HomeMy WebLinkAboutMS63966 FINAL DESIGN Stamped__DkoL1XCOVER PAGE
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-1
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
KHODIA PIERRE - MS63966
8006 SANTA CLARA BOULEVARD
FORT PEARCE, FL 34951
3057679117
GCP
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
10/13/2020
SYSTEM SIZE (DC ): 9.45 KW
27 MODULES: LG LG 350N1C-V5
27 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
COVER PAGE
SYSTEM INFORMATION
MODULE LG LG 350N1C-V5
INVERTER ENPHASE IQ7PLUS-72-2-US
RACKING ROOFTECH RT-MINI & SNAPNRACK ULTRA
RAIL 60 SYSTEM 2-RAIL
SYSTEM SIZE (DC)9.45 KW
LOCATION 27.5523839,-80.4059682
LG LG 350N1C-V5
350 WATT MODULE
66.4'' X 40'' X 1.57''(SEE DATASHEET)
STRUCTURAL STATEMENT:
THE EXISTING STRUCTURE IS ADEQUATE TO SUPPORT THE NEW LOADS IMPOSED BY THE PHOTOVOLTAIC MODULE
SYSTEM INCLUDING UPLIFT & SHEAR.EXISTING RAFTER SIZES & DIMENSIONS CONFORM TO 6TH EDITION 2017
FLORIDA RESIDENTIAL CODE, 6TH EDITION 2017 FLORIDA BUILDING CODE SECTION 1512 THROUGH 1525 AND
SECTION 1616 THROUGH 1626 FOR HIGH VELOCITY HURRICANE ZONES.
GENERAL NOTES:
THIS PV SYSTEM HAS BEEN DESIGNED TO MEET THE MINIMUM DESIGN STANDARDS FOR BUILDING AND OTHER
STRUCTURES OF THE ASCE 7-10, 6TH EDITION 2017 FLORIDA RESIDENTIAL CODE, 6TH EDITION 2017 FLORIDA
BUILDING CODE, 6TH EDITION 2017 FLORIDA FIRE PREVENTION CODE, NEC 2014 AND ALL LOCAL CODES &
ORDINANCES.
ROOF SHALL HAVE NO MORE THAN TWO LAYERS OF COVERING IN ADDITION TO THE SOLAR EQUIPMENT.
INSTALLATION OF SOLAR EQUIPMENT SHALL BE FLUSH MOUNTED, PARALLEL TO AND NO MORE THAN 6-INCHES
ABOVE THE SURFACE OF THE ROOF FOR SLOPED ROOF AND NO MORE THAN 10-INCHES ABOVE THE SURFACE OF
THE ROOF FOR FLAT ROOF.
ANY PLUMBING VENTS ARE NOT TO BE CUT OR COVERED FOR SOLAR EQUIPMENT INSTALLATION. ANY
RELOCATION OR MODIFICATION OF THE VENT REQUIRES A PLUMBING PERMIT AND INSPECTION.
ALL DESIGN, CALCULATIONS ARE PERFORMED BY DANIEL DUNZIK REGISTERED ARCHITECT. FLORIDA STATE
STATUTE 471.003(3) PROVIDES THAT LICENSED ARCHITECTS ARE EXEMPTED FROM THE PROVISIONS OF
CHAPTER 471 ENGINEERING AND NOT PRECLUDED FROM PERFORMING ENGINEERING SERVICES FOR INTEGRATED
SYSTEMS AND SERVICES THAT ARE INCIDENTAL TO THE DESIGN CONSTRUCTION OR ALTERATION OF BUILDINGS
AND STRUCTURES FOR HUMAN HABITATION.
INVERTER PLACEMENT:
SYSTEM UTILIZES "ENPHASE" MICRO-INVERTERS WITH RAPID SHUTDOWN CONTROL LOCATED ON THE BACK SIDE
OF EACH MODULE.
FSEC CERTIFICATION STATEMENT:
PER FL. STATUE 377.705 (REVISED 7/1/2017), I, MINA A. MAKAR PE# 86753, Certificate of Authorization #33404,
AN ENGINEER LICENSED PURSUANT TO CHAPTER 471,CERTIFY THAT THE PV ELECTRICAL SYSTEM AND
ELECTRICAL COMPONENTS ARE DESIGNED AND APPROVED USING THE STANDARDS CONTAINED IN THE MOST
RECENT VERSION OF THE FLORIDA BUILDING CODE. FBC 2017
BUILDING INFORMATION/B.O.M.
# STORIES 1/15
ROOF AREA 3115
P.V. AREA 487
ROOFING TYPE ASPHALT SHINGLES
ROOF PITCH 25
# RAILS 23
# L-FOOT ATTACHMENTS W/
ROOFTECH RT-MINI 56
# MODULES 27
# INVERTERS 27
# SKIRTS 10
# ENPHASE COMBINER BOXES 1
EATON 60A FUSIBLE SOLAR AC
DISCONNECT 1
45A FUSES 2
125A LINE TAPS 2
PLAN KEY
PV-1 COVER PAGE
PV-2 SITE PLAN
PV-3 PANEL SPECIFICATION
PV-3.1 PANEL LOAD TESTING RESULTS
PV-3.2 INVERTER SPECIFICATION
PV-3.3 COMBINER BOX SPECIFICATION
PV-3.4 JUNCTION BOX SPECIFICATION
PV-3.5 ATTACHMENT DETAIL
PV-3.6 STRUCTURAL CALCULATION
PV-3.7 SEALANT SPECIFICATION
PV-3.8 SEALANT SPECIFICATION CONT.
PV-3.9 CONDUIT SUPPORT SPECIFICATION
PV-4 THREE LINE DIAGRAM
PV-4.1 ELECTRICAL NOTES
PV-4.2 EQUIPMENT LABELS
PV-5 STRUCTURAL CERTIFICATION
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2020.10.13 07:10:49 -05:00
1 / 16
SCALE: 3/32" = 1'-0"
SITE PLAN
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-2
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
KHODIA PIERRE - MS63966
8006 SANTA CLARA BOULEVARD
FORT PEARCE, FL 34951
3057679117
GCP
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
10/13/2020
SYSTEM SIZE (DC ): 9.45 KW
27 MODULES: LG LG 350N1C-V5
27 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
NOTE:
1. ROOF COVERING MATERIAL IS COMPOSED OF
2. EXACT ATTACHMENT LOCATION AND QUANTITY OF ATTACHMENTS ARE BASED ON EXISTING RAFTER LOCATIONS OBTAINED FROM FIELD
MEASUREMENTS. . THE LOCATION AND QUANTITY OF ATTACHMENTS MAY VARY BASED ON RAFTER LAYOUT START POINT, SPACING
VARIATIONS AND ROOFING TYPE. VERIFY IN THE FIELD ALL RAFTER LOCATIONS AND ADJUST LAYOUT AS REQUIRED. A TILE ROOF WILL
PRODUCE A STAGERED ATTACHMENT LAYOUT BECAUSE OF EXISTING STAGERED TILE JOINT LOCATIONS
3. EXISTING RESIDENCE EQUIPPED WITH SMOKE/CO DETECTOR IN AND OUTSIDE OF ALL SLEEPING ROOMS HARDWIRED AND
INTERCONNECTED AS PER FEDERAL LAW
ASPHALT SHINGLES
SITE PLAN
SYMBOL LEGEND
MAIN SERVICE PANEL
UTILITY METER
SKYLIGHT
VENT
CHIMNEY
SUB-PANEL
MSP
SP
M
SOLAR
AC
DISC
UDC
LC
N3R
CB
SOLAR AC DISCONNECT
LOAD CENTER
NEMA 3R BOX W/ ENVOY-S
COMBINER BOX
PIPE VENT
FAN
SATELLITE DISH
MODULE
FIRE SETBACKS AS PER 6TH
EDITION 2017 FFPC
PITCH DIRECTION
UTILITY DISCONNECT
MIN 3'x3' GROUND ACCESS
POINT
WIND PRESSURE ZONE LINES
ROOF PANEL COUNT TILT AZIMUTH SHADING
R1 18 25°179°84%
R2 9 25°89°85%
RAFTER SPACING
24" O.C. (TYP)
CLAMPING MAX SPACING IN ZONE 1 72" O.C
AND IN ZONE 2 AND ZONE 3 48" O.C
23'-101
2"23'-10"
19'-61
2"
49'-01
2"
27'-21
2"
40'-01
2"
37'-01
2"
12'-6"
R1
R2
RIDGE
RIDGEHIPHI
PHIP
HI
PVALLEYGUTTER GUTTERMSP M
ELECTRICAL EQUIPMENT
SOLAR
AC
DISC
CB
J-BOX
J-BOX
FRONT OF RESIDENCE
SANTA CLARA
BOULEVARD
6'-0"
6'-0"
6'-0"
6'-0"
6'-0"
6'-0"
PZ1
PZ1
PZ2
PZ2
PZ2
PZ2
PZ3
PZ3
PZ3
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2020.10.13 07:10:49 -05:00
2 / 16
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
KHODIA PIERRE - MS63966
8006 SANTA CLARA BOULEVARD
FORT PEARCE, FL 34951
3057679117
GCP
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
10/13/2020
SYSTEM SIZE (DC ): 9.45 KW
27 MODULES: LG LG 350N1C-V5
27 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
PANEL SPECIFICATION
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2020.10.13 07:10:49 -05:00
3 / 16
PANEL LOAD TESTING
RESULTS
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.1
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
KHODIA PIERRE - MS63966
8006 SANTA CLARA BOULEVARD
FORT PEARCE, FL 34951
3057679117
GCP
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
10/13/2020
SYSTEM SIZE (DC ): 9.45 KW
27 MODULES: LG LG 350N1C-V5
27 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2020.10.13 07:10:49 -05:00
4 / 16
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.2
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
KHODIA PIERRE - MS63966
8006 SANTA CLARA BOULEVARD
FORT PEARCE, FL 34951
3057679117
GCP
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
10/13/2020
SYSTEM SIZE (DC ): 9.45 KW
27 MODULES: LG LG 350N1C-V5
27 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
INVERTER SPECIFICATION
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2020.10.13 07:10:49 -05:00
5 / 16
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.3
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
KHODIA PIERRE - MS63966
8006 SANTA CLARA BOULEVARD
FORT PEARCE, FL 34951
3057679117
GCP
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
10/13/2020
SYSTEM SIZE (DC ): 9.45 KW
27 MODULES: LG LG 350N1C-V5
27 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
COMBINER BOX SPECIFICATION
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2020.10.13 07:10:49 -05:00
6 / 16
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.4
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
KHODIA PIERRE - MS63966
8006 SANTA CLARA BOULEVARD
FORT PEARCE, FL 34951
3057679117
GCP
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
10/13/2020
SYSTEM SIZE (DC ): 9.45 KW
27 MODULES: LG LG 350N1C-V5
27 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
JUNCTION BOX SPECIFICATION
JUNCTION BOX SPECIFICATION FOR SHINGLE ROOFS
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2020.10.13 07:10:49 -05:00
7 / 16
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.5
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
KHODIA PIERRE - MS63966
8006 SANTA CLARA BOULEVARD
FORT PEARCE, FL 34951
3057679117
GCP
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
10/13/2020
SYSTEM SIZE (DC ): 9.45 KW
27 MODULES: LG LG 350N1C-V5
27 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
SNAPNRACK UR-60 RAIL AND SPLICE DETAILS BIN:
REFER TO SNAPNRACK INSTALLATION MANUAL FOR
5/16" DIA. HARDWARE TORQUE SPECIFICATIONS
SPLICE POSITIONING:
APPROVED - ANYWHERE ALONG RAIL SPAN
BETWEEN TWO ROOF ATTACHMENTS
NOT APPROVED - RAIL OVERHANGS /
CANTILEVERS SNAPNRACK, UR-60 RAIL
SNAPNRACK, UR-60 RAIL
FASTENS TO ROOF ATTACHMENTS
VIA THE "SNAPNRACK, ULTRA RAIL
MOUNTING HARDWARE"
SNAPNRACK, ULTRA
RAIL SPRING AND
SPRING CAGE, OPTIONAL
5/16" DIA.-18 BOLT, S.S.
LENGTH VARIES
SNAPNRACK, ULTRA
RAIL MOUNT, TAPPED
SNAPNRACK, ULTRA
RAIL MOUNT, THRU
TORQUE ALL FASTENERS TO
THE SPECIFIED VALUES PRIOR
TO INSTALLING PV MODULES
SNAPNRACK, UR-60 BONDING BRIDGE
SNAPNRACK ROOF
ATTACHMENT, VAIRES
SNAPNRACK, ULTRA RAIL MOUNTING HARDWARE
1 3/4"1 1/2"
SNAPNRACK, UR-60 SPLICE, SLEEVE
O-RING FOR 1/4" BOLT
SNAPNRACK, UR-60 SPLICE INSTALLED, FRONT
5/16" DIA.-18 X 3/4" FLANGE BOLT, S.S.TORQUE ALL FASTENERS TO
THE SPECIFIED VALUES PRIOR
TO INSTALLING PV MODULES
SNAPNRACK, UR-60 SPLICE
SNAPNRACK, UR-60 SPLICE INSTALLED, TOP SNAPNRACK, UR-60 RAIL
THERMAL EXPANSION GAP:
3/8" - 5/8"
N/A
SNAPNRACK, UR-60 SPLICE
REVISION:
1 5/7/2019 NEW DETAIL
2 7/17/2019 DRO-00138
MJA
MJA
2 1/4"2 1/4"
SNAPNRACK, UR-60 SPLICE, EXPLODED
SNAPNRACK, UR-60 SPLICE SNAPNRACK, UR-60 RAIL
Sunrun South LLC
595 MARKET STREET, 29TH FLOOR SAN FRANCISCO, CA 94105 USA
PHONE (415) 580-6900 FAX (415) 580-6902
Solar Mounting Solutions THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY
REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE
WRITTEN CONSENT OF SUNRUN SOUTH LLC.
DESIGNER:
APPROVED BY:
M.AFFENTRANGER
DRAFTER: M.AFFENTRANGER
B.PETERSON
SCALE:
DATE:
DNS
5/7/2019
DRAWING NUMBER:
SNR-DC-00331
DESCRIPTION:
ULTRA RAIL, COMPONENT DETAIL, UR-60 RAIL
AND SPLICE
REV:
2
ATTACHMENT DETAIL FOR SHINGLE ROOF
ATTACHMENT DETAIL
OVERVIEW OF THE SNAPNRACK ULTRA RAIL
SYSTEM INSTALLED ON A TYPICAL ROOF
SNAPNRACK, ADJUSTABLE END CLAMP.
SELECT TO MATCH MODULE HEIGHT
REFER TO SPECIFIC "ATTACHMENT DETAIL"
FOR DETAILS ON ATTACHING AND
WATERPROOFING THE VARIOUS
SNAPNRACK ROOF ATTACHMENT PRODUCTS
REFER TO SPECIFIC "COMPONENT DETAIL"
FOR DETAILS ON VARIOUS SNAPNRACK
ACCESSARY AND COMPONENT PRODUCTS
BOTH THE SNAPNRACK, UNIVERSAL END
CLAMP AND SNAPNRACK, ADJUSTABLE END
CLAMP CAN BE USED ON END MODULES
MODULES MAY BE CLAMPED ON SHORT OR
LONG SIDE PER MODULE MANUFACTURER
REQUIREMENTS
RAILS MAY BE MOUNTED UP/DOWN OR
ACROSS THE SLOPE OF THE ROOF
REFER TO SNAPNRACK INSTALLATION
MANUAL FOR 5/16" DIA. HARDWARE TORQUE
SPECIFICATIONS
SNAPNRACK, ADJUSTABLE
END CLAMP. SELECT TO
MATCH MODULE HEIGHT
PV MODULE, TYP.
"RAIL END OVERHANG"
DISTANCE FROM RAIL END
TO OUTER ROOF ATTACHMENT CENTER.
NOT TO EXCEED 34% OF ALLOWABLE SPAN
STRUCTURAL MEMBER
SNAPNRACK, MID CLAMP.
SELECT TO MATCH MODULE HEIGHT
"MODULE OVERHANG"
SNAPNRACK, ULTRA RAIL DISTANCE FROM RAIL SIDE TO MODULE EDGE.
NOT TO EXCEED 25% OF MODULE LENGTH OR
MODULE MANUFACTURER RECOMMENDATIONS
"RAIL SPAN" DISTANCE BETWEEN
CENTERS OF TWO ROOF ATTACHMENTS
DETAIL A:
SNAPNRACK, ADJUSTABLE END CLAMP
BA
SNAPNRACK, MID CLAMP.
SELECT TO MATCH
MODULE HEIGHT
PV MODULE, TYP.
SNAPNRACK, ULTRA RAIL
DETAIL B:
SNAPNRACK, MID CLAMP
DETAIL C:
BIN:
1/2" MODULE SPACING
PV MODULE, TYP.
SNAPNRACK, ULTRA RAIL PV MODULE FRAME, TYP.
SNAPNRACK, UNIVERSAL END CLAMP.
MODULE HEIGHT AGNOSTIC AND
HIDDEN BENEATH MODULES
SNAPNRACK, ULTRA RAIL
SNAPNRACK, UNIVERSAL END CLAMP
PV MODULE, TYP.
C
SNAPNRACK, ULTRA RAIL
SNAPNRACK ROOF ATTACHMENT,
VARIES WITH ROOF TYPE
ALL
REVISION:
1 5/7/2019 NEW DETAIL MJA
SNAPNRACK, ULTRA RAIL
END CAP, OPTIONAL
11
11 2"
21
15 8"
UR-40 RAIL | UR-60 RAIL
FOR USE WITH SNAPNRACK ULTRA SERIES RAILS
Sunrun South LLC
595 MARKET STREET, 29TH FLOOR SAN FRANCISCO, CA 94105 USA
PHONE (415) 580-6900 FAX (415) 580-6902
Solar Mounting Solutions THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY
REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE
WRITTEN CONSENT OF SUNRUN SOUTH LLC.
DESIGNER:
APPROVED BY:
M.AFFENTRANGER
DRAFTER: M.AFFENTRANGER
B.PETERSON
SCALE:
DATE:
DNS
5/7/2019
DRAWING NUMBER:
SNR-DC-00329
DESCRIPTION:
ULTRA RAIL, SYSTEM OVERVIEW, TYPICAL
REV
336/3661
4"
2"
ROOFING MATERIAL,
COMP SHINGLE SHOWN, TYP.
ROOF SHEATHING AND
UNDERLAYMENT MATERIAL, TYP.
STRUCTURAL MEMBER,
WOODEN RAFTER SHOWN, TYP.
SNAPNRACK ROOF ATTACHMENT, VAIRES WITH
ROOF TYPE. REFER TO SPECIFIC "ATTACHMENT DETAIL"
FOR ATTACHMENT & WATERPROOFING DETAILS
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2020.10.13 07:10:49 -05:00
8 / 16
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.6
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
KHODIA PIERRE - MS63966
8006 SANTA CLARA BOULEVARD
FORT PEARCE, FL 34951
3057679117
GCP
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
10/13/2020
SYSTEM SIZE (DC ): 9.45 KW
27 MODULES: LG LG 350N1C-V5
27 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
2-RAIL RACKING PLUS SOLAR SYSTEM DEAD LOAD
COMPONENT WEIGHT/UNIT #
MODULES 37.7 27
INVERTERS 4.0 27
RAILS (2-RAIL) @ 5.8LB/LF.1.8LB/LF 13.5
GRAVITY LOAD
ATTACHMENT/FLASHING 0.98 56
ARRAY TOTAL 487SF 1181
TOTAL LOAD/ATTACHMENT 21.09
2-RAIL RACKING SYSTEM ATTACHMENT TOTAL LOADS ASCE 7-10 30.4.2
WIND PRESSURE MIXED ZONE 1 & 2 -22.41
TOTAL WIND PRESSURE -10913.95
TOTAL ATTACHMENTS 56
TOTAL UPLIFT WIND LOAD ON ATTACHMENT -194.89
TOTAL UPLIFT FORCE/ATTACHMENT POINT -173.8LB
-173.8LB IS BELOW THE ALLOWABLE 1,276.8 X .33 = 421.34LB
STRUCTURAL CALCULATION
EXTERNAL PRESSURE COEFFIENT (GCp) (ASCE 7-10 FIGURE 30.4-2B)
ZONE 0 To 7 TILT 7 To 27 TILT 27 to 45 TILT DOWNWARD
1 -0.9 -0.8 -0.8 0.3
2 -1.1 -1.2 -1 0.3
3 -1.1 -2 -1 0.3
WIND LOAD CALCULATIONS (ASCE 7-10 30.3.2)
VELOCITY PRESSURE Qz = 0.00256 Kz*Kzt*Kd*V^2(LB/SQ-FT)
EXPOSURE B
Kz (VELOCITY PRESSURE EXPOSURE)0.57
Kzt (TOPOGRAPHIC FACTOR)1
Kd (WIND DIRECTIONALITY)0.85
V (WIND SPEED)160
MEAN HEIGHT 15.00
VELOCITY PRESSURE Qz 32.02
DESIGN WIND PRESSURE p = Qz * (GCp - GCpi) WHERE GCpi = -0.18
SOLAR MODULE TOTAL WIND PRESSURE p (ASCE 7-10 EQUATION 30.4-1)
ZONE 0 To 7 TILT 7 To 27 TILT 27 to 45 TILT DOWNWARD
1 N/A -19.85 N/A 15.37
2 N/A -32.66 N/A 15.37
3 N/A -58.27 N/A 15.37
10 % OF LEAST HORIZONTAL DIMENSION OR 40% OF THE BUILDING HEIGHT WHICHEVER IS
SMALLER BUT NOT LESS THAN EITHER 4% OF THE LEAST HORIZONTAL DIMENSION OR 3'-0"
WIND PRESSURE ZONE CALCULATION (ASCE 7-10 FIGURE 30.4-2A, 2B)
HORIZONTAL DIMENSION A 67'X 10% = 6.7'
HORIZONTAL DIMENSION B 61'X 10% = 6.1'
BUILDING HEIGHT 15'X 40% = 6'
PRESSURE ZONE WIDTH 6' 0 "
ALLOWABLE LOAD / ATTACHMENT 5/16” LAG SCREW W/ 3.00” EMBEDMENT INTO RAFTER BELOW
ACCORDING TO THE NATIONAL DESIGN SPECIFICIFICATION FOR WOOD CONSTRUCTION 2015
EDITION. = W' = W X CD X CT. - PER TABLE 11.3.1 NDS
5/16” DIA. 4" LONG LAG W/ 3.00” EMBEDMENT INTO 2X ROOF RAFTER (SEE SHEET PV-2 FOR SPACING)
W' = 266LB/IN EMBEDMENT (NDS11.3.1 TABLE 12.2A) FOR DF. LARCH, S.Y.P., AND S.P.F. SPECIES
CD = 1.6 (TABLE 2.3.2 2015 NDS)
CT = 1.0 (TABLE 10.3.4 2015 NDS)
W' = 266LB/IN X 3.00” X 1.6 X 1.0 = 1,276.8LBS = ULTIMATE
-THREAD MUST BE EMBEDDED IN THE SIDE GRAIN OF A TRUSSES OR OTHER STRUCTURAL MEMBER
INTEGRAL WITH THE BUILDING STRUCTURE.
-LAG BOLTS MUST BE LOCATED IN THE MIDDLE THIRD OF THE STRUCTURAL MEMBER.
-THESE VALUES ARE NOT VALID FOR WET SERVICE.
-INSTALL LAG BOLTS WITH HEAD AND WASHER FLUSH TO SURFACE (NO GAP). TORQUE AS PER
MANUFACTURERS SPECIFICATIONS. DO NOT OVER-TORQUE.
-WITHDRAWAL DESIGN VALUES FOR LAG SCREW CONNECTIONS SHALL BE MULTIPLIED BY
APPLICABLE ADJUSTMENT FACTORS IF NECESSARY. SEE TABLE 10.3.1 IN THE AMERICAN WOOD
COUNCIL NDS FOR WOOD CONSTRUCTION.
CERTIFICATION OF WIND LOAD PRESSURE CALCULATION THIS IS A 2-RAIL DESIGN
DESIGN LOAD CRITERIA. AS PER ASCE 7-10 (2.4.1)
FOR THIS PARTICULAR CASE, THE "DOWNFORCE" CASE 2 AND
UPLIFT HAVE BEEN TAKEN INTO CONSIDERATION.
P (PSF) = 1XD + 1X PNET (DOWNFORCE)
P (PSF) = 0.6XD + 1X PNET (UPLIFT)
(P = TOTAL DESIGN LOAD)
(PNET = WIND LOAD)
(D = DEAD LOAD)
PNET HAVE BEEN CALCULATED FOLLOWING THE ALLOWABLE STRESS DESIGN METHOD.
THE MAXIMUM ABSOLUTE VALUE OF THE 2 CASES IS THE UPLIFT LOAD.
THIS 2-RAIL DESIGN IS WELL UNDER THE CAPACITY OF THE INDIVIDUAL ATTACHMENT
CAPACITIES FOR THE DESIGN. THE PHOTOVOLTAIC MODULES USED IN CONJUNCTION WITH
SNAPNRACK2-RAIL ATTACHMENT SYSTEM ADDED HAVE A DESIGN CAPACITY OF -4,000 PA., 84
PSF. THIS DESIGN IS WITHIN THE LOADING CAPACITIES OF THE PHOTOVOLTAIC MODULE
2-RAIL DESIGN TESTING CAPACITIES THAT HAVE BEEN PERFORMED BY INDEPENDENT
TESTING BY THE PANEL MANUFACTURERS ENGINEERS. SEE ATTACHED MANUFACTURERS
TEST DATA.
SOLAR PANEL WEIGHTED UPLIFT PRESSURES (PSF)
ZONES ZONE RATIO 0 To 7 TILT 7 To 27 TILT 27 to 45 TILT
1 & 2 4:1 N/A -22.4106 N/A
1 & 2 3:2 N/A -24.9718 N/A
1 & 2 2:3 N/A -27.533 N/A
1 & 2 1:4 N/A -30.0942 N/A
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2020.10.13 07:10:49 -05:00
9 / 16
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.7
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
KHODIA PIERRE - MS63966
8006 SANTA CLARA BOULEVARD
FORT PEARCE, FL 34951
3057679117
GCP
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
10/13/2020
SYSTEM SIZE (DC ): 9.45 KW
27 MODULES: LG LG 350N1C-V5
27 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
SEALANT SPECIFICATION
SEALANT SPECIFICATION FOR SHINGLE ROOFS
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2020.10.13 07:10:49 -05:00
10 / 16
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.8
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
KHODIA PIERRE - MS63966
8006 SANTA CLARA BOULEVARD
FORT PEARCE, FL 34951
3057679117
GCP
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
10/13/2020
SYSTEM SIZE (DC ): 9.45 KW
27 MODULES: LG LG 350N1C-V5
27 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
SEALANT SPECIFICATION CONT.
Roofing Read Safety Data Sheets before using this product.
19 Flashing Cement
DESCRIPTION:
KARNAK 19 Flashing Cement is a scientifically compounded composition of
selected asphalts, mineral fibers, and refined solvents that are manufactured to a
heavy consistency for application by trowel to provide a durable, elastic
coating of excellent adhesion and high resistance to water and weathering. This
product dries to a tough, flexible, waterproof and corrosion proof coating which
gives excellent performance over wide ranges of temperature and weather
conditions. KARNAK 19 Flashing Cement is available in 3 consistencies: Summer,
Semi and Winter.
USES:
KARNAK 19 Flashing Cement is a general purpose cement for repairing leaks in
shingles, concrete, metal or asphalt roofs, flashings on walls, chimneys, flues,
downspouts and cornices. It is excellent for sealing cracks in concrete and brick, as
a joint filler for precast roof slabs and for general purpose use in maintenance of
exposed buildings and structures.
SURFACE PREPARATION:
All surfaces should be clean, dry and free from oil or grease, dust, dirt, loose paint
or other foreign matter. Recommended application temperature is 40°F to 120°F.
If applying at temperatures lower than 40°F, the substrate must be free of
moisture and/or ice crystals.
APPLICATION:
Spread KARNAK 19 Flashing Cement to an average thickness of 1/8”
(approximately 8 gallons per square) and press tightly into joints, seams or cracks.
To repair large cracks, breaks and blisters:
1. Spread KARNAK 19 Flashing Cement over the damaged area.
2. Embed KARNAK Cotton, Fiberglass or Poly-Mat Membrane reinforcement.
3. Apply another coat of KARNAK 19 Flashing Cement over the entire patch.
SPECIFICATIONS:
Federal Specification SS-C-153 Type I (Except Non-Asbestos)
ASTM D-4586 Type I Class I
Revised 12.14.18
330 CENTRAL AVENUE, CLARK, NJ 07066
732-388-0300 • 800-526-4236 • FAX: 732-388-9422
WEB: http://www.karnakcorp.com
Roofing Read Safety Data Sheets before using this product.
19 Flashing Cement
PHYSICAL PROPERTIES:
1. Consistency: A smooth, heavy trowel consistency which will readily spread on
and adhere to vertical and horizontal surfaces without sagging.
2. Character of Dried Film: Uniform, excellent adhesion to masonry, steel, cured
concrete, shingles, asphalt roofing and a variety of other surfaces.
3. The dried film retains its flexibility and ductility so that the coating will resist
extreme variations in temperature and weather.
4. Has excellent resistance to flow at high temperatures when used on a
vertical surface.
CAUTION:
Do not use near open flame. Material is for building exterior applications only.
Avoid breathing solvent fumes and prolonged contact with skin. Do not take
internally. If swallowed, do not induce vomiting. Call a physician immediately.
Keep out of reach of children. Keep container covered when not in use. Do not thin.
Dispose of in an environmentally safe manner. Cover air intakes during application
and while drying.
PACKAGING:
Available in 5 gallon, 3 gallon, 1 gallon cans and 10.1 oz. caulk tubes.
If further information is needed, contact Karnak Technical Services at
1-800-526-4236.
Revised 12.14.18
330 CENTRAL AVENUE, CLARK, NJ 07066
732-388-0300 • 800-526-4236 • FAX: 732-388-9422
WEB: http://www.karnakcorp.com
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2020.10.13 07:10:49 -05:00
11 / 16
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.9
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
KHODIA PIERRE - MS63966
8006 SANTA CLARA BOULEVARD
FORT PEARCE, FL 34951
3057679117
GCP
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
10/13/2020
SYSTEM SIZE (DC ): 9.45 KW
27 MODULES: LG LG 350N1C-V5
27 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
DESCRIPTION:DRAWN BY:
SNAPNRACK, CONDUIT SUPPORT COMP SHINGLE
PART NUMBER(S):
242-02106 A 595 MARKET STREET, 29TH FLOOR ● SAN FRANCISCO, CA 94105 USA
PHONE (415) 580-6900 ● FAX (415) 580-6902
THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY
REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE
WRITTEN CONSENT OF SUNRUN SOUTH LLC.
M.Watkins
REVISION:Solar Mounting Solutions
2
1
3
4
IT QTY
1
EM
2
3
4
MATERIALS:
DESIGN LOAD (LBS):
ULTIMATE LOAD (LBS):
TORQUE SPECIFICATION:
CERTIFICATION:
WEIGHT (LBS):
PARTS LIST
DESCRIPTION
1 SNAPNRACK, L FOOT FLASHING, 12IN X 12IN, BLACK GALV
1 SNAPNRACK, CONDUIT SUPPORT STANDOFF SUBASSEMBLY
1 SCREW, LAG, 5/16IN X 1-1/2IN, HEX, SS
1 SNAPNRACK, L FOOT BASE, MILL
6000 SERIES ALUMINUM, STAINLESS STEEL, ZINC PLATED STEEL, GALV STEEL
N/A
N/A
N/A LB-FT
N/A
1.11
DESCRIPTION:DRAWN BY:
SNAPNRACK, CONDUIT SUPPORT COMP SHINGLE
PART NUMBER(S):
242-02106
M.Watkins
REVISION:
A
Solar Mounting Solutions
595 MARKET STREET, 29TH FLOOR ● SAN FRANCISCO, CA 94105 USA
PHONE (415) 580-6900 ● FAX (415) 580-6902
THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY
REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE
WRITTEN CONSENT OF SUNRUN SOUTH LLC.
11.25 12.00
6.00
12.00
1.00
3.36
.271.82 1.00
.02
2.00
3.65
ALL DIMENSIONS IN INCHES CONDUIT SUPPORT
SPECIFICATION
Karnak Application
1- Apply Karnak #19 (2" dob)
2- Press Firmly down on Shingles to
spread Karnak #19
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2020.10.13 07:10:49 -05:00
12 / 16
ENPHASE 80A
AC COMBINER
BOX
10A BREAKER
(ENVOY)
20A BREAKER (A)
20A BREAKER (B)
20A BREAKER (C)
2A
2B
2C
3
GND
NEU
TERMINATION CAP
INSTALLED ON
END OF CABLE
=...==
INVERTERS
INSTALLED ON
RAIL SYSTEM
=...==
=...==
1A TO 1C
ROOF
JUNCTION
BOX
BRANCH CIRCUIT A
10 MICRO-INVERTERS
BRANCH CIRCUIT B
10 MICRO-INVERTERS
BRANCH CIRCUIT C
7 MICRO-INVERTERS
27 LG LG 350N1C-V5 350W MODULES PAIRED WITH
27 ENPHASE IQ7PLUS-72-2-US MICRO-INVERTERS
GND BUS
NEU BUS
POWER
GROUND
EXISTING SQUARE D 200A
MAIN SERVICE PANEL 240 V
MAIN BREAKER: 200A
200A
UTILITY
METER
GRID
GND BUS
NEU BUS
POWER
GROUND
EXISTING SQUARE D 200A
MAIN SERVICE PANEL 240 V
MAIN BREAKER: 200A
200A
UTILITY
METER
GRID
GND
NEU
4
EATON 60A FUSIBLE
SOLAR AC DISCONNECT
45A
45A FUSES
SOLAR CIRCUIT
DISCONNECTING MEANS
GND BUS
NEU BUS
POWER
GROUND
EXISTING SQUARE D 200A
MAIN SERVICE PANEL 240 V
MAIN BREAKER: 200A
200A
UTILITY
METER
GRID
PV SYSTEM CURRENT 40.8375 A
SOLAR
AC
DISCONNECT
EMPHASE
COMBINER
BOX
EXISTING
METER
MSP LOCATED INSIDE
OF STRUCTURE
MSP
#2/0 AWG SERVICE
CONDUCTOR FROM
UNDERGROUND
HOT LINE TAPS
MINUMUM BEND
RADIUS 4"
ENCLOSURE DIMENSIONS
LENGTH: 21.31"
WIDTH:10.3"
DEPTH:9.06"
#2/0 AWG SERVICE
CONDUCTOR FROM
UTILITY METER FOR
200AMP SERVICE
Wire Tag Conduit Wire Qty Wire
Gauge Wire Type Temp.
Rating
Wire
Ampacity (A)
Temp.
Derate
Conduit
Fill Derate
Derated
Ampacity (A)
Inverter
Qty NOC (A)NEC
Correction
Design
Current (A)
Ground
Size
Ground Wire
Type
1A TO 1C OPEN AIR 3 12 AWG Trunk Cable 90°C 30 0.96 1 28.80 10 1.21 1.25 15.13 06 AWG BARE CU
2A 1” PVC 2 10 AWG THWN-2 75°C 35 0.96 0.8 26.88 10 1.21 1.25 15.13 08 AWG THWN-2
2B 1” PVC 2 10 AWG THWN-2 75°C 35 0.96 0.8 26.88 10 1.21 1.25 15.13 08 AWG THWN-2
2C 1” PVC 2 10 AWG THWN-2 75°C 35 0.96 0.8 26.88 7 1.21 1.25 10.59 08 AWG THWN-2
3 1” PVC 3 + G 08 AWG THWN-2 75°C 50 0.96 1 48.00 27 1.21 1.25 40.84 08 AWG THWN-2
4 1” PVC 3 + G 06 AWG THWN-2 75°C 65 0.96 1 62.40 27 1.21 1.25 40.84 THWN-2
THREE LINE DIAGRAM
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-4
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
KHODIA PIERRE - MS63966
8006 SANTA CLARA BOULEVARD
FORT PEARCE, FL 34951
3057679117
GCP
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
10/13/2020
SYSTEM SIZE (DC ): 9.45 KW
27 MODULES: LG LG 350N1C-V5
27 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
ELECTRICAL SERVICE ELEVATION INTERCONNECTION DETAIL
FSEC CERTIFICATION STATEMENT:
PER FL. STATUE 377.705 (REVISED 7/1/2017), I, MINA A.
MAKAR PE# 86753 AN ENGINEER LICENSED PURSUANT TO
CHAPTER 471,CERTIFY THAT THE PV ELECTRICAL SYSTEM AND
ELECTRICAL COMPONENTS ARE DESIGNED AND APPROVED
USING THE STANDARDS CONTAINED IN THE MOST RECENT
VERSION OF THE FLORIDA BUILDING CODE. FBC 2017
NOTE: LETTER "G" IN WIRE QTY TAB STANDS FOR GROUNDING CONDUCTOR.
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2020.10.13 07:10:49 -05:00
13 / 16
ELECTRICAL NOTES
SUB PANEL
BREAKER SIZE
# OF MODULES PV BREAKER
PER BRANCH
UP TO 16 20A
PV MODULE RATINGS
MODULE MAKE LG
MODEL LG350N1C-V5
MAX POWER 350W
OPEN CIRCUIT VOLTAGE 41.3V
MPP VOLTAGE 35.3V
SHORT CIRCUIT CURRENT 10.61A
MPP CURRENT 9.92A
NUMBER OF MODULES 27
UL1703 COMPLIANT YES
INVERTER RATINGS
INVERTER MAKE ENPHASE
MODEL IQ7PLUS-72-2-
US
MAX OUTPUT POWER 290W
OPEN DC VOLTAGE 60V
NOMINAL AC VOLTAGE 240V
MAX AC CURRENT 1.21A
CEC INVERTER EFFICIENCY 97%
NUMBER OF INVERTERS 27
UL1703 COMPLIANT YES
VOLTAGE DROP CALCULATIONS
FORMULA USED PER NEC 2014 HANDBOOK 215.2(A)(4) WHERE APPLICABLE
WIRE RUN Vmp Imp R L (FT)Vo % Vo WIRE SIZE
BRANCH TO J-BOX 240.00
J-BOX TO LOAD
CENTER 240.00
LOAD CENTER TO AC
DISCONNECT 240.00
AC DISCONNECT TO
INTERCONNECTION 240.00
12.1 1.98 65.83 3.154 1.31%12 AWG
32.67 1.24 50.00 4.051 1.69%10 AWG
40.8375 0.778 3.00 0.191 0.08%08 AWG
40.8375 0.491 10.00 0.401 0.17%06 AWG
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-4.1
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
KHODIA PIERRE - MS63966
8006 SANTA CLARA BOULEVARD
FORT PEARCE, FL 34951
3057679117
GCP
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
10/13/2020
SYSTEM SIZE (DC ): 9.45 KW
27 MODULES: LG LG 350N1C-V5
27 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
THIS SOLAR PHOTOVOLTAIC SYSTEM COMPLIES WITH THE 2017
FLORIDA BUILDING CODE AND THE 2014 NATIONAL ELECTRICAL CODE
1.ALL CALCULATIONS FOR VOC, VMAX, IMP AND ISC HAVE BEEN
CALCULATED USING THE MANUFACTURED STRING CALCULATOR
BASED ON ASHRAE 2% HIGH AND EXTREME MINIMUM TEMPERATURE
COEFFICIENTS.
2.THE ENTIRE ARRAY IS BONDED ACCORDING TO (NEC 690.46 - 250.120
PARAGRAPH C). THE GROUND IS CARRIED AWAY FROM THE
GROUNDING LUG USING #6 BARE COPPER WIRE OR #8 THWN-2 COPPER
WIRE.
3.THIS SYSTEM COMPLIES WITH NEC 2014
4.BRANCH CIRCUIT CALCULATION FOR WIRE TAG 1 DISPLAYS THE
LARGEST BRANCH CIRCUIT IN SYSTEM. OTHER BRANCH CIRCUITS
SHALL HAVE LOWER DESIGN CURRENT THAN THE ONE SHOWN. IN
ADDITION, VOLTAGE DROP CALCULATIONS FROM PANELS TO THE
COMBINER BOX SHALL BE SHOWN IN A SIMILAR FASHION
5.ALL CONDUCTORS ARE SIZED BASED ON NEC 2014 ARTICLE 310
6.ALL EQUIPMENT INSTALLED IS RATED AT 75°C
7.INVERTER NOC (NOMINAL OPEN CURRENT) OBTAINED FROM
EQUIPMENT DATASHEET
8.CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH ALL
LOCAL AND NATIONAL CODE REQUIREMENTS.
9.EACH MODULE MUST BE GROUNDED ACCORDING TO USER
INSTRUCTIONS
10.ALL EQUIPMENT SHALL BE LISTED PER NEC 690.4(D)
11.PER NEC 690.17, PROVIDE A WARNING SIGN AT ALL LOCATIONS WHERE
TERMINALS OF THE DISCONNECTING MEANS MAY BE ENERGIZED IN
THE OPEN POSITION> SIGN SHALL READ *WARNING - ELECTRIC SHOCK
HAZARD - DO NOT TOUCH TERMINALS - OR EQUIVALENT.
12.PER NEC 705.10, PROVIDE A PERMANENT PLAQUE OR DIRECTORY
SHOWING ALL ELECTRIC POWER SOURCES ON THE PREMISES AT
SERVICE ENTRANCE.
13.INTERCONNECTION METHOD SHALL COMPLY WITH NEC 690.64
14.AND OPTION FOR A SINGLE CIRCUIT BRANCH TO BE SPLIT INTO TWO
SUB-CIRCUIT BRANCHES IS ACCEPTABLE.
ELECTRICAL NOTES:
15.ALL CONDUCTORS MUST BE COPPER.
16.NEUTRAL AND EQUIPMENT GROUNDING CONDUCTOR BONDED AS PER
NEC 250.24(C).
17.EQUIPMENT GROUNDING CONDUCTOR IS CONNECTED TO A
GROUNDING ELECTRODE SYSTEM PER 250.54(D).
18.FUSES FOR PV DISCONNECT HAVE AIC RATINGS OF 200KA AC AND 20KA
DC.
19.SUPPLY SIDE CONNECTION SHALL BE MADE USING ILSCO INSULATION
PIERCING CONNECTORS (IPC). MAKE, MODEL, AND RATING OF
INTERCONNECTION CAN BE SEEN ON TABLE 1 BELOW.
20.METHOD OF INTERCONNECTION CAN BE SEEN IN FIGURE 1.
21.UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL PHOTOVOLTAIC
SYSTEM COMPONENTS LOCATED AT THE SERVICE ENTRANCE.
22.WORKING CLEARANCES AROUND THE EXISTING AND NEW ELECTRICAL
EQUIPMENT WILL BE MAINTAINED IN ACCORDANCE WITH NEC ARTICLE
110.26.
23.CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT
RESISTANT PER NEC ARTICLE 300.6 (C)(1) AND ARTICLE 310.8 (D).
24.CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR
USE IN WET LOCATIONS PER NEC ARTICLE 310.8 (C).
25.TOTAL AREA OF ALL CONDUCTORS, SPLICES, AND TAPS INSTALLED AT
ANY CROSS SECTION OF THE WIRING DOES NOT EXCEED 75% OF THE
CROSS SECTIONAL AREA OF THE SPACE. NEC 312.8(2).
26.SYSTEM IS CONSIDERED AN AC MODULE SYSTEM. NO DC
CONDUCTORS ARE PRESENT IN CONDUIT, COMBINER, JUNCTION BOX,
DISCONNECT. AND COMPLIES WITH 690.6 - NO DC DISCONNECT AND
ASSOCIATED DC LABELING ARE REQUIRED.
27.SYSTEM COMPLIES WITH 690.12 RAPID SHUTDOWN AND ASSOCIATED
LABELING AS PER 690.56(C). AC VOLTAGE AND SYSTEM OPERATING
CURRENT SHALL BE PROVIDED 690.52.
28.CONDUCTORS IN CONDUIT ARE AC CONDUCTORS BRANCH CIRCUITS
AND NOT PV SOURCE CIRCUITS. 690.6.
29.ALL GROUNDING SHALL COMPLY WITH 690.47(A) IN THAT THE
AC MODULES WILL COMPLY WITH 250.64.
30.NO TERMINALS SHALL BE ENERGIZED IN THE OPEN POSITION
IN THIS AC MODULE SYSTEM 690.17, 690.6.
31. WHERE APPLICABLE: INTERCONNECTION SHALL COMPLY
WITH 705.12(D)(3), 705.12(D)(2)(3)(B), 705.12(A) AS PERMITTED
BY 230.86(6)
MAKE MODEL VOLTAGE
RATING
CONDUCTOR
RANGE MAIN
CONDUCTOR
RANGE TAP
ILSCO IPC 4020 600 V 4/0-4 AWG 6-14 AWG
ILSCO IPC 4006 600 V 4/0-2 AWG 2/0-6 AWG
INSTRUCTIONS FOR LINE TAPS
FIGURE 1:
1.ADJUST THE CONNECTOR NUT TO SUITABLE
LOCATION
2.PUT THE BRANCH WIRE INTO THE CAP SHEATH FULLY
3.INSERT THE MAIN WIRE, IF THERE ARE TWO LAYS OF
INSULATED LAY IN THE MAIN CABLE, SHOULD STRIP A
CERTAIN LENGTH OF THE FIRST INSULATED LAY
FROM INSERTED END
4.TURN THE NUT BY HAND, AND FIX THE CONNECTOR IN
SUITABLE LOCATION.
5.SCREW THE NUT WITH THE SLEEVE SPANNER.
6.SCREW THE NUT CONTINUALLY UNTIL THE TOP PART
IS CRACKED AND DROPPED DOWN
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2020.10.13 07:10:49 -05:00
14 / 16
QUANTITY LOCATION
A
LABELTAG
B
C
D
E
F
1
1
1
JUNCTION BOX
MAIN DISCONNECT
PANEL
1 UTILITY METER
1 COMBINER BOX
1 AC DISCONNECT
EXAMPLES
B
C
D
E
F
PHOTOVOLTAIC SYSTEM
INSTALLED BY MOMENTUM SOLAR
325 HIGH STREET
METUCHEN, NJ 08840
PHONE NUMBER:732-902-6224
OPERATING CURRENT
OPERATION VOLTAGE
A
264 V
PHOTOVOLTAIC SOLAR AC
DISCONNECT WARNING
ELECTRICAL SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING
ELECTRICAL SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH
RAPID SHUTDOWN
WARNINGWARNING
PHOTOVOLTAIC POWER SOURCE
THIS EQUIPMENT FED
BY MULTIPLE SOURCES. TOTAL RATING OF
ALL OVERCURRENT DEVICES, EXCLUDING
MAIN SUPPLY
OVERCURRENT DEVICE, SHALL NOT
EXCEED AMPACITY OF BUSBAR.
LINE SIDE TAP
DUAL POWER SOURCE
SECOND SOURCE IS PHOTOVOLTAIC
SYSTEM
WARNING
NOMINAL AC OPERATING VOLTAGE 240 V
RATED AC OPERATING CURRENT A
DUAL POWER SOURCE
SECOND SOURCE IS PHOTOVOLTAIC
SYSTEM
WARNING
PHOTOVOLTAIC SYSTEM
INSTALLED BY MOMENTUM SOLAR
325 HIGH STREET
METUCHEN, NJ 08840
PHONE NUMBER:732-902-6224
MAIN SERVICE
PANEL
32.67
32.67
A
EQUIPMENT LABELS
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-4.2
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
KHODIA PIERRE - MS63966
8006 SANTA CLARA BOULEVARD
FORT PEARCE, FL 34951
3057679117
GCP
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
10/13/2020
SYSTEM SIZE (DC ): 9.45 KW
27 MODULES: LG LG 350N1C-V5
27 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2020.10.13 07:10:49 -05:00
15 / 16
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
3096 HAMILTON BLVD, SOUTH PLAINFIELD, NJ
(732)902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-5
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
KHODIA PIERRE - MS63966
8006 SANTA CLARA BOULEVARD
FORT PEARCE, FL 34951
3057679117
GCP
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
10/13/2020
SYSTEM SIZE (DC ): 9.45 KW
27 MODULES: LG LG 350N1C-V5
27 INVERTERS: ENPHASE
IQ7PLUS-72-2-US
STRUCTURAL CERTIFICATION
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2020.10.13 07:10:49 -05:00
Powered by TCPDF (www.tcpdf.org)
16 / 16