HomeMy WebLinkAboutBuilding Plan CheckBUILDING PLAN CHECK
ST. LUCIE COUNTY -FORT PIERCE FIRE PREVENTION BUREAU
FORT PIERCE, FLORIDA
TELEPHONE 407-467-2312
FAX 407-467-2325
JURISDICTION:
St. Lucie Count
PROJECT NAME:
MAVERICK BOATS
CONTRACTOR:
Kennedy A/C Company
ARCHITECT:
OWNER:
LOCATION:
3054 Industrial 31st St.
BUILDING SIZE:
OCCUPANCY TYPE: Factory Industricl
CONSTRUCTION TYPE: SBCCI.
NFPA.
FIRE PROTECTION: Automatic Sprinkler Yes
No
Occupancy Hazard N.F.P.A. #13
Requirements:
PLAN NUMBER
#65278
BUILDING DEPT. NO.
PR-30090
PHONE NUMBER
407-778-8276
PHONE NUMBER
DATE RECEIVED
1-27-93
1-27-93
NUMBER OF STORIES
BUILDING HEIGHT
1. A separate permit is required for the spray booth sprinkler system.
2. Glass panels shall be tempered or wire glass.
3. Electrical installations within 3' of any booth opening shallil'be installed in Class I or
Class II division 1 according to NEC Article 500.
4. Provide a minimum of a 20BC rated fire extinguisher outside but adjacent to the spray booth
5. Filters shall be of a listed type.
REVIEWED BY:
CONTRACTORS RESPONSIBILITY TO NOTIFY BUREAU ON ALL INSPECTIONS
HOUR NOTICE REQUIRED ON ALL INSPECTIONS
DATE_L2 7. F,3
Sheet No. � of (