HomeMy WebLinkAboutProduct Evaluation ReportBUILDING DROPS
A Perfect Solution in Every Drop
Certificate of Authorization: 29578
i
JELD-WEN, Inc.
398 E. Dania Beach Blvd.
Suite 338
Dania Beach, FL 33004
954.399.8478 PH
954.744.4738 FX
contact@buildingdrops.com
Premium Atlantic Vinyl Single Hung - Impact
for
Florida Product Approval
Current Florida Building Code
Method: 1— A (Certificate)
Category: Windows
Sub — Category: Single Hung
Product: Premium Atlantic Vinyl Single Hung - Impact
Material: PVC
Product Dimensions: 3 6 " x 72" (O/X)
Prepared For:
JELD-WEN, Inc.
3737 Lakeport Blvd.
Klamath Falls, OR 97601
Prepared by: ``���ur, i i i,it11,1
Hermes F. Norero, P.E. .�� DES F. O '0:'
Florida Professional Engineer # 73778 �`� Q- ,..••'•' "w• . �` ��i
Date: 08/11/2014 �� Z�;' �,� '� �p
7
Contents:
Evaluation Report Pages 1— 4 = D. T T
Digitally signed by Hermes F. Norero,'�•.F�, •''••••••••'•• 'G�=�`
Reason: I am approving this document It E�����
Date: 2014.09.1916:31:49-04'00'
Hermes F. Norero, P.E.
Florida No. 73778
BUILDING DROPS
A Perfect Solution in Every Drop
Certificate of Authorization: 29578
Manufacturer:
Product Category:
Product Sub -Category:
Compliance Method:
JELD-WEN, Inc.
Windows
Single Hung
State Product Approval Method (1)(a)
Product Name: Premium Atlantic Vinyl Single Hung — Impact
(Impact)
36" x 72" (O/X)
Date: 08/11/2014
Report No: 3094
Scope: This is a Product Evaluation Report issued by Hermes F. Norero, P.E. (FL # 73778) for JELD-WEN, Inc.
based on Method 1a of the State of Florida Product Approval, Department of Business and
Professional Regulation - Florida Building Commission.
Limits of Use:
Hermes F. Norero, P.E. does not have nor will acquire financial interest in the company
manufacturing or distributing the product or in any other entity involved in the approval process of
the product named herein.
This product has been evaluated for use in locations adhering to the current Florida Building Code.
See Installation Instructions NCTL210-3875-1-FBC, signed and sealed by Hermes F. Norero, P.E. (FL #
73778) for specific use parameters.
1. This product has been evaluated and is in compliance with the current Florida Building Code,
including the "High Velocity Hurricane Zone" (HVHZ).
2. Product anchors shall be as listed and spaced as shown on details. Anchor embedment into
substrate material shall be beyond wall dressing or stucco.
3. When used in areas requiring wind borne debris protection this product complies with
Section 1609.1.2 of the current Florida Building Code and does not require an impact
resistant covering.
4. Site conditions that deviate from the details of drawing NCTL210-3875-1-FBC require further
engineering analysis by a licensed engineer or registered architect.
5. See Installation Instructions NCTL210-3875-1-FBC for size and design pressure limitations.
Hermes F. Norero, P.E.
Florida No. 73778
Page 2 of 4
BUILDING DROPS Rate: 0 °�4
Report Noo: : 3094
A Perfect Solution in Every Drop
Certificate of Authorization: 29578
Quality Assurance: The manufacturer has demonstrated compliance of products in accordance with the
Florida Building Code for manufacturing under a quality assurance program audited
by an approved quality assurance entity through National Accreditation and
Management Institute (FBC Organization #: QUA 1789).
Performance Standards: The product described herein has been tested per:
• TAS 201-94
• TAS 202-94
• TAS 203-94
Referenced Data: 1. Product Testing performed by National Certified Testing Laboratories NW
(FBC Organization # TST9341)
Report #: NCTL-210-3875-1, Report Date: 4/18/2013
2. Certification Agency
National Accreditation and Management Institute
(FBC Organization #: CER 1773)
3. Material Certification
Miami Dade RER— Product Control Section NOA
E.I. DuPont De Nemours & Co., Inc.: PVB Interlayer
4. Material Certification
Miami Dade RER— Product Control Section NOA
Quanex Building Products: PVC Extrusions
Hermes F. Norero, P.E.
Florida No. 73778
Page 3 of 4
ib
BUILDING DROPS Date: 0: 30 4
Report No: 94
A Perfect Solution in Every Drop q
Certificate of Authorization: 29578
Through Frame Installation: 1. Approved anchor types and substrates areas follows:
A. For concrete (Min. f c = 3000 psi) or masonry substrate (Min. f c = 1500 psi) where one
by (1X), non-structural, wood bucking is employed, use (1) 3/16" diameter ITW Tapcon
type concrete screw anchors per location of sufficient length to achieve minimum
embedment of 1.25" into concrete or masonry.
B. For concrete (Min. fc = 3000 psi) or masonry substrate (Min. fc = 1500 psi) where wood
bucking is NOT employed, use (1) 3/16" diameter ITW Tapcon type concrete screw
anchors per location of sufficient length to achieve minimum embedment of 1.25" into
concrete or masonry.
C. For steel substrate, use (1) #8 Tek Screw type steel frame (min. 18ga.) anchors per
location of sufficient length to achieve minimum three threads of penetration beyond
steel structure.
Nail Fin Installation (Where applicable):
A. For wood substrates (Min. S.G. = 0.42) use (1) #10 Wood Screw type installation anchors
per location of sufficient length to achieve a minimum embedment of 1.50" into the
wood substrate.
Refer to Installation Instructions (NCTL210-3875-1-FBC) for anchor spacing and more details of the
installation requirements.
Design Pressure:
Design Pressure
Positive 65 PSF
Negative 70 PSF
Hermes F. Norero, P.E.
Florida No. 73778
Page 4 of 4