HomeMy WebLinkAboutFire Prevention Plan Review7
ST LUCIE COUNTY FIRE DISTRICT
BUREAU OF FIRE PREVENTION
PLAN REVIEW 1
2400 Rhode Island Avenue
Ft Pierce, FL 34950
mew Construction ( )Tenant Improvement ( )Addition
Jurisdiction:
Occupancy:
Address:
Contractor
Contractor's Address:
Architect/Engineer:
Building Owner:
Occupancy Type:
Gross sq ft:
Occupant Load:
Construction Type:
SLC
Cold Air Distributors
3053 Industrial 31st St
RK Davis Construction
PO Box 186
Paul Welch
Storage
88,875
HellV=
Telephone: 561-462-2312
FAX: 561-462-2323
( )Renovation/alterations ( )Shell Only
F.P.B.:
B-01-67
Building Dept:
21020070
Number of stories:
1
Phone #
561-461-8335
City: .
Ft. Pierce
Phone #
561-785-9888
Review Date:
4/26/2001
Automatic sprinklers:
Required
Net sq ft:
Based On:
SBCCI Type:
IV unp
1. All revisions must be in compliance before the final inspection.
2. The Fire Marshal requires 24 hour notice on all inspections.
3. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
4. Permit fees are required to be paid in full prior to any inspections.
5. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. A copy of the required revision/s have been transmitted to the Architect () Contractor ( ).
7. Penetrations through rated assemblies shall be of proper UL design.
8. UL design criteria shall be submitted with the construction plans.
REVISIONS REQUIRED
KNOX BOX IS REQUIRED (XX) KNOX KEY SWITCH REQ
r /� �✓-
1. HVAC shutdown is indicated. See attached additional requirements. � Iv
2. A separate permit is required for the installation of the fire alarm system.
3. A fire sprinkler permit has been obtained.
,4: Handrails are required on both sides of the stairs:
5. The door leading to the foyer from the classroom shall be equipped with panic hardware.
6. Portable fire protection is required. Minimum classification is one 2A-10B:C rated extinguisher
every 75 feet of travel distance.
7. Exit and emergency lighting is not shown in the warehouse area. Provide exit and emergency
lighting throughout, including directional exit lights. This will be shown on the floor plan with the rack
setup.
8. Seal the fire wall at the roof with applicable UL fire caulk not drywall tape and mud.
Reviewed by: / N� Date: 4/26/2001