Loading...
HomeMy WebLinkAboutEnergy Calculation Form & Manual J's (2) Project $ Job:. RON HILL + Wrightsaoit® Pro j Summary Date: Dec 22,2016 Enure House By: CHEROKEE Project lnfo on For: RON HILL 3402AVENUE R, FT PIERCE, FL 34950 Notes: Design Information Weather: West Palm Beach, FL, US Winter Design Conditions Summer Design Conditions i Outside db 45 OF Outside db 94 OF Inside db 70 OF Inside db 75 OF Design TD 25 OF Design TD 19 OF Daily range L Relative humidity 50 % Moisture difference 68 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 0 Btuh Structure 23960 Btuh ' Ducts 0 Btuh Ducts 0 Btuh Central vent(0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping' 0 Btuh Equipment load 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.99 Infiltration Equipment sensible load 23721 Btuh Method; Simplified Latent Cooling Equipment Load Sizing- Construction quality Average Fireplaces 0 Structure 10219 Btuh Ducts 0 Btuh Heating Cooling Central vent (0 cfm) 0 Btuh Area(ftz) 0 1406 Equipment latent load 10219 Btuh Volume(ft3) 0 12654 Air_chart es/hour 0.61 0.23 (eq. quipment total load 33940 Btuh Equiv.AVF(cfm) 0 49 total capacity at 0.70 SHR 2.8 ton Heating Equipment Summary Cooling Equipment Summary Make 'Make Coleman, Unitary Products Group Trade Trade CHAMPION Model Cond TC73621 AHRI ref Coil AE36BX21+TXV AHRI ref ' RATED Efficiency 100 EFF Efficiency 13.0 EER,16.25 SEER Heating input 0 kW Sensible cooling 24780 Btuh Heating output 0 Btuh Latent cooling 10620 Btuh Temperature rise 0 OF Total cooling 35400 Btuh Actual air flow 1113 cfm Actual air flow 1113 cfm Air flow factor 0 cfm/Btuh '`Air flow factor 0.046 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat 11-oad sensible heat ratio 0.70 9 Bold/italic values have beeiImanually overridden Calculations approved.by ACCA to meet�all requirements of Manual J 8th Ed. 'wi� htso ft- 2016 Dec-22 16: e 1 , Right-Suite®Universal 2015 15.0.18 RSU15842 Page 1 Project2sup Calc=MJ8 Front Door faces: N f I wi t i _ l Prot S Job: RON HILL -�- wrightsoft Project Y ummar Date: Dec 22,2016 Entire House By: CHEROKEE v Projedt Information For: RON HILL 3402 AVENUE R, FT PIERCE, FL 34950 . Notes: Design Inforination Weather: West Palm Beach, FL, US Winter Design Conditions Summer Design Conditions Outside db 45 OF Outside db 94 OF Inside db 70 OF Inside db 75 OF Design TD 25 OF Design TD 19 OF Daily range L Relative humidity 50 % Moisture difference 68 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 0 Btuh Structure 23960 Btuh Ducts 0 Btuh Ducts 0 Stuh Central vent (0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 0 Btuh Use manufacturer's data n . Rate/swing multiplier 0.99 Infiltration Equipment sensible load 23721 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 10219 Btuh Ducts 0 Btuh Heating Cooling Central vent (0 cfm) 0 Btuh Area(ftl)' 0 1406 Equipment latent load 10219 Btuh Volume(ft3) 0 12654 Air changes/hour 0.61 0.23 .Equipment total load 33940 Btuh Equiv.AVF(cfm) 0 49 Req. total capacity at 0.70 SHR 2.8 ton Heating Equipment Summary Cooling Equipment Summary Make Make Coleman, Unitary Products Group Trade Trade CHAMPION Model Cond TC73621 AHRI ref Coil AE36BX21+TXV AHRI ref RATED Efficiency 100 EFF Efficiency 13.0 EER,16.25 SEER Heating input 0 kW Sensible cooling 24780 Btuh Heating output 0 Btuh Latent cooling 10620 Btuh Temperature rise 0 OF Total cooling 35400 Btuh Actual air flow 1113 cfm Actual air flow 1113 cfm Air flow factor 0 cfm/Btuh Air flow factor 0.046 cfm/Btuh' Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat -Load sensible heat ratio 0.70 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wr'l h tsC ft. yam Dec-22 16:age I Right-Suite®Universal 2015 15.0.18 RSU15842 ��1�°J'�`��{ Page Project2.rup' Calc=MJ8 Front Door faces: N r,.L 7N Akl� all, JV M-5 •O�Q qq V- "I oz � Ty -,N 1 rl "w" tO j Project Summary Job: RON HILL wrightsoW r/ Date: CDee H 22,201 Entire House y Project For: RON HILL 3402AVENUE R, FT PIERCE, FL 34950 Notes: I Design Information Weather: West Palm Beach, FL, US Winter Design Conditions Summer Design-Conditions Outside db 45 OF Outside db 94 OF Inside db 70 OF Inside db 75 OF Design TD 25 OF Design TD 19 OF Daily range L Relative humidity 50 % Moisture difference 68 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 0 Btuh Structure 23960 Btuh Ducts 0 Btuh Ducts 0 Btuh Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh i Piping 0 Btuh Equipment load 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.99 Infiltration Equipment sensible load 23721 Btuh Method. Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 10219 Btuh Ducts 0 Btuh Heating Cooling Central vent(0 cfm) 0 Btuh Area(ftz) 0 1406 Equipment latent load 10219 Btuh Volume,(ft3) 0 12654 r`) Air changes/hour 0.61 0.23 Equipment total load 33940 Btuh Equiv.AVF(cfm) 0 49 )2eq.total capacity at 0.70 SHR 2.8 ton Heating Equipment Summary Cooling Equipment Summary Make Make Coleman, Unitary Products Group Trade Trade CHAMPION Model Cond TC73621 AHRI ref Coil AE36BX21+TXV AHRI ref RATED Efficiency 100 EFF Efficiency 13.0 EER,16.25 SEER Heating input 0 kW Sensible cooling 24780 Btuh Heating output 0 Btuh Latent cooling 10620 Btuh Temperature rise 0 OF Total cooling 35400 Btuh Actual air flow 1113 cfm Actual air flow 1113 cfm C Air flow factor 0 cfm/Btuh 'Air flow factor 0.046 cfm/Btuh Static pressure 0 in H2O Space thermostat nLoad sensible heat ratio 0.70 in H2O l Bold/italic values have beebZ manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. we, hts0fto _ 2016-Dec-22 16:51:18 Right-Suited Universal 2015 15.0.18 RSU15642 Pagel 04C�Project2.rup Calc=MJ8 Front Door faces: N t ®N�RA�T®R COPY I Project Summary Job: RON HILL wrightSOft` ry Date: Dec 22,2016 Entire House By: CHEROKEE Project • For: RON HILL 3402AVENUE R, FT PIERCE, FL 34950 ; Notes: i Design Information Weather: West Palm Beach, FL, US Winter Design Conditions Summer Design Conditions Outside db 45 OF Outside db 94 OF Inside db 70 OF Inside db 75 OF Design TD 25 OF Design TD 19 OF Daily range L Relative humidity 50 % Moisture difference 68 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 0 Btuh Structure 23960 Btuh Ducts 0 Btuh Ducts 0 Btuh Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping ' 0 Btuh Equipment load 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.99 Infiltration Equipment sensible load 23721 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 10219 Btuh Ducts 0 Btuh Heating Cooling Central vent(0 cfm) 0 Btuh Area(ftZ) 0 1406 . Equipment latent load 10219 Btuh Volume(ft') 0 12654 Air changes/hour 0.61 0.23 Equipment total load 33940 Btuh Equiv.AVF(cfm) 0 49 Req. total capacity at 0.70 SHR 2.8 ton Heating Equipment Summary Cooling Equipment Summary Make Make Coleman, Unitary Products Group Trade Trade CHAMPION Model Cond TC73621 AHRI ref Coil AE36BX21+TXV AHRI ref RATED Efficiency 100 EFF Efficiency 13.0 EER,16.25 SEER Heating input 0 kW Sensible cooling 24780 Btuh Heating output 0 Btuh Latent cooling 10620 Btuh Temperature rise 0 OF Total cooling 35400 Btuh Actual air flow 1113 cfm Actual air flow 1113 cfm Air flow factor 0 cfm/Btuh Air flow factor 0.046 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.70 Bofd/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. �� �� � 2016-Dec-2216:51:18 Right-Suitee Universal 2015 15.0.18 RSU15842 �q p Pa ge 1 ACCK Project2.rup Calc=MJ8 Front Door faces: N CONTRACTOR C®®�