HomeMy WebLinkAboutProject Information STORAGE TANK IS ADEQUATELY i`� � Ferrellgas
PROPANE TANK BUOYANCY
ANCHORED TO PREVENT FLOATATION,
COLLAPSE OR LATERAL MOVEMENT MAX BUOYANCY = p•*g+Vt-A
DURING THE BASE FLOOD EVENT. = 1,94 slug/ft' 32.2 ft/s: • 16.04 ft' 3232 SE Dixie Hwy.
= 1002 LBS Stuart,FL 34997
ALL WORK SHALL BE IN ACCORDANCE WITH
NFPA 54-58, NATIONAL FUEL GAS CODE NET BUOYANCY = MAX BUOYANCY — WEIGHT OF EMPTY TANK
AND FLORIDA FUEL_GAS CODE 2014. = 1002 LBS — 245LBS
= 757 LBS
TANKS INSTALLED IN TRAFFIC AREAS
SHALL BE PROTECTED WITH GALV. STEEL FORCE ON r CABLE = 757 / 2 = 379 LBS
SCHED. 80 PIPE BOLLARDS (470) 6' LONG TENSILE STRENGTH OF r CABLE = 2000 LBS
X 3' BURY DEPTH NTH CAP ® 3' O.C.
FORCE ON AUGER ANCHOR = 379 / 2 = 190 LBS OZ
MIN. PULL—OUT RESISTANCE OF AUGER ANCHOR = 1360 LBS 0
O
—6,
GROUND LEVEL GROUND LEVEL
- I�I I I-1 I�I I I-1 11=1 I I=1 I I
-i i i-i i i-i i i-i i i-i i iiii
I LP TAN I U
i' 7x19 GALV.
AIRCRAFT CABLE
2 TOTAL (IN POLY.
SLEEVE)
AUGER ANCHOR, 4T
LONG W/ 6'0 HELIX
4 TOTAL
SIDE ELEVATION
SCALE 1/4' - 1'-0'
i
GRASS COVER
GROUNP LEVEL
111 -111.111-�-1 i i - - - -
1, TAN 1 (MAX COVER)1
I I
EXCAVATION SIZE:
6'L x SW x SD
9LB. ANODE BAG
r7X19 GALV ISSUE DATE:
AIRCRAFT CABLE
DRAWN:
STRAPPING BOLT. APPROVED:
DRAWING NUMBER
AUGER ANCHOR, 48'
LONG W/ 6"0 HELIX
FRONT ELEVATION0
SCALE 1/4' = 1'-0'
LP120