HomeMy WebLinkAboutMANJCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Oct-21 10:39:59 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Load Short Form Feb 12, 2020Date:Guest House Vicki Lynne BarenbergBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Gardner Residence, Groza Builders, IncFor: TBD Dunn Rd, Port St Lucie, FL 34983 Design Information InfiltrationClgHtg Blower doorMethod9041Outside db (°F) 3 (partial) / 1Shielding / stories7570Inside db (°F) 50 Pa / 0 cfmPressure / AVF1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Generic Make Generic Trade Trade Model SEER 18.0, HSPF 9.1 Cond SEER 18.0, HSPF 9.1 AHRI ref Coil AHRI ref Efficiency 9.1 HSPF Efficiency 14.7 EER, 18 SEER Heating input Sensible cooling Btuh3875 Heating output Btuh @ 47°F5508 Latent cooling Btuh1661 Temperature rise °F27 Total cooling Btuh5535 Actual air flow cfm185 Actual air flow cfm185 Air flow factor cfm/Btuh0.034 Air flow factor cfm/Btuh0.044 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.79 Capacity balance point = 39 °F ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) G Clst 18 0 0 0 0 G Bath 48 1165 478 39 21 G House 198 4284 3734 145 164 Guest House d 264 5449 4212 185 185 Other equip loads 0 0 Equip. @ 0.95 RSM 4018 Latent cooling 1118 TOTALS 264 5449 5136 185 185 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Oct-21 10:39:59 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2 ... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Load Short Form Feb 12, 2020Date:House Vicki Lynne BarenbergBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Gardner Residence, Groza Builders, IncFor: TBD Dunn Rd, Port St Lucie, FL 34983 Design Information InfiltrationClgHtg Blower doorMethod9041Outside db (°F) 3 (partial) / 1Shielding / stories7570Inside db (°F) 50 Pa / 0 cfmPressure / AVF1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond 14ACX-041-230* AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259379 Efficiency 80 AFUE Efficiency 13.0 EER, 16 SEER Heating input kW0 Sensible cooling Btuh27650 Heating output Btuh0 Latent cooling Btuh11850 Temperature rise °F0 Total cooling Btuh39500 Actual air flow cfm1317 Actual air flow cfm1317 Air flow factor cfm/Btuh0.057 Air flow factor cfm/Btuh0.051 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.78 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Bath 2 55 163 202 9 10 Bed 2 160 1451 1481 82 75 Bed 3 186 3725 2562 211 130 Great Room 429 6762 9520 383 481 Hallway 140 0 0 0 0 Kitchen/Nook 330 5334 7225 302 365 Laundry 42 125 834 7 42 Linen 9 0 0 0 0 Master Bath 98 1021 595 58 30 Master Suite 288 4140 3343 235 169 Pantry 39 0 0 0 0 WIC 52 515 271 29 14 Wtr Htr 14 0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Oct-21 10:39:59 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 3 ... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N House d 1840 23235 26032 1317 1317 Other equip loads 1543 819 Equip. @ 0.95 RSM 25616 Latent cooling 7560 TOTALS 1840 24778 33176 1317 1317 2020-Oct-21 10:39:59 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Building Analysis Feb 12, 2020Date:Guest House Vicki Lynne BarenbergBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Gardner Residence, Groza Builders, IncFor: TBD Dunn Rd, Port St Lucie, FL 34983 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) Blower doorMethod)L(15-Daily range (°F) 3 (partial) / 1Shielding / stories77-Wet bulb (°F) 50 Pa / 0 cfmPressure / AVF7.515.0Wind speed (mph) Heating Walls Glazing Other Ceilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 23.212652.7Walls 5.12809.0Glazing 1.2633.7Doors 4.82601.0Ceilings 34.218647.17.1Floors 19.010352.7Infiltration 12.5682Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.05449Total Cooling Walls Glazing Other Ceilings Infiltration Ducts Internal Gains % of loadBtuhBtuh/ft²Component 21.99232.0Walls 9.841413.3Glazing 1.5643.7Doors 11.24741.8Ceilings 000Floors 7.33080.8Infiltration 19.0799Ducts 00Ventilation 29.21230Internal gains 00Blower 0Adjustments 100.04212Total Latent Cooling Load = 1118 Btuh Overall U-value = 0.123 Btuh/ft²-°F Data entries checked. 2020-Oct-21 10:39:59 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2 ... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Building Analysis Feb 12, 2020Date:House Vicki Lynne BarenbergBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Gardner Residence, Groza Builders, IncFor: TBD Dunn Rd, Port St Lucie, FL 34983 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) Blower doorMethod)L(15-Daily range (°F) 3 (partial) / 1Shielding / stories77-Wet bulb (°F) 50 Pa / 0 cfmPressure / AVF7.515.0Wind speed (mph) Heating Walls Glazing Other Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 11.929462.6Walls 11.628838.7Glazing 0.3733.7Doors 7.318171.0Ceilings 19.949332.72.7Floors 16.340262.7Infiltration 26.56557Ducts 00Piping 00Humidification 6.21543Ventilation0Adjustments 100.024778Total Cooling Walls Glazing Other Ceilings Infiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 9.224682.2Walls 24.7664320.1Glazing 0.3743.7Doors 12.333081.8Ceilings 000Floors 4.511990.8Infiltration 27.37321Ducts 3.1819Ventilation 18.75020Internal gains 00Blower 0Adjustments 100.026852Total Latent Cooling Load = 7560 Btuh Overall U-value = 0.084 Btuh/ft²-°F Data entries checked. 2020-Oct-21 10:39:59 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Component Constructions Feb 12, 2020Date:House Vicki Lynne BarenbergBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Gardner Residence, Groza Builders, IncFor: TBD Dunn Rd, Port St Lucie, FL 34983 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) Blower doorMethod)L(15-Daily range (°F) 3 (partial) / 1Shielding / stories77-Wet bulb (°F) 50 Pa / 0 cfmPressure / AVF7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Block R-9 Wall: Blk Wall, Stucco Ext, 8" Thk, R-9 Foam Fill, 1/2" DW 7262.589.00.089282ne 6082.16 6622.167902.589.00.089306se 5632.166722.589.00.089261sw 6352.167582.589.00.089294nw 24682.1629462.589.00.0891143all Partitions (none) Windows Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (3 ft window ht, 1 ft sep.); 6.68 ft head ht 30917.21578.7000.30018ne 30917.21578.7000.30018nw 61917.23138.7000.30036all Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.19); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 5 ft overhang (5.2 ft window ht, 1 ft sep.); 6.68 ft head ht 37416.32068.9900.31023ne Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (5.2 ft window ht, 1 ft sep.); 6.68 ft head ht 21613.91368.7000.30016se 63713.94008.7000.30046se 31813.92008.7000.30023sw 71517.23628.7000.30042nw 53617.22718.7000.30031nw 242315.413698.7000.300157all Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.21); foreground = green grass (0.23); 8 ft overhang (6.5 ft window ht, 1 ft sep.); 6.68 ft head ht 57311.04528.7000.30052sw Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 8 ft overhang (5.2 ft window ht, 1 ft sep.); 6.68 ft head ht 959.17908.7000.30010sw Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.28); foreground = green grass (0.23); 2 ft overhang (6.5 ft window ht, 1 ft sep.); 6.68 ft head ht 33525.81138.7000.30013nw 72818.73398.7000.30039nw 106320.44528.7000.30052all 2020-Oct-21 10:39:59 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2 ... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N Doors Door, Mtl Fbrgl Type 743.73733.697.00.12720ne Ceilings Attic, Shingle Roof, R-30 Ceil Ins, 5/8" DW 1840 33081.8018170.9930.00.034 Floors On grade depth, Tile flr fnsh 00493328.700.989172 2020-Oct-21 10:39:59 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 3 ... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Component Constructions Feb 12, 2020Date:Guest House Vicki Lynne BarenbergBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Gardner Residence, Groza Builders, IncFor: TBD Dunn Rd, Port St Lucie, FL 34983 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) Blower doorMethod)L(15-Daily range (°F) 3 (partial) / 1Shielding / stories77-Wet bulb (°F) 50 Pa / 0 cfmPressure / AVF7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Block R-9 Wall: Blk Wall, Stucco Ext, 8" Thk, R-9 Foam Fill, 1/2" DW 2792.589.00.089108se 2342.16 2602.163102.589.00.089120sw 2312.162762.589.00.089107nw 7252.168652.589.00.089336all Partitions Frm Wall, 1/2" DW Ext, R-11 Cav Ins, 1/2" DW Int Fnsh, 2"x4" Wood Frm, 16" OC STUD 1981.464002.9411.00.101136 Windows Impact, Low-e: Impact, Low-e; NFRC rated (SHGC=0.19); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (5.2 ft window ht, 1 ft sep.); 6.68 ft head ht 20713.31408.9900.31016se 20713.31408.9900.31016sw 41413.32808.9900.31031all Doors Door, Mtl Fbrgl Type 643.73633.697.00.12717nw Ceilings Attic, Shingle Roof, R-30 Ceil Ins, 5/8" DW 264 4741.802600.9930.00.034 Floors On grade depth, Tile flr fnsh 00186428.700.98965 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Oct-21 10:39:59 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Project Summary Feb 12, 2020Date:Guest House Vicki Lynne BarenbergBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Gardner Residence, Groza Builders, IncFor:TBD Dunn Rd, Port St Lucie, FL 34983 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh4767 Structure Btuh3413 Ducts Btuh682 Ducts Btuh799Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0 (none) (none)Humidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh5449 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh4018 Method Latent Cooling Equipment Load SizingBlower door Shielding / stories 3 (partial) / 150 Pa / 0 cfmPressure / AVF Structure Btuh904 Ducts Btuh214Central vent (0 cfm) Btuh0 CoolingHeating (none)264264Area (ft²) Equipment latent load Btuh1118 21082108Volume (ft³)Air changes/hour 0.520.92 Equipment Total Load (Sen+Lat)Btuh5136 Equiv. AVF (cfm) 1832 Req. total capacity at 0.70 SHR ton0.5 Heating Equipment Summary Cooling Equipment Summary Make Generic Make GenericTrade Trade Model SEER 18.0, HSPF 9.1 Cond SEER 18.0, HSPF 9.1AHRI ref Coil AHRI refEfficiency 9.1 HSPF Efficiency 14.7 EER, 18 SEER Heating input Sensible cooling Btuh3875Heating output Btuh @ 47°F5508 Latent cooling Btuh1661 Temperature rise °F27 Total cooling Btuh5535Actual air flow cfm185 Actual air flow cfm185 Air flow factor cfm/Btuh0.034 Air flow factor cfm/Btuh0.044Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.79Capacity balance point = 39 °F Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Oct-21 10:39:59 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2 ... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Project Summary Feb 12, 2020Date:House Vicki Lynne BarenbergBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Gardner Residence, Groza Builders, IncFor:TBD Dunn Rd, Port St Lucie, FL 34983 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh16678 Structure Btuh18712 Ducts Btuh6557 Ducts Btuh7321Central vent (48 cfm) 1543 Btuh Central vent (48 cfm) Btuh819 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh24778 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh25616 Method Latent Cooling Equipment Load SizingBlower door Shielding / stories 3 (partial) / 150 Pa / 0 cfmPressure / AVF Structure Btuh3538 Ducts Btuh2152Central vent (48 cfm) Btuh1870 CoolingHeating Outside air18401840Area (ft²) Equipment latent load Btuh7560 1585815858Volume (ft³)Air changes/hour 0.270.48 Equipment Total Load (Sen+Lat)Btuh33176 Equiv. AVF (cfm) 71126 Req. total capacity at 0.70 SHR ton3.0 Heating Equipment Summary Cooling Equipment Summary Make Make LennoxTrade Trade LENNOX Model Cond 14ACX-041-230*AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259379Efficiency 80 AFUE Efficiency 13.0 EER, 16 SEER Heating input kW0 Sensible cooling Btuh27650Heating output Btuh0 Latent cooling Btuh11850 Temperature rise °F0 Total cooling Btuh39500Actual air flow cfm1317 Actual air flow cfm1317 Air flow factor cfm/Btuh0.057 Air flow factor cfm/Btuh0.051Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.78 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Oct-21 10:39:59Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Right-J® Worksheet Feb 12, 2020Date:Guest House Vicki Lynne BarenbergBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Guest House G Clst 2 Exposed wall 65.0 ft 3.0 ft 3 Room height 8.0 dft 8.0 heat/coolft 4 Room dimensions ft6.0x3.0 5 Room area 263.5 ft²18.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.3000.300 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.3100.310 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 sese 2.582.58 2.162.16 124 108 279 234 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3100.310 sese 8.998.99 13.2713.27 16 7 140 207 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 swsw 2.582.58 2.162.16 136 120 310 260 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3100.310 swsw 8.998.99 13.2713.27 16 7 140 207 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 2.162.16 124 107 276 231 24 24 62 52 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nwnw 3.693.69 3.733.73 17 17 63 64 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 136 136 400 198 0 0 0 0 CC Attic, Shingle Roof, 0.034Attic, Shingle Roof, 0.034 --0.990.99 1.801.80 264 264 260 474 18 18 18 32 FF On grade depth, Tile 0.989On grade depth, Tile 0.989 --28.6828.68 0.000.00 264 65 1864 0 18 3 86 0 6 c) AED excursion 0 0 Envelope loss/gain 3732 1874 166 84 12 a) Infiltration 1035 308 65 19 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 1 230 0 0 Appliances/other 1000 0 Subtotal (lines 6 to 13)4767 3413 230 103 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 -230 -103 14 Subtotal 4767 3413 0 0 15 Duct loads 14%23%682 799 14%23%0 0 Total room load 5449 4212 0 0 Air required (cfm)Air required (cfm)185 185 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Oct-21 10:39:59Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Right-J® Worksheet Feb 12, 2020Date:Guest House Vicki Lynne BarenbergBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name G Bath G House 2 Exposed wall 14.0 ft 48.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.0x8.0 ft197.5x1.0 5 Room area 48.0 ft²197.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.3000.300 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.3100.310 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 sese 2.582.58 2.162.16 0 0 0 0 124 108 279 234 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3100.310 sese 8.998.99 13.2713.27 0 0 0 0 16 7 140 207 WW Block R-9 WallBlock R-9 Wall 0.0890.089 swsw 2.582.58 2.162.16 0 0 0 0 136 120 310 260 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3100.310 swsw 8.998.99 13.2713.27 0 0 0 0 16 7 140 207 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 2.162.16 64 64 165 138 36 19 49 41 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nwnw 3.693.69 3.733.73 0 0 0 0 17 17 63 64 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --2.942.94 1.461.46 48 48 141 70 88 88 259 128 CC Attic, Shingle Roof, 0.034Attic, Shingle Roof, 0.034 --0.990.99 1.801.80 48 48 47 86 198 198 195 355 FF On grade depth, Tile 0.989On grade depth, Tile 0.989 --28.6828.68 0.000.00 48 14 402 0 198 48 1377 0 6 c) AED excursion 0 0 Envelope loss/gain 755 294 2812 1496 12 a) Infiltration 173 51 798 238 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 1 230 Appliances/other 0 1000 Subtotal (lines 6 to 13)927 346 3610 2963 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 92 41 138 62 14 Subtotal 1019 387 3748 3025 15 Duct loads 14%23%146 91 14%23%536 708 Total room load 1165 478 4284 3734 Air required (cfm)Air required (cfm)39 21 145 164 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Oct-21 10:39:59Right-Suite® Universal 2019 19.0.20 RSU27054 Page 3... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Right-J® Worksheet Feb 12, 2020Date:House Vicki Lynne BarenbergBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name House Bath 2 2 Exposed wall 172.0 ft 0 ft 3 Room height 8.6 dft 8.0 heat/coolft 4 Room dimensions ft6.5x8.5 5 Room area 1840.0 ft²55.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nene 2.582.58 2.162.16 343 282 726 608 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.3000.300 nene 8.708.70 17.1917.19 18 0 157 309 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.3100.310 nene 8.998.99 16.2816.28 23 0 206 374 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nene 3.693.69 3.733.73 20 20 73 74 0 0 0 0 11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 sese 2.582.58 2.162.16 368 306 790 662 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 8.708.70 13.8613.86 16 7 136 216 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 8.708.70 13.8613.86 46 20 400 637 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3100.310 sese 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 swsw 2.582.58 2.162.16 346 261 672 563 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 11.0211.02 52 52 452 573 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 13.8613.86 23 10 200 318 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 9.179.17 10 10 90 95 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3100.310 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 2.162.16 437 294 758 635 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 25.8025.80 13 0 113 335 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 18 0 157 309 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 42 0 362 715 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 31 0 271 536 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 18.6618.66 39 0 339 728 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC Attic, Shingle Roof, 0.034Attic, Shingle Roof, 0.034 --0.990.99 1.801.80 1840 1840 1817 3308 55 55 55 99 FF On grade depth, Tile 0.989On grade depth, Tile 0.989 --28.6828.68 0.000.00 1840 172 4933 0 55 0 0 0 6 c) AED excursion 1496 -2 Envelope loss/gain 12652 12493 55 97 12 a) Infiltration 4026 1199 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 4 920 0 0 Appliances/other 4100 0 Subtotal (lines 6 to 13)16678 18712 55 97 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 63 48 14 Subtotal 16678 18712 117 145 15 Duct loads 39%39%6557 7321 39%39%46 57 Total room load 23235 26032 163 202 Air required (cfm)Air required (cfm)1317 1317 9 10 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Oct-21 10:39:59Right-Suite® Universal 2019 19.0.20 RSU27054 Page 4... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Right-J® Worksheet Feb 12, 2020Date:House Vicki Lynne BarenbergBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 2 Bed 3 2 Exposed wall 10.5 ft 30.5 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft159.8x1.0 ft186.0x1.0 5 Room area 159.8 ft²186.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nene 2.582.58 2.162.16 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.3000.300 nene 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.3100.310 nene 8.998.99 16.2816.28 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 sese 2.582.58 2.162.16 84 68 176 148 100 77 198 166 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 8.708.70 13.8613.86 16 7 136 216 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 8.708.70 13.8613.86 0 0 0 0 23 10 200 318 GG Impact, Low-eImpact, Low-e 0.3100.310 sese 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 swsw 2.582.58 2.162.16 0 0 0 0 144 121 312 261 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 11.0211.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 13.8613.86 0 0 0 0 23 10 200 318 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 9.179.17 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3100.310 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 2.162.16 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 25.8025.80 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 18.6618.66 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC Attic, Shingle Roof, 0.034Attic, Shingle Roof, 0.034 --0.990.99 1.801.80 160 160 158 287 186 186 184 334 FF On grade depth, Tile 0.989On grade depth, Tile 0.989 --28.6828.68 0.000.00 160 11 301 0 186 31 875 0 6 c) AED excursion 62 -40 Envelope loss/gain 771 714 1968 1359 12 a) Infiltration 226 67 658 196 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 250 Subtotal (lines 6 to 13)997 1031 2626 1805 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 44 34 48 37 14 Subtotal 1041 1065 2674 1841 15 Duct loads 39%39%409 417 39%39%1051 720 Total room load 1451 1481 3725 2562 Air required (cfm)Air required (cfm)82 75 211 130 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Oct-21 10:39:59Right-Suite® Universal 2019 19.0.20 RSU27054 Page 5... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Right-J® Worksheet Feb 12, 2020Date:House Vicki Lynne BarenbergBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Great Room Hallway 2 Exposed wall 41.5 ft 4.5 ft 3 Room height 9.5 heat/coolft 8.0 heat/coolft 4 Room dimensions ft428.8x1.0 ft4.5x31.0 5 Room area 428.8 ft²139.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nene 2.582.58 2.162.16 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.3000.300 nene 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.3100.310 nene 8.998.99 16.2816.28 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 sese 2.582.58 2.162.16 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 8.708.70 13.8613.86 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 8.708.70 13.8613.86 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3100.310 sese 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 swsw 2.582.58 2.162.16 166 104 268 224 36 36 93 78 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 11.0211.02 52 52 452 573 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 13.8613.86 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 9.179.17 10 10 90 95 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3100.310 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 2.162.16 228 134 346 290 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 25.8025.80 13 0 113 335 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 42 0 362 715 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 18.6618.66 39 0 339 728 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC Attic, Shingle Roof, 0.034Attic, Shingle Roof, 0.034 --0.990.99 1.801.80 429 429 423 771 140 140 138 251 FF On grade depth, Tile 0.989On grade depth, Tile 0.989 --28.6828.68 0.000.00 429 42 1190 0 140 5 129 0 6 c) AED excursion 1273 -8 Envelope loss/gain 3585 5005 360 320 12 a) Infiltration 1063 316 97 29 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 0 0 Appliances/other 900 0 Subtotal (lines 6 to 13)4647 6682 457 349 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 206 161 -457 -349 14 Subtotal 4853 6843 0 0 15 Duct loads 39%39%1908 2677 39%39%0 0 Total room load 6762 9520 0 0 Air required (cfm)Air required (cfm)383 481 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Oct-21 10:39:59Right-Suite® Universal 2019 19.0.20 RSU27054 Page 6... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Right-J® Worksheet Feb 12, 2020Date:House Vicki Lynne BarenbergBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Kitchen/Nook Laundry 2 Exposed wall 37.0 ft 0 ft 3 Room height 9.5 heat/coolft 8.0 heat/coolft 4 Room dimensions ft15.0x22.0 ft6.5x6.5 5 Room area 330.0 ft²42.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nene 2.582.58 2.162.16 143 105 270 226 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.3000.300 nene 8.708.70 17.1917.19 18 0 157 309 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.3100.310 nene 8.998.99 16.2816.28 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nene 3.693.69 3.733.73 20 20 73 74 0 0 0 0 11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 sese 2.582.58 2.162.16 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 8.708.70 13.8613.86 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 8.708.70 13.8613.86 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3100.310 sese 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 swsw 2.582.58 2.162.16 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 11.0211.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 13.8613.86 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 9.179.17 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3100.310 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 2.162.16 209 160 412 345 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 25.8025.80 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 18 0 157 309 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 31 0 271 536 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 18.6618.66 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC Attic, Shingle Roof, 0.034Attic, Shingle Roof, 0.034 --0.990.99 1.801.80 330 330 326 593 42 42 42 76 FF On grade depth, Tile 0.989On grade depth, Tile 0.989 --28.6828.68 0.000.00 330 37 1061 0 42 0 0 0 6 c) AED excursion 262 -13 Envelope loss/gain 2726 2656 42 63 12 a) Infiltration 947 282 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 0 0 Appliances/other 1700 500 Subtotal (lines 6 to 13)3674 5098 42 563 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 155 96 48 37 14 Subtotal 3829 5193 90 599 15 Duct loads 39%39%1505 2032 39%39%35 234 Total room load 5334 7225 125 834 Air required (cfm)Air required (cfm)302 365 7 42 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Oct-21 10:39:59Right-Suite® Universal 2019 19.0.20 RSU27054 Page 7... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Right-J® Worksheet Feb 12, 2020Date:House Vicki Lynne BarenbergBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Linen Master Bath 2 Exposed wall 0 ft 6.5 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft2.5x3.5 ft6.5x15.0 5 Room area 8.8 ft²97.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nene 2.582.58 2.162.16 0 0 0 0 52 52 134 112 .GG Impact, Low-eImpact, Low-e 0.3000.300 nene 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.3100.310 nene 8.998.99 16.2816.28 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 sese 2.582.58 2.162.16 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 8.708.70 13.8613.86 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 8.708.70 13.8613.86 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3100.310 sese 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 swsw 2.582.58 2.162.16 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 11.0211.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 13.8613.86 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 9.179.17 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3100.310 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 2.162.16 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 25.8025.80 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 18.6618.66 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC Attic, Shingle Roof, 0.034Attic, Shingle Roof, 0.034 --0.990.99 1.801.80 9 9 9 16 98 98 96 175 FF On grade depth, Tile 0.989On grade depth, Tile 0.989 --28.6828.68 0.000.00 9 0 0 0 98 7 186 0 6 c) AED excursion 0 -8 Envelope loss/gain 9 15 417 280 12 a) Infiltration 0 0 140 42 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)9 15 557 322 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -9 -15 176 106 14 Subtotal 0 0 733 428 15 Duct loads 39%39%0 0 39%39%288 167 Total room load 0 0 1021 595 Air required (cfm)Air required (cfm)0 0 58 30 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Oct-21 10:39:59Right-Suite® Universal 2019 19.0.20 RSU27054 Page 8... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Right-J® Worksheet Feb 12, 2020Date:House Vicki Lynne BarenbergBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Master Suite Pantry 2 Exposed wall 33.5 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft288.0x1.0 ft3.5x11.0 5 Room area 288.0 ft²38.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nene 2.582.58 2.162.16 120 97 250 209 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.3000.300 nene 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.3100.310 nene 8.998.99 16.2816.28 23 0 206 374 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 sese 2.582.58 2.162.16 148 125 322 270 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 8.708.70 13.8613.86 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 8.708.70 13.8613.86 23 10 200 318 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3100.310 sese 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 swsw 2.582.58 2.162.16 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 11.0211.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 13.8613.86 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 9.179.17 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3100.310 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 2.162.16 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 25.8025.80 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 18.6618.66 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC Attic, Shingle Roof, 0.034Attic, Shingle Roof, 0.034 --0.990.99 1.801.80 288 288 284 518 39 39 38 69 FF On grade depth, Tile 0.989On grade depth, Tile 0.989 --28.6828.68 0.000.00 288 34 961 0 39 0 0 0 6 c) AED excursion -21 -2 Envelope loss/gain 2224 1668 38 68 12 a) Infiltration 722 215 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13)2946 2383 38 68 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 26 20 -38 -68 14 Subtotal 2972 2403 0 0 15 Duct loads 39%39%1168 940 39%39%0 0 Total room load 4140 3343 0 0 Air required (cfm)Air required (cfm)235 169 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Oct-21 10:39:59Right-Suite® Universal 2019 19.0.20 RSU27054 Page 9... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Right-J® Worksheet Feb 12, 2020Date:House Vicki Lynne BarenbergBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name WIC Wtr Htr 2 Exposed wall 4.5 ft 3.5 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft11.5x4.5 ft3.5x4.0 5 Room area 51.8 ft²14.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nene 2.582.58 2.162.16 0 0 0 0 28 28 72 60 .GG Impact, Low-eImpact, Low-e 0.3000.300 nene 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 .GG Impact, Low-eImpact, Low-e 0.3100.310 nene 8.998.99 16.2816.28 0 0 0 0 0 0 0 0 .DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 sese 2.582.58 2.162.16 36 36 93 78 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 8.708.70 13.8613.86 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 sese 8.708.70 13.8613.86 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3100.310 sese 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 swsw 2.582.58 2.162.16 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 11.0211.02 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 13.8613.86 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 swsw 8.708.70 9.179.17 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3100.310 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nwnw 2.582.58 2.162.16 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 25.8025.80 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 17.1917.19 0 0 0 0 0 0 0 0 GG Impact, Low-eImpact, Low-e 0.3000.300 nwnw 8.708.70 18.6618.66 0 0 0 0 0 0 0 0 DD Door, Mtl Fbrgl Type 0.127Door, Mtl Fbrgl Type 0.127 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" DW Ex 0.101Frm Wall, 1/2" DW Ex 0.101 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC Attic, Shingle Roof, 0.034Attic, Shingle Roof, 0.034 --0.990.99 1.801.80 52 52 51 93 14 14 14 25 FF On grade depth, Tile 0.989On grade depth, Tile 0.989 --28.6828.68 0.000.00 52 5 129 0 14 4 100 0 6 c) AED excursion -5 -3 Envelope loss/gain 273 166 186 83 12 a) Infiltration 97 29 75 22 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)370 195 262 106 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 -262 -106 14 Subtotal 370 195 0 0 15 Duct loads 39%39%145 76 39%39%0 0 Total room load 515 271 0 0 Air required (cfm)Air required (cfm)29 14 0 0 2020-Oct-21 10:40:01 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Duct System Summary Feb 12, 2020Date:Guest House Vicki Lynne BarenbergBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Gardner Residence, Groza Builders, IncFor: TBD Dunn Rd, Port St Lucie, FL 34983 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.561 / 0.139 in H2O in H2O0.561 / 0.139 Lowest friction rate in/100ft0.261in/100ft0.261 Actual air flow cfm185cfm185 Total effective length (TEL) ft268 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st1200.012.1VlFx0x04.00.26525471165hG Bath st1200.012.8VlFx0x06.00.26498871867cG House -A st1200.014.7VlFx0x06.00.26198871867cG House -B Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 221 221 0.261 634 8.0 0x0 VinlFlx Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb7 0x 2210 221 53.2 0.261 501 9.0 x0 0 VlFx 2020-Oct-21 10:40:01 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2 ... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Duct System Summary Feb 12, 2020Date:House Vicki Lynne BarenbergBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Gardner Residence, Groza Builders, IncFor: TBD Dunn Rd, Port St Lucie, FL 34983 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.534 / 0.166 in H2O in H2O0.534 / 0.166 Lowest friction rate in/100ft0.233in/100ft0.233 Actual air flow cfm1317cfm1317 Total effective length (TEL) ft300 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st3200.025.1VlFx0x04.00.2371211202cBath 2 st3200.018.8VlFx0x06.00.24490991451hBed 2 st3200.019.2VlFx0x08.00.2441552533725hBed 3 st5200.018.0VlFx0x09.00.2452892304760cGreat Room st5200.017.1VlFx0x09.00.2462892304760cGreat Room-B st4200.024.8VlFx0x08.00.2372191813612cKitchen/Nook st4200.026.2VlFx0x08.00.2362191813612cKitchen/Nook-A 100.07.8VlFx0x04.00.495518834cLaundry st2200.022.1VlFx0x05.00.24036691021hMaster Bath st2200.028.6VlFx0x07.00.2331011412070hMaster Suite st2200.028.9VlFx0x07.00.2331011412070hMaster Suite-A st3200.023.3VlFx0x04.00.2391635515hWIC Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st2 Peak AVF 351 239 0.233 643 10.0 0x0 VinlFlx st3 Peak AVF 398 274 0.237 730 10.0 0x0 VinlFlx st4 Peak AVF 363 438 0.236 804 10.0 0x0 VinlFlx st5 Peak AVF 460 578 0.245 736 12.0 0x0 VinlFlx 2020-Oct-21 10:40:01 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 3 ... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb3 0x 3170 219 71.3 0.233 580 10.0 x0 0 VlFx rb2 0x 990 90 41.8 0.398 502 6.0 x0 0 VlFx rb1 0x 2530 155 49.5 0.336 573 9.0 x0 0 VlFx rb5 0x 9110 1115 36.5 0.456 511 20.0 x0 0 VlFx 2020-Oct-21 10:40:01 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 1 ... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Manual S Compliance Report Feb 12, 2020Date:Guest House Vicki Lynne BarenbergBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Gardner Residence, Groza Builders, IncFor: TBD Dunn Rd, Port St Lucie, FL 34983 Cooling Equipment Design Conditions °F76.1Entering coil DB:Btuh4212Sensible gain:°F90.4Outdoor design DB: °F63.1Entering coil WB:Btuh1118Latent gain:°F77.4Outdoor design WB: Btuh5329Total gain:°F75.0Indoor design DB: cfm185Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ASHPEquipment type: SEER 18.0, HSPF 9.1Model:GenericManufacturer: cfm185Actual airflow: % of load92Btuh3875Sensible capacity: % of load149Btuh1661Latent capacity: %70SHR:% of load104Btuh5535Total capacity: Heating Equipment Design Conditions °F69.5Entering coil DB:Btuh5449Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Split ASHPEquipment type: SEER 18.0, HSPF 9.1Model:GenericManufacturer: cfm185Actual airflow: °F39Capacity balance:% of load101Btuh5508Output capacity: °F-99Economic balance:Btuh0Supplemental heat required: Meets all requirements of ACCA Manual S. 2020-Oct-21 10:40:01 Right-Suite® Universal 2019 19.0.20 RSU27054 Page 2 ... HVAC\TBD Dunn Rd PSL Gardner Residence GBI.rup Calc = MJ8 Front Door faces: N 672Job:Manual S Compliance Report Feb 12, 2020Date:House Vicki Lynne BarenbergBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Gardner Residence, Groza Builders, IncFor: TBD Dunn Rd, Port St Lucie, FL 34983 Cooling Equipment Design Conditions °F76.6Entering coil DB:Btuh26852Sensible gain:°F90.4Outdoor design DB: °F63.8Entering coil WB:Btuh7560Latent gain:°F77.4Outdoor design WB: Btuh34411Total gain:°F75.0Indoor design DB: cfm1317Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: 14ACX-041-230*+CBA27UHE-048-230*++TDRModel:LennoxManufacturer: cfm1317Actual airflow: % of load103Btuh27650Sensible capacity: % of load157Btuh11850Latent capacity: %70SHR:% of load115Btuh39500Total capacity: Heating Equipment Design Conditions °F68.5Entering coil DB:Btuh24778Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec furnaceEquipment type: Model:Manufacturer: cfm1317Actual airflow: °F0Temp. rise:% of load0Btuh0Output capacity: Meets all requirements of ACCA Manual S. Job #: 672 Performed by Vicki Lynne Barenberg for: Gardner Residence TBD Dunn Rd Port St Lucie, FL 34983 Air Calcs, LLC 7550 Hidden Hammock Ln Vero Beach, FL 32966 Phone: 772.800.8413 vickilynne@aircalcs.com Scale: 1 : 237 Page 1 Right-Suite® Universal 2019 19.0.20 RSU27054 2020-Oct-21 10:40:14 ...Rd PSL Gardner Residence GBI.rup N Level 1 Garage G House Master SuiteWICBed 2 LaundryBath 2 Bed 3 Master Bath Hallway Linen Pantry Wtr Htr Kitchen/Nook Great Room G BathG Clst 8 x 4 12 cfm 12 x 12 317 cfm 10 x 10 141 cfm 10 x 10 141 cfm 8 x 8 69 cfm 12 x 12 289 cfm 12 x 12 219 cfm12 x 12 219 cfm 36 x 18 1115 cfm 12 x 12 253 cfm 12 x 12 99 cfm 12 x 8 253 cfm 20 " 9 "6 " 9 "8 "8 " 5 " 7 "7 " 10 x 6 51 cfm 12 x 12 289 cfm 8 x 4 35 cfm10 x 6 99 cfm 4 " 9 " 4 " 10 " 12 x 12 221 cfm 8 "6 " 4 " 10 " 12 " 10 " 10 " 8 x 8 98 cfm 8 x 8 98 cfm 8 x 4 47 cfm 9 " 6 " 6 " 8 " 4 "