Loading...
HomeMy WebLinkAboutBuilding Plan CheckBUILDING PLAN CHECK ST. LUCIE COUNTY -FORT PIERCE FIRE PREVENTION BUREAU FORT PIERCE, FLORIDA TELEPHONE 407-467-2312 FAX 407-467-2325 JURISDICTION: St. Lucie Count PROJECT NAME: MAVERICK BOATS CONTRACTOR: Kennedy A/C Company ARCHITECT: OWNER: LOCATION: 3054 Industrial 31st St. BUILDING SIZE: OCCUPANCY TYPE: Factory Industricl CONSTRUCTION TYPE: SBCCI. NFPA. FIRE PROTECTION: Automatic Sprinkler Yes No Occupancy Hazard N.F.P.A. #13 Requirements: PLAN NUMBER #65278 BUILDING DEPT. NO. PR-30090 PHONE NUMBER 407-778-8276 PHONE NUMBER DATE RECEIVED 1-27-93 1-27-93 NUMBER OF STORIES BUILDING HEIGHT 1. A separate permit is required for the spray booth sprinkler system. 2. Glass panels shall be tempered or wire glass. 3. Electrical installations within 3' of any booth opening shallil'be installed in Class I or Class II division 1 according to NEC Article 500. 4. Provide a minimum of a 20BC rated fire extinguisher outside but adjacent to the spray booth 5. Filters shall be of a listed type. REVIEWED BY: CONTRACTORS RESPONSIBILITY TO NOTIFY BUREAU ON ALL INSPECTIONS HOUR NOTICE REQUIRED ON ALL INSPECTIONS DATE_L2 7. F,3 Sheet No. � of (