HomeMy WebLinkAboutBlgd plans, pg 3I.
ALL FOOTING ARE DESIGNED FOR A MINIMUM OF 2,500 PSF SOIL
9.
SLOPE ALL PORCH SLABS, COVERED WALK, ETC. AWAY
BEARING CAPACITY. IF ANY SUB -SOIL, MUCK OR NON -UNIFORM
FROM HOUSE TO DRAINS (IF PROVIDED) PER PLANS
CONDITIONS EXIST, REPORT TO ARCHITECT AND OBTAIN
PROPER ENGINEERING DATA FOR DESIGN,
2.
ALL SLABS AND FOOTINGS TO BE A MINIMUM 2,500 PSI AT 28 DAYS
10•
DESIGN LOADS ARE AS FOLLOWS:
ROOF (DL+LL) = 41 PSF
ALL COLUMNS, FILLED CELLS, AND BEAMS SHALL BE MIN. 3000 PSI
MIX AT 28 DAYS
WiND VELOCITY = PER PERMIT INFO BOX ON SHEET #I
BE 3000 PSI OR 4,000 PSI GROUT
EXPOSURE ="C"
3.
POISON SOIL AND COVER W/ 4 MIL. VISQUEEN WITHIN 24 HOURS. NO
SOIL POISONING TO BE ACCOMPLISHED OUTSIDE OF FOUNDATION.
11.
ALL REINFORCING STEEL SHALL BE GRADE 6O, MEETING ASTM A-14, t
4
GROUND FLOOR SLAB TO BE A MINIMUM 4" THICK W/ LXG 10/10
A-35 SPECIFICATIONS. ALL ANCHOR TO BE A - 301 STEEL.
WELDED WIRE MESH REINFORCING ON 6 MIL. POLYETHYLENE VAPOR
BARRIER TERMITE TREATED, CLEAN MACHINE COMPACTED FILL
12
ALL DOWELS, SLEEVES, CONDUITS, INSERTS, BLOCKOUTS, ANCHOR
5% DENSITY). LAP POLYETHYLENE 12" MINIMUM. FIBERMESH
(MINIMUM 95E
BOLTS AND FRAMES SHALL BE IN PLACE PRIOR TO POURING CONCRETE.
MIX MAY BE SUBSTITUTED FOR WELDED WIRE MESH.
FOR OPENINGS AND SPECIAL FEATURES OMITTED ON THESE PLANS,
SEE ARCHITECTURAL OR MECHANICAL PLANS WHERE APPLICABLE.
5
LOT TO BE CLEARED OF ALL SMALL PLANT GROWTH AND DEBRIS
BEFORE FILL IS BROUGHT IN. FILL TO BE SPREAD IN 12" LAYERS AND
MACHINE COMPACTED TO A MINIMUM OF 2500 PSI IN AREA OF
13.
MINIMUM CONCRETE PROTECTION FOR REINFORCING BARS:
BUILDING CONSTRUCTION
FOOTING: 3"
BEAMS: I-I/2"
6•
TEST FOR FILL COMPACTION MINIMUMS PRIOR TO FORMING SLAB.
14.
LAP ALL REINFORCING STEEL A MINIMUM OF 48 BAR DIAMETERS.
GENERAL CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND
DIMENSIONS. BRiNG ANY DISCREPANCIES OR OMISSIONS TO THE
IS.
USE STRUCTURAL GRADE WOOD WITH A MINIMUM Fb OF 1400 PSI
ATTENTION OF THE ARCHITECT.
IL.
ALL STANDARD LUMBER SHALL BE SYP WITH A MINIMUM Fb OF 1000
8•
GARAGE FLOORS TO BE SMOOTH TROWEL FINISH (SLOPPED PER
PSI OF NO.2 SOUTHERN PiNE, UNLESS NOTED OTHERWISE.
FOUNDATION PLAN). PROVIDE 1-1/2" RECESS FOR OVERHEAD DOOR
11•
ALL LUMBER IN CONTACT WITH ANY CONCRETE OR MASONRY SHALL BE
FO u A D,4T f O N I L A I C
PRESSURE TREATED. FASTENERS TO HAVE MIN. G185 RATING.
1. Any changes to plans must be submitted to the architect
for approval before proceeding with construction.
2. Contractor shall be responsible for verification of all
notation and dimensions before starting construction.
3. Soil conditions assumed to be 2500 psf. Should any other conditions be
encountered, the architect shall be notified in writing for revision
4. Verify all recess thickness at showers, tile, etc....
S. Contractor to provide filled cell with concrete and 1 99 bar vert. at 48"
O.C. max. Provide (1) filled cell on each side of openings up to 5'-11" Wide.
Provide (2) filled cells on each side of openings from ('-O" to 9'-11"
and Provide (3) filled (wells on each side of openings from 10'-0" and up
Contractor to see plans for any other condition used. Foundation walls
shall have filled cells at 24" o.c. unless otherwise noted (see section)
6. Contractor to provide for Form Board Survey - Form Board Survey
to be provided to Truss Company prior to truss construction
1. Contractor to provide for soil test prior to construction and provide
a copy of .5011 test to architect for review prior to construction
8. ALL Reinforcing steel shall be grade 60, meeting ASTM A-16 and
A-35 specifications. ALL. Anchors to be A-301 steel.
9. Provide a minimum of 3" concrete protection at footings and
1-1/2" concrete protection at beams for ALL reinforcing bars.
95 bar wart. w/ SEE TYPICAL
30" overlap ECT YPI
at each filled cell
ONIS
4" concrete slab with fibermash OR
6"x4" #lo/10 WWM on 10 and Visqueen over
clean compacted termite treated fill
Grade
E —
1 —1 I III I I I I- i f tine iwi h (2)cmonolithic #5 baracont
14"
TYPICAL FOOTING DETAIL
SCALE 1/2" = I'-O
4" concrete slab with fibermesh OR
6 xG #10/10 wwm on 10 mil Visqueen over
clean compacted termite treated fill
#5 bar cost.
Step per
o foundation plan
C
12" x 12" concrete column
block lilted with concrete
and (2) #1 bars vert. tied
into lintels above
Top of footer
16" below finished flogr_
L
#5 bars cost. bottom steel
12"
AT GARAGE STEPDOWN
SCALE 1/2" = 1'-0"
Verify house slab
height in field
,.•: ; •:".�^ '`: = 30"x30"xld" concrete
— column rooting with (4)
#S bars each way
30"
FOOTING DETAIL
SCALE 1/2"
Thicken edge to 8"x8"
with concrete and
one 45 bar continuous
GRADEI \
SCALE: 114" = 1'-0"
Termite Protection for New
Construction.
Soil treatment used for subterranean termite prevention
inside the foundation perimeter shall be done after all
excavation, backfilling and compaction is complete.
If soil area is disturbed after initial chemical soil treatment
area shall be re -treated with a chemical soil treatment
including spaces boxed or framed.
Treatment must be in accordance with the rules and laws
established by the Florida Department of Agriculture and
consumer services.
Protective sleeves around metallic piping penetrating
concrete slab on grade floors shall not be of cellulose
containing materials and shall receive application of
termicide in annular space between sleeve and pipe.
4" concrete slab with ribarmesh OR
6"x4" #10/10 WWM on 10 mil Visqueen over
clean compacted termite treated fill
PORCH SLAB EDGE DETAIL
SCALE 1/2" = I'-O"
$95 bar vert. w/
30" overlap
at each filled cell SEE TYPICAL
4""SECTIONS
Adjust curb height
based on gar. floor 4" concrete slab with fibermesh OR
slope. VW #10/10 WWM on 10 mil Visqueen over
#5 bar in curb clean compacted termite treated fill
O'-O"
Grade
dr-% fall
- m E _ —
14"w x 14"d concrete monolithic
footing with (2) #5 bars cont.
14"
n�J GARAGE CURB DETAIL
SCALE 1/2" = 1'-0"
2" x 4" PT wood secured with \
3/8"d(a. x 6" anchor bolt at 18" ox,
overhead door track secured to wood
jamb per manufacturer's product approval
Garage Door Jamb Detail
GARAGE DOOR TO WITHSTAND PRESSURES STATED N T 3
IN PERMIT INFO BOX ON SHEET #1. SEE PRODUCT
APPROVAL FORM FOR MANUFACTURER MAKE AND MODEL.
Filled Cell Masonry Column With One
#5 From Footing To Tie Beam
Conc. Fill To Be 3000 PSI
See Floor Plan For Location
je,ry�
Single Filled Cell Column
NTS
Filled Cell Masonry Column With One
#5 From Footing To Beam Each.
Conc. Fill To Be 3000 PSI
See Floor Plan For Location
Double Filled Cell Column
NTS
OBBraden t Braden AIA, PA
Architects - Planners
41l S.E. Coconut Avenue
Tel : (112) 281-8258
Fax : (712) 281-8283
E-mail: bradenaiascomcast.net
Stuart. FL 34996 #AAC000032
O
i
c
m
I
N
ai
U
A/C
14'-0" 20'-01,
0 0
—
FI
, °
F
J
I
QL —
Oi
Filled cell under
QI
FI
girder above
I
24
m
Rear Patio/Slab
r
n I
to
be poured separat
from the house slat
Thicken footing to
24% x 14"d x 24"L
F� under filled cell
I
°
a
under girder bearing.
I ° °
°
°—
—
T
— — — — —
Rear Patio/Slab to
be flush with
bottom
or
sliding door
recess.
Slope
1/2"
1.1
32'-8"
I
I 4" concrete slab with fiber esh OR
6"x6" #10/10 wWM on 4 mll V squeen over
clean compacted termite tr ated fill
I FI
I
I
I
I
I
4 fill dC Steel wnacrete 0
CQOI
�
avv
EinW I I
I 65 I
I E! I i
E I �—
a au
-II
) d I o
° I �O o Z I
I Oc (N F5I
IF5 ° emu, w I i
°I U (L I° O
x Q —
Ite
I
L — F5 recess for — _ _ _ I r l
Garage Boor — — —
Wynne tsuilcling L.orp.
�2' Grard Carlton II
Spanish Lakes
St. Lucie County Fibrida
JQ
F
6'-2„
12" x I
wih Conc
into hr
FOOTING
S(
Mark
size
De
FI
14"W
x 14"D
MONOLITHIC FOOTING
WI*
F
12"W
X 12"0
MONOLITHIC FOOTING
WI'
F
30"
x 30" x 16"D
COLUMN FOOTING WITH (
F
8"W
x 8"D
THICKEN SLAB EDGE
WI
FS
14"w
With
x 14"D
Curb at Garage
MONOLITHIC FOOTING
Wi
Date Drawn Revisions
3-1-14 10-18-14
GARAGE Drawn by: Approval
LEFT C•c.U.
Checked by:
D.R.B.