NOTICE OF ACCEPTANCE (NO
Southeastern Metals Manufacturing Co., Inc.
11801 Industry Drive
Jacksonville, FL 32218
SCOPE:
MIAMI-DADE COUNTY
PRODUCT CONTROL SECTION
H 805 SW 26 Street, Room 208
Miami, Florida 33175-2474
T (786) 315-2590 F (786) 315-2599
,.,v,Nvw.iniamidade.gov/ccononiv
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami -Dade County RER - Product Control Section to be
used in Miami -Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section
(in Miami -Dade County) and/or the AHJ (in areas other than Miami -Dade County) reserve the right to have this product
or material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner, the
manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use
of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance, if it is
determined by Miami -Dade County Product Control Section that this product or material fails to meet the requirements
of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: 5-V Crimp Metal Roofing Panel System
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following
statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for
sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of
this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA renews NOA No.11-0714.08 and consists of pages 1 through 5.
The submitted documentation was reviewed by Gaspar J Rodriguez.
FILE COPY
NOA No.: 16-0510.23
Expiration Date: 11/08/21
Approval Date: 06/30/16
Page 1 of 5
ROOFING SYSTEM APPROVAL
Category: Roofing
Sub -Category: Non -Structural Metal Roofing
Material: Steel
Maximum Design Pressure: -180 PSF
TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT:
Product Dimensions Test Specifications Product Description
5V Crimp Metal Length : various TAS 125 Corrosion resistant, galvalume or
Roof Panels Height :'/,6" galvanized performed, Kynar or
Width: 25 ''/2" SuperL II coated, pre -finished, metal
(Coverage width: 24") panels.
Thickness: 0.0217
Yield Strength: Min.53ksi
MANUFACTURING LOCATION:
1. Jacksonville, FL
EVIDENCE SUBMITTED:
Test Agency
Test Identifier
Test Name/Report
Date
PRI Construction Materials
SEM-011-02-05
TAS-125
11/23/10
Technologies
PRI Construction Materials
SEM-011-02-07
ASTM E 8
05/07/12
Technologies
Farabaugh Engineering and
T270-07
TAS-100
08/24/07
Testing, Inc.
Farabaugh Engineering and
T166-07
TAS-100
04/15/07
Testing, Inc.
Force Engineering & Testing,
188-0331T-06A-C
TAS-125
02/26/07
Inc.
Hurricane Test Laboratory, LLC.
0041-0906-07
TAS-125
09/12/07
BASF
Accelerated Weathering
ASTM G 154
07/12/07
BASF
Salt Spray
ASTM B 117
07/12/07
NOA No.: 16-0510.23
Expiration Date: 11/08/21
Approval Date: 06/30/16
Page 2 of 5
APPROVED ASSEMBLIES:
System: "5V-Crimp" Metal Panels
Deck Type: Wood, Non -insulated
Deck Description: 19/32" or greater plywood or wood plank.
Slope Range: 2": 12" or greater
Maximum Uplift
Pressure: See Table A Below
Deck Attachment:
In accordance with applicable building code, but in no case it shall be less than 8d annular
ring shank nails spaced at 6" o.c. In re -roofing, where deck is less than 19/32" thick (minimum
15/32") the above attachment method must be in addition to existing attachment.
Underlayment:
Minimum underlayment shall be an ASTM D 226 Type II installed with a minimum 4" side -
lap and 6" end -laps. Underlayment shall be fastened with corrosion resistant tin -caps and 12
gauge 1-'/a" annular ring -shank nails, spaced 6" o.c. at all laps and two staggered rows 12" o.c.
in the field of the roll. Or, any approved underlayment having a current NOA.
Valleys:
Valley construction shall be in compliance with Roofing Application Standard RAS 133 and
with current published installation instructions and details in Southeastern Metal
Manufacturing Metal Roofing Installation Manual.
Fire Barrier Board:
Any approved fire barrier having a current NOA. Refer to a current fire directory listing for
fire ratings of this roofing system assembly as well as the location of the fire barrier within the
assembly. See Limitation # 1.
Metal Panels and
Install the "5V-Crimp Panels" and accessories in compliance with the current published
Accessories:
installation instructions and details in Southeastern Metals Manufacturing Company's
Installation Manual. Flashings, penetrations, valley construction and other details shall be
constructed in compliance with Roofing Application Standard RAS 133.
1. At the eave, rake, and ridge, fasteners shall be located not more than 3" away from the
panel end.
2. The leading side edge of the panel should be the side with the anti -siphon groove; each
panel side will overlap this channel to provide a capillary brake.
3. The panels shall be fastened with metal roofing sealing washer screws with dimensions as
listed below in Table A, in the crown of the inverted V ribs as shown in the details herein.
4. The panel's width fasteners shall be spaced at 11 ''/z" to the center rib, Then 12 %Z" to the
next, perpendicular to the slope, through the overlapping panel. The flat area of the panel
as shown in the details herein.
5. The panels fastening pattern at the interior of the panel, shall be in rows spaced as listed in
Table A below, running parallel to the slope of the roof.
Table A
Maximum Desi n Pressure
Field
Perimeter and Corners
Perimeter and Corner,
Maximum Design Pressure
-67.25 PSF
-154.75 PSF
-180 PSF
Fastener Type
#9 x 2"
#9 x 2"
#10-14 x 2-1/2"
Maximum Fastener Spacing
16" OC
8" OC
8" OC
1. Extrapolation shall not be allowed
NOA No.: 16-0510.23
Expiration Date: 11/08/21
Approval Date: 06/30/16
Page 3 of 5
LIMITATIONS
1. Fire classification is not part of this acceptance; refer to a current Approved Roofing Materials Directory for fire
ratings of this product.
2. The maximum designed pressure listed herein shall be applicable to all roof pressure zones (i.e. field, perimeters,
and corners). Neither rational analysis, nor extrapolation shall be permitted for enhanced fastening at enhanced
pressure zones (i.e. perimeters, extended corners and corners).
3.. Panels may be rolls formed in continuous lengths from eave to ridge. Maximum lengths shall be as described in
Roofing Application Standard RAS 133
4. All panels shall be permanently labeled with the manufacturer's name and/or logo, and the following statement:
"Miami -Dade County Product Control Approved" or with the Miami -Dade County Product Control Sea] as seen
below. All clips shall be permanently labeled with the manufacturer's name and/or logo, and/or model.
of _ APpPROV,ED
5. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and
Rule 61G20-3 of the Florida Administrative Code.
NOA No.: 16-0510.23
MIAM�4DAD CCODUNTY Expiration Date: 11/08/21
Approval Date: 06/30/16
Page 4 of 5
"5-V CRIMP METAL ROOF PANELS
25 1/2"
111/2" 121/2"
f-/-1J I GINIIVV rI11 I GF%IN roll J V-%,V%I lVlr P11 IIN 1 I-l\l%Jl% Vl 1 rl%19LL
25 1/2"
111/2" 121/2" 1111--
FASTENING PATTERN FOR 5V-CRIMP AT EAVE & RIDGE
SeeTable A
Herein for Maximum
END OF THIS ACCEPTANCE
NOA No.: 16-0510.23
MIAMI•DAD, COUNTY Expiration Date: 11/08/21
Approval Date: 06/30/16
Page 5 of 5