HomeMy WebLinkAboutPiling Design AnalysisCool and Cobb Engineering Company
Date: 7 23 20
Job: Jade & Bryan Wright
Location: 6820 Wadsworth Terrace
Port St. Lucie, FL 34952
PILING DESIGN ANALYSIS
The load requirements for the pilings designed to assist in supporting the identified areas of the subject
residence were determined. The selected piling locations and the specific piling are identified on the Pier
Identification and Location Plan attached. The calculated total loads on the piles in the specific location,
including both dead and live loads are documented in the attached table which is designated as Attachment "A".
Based on the total load requirements for each of these piles, the 12ALS driver is to be employed. The 12ALS
torque driver should be employed with a selected gauge pressure of 1,000 psi, which will provide pile
capacity, including the 2 to 1 safety factor of 24,000 lbs. which is greater than the maximum calculated total
load of 12,000 lbs. which occurs on the pile identified as no. 1 . Based on this analysis, the use of the
12ALS torque driver for the piles with a specific gauge pressure of 1,000 , psi and a minimum depth of 10' is
approved and certified as meeting all of the requirements of the Florida Building Code 2017 6th Edition, and good
engineering practice. This is not to be the primary support structure, but a supplement support to assist in
support of the weight of the structure, which will reduce the total pressure on the existing soils. After
completion of installation, Cool and Cobb Engineering Company shall be supplied with a drilling log of the
location and depths of each pile installed so they can evaluate the installation and prepare the "As Built"
drawings.
General Notes:
1. All piles to be installed in accordance with ICC ES AC 358
2. A log of each pile to be kept by Contractor noting depth and final torque installed for each pile.
3. Minimum pile depth to be 10'-0"
4. Helical piles installed less than 48" apart are to be battered 10' away from each other.
5. This design is based on the loads of the structure placed on the shallow soils under the structure.
6. No deep soils geotechnical testing information was provided for this design.
7. This design does not address any possible sink hole activity as defined in Florida Statute § 627.706.
7 23 20
Carl Cool, P.E.
State of Florida
Professional Engineer No. 16921
/o
203 W. Main St.
Avon Park, FL 33825
Office: (863) 657-2323
Fax: (863) 657-2324
Solid Foundations
2704 SW Main Blvd
Lake City, FL 32025
855-227-0300
SF Represntative: Paul Kolzow
10 Cell: (407)907-2227
�, i+, ��� ', •i�I 241 Email: Paul(ftolidfoundations.com
CONTRACT DATE: July 15 2020
SUBMITTED TO: Jade & Bryan Wright
ADDRESS: 6820 Wadsworth Terrace
Port St. Lucie 34952
1
EMAIL: JADEALANA.LONC
Phone: 304-685-5282
I FOR
LIANCE
DUNTY
r
Push Pier Model 300: 0 Interior Pier: ® Polyurett?A ■
Push Pier Model 250: 0 Low Profile Bracket: 0 430: ■
Helical Pier: 0 1 - Porch Bracket: 0 Windows/Doors:
Crawl Space Pier: • 4x6 Wood Beam: 0 Floor Joist. z-=
Cool and Cobb Engineering Co.
7/23/2020 203 W. Main St.
Carl E. Cool, P.E. Avon Park, FL 33825
PE# 16921
Cool and Cobb Engineering Company
Date: 7/23/2020
Job: Jade & Bryan Wright
Location: 6820 Wadsworth Terrace
Port St. Lucie, FL 34952
Attachment "A"
Total Load on Pile (Live Load + Dead Load)
PILE NO. TOTAL CALCULATE LOAD
1 12,000 lbs
2 12,000 lbs
3 12,000 lbs
CODE CON Wu} g
I '�
IR
Maximum Total Load on Pile: 12,000 lbs
Cool and Cobb Engineering Co.
7/23/2020 203 W. Main St.
Carl E. Cool, P.E. 10
Avon Park, FL 33825
PE# 16921
=!DITMG' Helical Pier System
= MANUFACTURING
Lift Brackets
TMG Manufacturing offers 2 different foundation brackets designed to meet the
needs of any foundation support application. Choose between our heavy duty lift
bracket or our medium duty lift bracket. All of our brackets are made from high -
tensile strength steel and comprised of CNC machined parts, ensuring precision
and accuracy. In addition, all brackets are robotically welded guaranteeing a
quality product every time. All brackets have been field and lab -tested and can
be powder -coated or galvanized.
Helical Piers
TMG manufactures various sized helical underpinning pipe. Helical pipe can
be ordered with single, double or triple helixes, with 8", 10" or 12" blades (or
a combination of each). The helical pipe is made of 2.875" O.D. schedule 40
or schedule 80 pipe with two bolt holes and an outer nipple connector. Helical
extensions are also available. Standards lengths are 4', 5', 6' and 7'. Optional
powder -coating or galvanization available.
7/23/
Carl E. Cool
, P.E.
PE# 16921