EVALUATION REPORT
Polyglass USA,Inc. Evaluation Report P9290.02.08-1116
150 Lyon Drive F1.1654-1118
Fernley, NV 89408 Date of Issuance:02/11/2008
Revision 16:02/08/2016
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida.The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for
compliance with the 5 h Edition(2014) Florida Building Code sections noted herein.
DESCRIPTION: Polyglass SBS and APP Modified Bitumen Roof Systems
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein. .
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s)changes,the referenced
Quality Assurance documentation changes,or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity)ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT:The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done in its entirety.
INSPECTION: Upon request,a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
5.T. gF rpL'T n � 7SI0\This Evaluation Report consists of pages 1 through 5,plus a 45- a e Appendix.REVTFJ`' - - LCI)ryED FOR CO3,�1PLLAA--CE
Prepared by: ..�,attttt,r,,,,, RE.VILIVED BY
DATE
PLANS AND PERMI
OI?NO 11YITST BE h:EPT O'r JOE LNSPECTION jV ILL 33E MADE.
:O'•' - -> 1 - The facsimile seal appearing was authorized
J, -•••- .cs•.. by Robert Nieminen,P.E.on 02/08/2016
Robert J.M.Nieminen,P.E. i,hllii iV—..Nv k? This does not serve as an electronically signed document.Signed,
Florida Registration No.59166,Florida DC4 ANE1983 sealed hardcopies have been transmitted to the Product Approval
Administrator and to the named client
CERTIFICATION OF INDEPENDENCE:
1. Exterior Research&Design,LLC.d/b/a Trinity I ERD does not have,nor does it intend to acquire or will it acquire,a financial interest
in any company manufacturing or distributing products it evaluates.
2. Exterior Research & Design, LLC. d/b/a Trinity I ERD is not owned, operated or controlled by any company manufacturing or
distributing products it evaluates.
3. Robert Nieminen,P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen,P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way,the Designer of Record for any
project on which this Evaluation Report,or previous versions thereof,is/was used for permitting or design guidance unless retained
specifically for that purpose.
i
i
TRINITY JERD
ROOFING SYSTEMS EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub-Category: Modified Bitumen Roof Systems
Compliance Statement: Polyglass SBS and APP Modified Bitumen Roof Systems, as produced by Polyglass USA, Inc., have
demonstrated compliance with the following sections of the Florida Building Code through testing in accordance with the
following Standards. Compliance is subject to the Installation Requirements and Limitations/Conditions of Use set forth herein.
2. STANDARDS:
Section Property Standard Year
1504.3.1 Wind FM 4474 2004
1504.7 Impact FM 4470 1992
1507.11.2 Physical Properties ASTM D6162 2000
1507.11.2 Physical Properties ASTM D6163 2000
1507.11.2 Physical Properties ASTM D6164 2005
1507.11.2 Physical Properties ASTM D6222 2008
1507.11.2 Physical Properties ASTM D6509 2009
3. REFERENCES:
Enti Examination Reference Date
EAD(TST6049) Physical Properties P10490.10.08-2 10/30/2008
ERD(TST6049) FM 4470/4474 P13760.09.09 09/10/2009
ERD(TST6049) FM 4470/4474 P13770.09.09 09/10/2009
ERD(TST6049) FM 4470/4474 P30540.11.09-R1 11/30/2009
ERD(TST6049) FM 4470/4474 P30550.12.09 12/02/2009
ERD(TST6049) Physical Properties P33960.12.10 12/30/2010
ERD(TST6049) FM 4470/4474 P33970.03.11 03/15/2011
ERD(TST6049) Physical Properties P37590.03.13-3A 03/06/2013
ERD(TST6049) FM 4470/4474 P39680.03.13 03/04/2013
ERD(TST6049) Physical Properties P37590.03.13-1-R1 06/26/2013
ERD(TST6049) Physical Properties P37590.03.13-2-R3 07/01/2013
ERD(TST6049) Physical Properties P37590.07.13-2 07/01/2013
ERD(TST6049) Physical Properties P37590.03.13-5-R1 07/01/2013
ERD(TST6049) Physical Properties P37590.07.13-1 07/02/2013
ERD(TST6049) FM 4470/4474 P41630.08.13 08/06/2013
ERD(TST6049) Physical Properties P45940.09.13 09/04/2013
ERD(TST6049) Physical Properties P44370.10.13 10/04/2013
ERD(TST6049) FM 4470/4474 SC6160.11.14 11/10/2014
ERD(TST6049) Physical Properties PLYG-P45440SC.03.15-1 03/31/2015
ERD(TST6049) Physical Properties SC5170.05.15 05/08/2015
ERD(TST6049) FM 4474 SC8085.05.15 05/19/2015
ERD(TST6049) FM 4470/4474 SC8905.15 01/18/2016
ERD(TST6049) Physical Properties SC5170.12.15 12/29/2015
FM Approvals(TST1867) FM 4470 2W7A7.AM 08/04/1994
FM Approvals(TST1867) FM 4470 OD3A3.AM 04/04/1997
FM Approvals(TST1867) FM 4470 2DOAO.AM 12/23/1998
FM Approvals(TST1867) FM 4470 2D5A9.AM 06/22/1999
FM Approvals(TST1867) FM 4470 3006646 01/04/2000
FM Approvals(TST1867) FM 4470 3001334 01/25/2000
FM Approvals(TST1867) FM 4470 3001334 02/15/2000
FM Approvals(TST1867) FM 4470 3000857 01/12/2000
FM Approvals(TST1867) FM 4470 3004091 01/12/2000
FM Approvals(TST1867) FM 4470 3006115 05/02/2001
FM Approvals(TST1867) FM 4470 3012321 07/29/2002
FM Approvals(TST1867) FM 4470 3014692 08/05/2003
FM Approvals(TST1867) FM 4470 3014751 08/27/2003
FM Approvals(TST1867) FM 4470 3007170 01/13/2004
FM Approvals(TST1867) FM 4470 3019317 06/30/2004
FM Approvals(TST1867) FM 4470 3020703 07/30/2004
FM Approvals(TST1867) FM 4470/4474 3018332 01/31/2006
Exterior Research and Design,I.I.C. Evaluation Report 139290.02.08-1116
Certificate of Authorization#9503 FL1654-R18
Revision 16:02/08/2016
Page 2 of 5
I
I
' I
��TPJNJTYJERD
Enti Examination Reference Date
FM Approvals(TST1867) FM 4470/4474 3023368 03/20/2006
FM Approvals(TST1867) FM 4470/4474 3024594 05/23/2006
FM Approvals(TST1867) FM 4470/4474 3023458 07/18/2006
FM Approvals(TST1867) FM 4470/4474 3030668 09/12/2007
FM Approvals(TST1867) FM 4470/4474 3032172 06/12/2009
FM Approvals(TST1867) FM 4470/4474 3049631 04/21/2014
PRI(TST5878) Physical Properties PUSA-062-02-01 12/04/2007
PRI(TST5878) Physical Properties PUSA-061-02-02 01/28/2008
PRI(TST5878) Physical Properties PUSA-064-02-02 02/27/2008
PRI(TST5878) Physical Properties PUSA-062-02-02 12/04/2008
Miami-Dade(CER1592) HVHZ Compliance Various NOAs Various
Miami-Dade(CER1592) Proposal for Review 10-0823 10/12/2010
UL LLC (QUA9625) Quality Control Service Confirmation,R14571 Exp.10/06/2018
4. PRODUCT DESCRIPTION:
This Evaluation Report covers Polyglass Modified Bitumen Roof Systems installed in accordance with Polyglass USA,Inc.published
installation instructions and the Limitations/Conditions of Use herein. The following Polyglass membranes make up the subject
systems.
TABLE I:ROLL-GOODS FOR POLYGLASS'MODIFIED BITUMEN ROOF VSTEMS,;n
Type Product Specification
Reference Grade Type
Polyglass G2 Base ASTM D4601 N/A II
Base Sheets Polyflex SA Base ASTM D4601 N/A II
Polyglass APP Base ASTM D6509 N/A N/A
Polyglass HT Base650 ASTM D6162 S III
Elastobase ASTM D6163 S 1
Elastoflex V ASTM D6163 S I
Elastoflex SA V Base ASTM D6163,Table 2 S I
Elastoflex SA V FR Base ASTM D6163,Table 2 S I
Elastoflex SA V Plus ASTM D6163 S I
Elastoflex SA V Plus FR ASTM D6163 S I
Elastobase Poly ASTM D6164 S I
Elastoflex S6 ASTM D6164 5 1
SBS Membranes Elastoflex VG ASTM D6163 G I
Elastoflex VG FR ASTM D6163 G I
Elastoflex S6 G ASTM D6164 G I
Elastoflex S6 G FR ASTM D6164 G I
Polyfresko G SBS(sand or poly-fiim backed) ASTM D6164 G I
Polyfresko G SBS FR(sand or poly-film backed) ASTM D6164 G I
Elastoshield TS G ASTM D6164 G I
Elastoshield TS G FR ASTM D6164 G I
Elastoflex SA P ASTM D6164 G I
Elastoflex SA P FR ASTM D6164 G I
Polyreflect ASTM D6164 S I
Polyflex ASTM D6222 S I
Polyflex G ASTM D6222 G I
Polyflex G FR ASTM D6222 G 1
Polyfresko G ASTM D6222 G I
Polyfresko G FR ASTM D6222 G I
APP Membranes Polybond ASTM D6222 S 1
Polybond G ASTM D6222 G I
Polyflex SA P ASTM D6222 G 1
Polyflex SA P FR ASTM D6222 G I
Polyfresko G SA ASTM D6222 G I
Polykool ASTM D6222 S I
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity ERD nor Robert Nieminen,P.E.are,in anyway,the Designer of Record
for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design
guidance unless retained specifically for that purpose.
Exterior Research and Design,I.I.C. Evaluation Report 139290.02.08-1136
Certificate of Authorization#9503 F1.1654-1118
Revision 16:02/08/2016
Page 3 of 5
i
VTRINITY 1 ER®
5.2 This Evaluation Report is not for use in HVHZ.
5.3 Refer to a current Roofing Materials Directory for fire ratings of this product.
5.4 For steel deck installations,foam plastic insulation shall be separated from the building interior in accordance with FBC
2603.4 unless the exceptions stated in FBC 2603.4.1 and 2603.6 apply.
5.5 The roof system evaluation herein pertains to above-deck roof components. Roof decks and structural members shall be
in accordance with FBC requirements to the satisfaction of the AHJ. Load resistance of the roof deck shall be documented
through proper codified and/or FBC Approval documentation.
5.6 For recover installations,the existing roof shall be examined in accordance with FBC 1510.
5.7 For mechanically attached insulation or membrane or strip-bonded insulation, the maximum design pressure for the
selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 16. Zones
2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure
criteria. Commonly used methods are RAS 117 and FM LPDS 1-29. Assemblies marked with an asterisk* carry the
limitations set forth in Section 2.2.1.5.1(a)of FM LPDS 1-29 for Zone 2/3 enhancements.
5.8 For fully-adhered insulation,the maximum design pressure for the selected assembly shall meet or exceed critical design
pressure determined in accordance with FBC Chapter 16. No rational analysis is permitted for these systems
5.9 For mechanically attached insulation or membrane over existing roof decks,fasteners shall be tested in the existing deck
for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum
requirements for the system. Testing and analysis shall be in accordance with TAS 105 or ANSI/SPRI FX-1.
5.10 For bonded insulation or membrane over existing substrates in a re-roof(tear off)or recover installation,the existing deck
or existing roof surface shall be examined for compatibility with the adhesive to be installed. If any surface conditions
exist that bring system performance into question, field uplift testing in accordance with ASTM E907, FM LPDS 1-52,
iANSI/SPRI IA-1 or TAS 124 shall be conducted on mock-ups of the proposed new roof assembly.
5:11 For bonded insulation or membrane over existing substrates in a recover installation,the existing roof system shall be
capable of resisting project design pressures on its own merit to the satisfaction of the AHJ,as documented through field
uplift testing in accordance with ASTM E907,FM LPDS 1-52 or TAS 124.
5J2 Metal edge attachment(except gutters),shall be designed and installed for wind loads in accordance with FBC Chapter 16
and tested for resistance in accordance with ANSI/SPRI ES-1 or RAS,111,except the basic wind speed shall be determined
from FBC Figure 1609.
5.13 All products in the roof assembly shall have quality assurance audit in accordance with the FBC and F.A.C.Rule 61G20-3.
6. INSTALLATION:
6.1 Polyglass Modified Bitumen roof systems shall be installed in accordance with Polyglass USA, Inc. published installation
instructions,subject to the Limitations/Conditions of Use noted herein.
6.2 System attachment requirements for wind load resistance are set forth in Appendix 1. "MDP" = Maximum Design
Pressure is the result of testing for wind load resistance based on allowable wind loads,and reflects the ultimate passing
pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FBC 1609 for
determination of design wind loads.
6.3 Any of the following FBC Approved coatings may be applied to the top roof membrane without adverse effect on the
system wind load performance. Refer to current Roofing Materials Directory for fire ratings associated with coating usage.
➢ PG200 Non-Fibered Roof Coating;
➢ PG300 Fibered Roof Coating;
➢ PG600 Non-Fibered Aluminum Roof Coating;
➢ PG650 Fibered Aluminum Roof Coating;
➢ PG700 High Quality Elastomeric Roof Coating or KM Acryl 25;
➢ PG700QS(Quick-Set)High Quality Elastomeric Roof Coating or KM Acryl 25-QS (over granule-surfaced APP or SBS only);
➢ PG800 Asphalt Emulsion Roof Coating;
➢ Polyplus 60 Premium Non-Fibered Aluminum Roof Coating;
➢ Polyplus 65 Premium Fibered Aluminum Roof Coating;
➢ Polybrite 70 Premium Grade Elastomeric Roof Coating or KM Acryl 15;
➢ Polybrite 70QS(Quick-Set)Premium Grade Elastomeric Roof Coating or KM Acryl 15-QS(over granule-surfaced APP or SBS only);
➢ Polybrite 90 High Solids Silicone Roof Coating;
➢ Polybrite 95 Silicone Roof Coating.
Exterior Research and Design,LLC. Evaluation Report P9290.02.08-R16
Certiftcate of Authorization#9503 F1.3654-1118
Revision 16:02/08/2016
Page 4 of 5
I
TRINIW ER®
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product.
8. MANUFACTURING PLANTS:
Contact the noted CIA agency for information on product locations covered for F.A.C.Rule 61G20-3 QA requirements
9. QUAUTYASSURANCE ENTITY:
UL LLC—QUA9625;(314)578-3406,k.chancellor@us.ul.com.
-THE 45-PAGES THAT FOLLOW FORM PART OF THIS EVALUATION REPORT-
I
I
i
Exterior Research and Design,LLC. Evaluation Report P9290.02.08-1116
Certificate of Authorization#9503 FL1654-RIS
Revision 16:02/08/2016
Page 5 of 5
I
TABLE 1F-2:WOOD DECKS—NEW CONSTRUCTION,REROOF(TEAR-OFF)oaRECovea qTRRINI-ryl ERD --
SYSTEM TYPE E:NON-INSULATED,MECHANICALLY ATTACHED BASE SHEET(SCREWS&PLATES),BONDED ROOF COVER
System Deck(See Base Sheet Roof Cover(See Table 1) MDP
No. Note 1) Type Fasten Attach Base Ply Cap (psf)
Elastobase,Elastobase P,Polyglass OMG Flat Bottom Plates(square)with Roofgrip SBS-SA,APP-SA,
Min.19/32- G2 Base,CertainTeed Glasbase, 12-inch o.c.in 4-inch lap and 12-inch o.c.in two BP-AA,SBS-AA,SBS-#14,Dekfast Hex with Dekfast#14 or Trufast 3" SBS-AA,SBS-TA, -52.5
inch plywood Firestone MB Base,1M Perma-Ply 28, Metal Insulation Plate with Trufast HD (2),equally spaced,staggered center rows TA,APP-TA APP-TA
Tamko Glass Base or GAFGLAS#75
Min.19/32- OMG Flat Bottom Plates(square)with Roofgrip 12-inch o.c.in 4-inch lap and 12-inch o.c.in two BP-AA,SBS-AA,SBS- SBS-SA,APP-SA,
W-123 inch plywood Elastobase,Elastobase P #12 (2),equally spaced,staggered center rows TA,APP-TA• SBS-AA,SBS-TA, -60.0
APP-TA r
Dekfast Hex Plates with Dekfast#14,OMG 3" SBS-SA,APP-SA,
W-124 Min.15/32- Polyglass G2 Base,Elastobase, Round Metal Plate with OMG HD,OMG Flat 10-inch o.c.in 4-inch lap and 10-inch o.c.in three BP-AA,SBS-AA,SBS- SBS-AA,SBS-TA, -75.0
inch plywood Elastobase P Bottom Plate(Accutrac)with Roofgrip#14 or (3),equally spaced,staggered center rows TA,APP-TA APP-TA
Trufast 3"Metal Insulation Plate with Trufast HD.
Dekfast Hex Plates with Dekfast#14,OMG 3"
W-125 Min.15/32- Polyglass APP Base Round Metal Plate with OMG HD,OMG Flat 10-inch o.c.in 4-inch lap and 10-inch o.c.in three APP-TA APP-TA -75.0
inch plywood Bottom Plate(Accutrac)with Roofgrip#14 or (3),equally spaced,staggered center rows
Trufast 3"Metal Insulation Plate with Trufast HD,
Dekfast Hex Plates with Dekfast#14,OMG 3" SBS-SA,APP-SA,
W-126 Min.15/32- Polyglass G2 Base,Elastobase, Round Metal Plate with OMG HD,OMG Flat 9-inch o.c.in 4-inch lap and 9-inch o.c.in four(4), BP-AA,SBS-AA,SBS- SBS-AA,SBS-TA, -90.0
inch plywood Elastobase P Bottom Plate(Accutrac)with Roofgrip#14 or equally spaced,staggered center rows TA,APP-TA APP-TA
Trufast 3"Metal Insulation Plate with Trufast HD.
Dekfast Hex Plates with Dekfast#14,OMG 3"
Min.15/32- Round Metal Plate with OMG HD,OMG Flat 9-inch o.c,in 4-Inch lap and 9-inch o.c.in four(4),
W-127 inch plywood Polyglass APP Base Bottom Plate(Accutrac)with Roofgrlp#14 or equally spaced,staggered center rows APP-TA APP-TA 90.0
Trufast 3"Metal Insulation Plate with Trufast HD.
Min.15/32- Trufast#12 DP or Trufast#14 HD with Trufast 3" 6-inch o.c.at 4-inch lap and 6-inch o.c.in three
W-128 inch plywood Elastobase,Elastobase P Metal Insulation Plates (3),equally spaced,staggered center rows BP-AA or SBS-AA SBS-AA 90.0
OMG#12 Standard Roofgrip or OMG#14 Heavy SBS-SA,APP-SA,
W-129 Min.plywood
Elastobase,Elastobase P Duty(min.1-5/8-inch long)with OMG 3"Round (-inch all s a Inch lap and(-inch ceo.nter
r in three BP-AA,SBS-AA,SBS- SBS-AA,SBS-TA, -90.0
inch plywood Metal Plates or OMG Flat Bottom Metal Plates (3),equally spaced,staggered center rows TA,APP-TA APP-TA )
Min.15/32- OMG#12 Standard Roofgrip or OMG#14 Heavy 6-inch o.c.at 4-Inch lap and 6-inch o.c.in three
W-130 inch plywood Polyglass APP Base Duty with OMG 3"Round Metal Plates or OMG (3) equally spaced,staggered center rows APP-TA APP-TA -90.0-
Flat Bottom Metal Plates
W-131 Min.15/32- Elastobase,Elastobase P Trufast#12 DP or Trufast#14 HD with Trufast 3" 6-inch o.c.at 4-inch lap and 6-inch o.c.in five(5), BP-AA or SBS-AA SBS-AA -120.0
inch plywood Metal Insulation Plates equally spaced,staggered center rows
OMG#12 Standard Roofgrip or OMG#14 Heavy SBS-SA,APP-SA,
inch plywood W-132 Min. lyw2-ood Elastobase,Elastobase P Duty with OMG 3"Round Metal Plates or OMG equally spaced staggered center rows TA APP-TA 6-inch o.c.at 4-inch lap and(-inch o.c.in five(5), BP-AA,SBS-AA,SBS- SBS-AA,SBS-TA, -120.0
Flat Bottom Metal Plates , , APP-TA
Min.15/32- OMG#12 Standard Roofgrip or OMG#14 Heavy 6-inch o.c.at 4-Inch lap and 6-inch o.c.In five(5),
W-133 inch plywood Polyglass APP Base Duty with OMG 3' Round Metal Plates or OMG equally spaced,staggered center rows APP-TA APP-TA -120.0
Flat Bottom Metal Plates
'SELF-ADHERING BASE PLY:
Exterior Research and Design,LLC.d/b/a Trinity)ERD Evaluation Report P9290.02.08-1116 for F1.1654-1118
Certificate of Authorization#9503 Revision 16:02/08/2016
Prepared by: Robert Nieminen,PE-59166 Appendix 1,Page 20 of 45