HomeMy WebLinkAboutFire dept reviewSAINT LUCIE COUNTY FIRE DISTRICT
PLAN REVIEW FORM
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
Telephone: 772-621-3322
Fax: 772-621-3604
Web Address: www.slcfd.com
Building Dept.
SLC —
^�
FMO Permit # B-20-320 -
i
Project Name
High Caliber BArber Shop -
I
_
BLQG Permit #
Address
10552 Sotuh US Hwy 1
�
City PSL
Contractor J Griffin Dev Inc
Address 1321 SE Riverside Drive ! City Stuart
�itate FL— -- Zip 34946 -� Telephone (772) 341-3423
Architect/Engineer Joseph P. McCarty - Telephone
Occupancy Type Business i Construction Type Square Feet 800
�L -- - -1
ccupant Load 8 per plans Number of Stories I Access Box i Access Key Switch—J
AFS Permit �^ ^' FA Permit I _ FFP Permit I
I L I --General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. A Radio coverage Pre -Survey Signal Strength inspection is required before any final inspection is scheduled.
5. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
6. Failed inspections require payment of fee prior to rescheduling of further inspections.
7. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
8. Fire alarm panels shall be located indoors within air conditioned space.
9. Plans and construction are subject to corrections in the field to maintain code compliance.
10. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
11. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE CURRENTLY ADOPTED VERSION OF THE FLORIDA FIRE PREVENTION CODE IS ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
1. Portable fire extinguishers from a licensed contractor are required
j�� —�
Page E1 of Reviewed by JTony Jerger- J� _ �_ � I Date 10-15-2020