HomeMy WebLinkAboutEnergy Calculation Form & Manual J's (2) Project $ Job:. RON HILL
+ Wrightsaoit® Pro j Summary Date: Dec 22,2016
Enure House By: CHEROKEE
Project lnfo on
For: RON HILL
3402AVENUE R, FT PIERCE, FL 34950
Notes:
Design Information
Weather: West Palm Beach, FL, US
Winter Design Conditions Summer Design Conditions
i
Outside db 45 OF Outside db 94 OF
Inside db 70 OF Inside db 75 OF
Design TD 25 OF Design TD 19 OF
Daily range L
Relative humidity 50 %
Moisture difference 68 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 0 Btuh Structure 23960 Btuh
' Ducts 0 Btuh Ducts 0 Btuh
Central vent(0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping' 0 Btuh
Equipment load 0 Btuh Use manufacturer's data n
Rate/swing multiplier 0.99
Infiltration Equipment sensible load 23721 Btuh
Method; Simplified Latent Cooling Equipment Load Sizing-
Construction quality Average
Fireplaces 0 Structure 10219 Btuh
Ducts 0 Btuh
Heating Cooling Central vent (0 cfm) 0 Btuh
Area(ftz) 0 1406 Equipment latent load 10219 Btuh
Volume(ft3) 0 12654
Air_chart es/hour 0.61 0.23 (eq.
quipment total load 33940 Btuh
Equiv.AVF(cfm) 0 49 total capacity at 0.70 SHR 2.8 ton
Heating Equipment Summary Cooling Equipment Summary
Make 'Make Coleman, Unitary Products Group
Trade Trade CHAMPION
Model Cond TC73621
AHRI ref Coil AE36BX21+TXV
AHRI ref ' RATED
Efficiency 100 EFF Efficiency 13.0 EER,16.25 SEER
Heating input 0 kW Sensible cooling 24780 Btuh
Heating output 0 Btuh Latent cooling 10620 Btuh
Temperature rise 0 OF Total cooling 35400 Btuh
Actual air flow 1113 cfm Actual air flow 1113 cfm
Air flow factor 0 cfm/Btuh '`Air flow factor 0.046 cfm/Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat 11-oad sensible heat ratio 0.70
9
Bold/italic values have beeiImanually overridden
Calculations approved.by ACCA to meet�all requirements of Manual J 8th Ed.
'wi� htso ft- 2016 Dec-22 16: e 1
, Right-Suite®Universal 2015 15.0.18 RSU15842 Page 1
Project2sup Calc=MJ8 Front Door faces: N f I wi t
i _ l
Prot S Job: RON HILL
-�- wrightsoft Project Y
ummar Date: Dec 22,2016
Entire House By: CHEROKEE
v
Projedt Information
For: RON HILL
3402 AVENUE R, FT PIERCE, FL 34950 .
Notes:
Design Inforination
Weather: West Palm Beach, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 45 OF Outside db 94 OF
Inside db 70 OF Inside db 75 OF
Design TD 25 OF Design TD 19 OF
Daily range L
Relative humidity 50 %
Moisture difference 68 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 0 Btuh Structure 23960 Btuh
Ducts 0 Btuh Ducts 0 Stuh
Central vent (0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 0 Btuh Use manufacturer's data n .
Rate/swing multiplier 0.99
Infiltration Equipment sensible load 23721 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 10219 Btuh
Ducts 0 Btuh
Heating Cooling Central vent (0 cfm) 0 Btuh
Area(ftl)' 0 1406 Equipment latent load 10219 Btuh
Volume(ft3) 0 12654
Air changes/hour 0.61 0.23 .Equipment total load 33940 Btuh
Equiv.AVF(cfm) 0 49 Req. total capacity at 0.70 SHR 2.8 ton
Heating Equipment Summary Cooling Equipment Summary
Make Make Coleman, Unitary Products Group
Trade Trade CHAMPION
Model Cond TC73621
AHRI ref Coil AE36BX21+TXV
AHRI ref RATED
Efficiency 100 EFF Efficiency 13.0 EER,16.25 SEER
Heating input 0 kW Sensible cooling 24780 Btuh
Heating output 0 Btuh Latent cooling 10620 Btuh
Temperature rise 0 OF Total cooling 35400 Btuh
Actual air flow 1113 cfm Actual air flow 1113 cfm
Air flow factor 0 cfm/Btuh Air flow factor 0.046 cfm/Btuh'
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat -Load sensible heat ratio 0.70
Bold/italic values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wr'l h tsC ft. yam Dec-22 16:age I
Right-Suite®Universal 2015 15.0.18 RSU15842 ��1�°J'�`��{ Page
Project2.rup' Calc=MJ8 Front Door faces: N r,.L
7N
Akl�
all,
JV
M-5 •O�Q
qq V-
"I oz �
Ty
-,N 1 rl
"w" tO
j
Project Summary Job: RON HILL
wrightsoW r/ Date: CDee H 22,201
Entire House y
Project
For: RON HILL
3402AVENUE R, FT PIERCE, FL 34950
Notes:
I
Design Information
Weather: West Palm Beach, FL, US
Winter Design Conditions Summer Design-Conditions
Outside db 45 OF Outside db 94 OF
Inside db 70 OF Inside db 75 OF
Design TD 25 OF Design TD 19 OF
Daily range L
Relative humidity 50 %
Moisture difference 68 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 0 Btuh Structure 23960 Btuh
Ducts 0 Btuh Ducts 0 Btuh
Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
i Piping 0 Btuh
Equipment load 0 Btuh Use manufacturer's data n
Rate/swing multiplier 0.99
Infiltration Equipment sensible load 23721 Btuh
Method. Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 10219 Btuh
Ducts 0 Btuh
Heating Cooling Central vent(0 cfm) 0 Btuh
Area(ftz) 0 1406 Equipment latent load 10219 Btuh
Volume,(ft3) 0 12654 r`)
Air changes/hour 0.61 0.23 Equipment total load 33940 Btuh
Equiv.AVF(cfm) 0 49 )2eq.total capacity at 0.70 SHR 2.8 ton
Heating Equipment Summary Cooling Equipment Summary
Make Make Coleman, Unitary Products Group
Trade Trade CHAMPION
Model Cond TC73621
AHRI ref Coil AE36BX21+TXV
AHRI ref RATED
Efficiency 100 EFF Efficiency 13.0 EER,16.25 SEER
Heating input 0 kW Sensible cooling 24780 Btuh
Heating output 0 Btuh Latent cooling 10620 Btuh
Temperature rise 0 OF Total cooling 35400 Btuh
Actual air flow 1113 cfm Actual air flow 1113 cfm
C Air flow factor 0 cfm/Btuh 'Air flow factor 0.046 cfm/Btuh
Static pressure 0 in H2O
Space thermostat nLoad sensible heat ratio 0.70 in H2O
l
Bold/italic values have beebZ manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
we, hts0fto _ 2016-Dec-22 16:51:18
Right-Suited Universal 2015 15.0.18 RSU15642 Pagel
04C�Project2.rup Calc=MJ8 Front Door faces: N t ®N�RA�T®R COPY
I
Project Summary Job: RON HILL
wrightSOft` ry Date: Dec 22,2016
Entire House By: CHEROKEE
Project
• For: RON HILL
3402AVENUE R, FT PIERCE, FL 34950
;
Notes:
i
Design Information
Weather: West Palm Beach, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 45 OF Outside db 94 OF
Inside db 70 OF Inside db 75 OF
Design TD 25 OF Design TD 19 OF
Daily range L
Relative humidity 50 %
Moisture difference 68 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 0 Btuh Structure 23960 Btuh
Ducts 0 Btuh Ducts 0 Btuh
Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping ' 0 Btuh
Equipment load 0 Btuh Use manufacturer's data n
Rate/swing multiplier 0.99
Infiltration Equipment sensible load 23721 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 10219 Btuh
Ducts 0 Btuh
Heating Cooling Central vent(0 cfm) 0 Btuh
Area(ftZ) 0 1406 . Equipment latent load 10219 Btuh
Volume(ft') 0 12654
Air changes/hour 0.61 0.23 Equipment total load 33940 Btuh
Equiv.AVF(cfm) 0 49 Req. total capacity at 0.70 SHR 2.8 ton
Heating Equipment Summary Cooling Equipment Summary
Make Make Coleman, Unitary Products Group
Trade Trade CHAMPION
Model Cond TC73621
AHRI ref Coil AE36BX21+TXV
AHRI ref RATED
Efficiency 100 EFF Efficiency 13.0 EER,16.25 SEER
Heating input 0 kW Sensible cooling 24780 Btuh
Heating output 0 Btuh Latent cooling 10620 Btuh
Temperature rise 0 OF Total cooling 35400 Btuh
Actual air flow 1113 cfm Actual air flow 1113 cfm
Air flow factor 0 cfm/Btuh Air flow factor 0.046 cfm/Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat Load sensible heat ratio 0.70
Bofd/italic values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
�� �� � 2016-Dec-2216:51:18
Right-Suitee Universal 2015 15.0.18 RSU15842 �q p Pa
ge 1
ACCK Project2.rup Calc=MJ8 Front Door faces: N CONTRACTOR C®®�