.52
40
33
0.330
0
9.57
313
21.2
692
47
0.330
0
9.57
448
8.52
399
16
0.330
0
9.57
156
8.52
139
49
0.330
0
9.57
469
22.7
1113
65
0.330
0
9.57
626
19.2
1252
18
0.550
0
16.0
285
16.2
289
33
0.330
0
9.57
313
8.52
279
-.1 -Pk wr ghtsaft. 2020-Feb-12 10:23:03
C% .r•, .. w..., ., Right -Suite® Universal 2019 19.0.12 RSU23828 Page 1
...10AGL\Lot378lk50-7lndianRiverEstates2010AGL.rup Calc = MJ8 Front Door faces: E
f
Doors I
11JO: Door, mtl fbrgl type
Ceilings
16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2"
gypsum board int fnsh
Floors
22A-tpl: Bg floor, light dry soil, on grade depth
e 20
0.600
6.3
17.4
350
17.6
353
2137
0.032
30.0
0.93
1983
1.69
3611
163
0.989
0
28.7
4687
0
0
1 _rk wrightsofitl 2020-Feb-1210:23:03
,436A .t-, ,.x.�,« .,.,., Right -Suite® Universal 2019 19.0.12 RSU23828 Page 2
... 10AGL\Lot37Blk50-7lndianRiverEstates2010AGL.rup Calc = MJ8 Front Door faces: E
DEL -AIR Project Summary Job: Lot 37Block 50-7Indian
...
6 Y Date: 12.29.08
lxllnnns•ton conomonuao Entire House By: M.DAVIS
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM
Project• •
For: ADAMS HOMES
5213 Birch Drive, Fort Pierce, FL 34982
Notes: RVSD 11.15.10 JB
8-19-15 JA
L. S. 2-12-20 VWK
Design Information
Weather
Winter Design Conditions
Outside db
41
OF
Inside db
70
OF
Design TD
29
OF
Heating Summary
Structure
16950
Btuh
Ducts
8119
Btuh
Central vent (0 cfm)
0
Btuh
(none)
Humidification
0
Btuh
Piping
0
Btuh
Equipment load
25070
Btuh
Infiltration
Method
Construction quality
Fireplaces
St Lucie Co Intl, FL, US
Simplified
Average
0
Heatin Coolin
Area (ft2) 201� 201�
Volume (ft3) 17400 17400
Air changes/hour 0.32 0.16
Equiv. AVF (cfm) 93 46
Heating Equipment Summary
Make Carrier
Trade CARRIER
Model 25H BC537AO030
AHRI ref 10487322
Efficiency
Heating input
Heating output
Temperature rise
Actual air flow
Air flow factor
Static pressure
Space thermostat
Capacity balance point = 33 OF
Backup:
8.5 HSPF
34600
Btuh @ 470F
27
OF
1167
cfm
0.047
cfm/Btuh
0.30
in H2O
Input = 7 kW, Output = 24078 Btuh, 100 AFUE
Summer Design Conditions
Outside db
90
OF
Inside db
75
OF
Design TD
15
OF
Daily range
L
Relative humidity
50
%
Moisture difference
57
gr/lb
Sensible Cooling Equipment Load Sizing
Structure
16981
Btuh
Ducts
9900
Btuh
Central vent (0 cfm)
0
Btuh
( none)
Blower
0
Btuh
Use manufacturer's data
Rate/swing multiplier
y
1.00
Equipment sensible load
26881
Btuh
Latent Cooling Equipment Load Sizing
Structure
2593
Btuh
Ducts
2222
Btuh
Central vent (0 cfm)
0
Btuh
(pone)
Equipment latent load
4815
Btuh
Equipment Total Load (Sen+Lat)
31696
Btuh
Req. total capacity at 0.75 SHR
3.0
ton
Cooling Equipment Summary
Make Carrier
Trade CARRIER
Cond 25HBC537AO030
Coil FX4DNB037L
AHRI ref 10487322
Efficiency 12.5 EER, 15.5
SEER
Sensible cooling
26250
Btuh
Latent cooling
8750
Btuh
Total cooling
35000
Btuh
Actual air flow
1167
cfm
Air flow factor
0.043
cfm/Btuh
Static pressure
0.30
in H2O
Load sensible heat ratio
0.85
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wrightsoft- 2020-Feb-12 10:23:03
% Right -Suite@ Universal 2019 19.0.12 RSU23828 Page 1
..10AGL1Lot37Blk50-7lndianRiverEstates2010AGL.rup Calc = MJ8 Front Door faces: E
DEL --AIR Right-M Worksheet
19MG • am eoxnmoxNr Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM
Job: Lot 37 Block 50-7 Indian Riv...
Date: 12.29.08
By: KDAVIS
1
Room name
Entire House
M. BATH
2
Exposed wall
163.4 It
13.5 ft
3
Room height
8.6 It d
8.0 ft heat/cool
4
Room dimensions
1.0 x 146.3 It
5
Room area
2016.0 ft2
146.3 ft2
Ty
Construction
U-value
Or
HTM
Area (ft2)
Load
Area (112)
Load
number
(Btuh/ft2°F)
(Btuh/ft2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
Vjl
$Ik wall stucco ext`
�2A
0143
n `:
415
2.59
288
283
a s ` 11 ,5
733
36
31
130
--j-,.
81
! . _. G
2ov_
Q 330
n
_ .=�._9:57
8.52
>5
. w_ . _Q
5
.. 40
�_ _.__5._.
_� 40
W
Blk wall, stucco ext
0.143
a
4.15
2.59
284
184
765
477
0
0
0
0
2A-20v
0.330
a
9.57
21.17
33
1
313
692
0
0
0
0
11
2A-2ov
0.330
a
9.57
8.52
47
46
448
399
0
0
0
0
D
11J0
0 600
a
17.40
17.58
20
20
350
353
0
0
0
0
W
Blk wall stucco ext
0143
s:T
4 15
2.58
288
272
1127
_ 703
0
" 0
_
0
0
_
139
Blk wall, stucco ext
10C-v
0.143
0.550
w
w
4.15
15.95
2.59
16.20
448
18
348
18
1445
285
902
289
72
0
72
0
299
0
186
0
2A-2ov
0.330
w
9.57
22.70
49
2
469
1113
0
0
0
0
2A 2ov..
0.330
w
9.57
8.52
33
33
313
0
0
0
_ .
F0
2'64
_ _w 1 31
:.r>164
_- . _
.. 16¢
_._ . 433
-. _ ,t279
.: .._215
,
.:._.9
R . r_0
. _ _.._
_
C -
166 30ad
_ _ 0.032
-,.
_ 0.93
1.69
2137
2137
1983
3611
146
146
136
247
F
�':22A tpl _.�
_ �Q989
ate,
_ 28.88
.,0:00
_v_.w2016
__-. 163
_
, �,:�.4687
,w
v ..R 0
_ _ _146
=_ 14
__,_ _387
_u._�_..zQ
._..«.
..r _....
7-.-a. ..�__..
...;.
-
.
_
_
6
c) AED excursion
1430
-27
Envelope loss/gain
13993
11376
996
527
12
a) Infiltration
2958
785
244
65
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants Qa 230
4
920
0
0
Appliances/other
3900
0
Subtotal (lines 6 to 13)
16950
16981
1240
592
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
16950
16981
1240
592
15
Duct loads
48%
58%
8119
9900
48%
58%
594
345
Total room load
25070
26881
1835
937
Air required (cfm)
1167
1167
85
41
Calculations approved by ACCA to meet all reauirements of Manual J 8th Ed.
-*_ wrigF�tsoft^ 2020-Feb-1210:23:03
�A "'"'-"' ' '"-`•` m Right -Suite® Universal 2019 19.0.12 RSU23828 Page 1
..10AGL\Lot37Blk50-7lndianRiverEstates2010AGL.rup Calc = MJ8 Front Door faces: E
• DEL -AIR Right-M Worksheet
M'°°°'M°°M"'°M° Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM
Job: Lot 37 Block 50-7 Indian Riv..
Date: 12.29.08
By: M.DAVIS
1
Room name
M. BDRM
M. WC
2
Exposed wall
30.5 It
10.0 ft
3
Room height
8.0 It heat/cool
8.0 ft heat/cool
4
Room dimensions
12.5 x 18.0 ft
3.5 x 6.5 ft
5
Room area
225.0 ft2
22.8 ft2
TY
Construction
U-value
Or
HTM
Area (ft2)
Load
Area (ft2)
Load
number
(Btuh/ft2-0F)
(Btuh/ft2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
o.e415
916
373
52
52
216
135
.2A 2ov a �b_ w
0, 330
_ _n:..:
9 57
8:52
_. `0
_.:_0
W
Blk wall, stucco ext
0.143
e
4.15
2.59
100
67
279
174
0
0
0
0
2A-2ov
0.330
a
9.57
21.17
33
1
313
692
0
0
0
0
11
2A-2ov
0.330
a
9.57
8.52
0
0
0
0
0
0
0
0
D
11JO
0600
a
1740
1758
0
0
0
0
0
0
0
0
W
Blk wall stucco -ext'--
70
0
0
0
0
0
0
a -G..2A
2oLr _. �_
_,. A 330
w
? 9 57
$`52
. -_-0
_ _a.__.: _ 0
,.rw :� 0
_ _e 0
_ _N_. __R
A
� .._.,��Q
_4
Blk wall, stucco ext
10C-v
0.143
0.550
w
w
4.15
15.95
2.59
16.20
0
0
0
0
0
0
0
0
28
0
28
0
116
0
72
0
2A-2ov
0.330
w
9.57
22.70
0
0
0
0
0
0
0
0
2A 2ov
0.330
w
9.57
8.52
0
0
0
0
0.
0_
0
ro
-0swsy.�
° .0 091
.�
_ _Z 6i
_a. 1 31�
.... .,_0
M 'I' �..0
0
_- � 0
-7- . ..,.Q
.,._-_ _� Q
.�._ . 0
_0
� Q
C
166 30ad
0.032
0.93
1.69
225
225
209
380
23
23
21
38
_
_l 04
_
. _.
v 0
777-7
7-
1-7
.,
.>....
....__
-wi._ _
...., r
.y.-.._.
_
_.__
_...._._......
6
c) AED excursion
87
-13
Envelope loss/gain
2273
1706
640
233
12
a) Infiltration
552
146
181
48
b) Room ventilation
0
0
0
.0
13
Internal gains: Occupants @ 230
1
230
0
0
Appliances/other
600
0
Subtotal (lines 6 to 13)
2824
2683
1821
281
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
2824
2683
821
281
15
Duct loads
48%
58%
1353
1564
48%
58%
393
164
Total room load
4177
4247
1
1214
444
Air required (cfm)
194
184
56
19
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
C •-rk- 2020-Feb-1210:23:03
Right -Suite® Universal 2019 19.0.12 RSU23828 Page 2
... 10AGL\Lot37Blk50-7lndianRiverEstates2010AGL.rup Calc = MJ8 Front Door faces: E
PDEL-AIR Right-J@WOrksheet Job: Lot 37Block 50-7Indian Riv...
19MG-nmconnmormmo Entire House Date: 12.29.08
By: M.DAVIS
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM
1
Room name
M. OWIC
M. IWIC.
2
Exposed wall
7.0 ft
0 ft
3
Room height
8.0 ft heat/cool
8.0 ft heat/cool
4
Room dimensions
4.0 x 7.0 ft
4.0 x 7.0 ft
5
Room area
28.0 ft2
28.0 ft2
Ty
Construction
U-value
Or
HTM '
Area (W)
Load
Area (ft2)
Load
number
(Btuh/ft--F)
(Btuh/ftz)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
Blk wall stucco ext .
0143
n'
415
2 59
56
56
m 232
145
0
_,!—C
:2A_29v - , ._.
_,�_.w 0 330
ri
�_ 9 57_
__8 52
w_0
v . _w 0
�0 Q.
_. _._0
_ µ. _..._ _0
w. �Q
`0
11
Blk wall, stucco ext
2A-20v
0.143
0.330
e_
a
4.15
9.57
2.59
21.17
0
0
0
0
0
0
0
6
0
0
0
6
�_
0
0
_0
0
0
2A-2ov
0.330
a
9.57
8.52
0
0
0
0
0
0
0
0
11J0
0600
a
1740
1758
0
0
0
0
0
0
0
0
Blk wall stucCO ext
0143
s
4 15
` r 2. 59
6
0
0
0
0
0
_.0
_
.r _-0
�.v -0
_
_ _ �.P_
Blk wall, stucco ext
10C-v
0.143
0.550
w
w
4.15
15.95
2.59
16.20
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
2A-2ov
0.330
w
9.57
22.70
0
0
0
0
0
0
0
0
2A 2ov
0.330
w
9.57
8.52
0
0
0
0
0
0,
0
0
P..�.�.;12COsw°
w_:
_.� 0091,
_ 2.64.
.�_1 1;
?
0-
E� .0_
0
C
1 BB 30ad
0.032
_
0.93
1.69
28
28
26
47
28
28
26
47
=�_7
. n .._ „n
.;.. ., e...:.-+.. .-.-.-.s-.+ w'.:. .
4, c.c.. t:_.,.. A.
..v., ,..
._ �... _:._.
..«. ✓a n ......
-.. _.^.,-.. a...:r:.c
..t., .:�:. .« J
....c. r...`�...-...
.-.: .... . _.�
..... ....r ....
..._... ...
_....,._._
-
....._.., �,.
o
6
c) AED excursion
-10
-2
Envelope loss/gain
459
182
26
45
12
a) Infiltration
127
34
0
0
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
0
0
Appliances/other
0
0
Subtotal (lines 6 to 13)
586
216
26
45
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
586
216
26
45
15
Duct loads
48%
58%
281
126
48%
58%
12
26
Total room load
866
342
1
38
72
Air required (cfm)
40
15
2
3
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
- -*- wrigtit�so � 2020-Feb-12 10:23:03
Right -Suite® Universal 2019 19.0.12 RSU23828 Page 3
...10AGL1Lot37Blk50-7lndianRiverEstates2010AGL.rup Calc = MJ8 Front Door faces: E
DEL --AIR
19=
Right-JO Worksheet
Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM
Job: Lot 37 Block 50-7 Indian Riv...
Date: 12.29.08
By: M.DAVIS
1
Room name
STUDY
FOYER/DINING
2
Exposed wall
10.0 ft
13.0 ft
3
Room height
8.0 ft heat/cool
8.0 It heat/cool
4
5
Room dimensions
Room area
10.0 x 12.0 ft
120.0 ft2
14.0 x 12.0 it
168.0 ftz
Ty
Construction
U-value
Or
HTM
Area (ftz)
Load
Area (ftz)
Load
number
(Btuh/ftZ°F)
(BtuMl:2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
y/
_�-G
Blk wall stucco sxt
:2A 2ov_---._ F ._�.,
Blk wall, stucco ext
0143
--.-.__0330
0.143
n
n .
a
4 15
__ _ 9:57_
4.15
2.59
-8.52
2.59
0
__ __
' 0
__� 0
57
0
._.-�
235
. ___ _ 0
_.-:_.t0
146
O
_-_--.-0
104
-0
60
251
157
80
11
D
y/
,L-G
2A-2ov
2A-2ov
11J0
Blk wall `stuccaext
.2A.2ov..____
Blk wall, stucco ext
10C-v
0.330
0.330
0.600
0,143
-_._ 0,330-
0.
0.550 550
a
a
a
s ,
s,-.
w
w
9.57
9.57
17.40
21.17
8.52
17.58
2 59
2.
16.2020
0
23
0
0
__a__..___0
0
0
0
23
0
0
____...,__0
0
0
0
224
0
0
199
0
0
0
0
23
20
0
0
0
23
_ _ 200
0
0
0
224
. 3500
0
0
0
199
3533
0
0
4. 5
_-:957.__._852
4.
15.95 95
0
_.,_, ...___0'm-
0
0
2A-2ov
2A 2ov
0.330
_. , 0.330
0.091
w
w
m.,
___
9.57
9.57
_.__.2.64
22.70
8.52
_
1.31.
0
0
0
0
0
_._v0
0
0_
._._-_--_0
0
_,, __ 0
- 0
0
_ 0
. 8
0
0
_ __...__-8
0
__ 0
-_�21_
0
0
C _
161330ad _
_ _0.032
-8.68,
__ 0,00
, ___._120
._ 10
;_v::287
0
. - 168
--- 13
L
6
c) AED excursion
-40
-57
Envelope loss/gain
857
509
1374
946
12
a) Infiltration
181
48
235
62
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
1
230
Appliances/other
300
0
Subtotal (lines 6 to 13)
1038
857
1610
1239
Less external load
0
0
0
0
14
Less transfer
Redistribution
Subtotal
0
0
1038
0
0
857
0
0
1610
0
0
1239
151
Duct loads
48%
58%
497
500
48%
58%
771
722
Total room load
Air required (cfm)
171
1535
1357
59
2381
111
1961
85
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
- wrigl�tsoft� Right -Suite® Universal 2019 19.0.12 RSU23828 2020-Feb-1210:23:03Page 4
...10AGL\Lot37Blk50-7lndianRiverEstates2010AGL.rup Calc = MJ8 Front Door faces: E
DEL --AIR Right-J® Worksheet
n=C.-AMCOND` OMHO Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM
Job: Lot 37 Block 50-7 Indian Riv...
Date: 12.29.08
By: M.DAVIS
1
Room name
LIVING
KITCHEN/NOOK
2
Exposed wall
17.0 ft
13.0 ft
3
Room height
9.6 ft heat/cool
9.9 ft heat/cool
4
Room dimensions
1.0 x 484.5 ft
1.0 x 258.0 ft
5
Room area
484.5 ft'
258.0 ftz
Ty
Construction
U-value
Or
HTM
Area (ftz)
Load
Area (ftz)
Load
number
(Btuh/ftZ°F)
(Btuh/ftz)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
Blk wall stucco ext -
0.143
ri ':
is 0
O
F 0
0
2A2ov.w
Q.380
_n»;
_ 9,57
_ 8,52
__.a _ 0
__._ _0
._ -_ ; 0
w. _0
- �__...0.
_ 0
Blk wall, stucco ext
0.143
a
4.15
2.59
0
0
0
0
0
0
0
0
2A-2ov
0.330
a
9.57
21.17
0
0
0
0
0
0
0
0
11
2A-2ov
0.330
a
9.57
8.52
0
0
0
0
0
0
0
0
11 JO
0.600
a
17.40
17.58
0
0
0
0
0
0
0
0
Blk wall stucco ext
D-143
s`
415'
2 59
0
0
0
0
0
0.
0
0;
330
_�s�
9 57:
8.52
. m
222
285
Blk wall, stucco ext
10C-v
0.143
0.550
w
w
4.15
15.95
2.59
16.20
136
0
103
0
428
0
267
0
104
18
53
18
138
289
2A-2ov
0.330
w
9.57
22.70
0
0
0
0
33
1
313
742
2A-2ov
0.330
w
9.57
8.52
33
33
313
279
0
0
0
0
P .,
',72Cosw.__A091
_
_
. >
264
.w_131'
0
_- »0
0
_ µ
9
_
0
�283
_
C
16B-30ad
0.032
0.93
1.69
559
559
519
944
305
305
515
Q.989
w
485
... _17
.. .488
x _ _0
' .,...� 2`v8
..v1.$
3J3
.
0.
,...... ,w;.:.
.:.. ..... :a...'r ........:_._..
_ u....x..w .....-..<
,... a '::.,..
.._d..=...«.�.-:
1 n,�x..d.
r....... �..-,,.a..
.<.,:
w
.,-...u....a
........-. s....-
.....�.....--
p.
..
...
N ...
r.
..
..r...w
,.mom,._.-.-.
..... »....,,
,_ ••,:
._. .. „..'.J,._..,.a.....,-
-•
-
. u_w'..._
...+,..... _
..... .
.rein
...._...,...
�.. _-,., ..
...`.�...
_..�._..._J
... .......-v ...._
.a
.0 ....
,.aw-.., .... m.. .v..... ..-...
�....a..r.-
...
m�..,_.�
_ _,.
. ,.a_
.,»�..,.,..
�......... ..c..
-77
.._........
d' ... .em
.».�,<. .+.
L4r.1-.......,.
......_._..
.__ ,.
.a...... ....t.+1..e..,... ...
_.,.,.. .a_._
W.
.__s.....a.
__._ ..
_.t _....
b.._ ...-.
u.. a.m. ,)......._.
....._,... ...
........ ......_
_. .. �>
_...r, c. .w.
-.w .�..,
.._ . � <..<.�' ,, ..-«__s ...":-....
.a ..,.-.. ... �::..5...,....�-
:
,.
..�.. e. n::.
..., exr ..-.:a
..
- � trtw... ..
...... ... ::..
..- n......�.........
...;L�..-... ...
-...:. ...-.�.....w.e,
w ...
.v _..«.
. - ,_ ,.. u
6
c) AED excursion
486
968
Envelope loss/gain
1747
1977
1475
2653
12
a) Infiltration
308
82
235
62
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
2
460
0
0
Appliances/other
600
1200
Subtotal (lines 6 to 13)
2055
3118
1710
3916
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
2055
3118
1710
3916
15
Duct loads 1
48%
58%1
984
1818
48%1
589/6
8191
2283
Total room load
3039
4936
2530
6199
Air required (cfm)
141
214
118
269
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
-f'}►- wrYgt�tsoPt� 2020-Feb-12 10:23:03
�e� """'-"' ^""'-^ Right -Suite® Universal 2019 19.0.12 RSU23828 Page 5
..10AGL\Lot37Blk50-7lndianRiverEstates2010AGL.rup Calc = MJ8 Front Door faces: E
DEL Ali
Right-JO Worksheet
Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM
Job: Lot 37 Block 50-7 Indian Riv...
Date: 12.29.08
By: M.DAVIS
1
Room name
UTIL
BDRM 3
2
Exposed wall
0 ft
14.9 ft
3
Room height
8.0 ft heat/cool
8.0 It heat/cool
4
Room dimensions
6.0 x 12.0 ft
1.0 x 198.0 ft
5
Room area
72.0 ft2
198.0 ft2
Ty
Construction
U-value
Or
HTM
Area (ft2)
Load
Area (ft2)
Load
number
(Btuh/ftZ°F)
(Btuh/ft2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
Blk wall stucco ext
A.143
n
415
2:59
Blk wall, stucco ext
0.143
n,_:i
a
w,.._.9.57..._.._:8.52
4.15
2.59
_.. _ ,_.�0
0
:. _0
0
.._.__w.;..__0
0
.._0
0
_ _ ._0
0
_._. __.... 0
0
_ __.._. 0
0
___ _ _.'0
0
2A-2ov
0.330
a
9.57
21.17
0
0
0
0
0
0
0
0
11
2A-2ov
0.330
a
9.57
8.52
0
0
0
0
0
0
0
0
D
11J0
0600
a
1740
1758
0
0
0
0
0
0
0
0
U�/
BIk wall stucco ext
0 143
s
415
2 59
0
0
0
ry 0
120
104
Y 430
2613
5.
_.9 57:
,__ 8 52
0
_._ _ , _0
_.,_:. _0
w_ 0,
_., 16
.� ? 6
,' _ _... _156
BIk wall, stucco ext
10C-v
0.143
0.550
w
w
4.15
15.95
2.59
16.20
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
2A-2ov
0.330
w
9.57
22.70
0
0
0
0
0
0
0
0
2A-2ov
0.330
w
9.57
8.52
0
0
0
0
0
0
0
0
12C.Osw _ _,_ _ `;_._
_ Q.091
_..
. 2 64.._..r-1
31
48
_ ___ 's 4$
_ . _ 127
r. _.e _-_ 83
------ 108
_ r _. u 10$
_ ,.. 285
.__...: 142
C
1613-30ad
0.032
0.93
1.69
72
72
67
122
198
198
184
335
_198
. .__ ._ 15
_ 428.
_.
""
r:
..
..
6
c) AED excursion
-35
-56
Envelope loss/gain
193
150
1483
828
12
a) Infiltration
0
0
271
72
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
0
0
Appliances/other
600
300
Subtotal (lines 6 to 13)
193
750
1754
1200
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
193
750
1754
1200
151
Duct loads
48 %
58 %
93
437
48%
58%1
840
700
Total room load
286
1187
2594
1900
Air required (cfm)
13
521
121
82
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
-P}&- 2020-Feb-1210:23:03
CA Right -Suite® Universal 2019 19.0.12 RSU23828 Page 6
...10AGL\Lot37Blk5O-7lndianRiverEstates2010AGL.rup Calc = MJ8 Front Door faces: E
DEL --AIR Right-JO Worksheet
'1 N4' °01 C0M0m0N1 N° Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM
Job: Lot 37 Block 50-7 Indian Riv...
Date: 12.29.08
By: KDAVIS
1
Room name
BATH
BDRM 2
2
Exposed wall
6.0 ft
28.5 it
3
Room height
8.0 it heat/cool
8.0 It heat/cool
4
Room dimensions
10.5 x 6.0 ft
13.5 x 15.0 ft
5
Room area
63.0 ft2
202.5 ft2
Ty
Construction
U-value
Or
HTM
Area (ft2)
Load
Area (ftz)
Load
number
(Btuh/ftz°F)
(Btuh/ft2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
cool
6
Blk wall stucco ext" _
0143
n.
4 5
2;59
0
,-0
0
0
0
0
0
4 a
� 0
_2A 2ov
Q, 330
_R..
9 57
�w8;52
_
_ `L-o
, _.,_0
__M w_- Q
_ �_0
__ __w9
_,_ __M0
Blk wall, stucco ext
0.143
a
4.15
2.59
0
0
0
0
0
0
0
0
2A-2ov
0.330
a
9.57
21.17
0
0
0
0
0
0
0
0
11
2A-2ov
0.330
a
9.57
8.52
0
0
0
0
0
0
0
0
111,10
0600
a
1740
1758
0
0
0
0
0
0
0
0
VI/
BIk wall stucco ext :
0:143
s J
4 15
259
48
48
199
124
120
120
498
31,1.
__..G,
2A 2ov, - -2
_. _ 4 :.0
Blk wall, stucco ext
10C-v
0.143
0.550
w
w
4.15
15.95
2.59
16.20
0
0
0
0
0
0
0
0
108
0
92
0
380
0
237
0
2A-2ov
0.330
w
9.57
22.70
0
0
0
0
16
1
156
371
2A 2ov
0.330
w
9.57
8.52
0
0
0
0
0
0
0
0
_0.091
»z
2¢4'
JAl.._
7
_
__0
_ . 0'
_
0
_ 0
C
161330ad
0.032
0.93
1.69
63
63
58
106
203
203
188
342
_ _
z..._.._+....,.�
_,-,_.�..:....,.1 __
..:....�..s.i......v.a,._..;....
.28.8829
P
.....ri_._._utt.,_
...,...c.....[...._..-.w._......._-,..__
_
..............w.
_ _
_,s'�:........ _..,ter.
_
:...._._._.a,._,,. a.
,L .. _ j17
.. _.__._.:. _-.a
w- ...._._..,..,
.. '.
»
{
S,..,.. .,.:..
._.......»h.x ..._._.a_ , ...H.:.._ ro
......a _... �>
.e.._ _s
. ......... :..
. ..t...... _.
'::�.
...
,ran. _.
._. _-..._... ,
.__..._.
., .._...,.
6
c) AED excursion
-11
140
Envelope loss/gain
430
219
2039
1401
12
a) Infiltration
109
29
516
137
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
0
0
Appliances/other
0
300
Subtotal (lines 6 to 13)
538
248
2555
1837
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
538
248
2555
1837
15
Duct loads
48%
58%
258
145
48%
58%
1224
1071
Total room load
796
393
3779
2909
Air required (cfm)
37
17
176
126
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
-rw w�OgF�tsgft� 2020-Feb-1210:23:03
Right-Suite® Universal 2019 19.0.12 RSU23828 Page 7
10AGL\Lot37Blk50-7lndianRiverEstates2010AGL.rup Calc = MJ8 Front Door faces: E
Duct System Summary
Job:
Lot 37Block 50-7Indian ...
DEL -AIR
HUHNG•AIR CONDITIONING
Entire House
Date:
By:
12.29.08
M.DAVIS
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM
e-roject information
For: ADAMS HOMES
5213 Birch Drive, Fort Pierce, FL 34982
External static pressure
Pressurelosses
Available static pressure
Supply / return available pressure
Lowest friction rate
Actual air flow
Total effective length (TEL)
Heating
0.30
in H2O
0.06
in H2O
0.24
in H2O
0.120 / 0.120
in H2O
0.165
in/100ft
1167
cfm
146 ft
Cooling
0.30 in H2O
0.06 in H2O
0.24 in H2O
0.120 / 0.120 in H2O
0.165 in/100ft
1167 cfm
Supply Branch Detail Table
Name
Design
(Btuh)
Htg
(cfm)
Clg
(cfm)
Design
FR
Diam
(in)
H x W
(in)
Duct
Matl
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
BATH
h 796
37
17
0.300
4.,0
Ox 0
VIFx
9.9
70.0
BDRM 2
h 3779
176
126
0.276
7.0
Ox 0
VIFx
16.8
70.0
BDRM 3
h 2594
121
82
0.315
6.0
Ox 0
VIFx
6.1
70.0
FOYER/DINING
h 2381
111
85
0.223
6.0
Ox 0
VIFx
22.7
85.0
sti
KITCHEN/NOOK
c 6199
118
269
0.221
9.0
Ox 0
VIFx
23.5
85.0
st1
LIVING
c 4936
141
214
0.217
8.0
Ox 0
VIFx
25.6
85.0
st1
M. BATH
h 1835
85
41
0.173
6:0
Ox 0
VIFx
38.6
100.0
st2
M. BDRM
h 4177
194
184
0.173
8.0
Ox 0
VIFx
38.6
100.0
st2
M. IWIC
c 72
2
3
0.178
4.0
Ox 0
VIFx
34.7
100.0
st2
M. owlc
h 866
40
15
0.170
4.0
Ox 0
VIFx
41.1
100.0
st2
M. We
h 1214
56
19
0.165
5.0
Ox 0
VIFx
45.8
100.0
st2
STUDY
h 1535
71
59
0.211
6.0
Ox 0
VIFx
28.6
85.0
sti
UTIL
c 1187
13
52
0.315
5.0
Ox 0
VIFx
6.1
70.0
Supply Trunk Detail Table
Trunk
Htg
Clg
Design
Veloc
Diam
H x W
Duct
Name
Type
(cfm)
(cfm)
FR
(fpm)
(in)
(in)
Material
Trunk
st1
Peak AVF
820
890
0.165
637
16.0
0 x 0
VinlFlx
st2
Peak AVF
378
262
0.165
482
12.0
0 x 0
VinlFlx
St1
-�- wri�ghtsoftm
m Right -Suite® Universal 2019 19.0.12 RSU23828
ACCK ..10AGL\Lot37Blk50-7lndianRiverEstates2010AGL.rup Calc = MJ8 Front Door faces:
2020-Feb-12 10:23:04
Page 1
Return Branch Detail Table
Name
Grille
Size (in)
Htg
(cfm)
Clg
(cfm)
TEL
(ft)
Design
FR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Stud/Joist
Opening (in)
Duct
Matl
Trunk
rbi
Ox 0
1167
1167
0
0
0
0
Ox 0
VIFx
1 * Wright5Of't° 2020-Feb-1210:23:04
IC�wAM,, 1 1.1.,��..n,y Right -Suite@ Universal 2019 19.0.12 RSU23828 Page 2
..10AGL\Lot37Blk50-7lndianRiverEstates2010AGL.rup Calc = MJ8 Front Door faces: E
2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Lot 37 Block 50-7 Indian River Estate 2010AGL Builder Name: ADAMS HOMES
Street: 5213 Birch Drive Permit Office:
City, State, Zip: Fort Pierce , FL , 34982 Permit Number:
Y
U
Owner: Jurisdiction: 661000
W
Design Location: FL, ST_LUCIE_CO_INTL
U
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
requirements
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
Breaks or joints in the air barrier shall be sealed.
Ceiling/attic
The air barrier in any dropped ceiling/soffit shall be aligned with
The insulation in any dropped ceiling/soffit
the insulation and any gaps in the air barrier shall be sealed.
shall be aligned with the air barrier.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed.
Cavities within comers and headers of frame walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity
sealed.
with a material having a thermal resistance of R-3
Knee walls shall be sealed.
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/doorjambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of
Floor framing cavity insulation shall be installed to
(including
insulation.
maintain permanent contact with the underside of
above -garage
subfloor decking, or floor framing cavity insulation
and cantilevered
shall be permitted to be in contact with the top side
floors)
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
Narrow cavities
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spac
as.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the drywall.
thermal envelope shall be air tight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
extend behind pffip*na and wormna.
Shower/tub
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
on exterior wall
tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC register boots that penetrate building thermal envelope shall
be sealed to the sub -floor or drywall.
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sprinklers
sealed in a manner that is recommended by the manufacturer.
I
Caulking or other adhesive sealants shall not be used to fill voids
between fire sprinkler cover nliites and walls or cemlffinas- I
a. In addition, inspection of log walls shall be in accordance with the provisions of ]CC-400.
2/12/2020 10:32 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
` FORM'R405-2017
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2017 Florida Building Code, Energy Conservation via the
residential Simulated Performance Method shall include;
❑ This checklist
❑ A Form R405 report that documents that the Proposed Design complies with Section
R405.3 of the Florida Energy Code. This form shall include a summary page
indicating home address, a -ratio and the pass or fail status along with summary
areas and types of components, whether the home was simulated as a worst -case
orientation, name and version of the compliance software tool, name of individual
completing the compliance report (one page) and an input summary checklist that can
be used for field verification (usually four pages/may be greater).
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO for the Performance Method:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 -
one page)
❑ A completed Envelope Leakage Test Report (usually one page)
❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed
Form R405 Duct Leakage Test Report (usually one page)
2/12/2020 10:31:28 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2017 Florida Building Code, Energy Conservation, 6th Edition
Jurisdiction: 661000
Permit #:
46bhfortnation
,
Builder: ADAMS HOMES Community: Lot: 37
Address: 5213 Birch Drive
City: Fort Pierce State: FL Zip: 34982
Air Leakage `Test Restilfis Passtng iestitts must meet etther,the Performance, Prescrlphve,o'r ERI Method
v, .. d
a.
°O PRESCRIPTIVE METHO(>•The building or dwelling urnt``shall be tested and verified as having an a'ir leakage rate of notexceeding 7 air
changes,per hour at a pressure of 0�2'inch W.g,`(50 Pascals) m Climate Zones 1=_'and 2
k h 4
PERFORMANCE or-ERI METHOD -The building or dwelling unit shall be tested and'venfied,as having; an air leakage rate of not exceeding
thesetected ACH(50} value, as shown on Form R405 2017 (Performance) or R406 2017; (ERI),, section; labeled as infiltration, sub -section ACH50
AGH(5D) specified on Form R405201TEnergy'Oalc (Performance)' or R406 201 Z (ERI): 7.000
x 60 _ 17286 = Method for calculating building volume:
CFM(50) Building Volume ACH(50)
O Retrieved from architectural plans
F-1 PASS 1 Code
• software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing;Company
Company Name: Phone:
hereby verify that the above Air Leakage results are in accordance with the 2017 6th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
2/12/2020 10:32:28 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 6th Edition (2017)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
FADDRESS: 5213 Birch Drive Permit Number:
Fort Pierce , FL , 34982
MANDATORY REQUIREMENTS See individual code sections for full details.
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
(Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
❑ R402.4.1 Building thermal enveld-ftm building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.
The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
R402.4.1.1 Installation The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
❑ R402.4.3 Fenestration air IeakagdNindows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per
square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
2/12/2020 10:32 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
❑ R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
R403.1 Controls. SECTION R403 SYSTEMS
❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (1), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1, Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the
manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test.
2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the
entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the
test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
❑R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
F-1R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C)
or below 55°F (13°C) shall be insulated to a minimum of R-3.
❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory)Heated water circulation systems shall be in
accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2.
Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return
❑ pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited.
Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the
occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and
when there is no demand for hot water.
R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems
shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance
with the times when heated water is used in the occupancy.
2/12/2020 10:32 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
ElR403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3'/2 inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
ri R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100°F to 140°F (38°C to 60°C).
R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main bumer(s) of
combustion types of service water -heating systems to be turned off.
R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TMA , Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where whole -house mechanical ventilation fans are integral to tested and listed HVAC equipment, they shall be
powered by an electronically commutated motor.
R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10
otherwise.
R403.7 Heating and cooling equipment (Mandatory).
R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the
equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies,
based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and
indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions
described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that
affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such
as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency
rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed.
TABLE R403.6.1
WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIRFLOW RATE MINIMUM
(CFM)
MINIMUM EFFICACY a
(CFM/WATT)
AIRFLOW RATE MAXIMUIV
(CFM)
Range hoods
Any
2.8 cfm/watt
Any
In -line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1.4 cfm/watt
<90
Bathroom, utility room
90
2.8 cfm/watt
Any
For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916
2/12/2020 10:32 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section 403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
❑ C403 and C404 of the IECC—Commercial Provisions in lieu of Section R403.
❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40oF (4.8°C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
❑ R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
❑ R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
2/12/2020 10:32 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 5
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
R403.11 Portable spas (Mandatoryhe energy consumption of electric -powered portable spas shall be controlled by the
requirements ofAPSP-14.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment (Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be
high -efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high -efficacy lamps.
Exception: Low -voltage lighting.
R404.1.1 Lighting equipment (Mandatory)Fuel gas lighting systems shall not have continuously burning pilot lights.
2/12/2020 10:32 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 5 of 5