HomeMy WebLinkAboutWS 6 - Revised Mechanical Layout & CalcsEnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 410/26/2020 2:54 PM
Project Name:
Owner:
Builder Name:
Permit Office:
Jurisdiction:
ST LUCIE COUNTY
K. HOVNANIAN
WATERSTONE LOT-6
WATERSTONE LOT-6 LENNOX
Street:
City, State, Zip:FT. PIERCE , FL , 34951 Permit Number:
Design Location:FL, Fort Pierce County:St. Lucie (Florida Climate Zone 2 )
1. New construction or existing
2. Single family or multiple family
3. Number of units, if multiple family
4. Number of Bedrooms
5. Is this a worst case?
6. Conditioned floor area above grade (ft²)
New (From Plans)
Single-family
1
No
1616
7. Windows
a. U-Factor:
S H G C :
b. U-Factor:
S H G C :
c. U-Factor:
S H G C :
d. U-Factor:
S H G C :
Dbl, U=0.32 105.67 ft²
SHGC=0.30
Dbl, U=0.55 41.00 ft²
SHGC=0.34
Dbl, U=0.32 15.50 ft²
SHGC=0.27
N/A f t ²
8. Floor Types
a. Slab-On-Grade Edge Insulation
b. N/A
c. N/A
R=0.0 1616.00 ft²
R=f t ²
R=f t ²
9. Wall Types
a. Concrete Block - Ext Insul, Exterior R=4.1 1450.90 ft²
b. Frame - Wood, Adjacent R=11.0 265.78 ft²
c. N/A R=f t ²
10. Ceiling Types
a. Under Attic (Vented)R=30.0 1616.00 ft²
f t ² R=b. N/A
c. N/A R = f t ²
11. Ducts
a. Sup: Attic, Ret: Attic, AH: Main
12. Cooling systems
13. Heating systems
14. Hot water systems
a. Electric Cap: 40 gallons
b. Conservation features
None
d. N/A R=f t ²
Area Weighted Average Overhang Depth:4.657 ft.
Area Weighted Average SHGC:0.307
Description Area
Insulation Area
Insulation Area
Insulation Area
15. Credits Pstat
4
(162.2 sqft.)
(1716.7 sqft.)
(1616.0 sqft.)
(1616.0 sqft.)
Conditioned floor area below grade (ft²)0
a. Central Unit
a. Electric Strip Heat
k B t u / h r
29.0 SEER:16.00
Efficiency
k B t u / h r Efficiency
19.1 COP:1.00
f t ² R
6 641
EF: 0.920
Glass/Floor Area:0.100 Total Proposed Modified Loads:
Total Baseline Loads:
51.83
56.92 PASS
I hereby certify that the plans and specifications covered by
this calculation are in compliance with the Florida Energy
Code.
PREPARED BY:
DATE:
I hereby certify that this building, as designed, is in compliance
with the Florida Energy Code.
OWNER/AGENT:
DATE:
BUILDING OFFICIAL:
DATE:
Review of the plans and
specifications covered by this
calculation indicates compliance
with the Florida Energy Code.
Before construction is completed
this building will be inspected for
compliance with Section 553.908
Florida Statutes.
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.3.2.1.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 6.00 ACH50 (R402.4.1.2).
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
FORM R405-2017
10/26/2020
10/26/2020
PROJECT
Title:
Owner Name:
# of Units:
Builder Name:
Permit Office:
Jurisdiction:
ST LUCIE COUNTY
K. HOVNANIAN
1
WATERSTONE LOT-6
WATERSTONE LOT-6 LENN
Family Type:
New/Existing:
Bedrooms:
Conditioned Area:
Total Stories:
Worst Case:
Rotate Angle:0
No
1
1616
4
New (From Plans)
Single-family
Address Type:
Lot #
Block/Subdivision:
PlatBook:
Street:
County:
City, State, Zip:
FL , 34951
FT. PIERCE ,
St. Lucie
3/ WATERSTONE
6
Lot Information
Comment:
Building Type:User
Cross Ventilation:No
Whole House Fan:No
TMY Site
Design Temp Int Design Temp Heating Design Daily Temp
Design Location 2.5 %97.5 %Degree Days Moisture RangeWinterSummer
CLIMATE
90 70 75 299 62 Low39FL_VERO_BEACH_MUNIFL, Fort Pierce______
Number Name Area Volume
BLOCKS
1 Block1 1616 14059.2
Number Name Area Volume
SPACES
Kitchen Occupants Bedrooms Cooled HeatedInfil ID Finished
1 Main 1616 14059.2 Yes 5 4 Yes Yes1Yes
#Floor Type Area Tile Wood Carpet
FLOORS
R-ValueSpacePerimeter
1 1616 ft² 0 0 1______Slab-On-Grade Edge Insulatio - - - -0197.8 ft Main
#Type Materials Color Absor.
Roof Solar Deck
Insul.
Pitch
ROOF
Tested
Roof
Area
Gable
Area
Emitt
Tested
EmittSA
(deg)
Rad
Barr
1 Hip Composition shingles 1750 ft² Medium 0.4 0 22.6______N0 ft² 0.9 NoN
ATTIC
#Type Ventilation Area RBS IRCCVent Ratio (1 in)
______1 Full attic Vented 1616 ft² N N150
#Ceiling Type R-Value Area Framing Frac Truss Type
CEILING
Space Ins Type
1 Under Attic (Vented)30 1616 ft² 0.1 Wood______Main Blown
10/26/2020 2:54 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 2 of 4
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
WALLS
#Wall Type R-Value Area
Adjacent Framing Solar
Ornt Fraction Absor.
HeightWidth
Ft In Ft InTo
Cavity Sheathing
R-ValueSpace Grade%
Below
1 4.1 0Main080258NEConcrete Block - Ext Insul 0.30Exterior216.7 ft² ____
2 4.1 0Main080528SEConcrete Block - Ext Insul 0.30Exterior450.7 ft² ____
3 4.1 0Main084168SWConcrete Block - Ext Insul 0.30Exterior141.6 ft² ____
4 4.1 0Main085558NWConcrete Block - Ext Insul 0.30Exterior480.3 ft² ____
5 11 0Main088308-Frame - Wood 0.30.25Garage265.8 ft² ____
6 4.1 0Main08888NWConcrete Block - Ext Insul 0.30Exterior75.1 ft² ____
7 4.1 0Main080108NEConcrete Block - Ext Insul 0.30Exterior86.7 ft² ____
#Door Type U-Value AreaStorms
DOORS
Ornt Space Width
Ft In Ft In
Height
1 Insulated .16 20 ft² None______SW Main 863
2 Wood .28 17.8 ft² None______-Main 8682
#Ornt Panes NFRC U-Factor SHGC Area Depth Separation Int ShadeFrame Screening
WINDOWS
Overhang
Orientation shown is the entered, Proposed orientation.
Wall
ID Imp
1 NE Double (Clear)0.32 0.3 49.8 ft² 1 ft 0 in 1 ft 0 in NoneVinyl None______Yes1 N
2 NE Double (Clear)0.32 0.3 24.9 ft² 10 ft 0 in 1 ft 0 in NoneVinyl None______Yes7 N
3 SE Double (Clear)0.32 0.3 15.5 ft² 1 ft 0 in 1 ft 0 in NoneVinyl None______Yes2 N
4 SW Double (Clear)0.32 0.27 15.5 ft² 1 ft 0 in 1 ft 0 in NoneVinyl None______Yes3 N
5 NW Double (Clear)0.32 0.3 15.5 ft² 1 ft 0 in 1 ft 0 in NoneVinyl None______Yes4 N
6 NW Double (Clear)0.55 0.34 41.0 ft² 10 ft 0 in 1 ft 0 in NoneVinyl None______Yes6 N
#Floor Area Ceiling Area Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation
GARAGE
1 380 ft² 380 ft² 48 ft 8.7 ft 1______
Method CFM 50 ACH 50ELASLAScope
INFILTRATION
ACHEqLA#
1405.9 677.18.000332Wholehouse .1189145.15Proposed ACH(50)1
HEATING SYSTEM
#System Type Efficiency Capacity DuctsSubtypeBlockSpeed
1 Electric Strip Heat/COP:1 19.12 kBtu/hr ______sys#1None1
10/26/2020 2:54 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 4
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
#System Type Efficiency Capacity Air Flow SHR
COOLING SYSTEM
DuctsSubtypeBlockSubtype
1 Central Unit/SEER: 16 29 kBtu/hr c f m 0.7______sys#1Split1 Singl
#System Type EF Cap Use SetPnt Conservation
HOT WATER SYSTEM
SubType Location
1 Electric 0.92 40 gal 60.9 gal 120 deg None______None Garage
FSEC
Company Name System Model #Collector Model #
Collector
SOLAR HOT WATER SYSTEM
Storage
FEFCert #Area Volume
None None f t ² ______
#Location R-Value Area Location Area
---- Supply -------- Return ----
Leakage Type Handler
CFM 25Air
QN RLF
DUCTS
Heat Cool
HVAC #
TOT OUT
CFM25
1 Attic 6 641 ft² Attic 68 ft² Default Leakage Main ( D e f a u l t ) ______1 1 ( D e f a u l t )
TEMPERATURES
Programable Thermostat: Y Ceiling Fans:
Cooling [ ] Jan [ ] Feb [ ] Mar [ ] Apr [ ] May [X] Jul [X] Aug [X] Sep [ ] Oct [ ] Nov [ ] Dec
[ ] Dec
[X] Dec[X] Nov
[X] Nov
[ ] Oct
[X] Oct
[ ] Sep
[ ] Sep
[ ] Aug
[ ] Aug
[ ] Jul
[ ] Jul[ ] Jun
[ ] Jun
[X] Jun
[ ] May
[ ] May
[ ] Apr
[X] Apr
[X] Mar
[X] Mar
[X] Feb
[ ] Feb
[X] Jan
[ ] Jan
Heating
Venting
Thermostat Schedule:HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling (WD)AM
PM
78
80
78
80
78
78
78
78
78
78
78
78
78
78
78
78
80
78
80
78
80
78
80
78
Cooling (WEH)AM
PM
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
Heating (WD)AM
PM
66
68
66
68
66
68
66
68
66
68
68
68
68
68
68
68
68
68
68
68
68
66
68
66
Heating (WEH)AM
PM
66
68
66
68
66
68
66
68
66
68
68
68
68
68
68
68
68
68
68
68
68
66
68
66
MASS
Mass Type Area Thickness Furniture Fraction Space
Default(8 lbs/sq.ft.0 ft² 0 ft 0.3 Main
10/26/2020 2:54 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 4
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
2017 EPL DISPLAY CARD
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 91
The lower the Energy Performance Index, the more efficient the home.
1. New home or, addition 1. __________ New (From Plans)
2. Single-family or multiple-family 2. __________ Single-family
3. No. of units (if multiple-family) 3. __________ 1
4. Number of bedrooms 4. __________ 4
5. Is this a worst case? (yes/no) 5. __________No
6. Conditioned floor area (sq. ft.) 6. __________1616
7. Windows, type and area
a) U-factor:(weighted average) 7a._________0.378
b) Solar Heat Gain Coefficient (SHGC) 7b._________0.307
c) Area 7c._________162.2
8. Skylights
a) U-factor:(weighted average) 8a._________NA
b) Solar Heat Gain Coefficient (SHGC) 8b._________NA
9. Floor type, insulation level:
a) Slab-on-grade (R-value) 9a._________0.0
b) Wood, raised (R-value) 9b._________
c) Concrete, raised (R-value) 9c._________
10. Wall type and insulation:
A. Exterior:
1. Wood frame (Insulation R-value) 10A1.________
2. Masonry (Insulation R-value) 10A2.________4.1
B. Adjacent:
1. Wood frame (Insulation R-value) 10B1.________11.0
2. Masonry (Insulation R-value) 10B2.________
11. Ceiling type and insulation level
a) Under attic 11a.________30.0
b) Single assembly 11b.________
c) Knee walls/skylight walls 11c.________
d) Radiant barrier installed 11d.________No
12. Ducts, location & insulation level
a) Supply ducts R_______6.0
b) Return ducts R_______6.0
c) AHU location Main
13. Cooling system: Capacity_______29.0
a) Split system SEER_______16.0
b) Single package SEER_______
c) Ground/water source SEER/COP_______
d) Room unit/PTAC EER_______
e) Other __________
14. Heating system: Capacity_______19.1
a) Split system heat pump HSPF_______
b) Single package heat pump HSPF_______
c) Electric resistance COP_______1.0
d) Gas furnace, natural gas AFUE_______
e) Gas furnace, LPG AFUE_______
f) Other
15. Water heating system
a) Electric resistance EF_______0.92
b) Gas fired, natural gas EF_______
c) Gas fired, LPG EF_______
d) Solar system with tank EF_______
e) Dedicated heat pump with tank EF_____
f) Heat recovery unit HeatRec%_______
g) Other
16. HVAC credits claimed (Performance Method)
a) Ceiling fans _________
b) Cross ventilation _________No
c) Whole house fan _________No
d) Multizone cooling credit _________
e) Multizone heating credit _________
f) Programmable thermostat _________Yes
*Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
I certify that this home has complied with the Florida Building Code, Energy Conservation, through the above energy
saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL
display card will be completed based on installed code compliant features.
Builder Signature:_________________________________________ Date:____________________________________
Address of New Home: ____________________________________ City/FL Zip: ________________________________FT. PIERCE, FL 34951
10/26/2020 2:54:30 PM EnergyGauge® USA 6.0.04 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
10/26/2020
5206 Armina Place
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
Florida Building Code, Energy Conservation, 6th Edition (2017)
ADDRESS:
FT. PIERCE , FL , 34951
Permit Number:
The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
(Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
MANDATORY REQUIREMENTS - See individual code sections for full details.
R402.4 Air leakage (Mandatory).
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per
square foot (1.5 L/s/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 L/s/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
R401.3 Energy Performance Level (EPL) display card (Mandatory).
10/26/2020 2:54 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 5
R402.4.3 Fenestration air leakage.
R402.4.1.1 Installation.
Exception: Site-built windows, skylights and doors.
R402.4.2 Fireplaces. New wood-burning fireplaces shall have tight-fitting flue dampers or doors, and outdoor combustion air. Where
using tight-fitting doors on factory-built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight-fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
Exception:
R402.4.1.2 Testing.
R402.4.1 Building thermal envelope.
The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer’s instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.
The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
SECTION R401 GENERAL
MANDATORY REQUIREMENTS - (Continued)
Building framing cavities shall not be used as ducts or plenums.
Mechanical system piping capable of carrying fluids above 105°F (41°C)
or below 55°F (13°C) shall be insulated to a minimum of R-3.
R403.4.1 Protection of piping insulation.
Heated water circulation systems shall be in
accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2.
Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
10/26/2020 2:54 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 2 of 5
R403.3.5 Building cavities (Mandatory).
R403.4 Mechanical system piping insulation (Mandatory).
R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory).
SECTION R403 SYSTEMS
R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
R402.4.4 Rooms containing fuel-burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric-resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be “substantially leak free” in
accordance with Section R403.3.3.
Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the
entire system, including the manufacturer’s air handler enclosure. Registers shall be taped or otherwise sealed during the
test.
Rough-in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the
manufacturer’s air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test.
2.
1.
Exceptions:
A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
Duct testing is not mandatory for buildings complying by Section 405 of this code.2.
1.
R403.1 Controls.
R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer’s designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
1.
2.
R403.5.1.1 Circulation systems.
R403.5.1.2 Heat trace systems.
Heated water circulation systems shall be provided with a circulation pump. The system return
pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited.
Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the
occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and
when there is no demand for hot water.
Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems
shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance
with the times when heated water is used in the occupancy.
MANDATORY REQUIREMENTS - (Continued)
10/26/2020 2:54 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 5
R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3 ½ inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
R403.5.6.1.1 Automatic controls. Service water-heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100°F to 140°F (38°C to 60°C).
R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of
combustion types of service water-heating systems to be turned off.
R403.5.6.2 Water-heating equipment. Water-heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water-heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
R403.5.6.2.1 Solar water-heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water-heating systems should meet the following criteria:
Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and
Be installed at an orientation within 45 degrees of true south.
1.
2.
R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
R403.7 Heating and cooling equipment (Mandatory).
R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the
equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies,
based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and
indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions
described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that
affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such
as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency
rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed.
When installed to function as a whole-house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
R403.6.1 Whole-house mechanical ventilation system fan efficacy.
E x c e p t i o n :
R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
Where whole-house mechanical ventilation fans are integral to tested and listed HVAC equipment, they shall be
powered by an electronically commutated motor.
The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10
otherwise.
1.
2.
3.
TABLE R403.6.1
WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
For SI: 1 cfm = 28.3 L/min.a.When tested in accordance with HVI Standard 916
Range hoods
In-line fan
Bathroom, utility room
Bathroom, utility room
FAN LOCATION AIRFLOW RATE MINIMUM MINIMUM EFFICACY AIRFLOW RATE MAXIMUM
(CFM)(CFM/WATT)
a
Any
Any
10
90
2.8 cfm/watt
2.8 cfm/watt
1.4 cfm/watt
2.8 cfm/watt
Any
Any
<90
Any
(CFM)
MANDATORY REQUIREMENTS - (Continued)
R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on-off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas-fired heaters shall not be equipped with continuously burning ignition pilots.
R403.10.4 Gas- and oil-fired pool and spa heaters. All gas- and oil-fired pool and spa heaters shall have a minimum thermal
efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
Where public health standards require 24-hour pump operation.
R403.10.2 Time switches.
Pumps that operate solar- and waste-heat-recovery pool heating systems.
Where pumps are powered exclusively from on-site renewable generation.3.
2.
1.
R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor-retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site-recovered
energy, such as from a heat pump or solar energy source, covers or other vapor-retardant means shall not be required.
10/26/2020 2:54 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 5
R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
C403 and C404 of the IECC—Commercial Provisions in lieu of Section R403.
R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice-melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C).
R403.7.1.2 Heating equipment capacity.
R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1.A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2.A variable capacity system sized for optimum performance during base load periods is utilized.
R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section 403.7, or the closest available size provided by the manufacturer’s product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
Design values for entering wet-bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1.
2.
Attached single- and multiple-family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
When signed and sealed by a Florida-registered engineer, in attached single- and multiple-family units, the capacity of
equipment may be sized in accordance with good design practice.
The published value for AHRI total capacity is a nominal, rating-test value and shall not be used for equipment sizing. Manufacturer’s
expanded performance data shall be used to select cooling-only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water-source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet-bulb temperature and the design value for entering dry-bulb temperature.
R404.1 Lighting equipment (Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be
high-efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high-efficacy lamps.
Exception:
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
Low-voltage lighting.
SECTION R404
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions-Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
R403.11 Portable spas (Mandatory). The energy consumption of electric-powered portable spas shall be controlled by the
requirements of APSP-14.
ELECTRICAL POWER AND LIGHTING SYSTEMS
Page 5 of 510/26/2020 2:54 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software
Project Name:
Owner:
Builder Name:
Permit Office:
Jurisdiction:
ST LUCIE COUNTY
K. HOVNANIAN
WATERSTONE LOT-6
WATERSTONE LOT-6 LENNOX
Street:
City, State, Zip:FT. PIERCE , FL , 34951 Permit Number:
Design Location:FL, Fort Pierce CHECKAIR BARRIER CRITERIA
A continuous air barrier shall be installed in the building envelope.
The exterior thermal envelope contains a continuous air barrier.
Breaks or joints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with
the insulation and any gaps in the air barrier shall be sealed.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
The junction of the foundation and sill plate shall be sealed.
The junction of the top plate and the top of exterior walls shall be
sealed.
Knee walls shall be sealed.
The space between window/door jambs and framing, and
skylights and framing shall be sealed.
Rim joists shall include the air barrier.
The air barrier shall be installed at any exposed edge of
insulation.
Exposed earth in unvented crawl spaces shall be covered with
a Class I vapor retarder with overlapping joints taped.
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Narrow cavities
Shafts, penetrations
Crawl space walls
Floors
(including
above-garage
and cantilevered
floors)
Rim joists
Windows, skylights
Walls
Ceiling/attic
General
COMPONENT
Garage separation
Recessed lighting
Plumbing and wiring
S h o w e r / t u b
HVAC register boots HVAC register boots that penetrate building thermal envelope shall
be sealed to the sub-floor or drywall.
The air barrier shall be installed behind electrical or communication
boxes or air-sealed boxes shall be installed.
The air barrier installed at exterior walls adjacent to showers and
tubs shall separate them from the showers and tubs.
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
extend behind piping and wiring.
Recessed light fixtures installed in the building thermal envelope
shall be sealed to the drywall.
Air sealing shall be provided between the garage and conditioned spaces.
When required to be sealed, concealed fire sprinklers shall only be
sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
between fire sprinkler cover plates and walls or ceilings.
C o n c e a l e d
Electrical/phone box on
exterior walls
Batts in narrow cavities shall be cut to fit, or narrow
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
INSULATION INSTALLATION CRITERIA
EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software10/26/2020 2:54 PM Page 1 of 1
Air-permeable insulation shall
not be used as a sealing material.
The insulation in any dropped ceiling/soffit
shall be aligned with the air barrier.
Cavities within corners and headers of frame walls
shall be insulated by completely filling the cavity
with a material having a thermal resistance of R-3
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Rim joists shall be insulated.
Floor framing cavity insulation shall be installed to
maintain permanent contact with the underside of
subfloor decking, or floor framing cavity insulation
shall be permitted to be in contact with the top side
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
and doors
on exterior wall
requirements
Recessed light fixtures installed in the building
thermal envelope shall be air tight and IC rated.
sprinklers
Where provided instead of floor insulation, insulation
shall be permanently attached to the crawlspace
Exterior walls adjacent to showers and tubs shall
be insulated.
2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
a. In addition, inspection of log walls shall be in accordance with the provisions of ICC-400.
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2017 Florida Building Code, Energy Conservation, 6th Edition
Jurisdiction: Permit #:
Job Information
Builder: K. HOVNANIAN Community: Lot: 6
Address:
City: FT. PIERCE State: FL Zip: 34951
Air Leakage Test Results Passing results must meet either the Performance, Prescriptive, or ERI Method
PRESCRIPTIVE METHOD-The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air
changes per hour at a pressure of 0.2 inch w.g. (50 Pascals) in Climate Zones 1 and 2.
PERFORMANCE or ERI METHOD-The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding
the selected ACH(50) value, as shown on Form R405-2017 (Performance) or R406-2017 (ERI), section labeled as infiltration, sub-section ACH50.
ACH(50) specified on Form R405-2017-Energy Calc (Performance) or R406-2017 (ERI): 6.000
_________ x 60 ÷ ______________ = ____________14059
CFM(50) Building Volume ACH(50)
PASS
When ACH(50) is less than 3, Mechanical Ventilation installation
must be verified by building department.
Method for calculating building volume:_____________________________
Retrieved from architectural plans
Code software calculated
Field measured and calculated
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals).
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company
Company Name: ______________________________________ Phone: ________________________
I hereby verify that the above Air Leakage results are in accordance with the 2017 6th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: ____________________________________ Date of Test: ______________________
Printed Name of Tester: _________________________________
License/Certification #: _____________________________ Issuing Authority: _________________________
10/26/2020 2:55:10 PM EnergyGauge® USA 6.0.04 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
2020-Oct-26 15:02:58
Right-Suite® Universal 2019 19.0.21 RSU29964 Page 1
...nts\Wrightsoft HVAC\WATERSTONE LOT-6 LENNOX.rup Calc = MJ8 Front Door faces: W
Job:Manual S Compliance Report May 4, 2020Date:Entire House By:
Project Information
WATERSTONE LOT-6For:
TBD, FT. PIERCE, FL 34951
Cooling Equipment
Design Conditions
°F76.9Entering coil DB:Btuh22129Sensible gain:°F90.5Outdoor design DB:
°F63.5Entering coil WB:Btuh8826Latent gain:°F77.7Outdoor design WB:
Btuh30955Total gain:°F75.0Indoor design DB:
cfm875Estimated airflow:%50Indoor RH:
Manufacturer's Performance Data at Actual Design Conditions
Split ACEquipment type:
ML14XC1S030-230A**+CBA27UHE-030-230*++TDRModel:LennoxManufacturer:
cfm875Actual airflow:
% of load95Btuh21004Sensible capacity:
% of load80Btuh7040Latent capacity:
%75SHR:% of load91Btuh28044Total capacity:
Heating Equipment
Design Conditions
°F69.4Entering coil DB:Btuh20135Heat loss:°F43.1Outdoor design DB:
°F70.0Indoor design DB:
Manufacturer's Performance Data at Actual Design Conditions
Elec stripEquipment type:
Model:Manufacturer:
cfm875Actual airflow:
°F50Temp. rise:% of load95kW5.6Output capacity:
Meets all requirements of ACCA Manual S.
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Oct-26 15:02:58
Right-Suite® Universal 2019 19.0.21 RSU29964 Page 1
...nts\Wrightsoft HVAC\WATERSTONE LOT-6 LENNOX.rup Calc = MJ8 Front Door faces: W
Job:Load Short Form May 4, 2020Date:Entire House By:
Project Information
WATERSTONE LOT-6For:
TBD, FT. PIERCE, FL 34951
Design Information
InfiltrationClgHtg
SimplifiedMethod9143Outside db (°F)
Semi-tightConstruction quality7570Inside db (°F)
0Fireplaces1627Design TD (°F)
L-Daily range
5040Inside humidity (%)
5911Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make Lennox
Trade Trade LENNOX
Model Cond ML14XC1S030-230A**
AHRI ref Coil CBA27UHE-030-230*++TDR
AHRI ref 10259437
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW5.6 Sensible cooling Btuh20300
Heating output Btuh19119 Latent cooling Btuh8700
Temperature rise °F20 Total cooling Btuh29000
Actual air flow cfm875 Actual air flow cfm875
Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.040
Static pressure in H2O0.50 Static pressure in H2O0.50
Space thermostat Load sensible heat ratio 0.71
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
OWNERS SUITE 178 2758 3259 120 129
DINING AREA 147 2699 3631 117 144
GREAT ROOM 219 2897 2861 126 113
BEDROOM 4 150 2039 2557 89 101
KITCHEN 145 319 1759 14 70
OS BATH 60 58 233 3 9
OS WIC 64 1029 635 45 25
FOYER 151 0 0 0 0
MECH 17 0 0 0 0
HALL BATH 79 1305 822 57 33
BEDROOM 3 168 3937 2983 171 118
LAUNDRY 51 737 1058 32 42
BEDROOM 2 147 2357 2330 102 92
HOV HALL 31 0 0 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Oct-26 15:02:58
Right-Suite® Universal 2019 19.0.21 RSU29964 Page 2
...nts\Wrightsoft HVAC\WATERSTONE LOT-6 LENNOX.rup Calc = MJ8 Front Door faces: W
Entire House 1607 20135 22129 875 875
Other equip loads 0 0
Equip. @ 1.00 RSM 22129
Latent cooling 8826
TOTALS 1607 20135 30955 875 875
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Oct-26 15:02:58
Right-Suite® Universal 2019 19.0.21 RSU29964 Page 1
...nts\Wrightsoft HVAC\WATERSTONE LOT-6 LENNOX.rup Calc = MJ8 Front Door faces: W
Job:Project Summary May 4, 2020Date:Entire House By:
Project Information
WATERSTONE LOT-6For:TBD, FT. PIERCE, FL 34951
Notes:
Design Information
Vero Beach Municipal AP, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F43 Outside db °F91Inside db °F70 Inside db °F75
Design TD °F27 Design TD °F16Daily range L
Relative humidity %50Moisture difference gr/lb59
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh17922 Structure Btuh18349
Ducts Btuh2212 Ducts Btuh3780Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0
(none) (none)Humidification Btuh0 Blower Btuh0
Piping Btuh0Equipment load Btuh20135 Use manufacturer's data y
Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh22129
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Semi-tight0Fireplaces Structure Btuh7801
Ducts Btuh1025Central vent (0 cfm) Btuh0
CoolingHeating (none)16071607Area (ft²) Equipment latent load Btuh8826
1398413984Volume (ft³)Air changes/hour 0.140.26 Equipment Total Load (Sen+Lat)Btuh30955
Equiv. AVF (cfm) 3361 Req. total capacity at 0.70 SHR ton2.6
Heating Equipment Summary Cooling Equipment Summary
Make Make LennoxTrade Trade LENNOX
Model Cond ML14XC1S030-230A**AHRI ref Coil CBA27UHE-030-230*++TDR
AHRI ref 10259437Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW5.6 Sensible cooling Btuh20300Heating output Btuh19119 Latent cooling Btuh8700
Temperature rise °F20 Total cooling Btuh29000Actual air flow cfm875 Actual air flow cfm875
Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.040Static pressure in H2O0.50 Static pressure in H2O0.50
Space thermostat Load sensible heat ratio 0.71
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Oct-26 15:02:58Right-Suite® Universal 2019 19.0.21 RSU29964 Page 1...nts\Wrightsoft HVAC\WATERSTONE LOT-6 LENNOX.rup Calc = MJ8 Front Door faces: W
Job:Right-J® Worksheet May 4, 2020Date:Entire House By:
1 Room name Entire House OWNERS SUITE
2 Exposed wall 197.8 ft 26.7 ft
3 Room height 8.7 ft 8.7 heat/coolft
4 Room dimensions ft13.3x13.3
5 Room area 1607.3 ft²177.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 3.853.85 2.572.57 305 230 886 593 116 91 351 235
.GG 4A5-2ob4A5-2ob 0.5600.560 nene 15.0615.06 34.0334.03 49 0 745 1683 25 0 373 842
.GG 4A5-2ob4A5-2ob 0.5600.560 nene 15.0615.06 34.0334.03 25 0 373 842 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 sese 3.853.85 2.572.57 452 437 1680 1124 116 116 446 299
11 GG 4A5-2ob4A5-2ob 0.5600.560 sese 15.0615.06 32.1232.12 16 2 235 501 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 swsw 3.853.85 2.572.57 142 106 409 274 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 swsw 15.0615.06 32.1232.12 16 2 235 501 0 0 0 0
DD 11J011J0 0.6000.600 swsw 16.1416.14 11.1011.10 20 20 324 223 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 3.853.85 2.572.57 557 500 1925 1288 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 nwnw 15.0615.06 34.0334.03 16 0 235 531 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 nwnw 15.0615.06 34.0334.03 41 0 615 1388 0 0 0 0
PP 12C-0sw12C-0sw 0.0910.091 --2.452.45 1.301.30 267 248 607 322 0 0 0 0
DD 11D011D0 0.3900.390 nn 10.4910.49 11.3911.39 19 19 199 216 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 --0.860.86 1.691.69 1607 1607 1384 2711 178 178 153 300
FF 22A-tpm22A-tpm 1.1801.180 --31.7431.74 0.000.00 1607 198 6280 0 178 27 846 0
6 c) AED excursion 96 -121
Envelope loss/gain 16131 12293 2169 1554
12 a) Infiltration 1791 556 285 89
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 5 1150 2 460
Appliances/other 4350 600
Subtotal (lines 6 to 13)17922 18349 2455 2702
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 17922 18349 2455 2702
15 Duct loads 12%21%2212 3780 12%21%303 557
Total room load 20135 22129 2758 3259
Air required (cfm)Air required (cfm)875 875 120 129
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Oct-26 15:02:58Right-Suite® Universal 2019 19.0.21 RSU29964 Page 2...nts\Wrightsoft HVAC\WATERSTONE LOT-6 LENNOX.rup Calc = MJ8 Front Door faces: W
Job:Right-J® Worksheet May 4, 2020Date:Entire House By:
1 Room name DINING AREA GREAT ROOM
2 Exposed wall 20.3 ft 26.6 ft
3 Room height 8.7 heat/coolft 8.7 heat/coolft
4 Room dimensions ft147.0x1.0 ft219.2x1.0
5 Room area 147.0 ft²219.2 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 3.853.85 2.572.57 101 77 295 198 87 62 240 160
.GG 4A5-2ob4A5-2ob 0.5600.560 nene 15.0615.06 34.0334.03 25 0 373 842 0 0 0 0
.GG 4A5-2ob4A5-2ob 0.5600.560 nene 15.0615.06 34.0334.03 0 0 0 0 25 0 373 842
.WW 13A-4ocs13A-4ocs 0.1430.143 sese 3.853.85 2.572.57 0 0 0 0 0 0 0 0
11 GG 4A5-2ob4A5-2ob 0.5600.560 sese 15.0615.06 32.1232.12 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 swsw 3.853.85 2.572.57 0 0 0 0 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 swsw 15.0615.06 32.1232.12 0 0 0 0 0 0 0 0
DD 11J011J0 0.6000.600 swsw 16.1416.14 11.1011.10 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 3.853.85 2.572.57 75 35 133 89 145 145 558 373
GG 4A5-2ob4A5-2ob 0.5600.560 nwnw 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 nwnw 15.0615.06 34.0334.03 41 0 615 1388 0 0 0 0
PP 12C-0sw12C-0sw 0.0910.091 --2.452.45 1.301.30 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 nn 10.4910.49 11.3911.39 0 0 0 0 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 --0.860.86 1.691.69 147 147 127 248 219 219 189 370
FF 22A-tpm22A-tpm 1.1801.180 --31.7431.74 0.000.00 147 20 643 0 219 27 844 0
6 c) AED excursion 179 -105
Envelope loss/gain 2185 2943 2202 1640
12 a) Infiltration 218 68 285 89
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 600
Subtotal (lines 6 to 13)2403 3011 2488 2329
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 91 44
14 Subtotal 2403 3011 2579 2372
15 Duct loads 12%21%297 620 12%21%318 489
Total room load 2699 3631 2897 2861
Air required (cfm)Air required (cfm)117 144 126 113
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Oct-26 15:02:58Right-Suite® Universal 2019 19.0.21 RSU29964 Page 3...nts\Wrightsoft HVAC\WATERSTONE LOT-6 LENNOX.rup Calc = MJ8 Front Door faces: W
Job:Right-J® Worksheet May 4, 2020Date:Entire House By:
1 Room name BEDROOM 4 KITCHEN
2 Exposed wall 13.7 ft 0 ft
3 Room height 8.7 heat/coolft 8.7 heat/coolft
4 Room dimensions ft13.7x11.0 ft14.0x10.3
5 Room area 150.3 ft²144.7 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 3.853.85 2.572.57 0 0 0 0 0 0 0 0
.GG 4A5-2ob4A5-2ob 0.5600.560 nene 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
.GG 4A5-2ob4A5-2ob 0.5600.560 nene 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 sese 3.853.85 2.572.57 0 0 0 0 0 0 0 0
11 GG 4A5-2ob4A5-2ob 0.5600.560 sese 15.0615.06 32.1232.12 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 swsw 3.853.85 2.572.57 0 0 0 0 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 swsw 15.0615.06 32.1232.12 0 0 0 0 0 0 0 0
DD 11J011J0 0.6000.600 swsw 16.1416.14 11.1011.10 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 3.853.85 2.572.57 119 103 397 266 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 nwnw 15.0615.06 34.0334.03 16 0 235 531 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 nwnw 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
PP 12C-0sw12C-0sw 0.0910.091 --2.452.45 1.301.30 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 nn 10.4910.49 11.3911.39 0 0 0 0 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 --0.860.86 1.691.69 150 150 129 254 145 145 125 244
FF 22A-tpm22A-tpm 1.1801.180 --31.7431.74 0.000.00 150 14 434 0 145 0 0 0
6 c) AED excursion 119 -62
Envelope loss/gain 1196 1169 125 182
12 a) Infiltration 146 45 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 1 230 0 0
Appliances/other 300 1200
Subtotal (lines 6 to 13)1342 1745 125 1382
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 473 376 159 76
14 Subtotal 1815 2120 284 1458
15 Duct loads 12%21%224 437 12%21%35 300
Total room load 2039 2557 319 1759
Air required (cfm)Air required (cfm)89 101 14 70
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Oct-26 15:02:58Right-Suite® Universal 2019 19.0.21 RSU29964 Page 4...nts\Wrightsoft HVAC\WATERSTONE LOT-6 LENNOX.rup Calc = MJ8 Front Door faces: W
Job:Right-J® Worksheet May 4, 2020Date:Entire House By:
1 Room name OS BATH OS WIC
2 Exposed wall 0 ft 11.3 ft
3 Room height 8.7 heat/coolft 8.7 heat/coolft
4 Room dimensions ft11.3x5.3 ft11.3x5.7
5 Room area 60.4 ft²64.2 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 3.853.85 2.572.57 0 0 0 0 0 0 0 0
.GG 4A5-2ob4A5-2ob 0.5600.560 nene 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
.GG 4A5-2ob4A5-2ob 0.5600.560 nene 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 sese 3.853.85 2.572.57 0 0 0 0 99 99 379 254
11 GG 4A5-2ob4A5-2ob 0.5600.560 sese 15.0615.06 32.1232.12 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 swsw 3.853.85 2.572.57 0 0 0 0 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 swsw 15.0615.06 32.1232.12 0 0 0 0 0 0 0 0
DD 11J011J0 0.6000.600 swsw 16.1416.14 11.1011.10 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 3.853.85 2.572.57 0 0 0 0 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 nwnw 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 nwnw 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
PP 12C-0sw12C-0sw 0.0910.091 --2.452.45 1.301.30 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 nn 10.4910.49 11.3911.39 0 0 0 0 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 --0.860.86 1.691.69 60 60 52 102 64 64 55 108
FF 22A-tpm22A-tpm 1.1801.180 --31.7431.74 0.000.00 60 0 0 0 64 11 360 0
6 c) AED excursion -9 -24
Envelope loss/gain 52 93 794 338
12 a) Infiltration 0 0 121 38
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 100 150
Subtotal (lines 6 to 13)52 193 916 526
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 52 193 916 526
15 Duct loads 12%21%6 40 12%21%113 108
Total room load 58 233 1029 635
Air required (cfm)Air required (cfm)3 9 45 25
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Oct-26 15:02:58Right-Suite® Universal 2019 19.0.21 RSU29964 Page 5...nts\Wrightsoft HVAC\WATERSTONE LOT-6 LENNOX.rup Calc = MJ8 Front Door faces: W
Job:Right-J® Worksheet May 4, 2020Date:Entire House By:
1 Room name FOYER MECH
2 Exposed wall 16.3 ft 0 ft
3 Room height 8.7 heat/coolft 8.7 heat/coolft
4 Room dimensions ft150.7x1.0 ft3.7x4.7
5 Room area 150.7 ft²17.1 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 3.853.85 2.572.57 0 0 0 0 0 0 0 0
.GG 4A5-2ob4A5-2ob 0.5600.560 nene 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
.GG 4A5-2ob4A5-2ob 0.5600.560 nene 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 sese 3.853.85 2.572.57 0 0 0 0 0 0 0 0
11 GG 4A5-2ob4A5-2ob 0.5600.560 sese 15.0615.06 32.1232.12 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 swsw 3.853.85 2.572.57 38 18 68 45 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 swsw 15.0615.06 32.1232.12 0 0 0 0 0 0 0 0
DD 11J011J0 0.6000.600 swsw 16.1416.14 11.1011.10 20 20 324 223 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 3.853.85 2.572.57 0 0 0 0 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 nwnw 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 nwnw 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
PP 12C-0sw12C-0sw 0.0910.091 --2.452.45 1.301.30 104 104 256 136 0 0 0 0
DD 11D011D0 0.3900.390 nn 10.4910.49 11.3911.39 0 0 0 0 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 --0.860.86 1.691.69 151 151 130 254 17 17 15 29
FF 22A-tpm22A-tpm 1.1801.180 --31.7431.74 0.000.00 151 16 518 0 17 0 0 0
6 c) AED excursion -29 -14
Envelope loss/gain 1296 629 15 15
12 a) Infiltration 46 14 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 300
Subtotal (lines 6 to 13)1342 644 15 315
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -1342 -644 -15 -315
14 Subtotal 0 0 0 0
15 Duct loads 12%21%0 0 12%21%0 0
Total room load 0 0 0 0
Air required (cfm)Air required (cfm)0 0 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Oct-26 15:02:58Right-Suite® Universal 2019 19.0.21 RSU29964 Page 6...nts\Wrightsoft HVAC\WATERSTONE LOT-6 LENNOX.rup Calc = MJ8 Front Door faces: W
Job:Right-J® Worksheet May 4, 2020Date:Entire House By:
1 Room name HALL BATH BEDROOM 3
2 Exposed wall 11.0 ft 40.0 ft
3 Room height 8.7 heat/coolft 8.7 heat/coolft
4 Room dimensions ft79.4x1.0 ft14.0x12.0
5 Room area 79.4 ft²168.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 3.853.85 2.572.57 0 0 0 0 0 0 0 0
.GG 4A5-2ob4A5-2ob 0.5600.560 nene 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
.GG 4A5-2ob4A5-2ob 0.5600.560 nene 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 sese 3.853.85 2.572.57 0 0 0 0 122 122 469 314
11 GG 4A5-2ob4A5-2ob 0.5600.560 sese 15.0615.06 32.1232.12 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 swsw 3.853.85 2.572.57 0 0 0 0 104 89 342 229
GG 4A5-2ob4A5-2ob 0.5600.560 swsw 15.0615.06 32.1232.12 0 0 0 0 16 2 235 501
DD 11J011J0 0.6000.600 swsw 16.1416.14 11.1011.10 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 3.853.85 2.572.57 96 96 368 246 122 122 469 314
GG 4A5-2ob4A5-2ob 0.5600.560 nwnw 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 nwnw 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
PP 12C-0sw12C-0sw 0.0910.091 --2.452.45 1.301.30 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 nn 10.4910.49 11.3911.39 0 0 0 0 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 --0.860.86 1.691.69 79 79 68 134 168 168 145 283
FF 22A-tpm22A-tpm 1.1801.180 --31.7431.74 0.000.00 79 11 349 0 168 40 1270 0
6 c) AED excursion -18 100
Envelope loss/gain 786 362 2928 1740
12 a) Infiltration 118 37 428 133
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 1 230
Appliances/other 0 300
Subtotal (lines 6 to 13)903 399 3356 2403
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 258 283 148 71
14 Subtotal 1161 682 3504 2474
15 Duct loads 12%21%143 140 12%21%433 510
Total room load 1305 822 3937 2983
Air required (cfm)Air required (cfm)57 33 171 118
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Oct-26 15:02:58Right-Suite® Universal 2019 19.0.21 RSU29964 Page 7...nts\Wrightsoft HVAC\WATERSTONE LOT-6 LENNOX.rup Calc = MJ8 Front Door faces: W
Job:Right-J® Worksheet May 4, 2020Date:Entire House By:
1 Room name LAUNDRY BEDROOM 2
2 Exposed wall 0 ft 24.3 ft
3 Room height 8.7 heat/coolft 8.7 heat/coolft
4 Room dimensions ft6.7x7.7 ft13.3x11.0
5 Room area 51.1 ft²146.7 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nene 3.853.85 2.572.57 0 0 0 0 0 0 0 0
.GG 4A5-2ob4A5-2ob 0.5600.560 nene 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
.GG 4A5-2ob4A5-2ob 0.5600.560 nene 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 sese 3.853.85 2.572.57 0 0 0 0 116 100 386 258
11 GG 4A5-2ob4A5-2ob 0.5600.560 sese 15.0615.06 32.1232.12 0 0 0 0 16 2 235 501
WW 13A-4ocs13A-4ocs 0.1430.143 swsw 3.853.85 2.572.57 0 0 0 0 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 swsw 15.0615.06 32.1232.12 0 0 0 0 0 0 0 0
DD 11J011J0 0.6000.600 swsw 16.1416.14 11.1011.10 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 3.853.85 2.572.57 0 0 0 0 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 nwnw 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
GG 4A5-2ob4A5-2ob 0.5600.560 nwnw 15.0615.06 34.0334.03 0 0 0 0 0 0 0 0
PP 12C-0sw12C-0sw 0.0910.091 --2.452.45 1.301.30 0 0 0 0 96 96 234 125
DD 11D011D0 0.3900.390 nn 10.4910.49 11.3911.39 0 0 0 0 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 --0.860.86 1.691.69 51 51 44 86 147 147 126 247
FF 22A-tpm22A-tpm 1.1801.180 --31.7431.74 0.000.00 51 0 0 0 147 24 772 0
6 c) AED excursion -25 118
Envelope loss/gain 44 61 1754 1250
12 a) Infiltration 0 0 143 44
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 1 230
Appliances/other 500 300
Subtotal (lines 6 to 13)44 561 1897 1824
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 612 317 201 108
14 Subtotal 656 878 2098 1932
15 Duct loads 12%21%81 181 12%21%259 398
Total room load 737 1058 2357 2330
Air required (cfm)Air required (cfm)32 42 102 92
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Oct-26 15:02:58Right-Suite® Universal 2019 19.0.21 RSU29964 Page 8...nts\Wrightsoft HVAC\WATERSTONE LOT-6 LENNOX.rup Calc = MJ8 Front Door faces: W
Job:Right-J® Worksheet May 4, 2020Date:Entire House By:
1 Room name HOV HALL
2 Exposed wall 7.7 ft
3 Room height 8.7 heat/coolft
4 Room dimensions ft4.0x7.7
5 Room area 30.7 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area Load
number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 W 13A-4ocs 0.143 ne 3.85 2.57 0 0 0 0
.G 4A5-2ob 0.560 ne 15.06 34.03 0 0 0 0
.G 4A5-2ob 0.560 ne 15.06 34.03 0 0 0 0
.W 13A-4ocs 0.143 se 3.85 2.57 0 0 0 0
11 G 4A5-2ob 0.560 se 15.06 32.12 0 0 0 0
W 13A-4ocs 0.143 sw 3.85 2.57 0 0 0 0
G 4A5-2ob 0.560 sw 15.06 32.12 0 0 0 0
D 11J0 0.600 sw 16.14 11.10 0 0 0 0
W 13A-4ocs 0.143 nw 3.85 2.57 0 0 0 0
G 4A5-2ob 0.560 nw 15.06 34.03 0 0 0 0
G 4A5-2ob 0.560 nw 15.06 34.03 0 0 0 0
P 12C-0sw 0.091 -2.45 1.30 67 48 117 62
D 11D0 0.390 n 10.49 11.39 19 19 199 216
C 16B-30ad 0.032 -0.86 1.69 31 31 26 52
F 22A-tpm 1.180 -31.74 0.00 31 8 243 0
6 c) AED excursion -14
Envelope loss/gain 586 316
12 a) Infiltration 0 0
b) Room ventilation 0 0
13 Internal gains: Occupants @ 230 0 0
Appliances/other 0
Subtotal (lines 6 to 13)586 316
Less external load 0 0
Less transfer 0 0
Redistribution -586 -316
14 Subtotal 0 0
15 Duct loads 12%21%0 0
Total room load 0 0
Air required (cfm)0 0
Job #:
Performed for:
WATERSTONE LOT-6
TBD
FT. PIERCE, FL 34951
Scale: 1 : 101
Page 1
Right-Suite® Universal 2019
19.0.21 RSU29964
2020-Oct-26 15:03:17
...HVAC\WATERSTONE LOT-6 LENNO...
N
Sheet 1
OWNERS SUITEDINING AREA
GREAT ROOM
BEDROOM 4
KITCHEN
OS BATH OS WIC
FOYER
MECH
HALL BATH
BEDROOM 3
GALLERY
LAUNDRY BEDROOM 2
HOV HALL
45 cfm
129 cfm144 cfm
126 cfm
101 cfm
42 cfm
102 cfm
70 cfm
9 cfm
57 cfm
171 cfm
875 cfm
12 "12 "
12 "12 "
12 "
8 "
8 "
5 "
8 "
6 "
4 "
6 "
16 "
14 "
7 "
8 "
7 "
6 "
2020-Oct-26 15:02:59
Right-Suite® Universal 2019 19.0.21 RSU29964 Page 1
...nts\Wrightsoft HVAC\WATERSTONE LOT-6 LENNOX.rup Calc = MJ8 Front Door faces: W
Job:Duct System Summary May 4, 2020Date:Entire House By:
Project Information
WATERSTONE LOT-6For:
TBD, FT. PIERCE, FL 34951
CoolingHeating
External static pressure in H2O0.50in H2O0.50
Pressure losses in H2O0.31in H2O0.31
Available static pressure in H2O0.19in H2O0.19
Supply / return available pressure 0.135 / 0.055 in H2O in H2O0.135 / 0.055
Lowest friction rate in/100ft0.089in/100ft0.089
Actual air flow cfm875cfm875
Total effective length (TEL) ft213
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st1115.030.0VlFx0x07.00.093921022357hBEDROOM 2
95.012.1VlFx0x08.00.1261181713937hBEDROOM 3
95.012.0VlFx0x07.00.126101892557cBEDROOM 4
st1115.031.4VlFx0x08.00.0921441173631cDINING AREA
95.016.6VlFx0x08.00.1211131262897hGREAT ROOM
95.06.0VlFx0x06.00.13433571305hHALL BATH
st1115.022.4VlFx0x06.00.09870141759cKITCHEN
95.013.3VlFx0x05.00.12542321058cLAUNDRY
st1115.031.5VlFx0x04.00.09293233cOS BATH
st1115.033.0VlFx0x06.00.09125451029hOS WIC
st1115.035.9VlFx0x08.00.0891291203259cOWNERS SUITE
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st1 Peak AVF 401 468 0.089 438 14.0 0x0 VinlFlx
2020-Oct-26 15:02:59
Right-Suite® Universal 2019 19.0.21 RSU29964 Page 2
...nts\Wrightsoft HVAC\WATERSTONE LOT-6 LENNOX.rup Calc = MJ8 Front Door faces: W
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb1 0x 8750 875 61.7 0.089 627 16.0 x0 0 VlFx