HomeMy WebLinkAboutFire District Plan Reviewr
P.O. BOX 3030
FT. PIERCE FL. 34948-3030
2400 RHODE ISLAND AVE.
FT. PIERCE FL. 34950
ST. LUCIE COUNTY FIRE DISTRICT
BUREAU OF FIRE PREVENTION
PLAN REVIEW
JURISDICTION: St. Lucie County
OCCUPANCY: Glyco International
ADDRESS: 15965 West Parl Lane
CONTRACTOR: Brian Hacht (OB).
ARCHITECT/ENGINEER: H. Steve Clark
BUILDING OWNER:
OCCUPANCY TYPE: Flammable Liquid Tank Containment
GROSS SQ FT:
OCCUPANT LOAD:
CONSTRUCTION TYPE:( NFPA-220) Type:.
New Construction: X Automatic Sprinkler: Contractor:
Tenant Improvement: Fire Alarm System Contractor:
Shell Only: Fixed Fire Suppression: Contractor:
Addition: Hood & Duct System: Contractor:
Renovation: Fuel Storage: Contractor:
TELEPHONE
FAX NO.
(561)-462-2312
(561)-462-2323
F.P.B. # 1043
BUILDING DEPT. NO: 9806-0505
NUMBER OF STORIES:
PHONE NO: 465-1280
PHONE NO:
REVIEW DATE:
AUTOMATIC SP'KLRS:
NET SQ FT:
BASED ON:
SBCCI: Type: Unprotected
1. All revisions must be in compliance before the final inspection, or so noted.
2. The Fire Marshal requires 24 hr. notice on all inspections.
" 3. The Building Departments schedule all final inspections by the Fire Marshal.
4. A copy of the required revisions has been mailed to the Architect: — Contractor: _ Yes: _ No: X
Required Revisions:
Containment Areas (3) for the storage of six 3,500 gal above ground storage tanks.
1. The Volumetric Capacity of the containment area shall not be less than the greatest amount
of liquid that can be released from the largest tank to be filled.
2. The floor drain shall be equipped with not less than a non combustible 2 inch drain. The
drain shall be equipped with a non-combustible valve and lock. Because the liquid is classified as
a Class, 1-13 Flammable piping and valves shall be brass or other material that will not cause a
spark.
3. A.Slope of not less than 1 percent away from the tank(s) and toward the floor drain shall be
provided. '
4. Emergency venting and normal venting for the tanks shall meet the requirements of NFPA.
- #30
5. Wall and floors of the containment area shall be concrete or masonry design an liquid tight
and non -absorbent
6. The minimum distance between the tank and the containment wall shall be not less
than three feet.
.-j .
7. The minimum distance between any two tanks in a single containment area shall be 3
ft.
8. Provide a 20A-120 B/C rated fire extinguisher for each 50 ft of travel distance.
9. The business owner shall prepare and submit a hazardous chemical data sheet
indicating the flammable liquid hazard and relative information necessary for the haz-mat
control team. This data sheet shall be submitted to the St. Lucie County Fire Marshal's office. t
Revie Date: July 6, 1998
John K. Hay n