HomeMy WebLinkAboutBarcelona 900 Concrete Roof Tile
NOA No.: 19-1021.11
Expiration Date: 04/26/22
Approval Date: 11/21/19
Page 1 of 7
MIAMI-DADE COUNTY
PRODUCT CONTROL SECTION
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208
BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474
T (786) 315-2590 F (786) 315-2599
NOTICE OF ACCEPTANCE (NOA) www.miamidade.gov/economy
Boral Roofing, LLC
7575 Irvine Center Drive, Suite 100
Irvine, CA 92618
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami-Dade County RER - Product Control Section to be
used in Miami-Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami-Dade County Product Control Section
(in Miami-Dade County) and/or the AHJ (in areas other than Miami-Dade County) reserve the right to have this
product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted
manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or
suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance,
if it is determined by Miami-Dade County Product Control Section that this product or material fails to meet the
requirements of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: Barcelona 900 Concrete Roof Tile
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following
statement: "Miami-Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product,
for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section
of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami-Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA revises NOA No.19-0408.02 and consists of pages 1 through 7.
The submitted documentation was reviewed by Freddy Semino
NOA No.: 19-1021.11
Expiration Date: 04/26/22
Approval Date: 11/21/19
Page 2 of 7
ROOFING ASSEMBLY APPROVAL
Category: Roofing
Sub-Category: Roofing Tiles
Material: Concrete
1. SCOPE
This approves a roofing system using Barcelona 900 Concrete Roof Tile, as manufactured Boral Roofing LLC
in Lake Wales, FL and described this Notice of Acceptance. For locations where the pressure requirements, as
determined by applicable Building Code, do not exceed the design pressure values obtained by calculations in
compliance with RAS 127 using the values listed in the installation section herein. The attachment calculations
shall be done as a moment based system.
2. PRODUCT DESCRIPTION
Manufactured by
Applicant
Dimensions
Test
Specifications
Product
Description
Barcelona 900 Length = 17"
Width = 13"
½" thick
TAS 112
Type – 1a
High profile, interlocking, one-piece, 'S' shaped,
high-pressure extruded concrete roof tile
equipped with three nail holes. For direct deck
or battened nail-on, mechanically fastened,
mortar set or adhesive set applications.
Trim Pieces Length: varies
Width: varies
varying thickness
TAS-112 Accessory trim, boosted Barcelona, concrete
roof pieces for use at hips, rakes, ridges and
valley terminations manufactured for each tile
profile.
2.1 PRODUCTS MANUFACTURED BY OTHERS
Product Name Product Description Manufacturer
(With Current NOA)
ICP Adhesives Polyset® AH-160
Two component polyurethane
foam adhesive.
ICP Adhesives and Sealants, Inc.
TILE BONDTM Roof Tile Adhesive Single component polyurethane
foam roof tile adhesive.
The Dow Chemical Company
DAP Foam Touch N Seal
StormBond® 2 Roof Tile Adhesive
Two component polyurethane
foam adhesive.
Dap Foam Inc.
2.2 MANUFACTURING LOCATION
2.2.1. Lake Wales, FL
NOA No.: 19-1021.11
Expiration Date: 04/26/22
Approval Date: 11/21/19
Page 3 of 7
2.3 SUBMITTED EVIDENCE:
Test Agency Test Identifier Test Name/Report Date
Redland Technologies 7161-03
Appendix III
Static Uplift Testing
TAS 102 & TAS 102(A)
Dec. 1991
Redland Technologies 7161-03
Appendix II
Wind Tunnel Testing
TAS 108(Nail-On)
Dec. 1991
Redland Technologies P0402 Withdrawal Resistance
Testing of screw vs. smooth
shank nails
Sept. 1993
Redland Technologies Letter Dated Aug. 1,
1994
Wind Tunnel Testing
TAS 108 (Nail-On)
Aug. 1994
Redland Technologies P0631-01 Wind Tunnel Testing
TAS 108 (Mortar Set)
July 1994
Professional Service Industries, Inc. IC-1320-94 Physical Properties
TAS 112
Feb. 1995
The Center for Applied Engineering, Inc. 25-7688-3
25-7688-10
TAS 101 (Adhesive Set)
TAS 101 (Mortar Set)
June 1996
July 1996
The Center for Applied Engineering, Inc. 25-7688-5 Static Uplift Testing
TAS 102
(3" Headlap, Nails, Direct
Deck, New Construction)
June 1996
The Center for Applied Engineering, Inc. 25-7688-4 Static Uplift Testing
TAS 102
(4" Headlap, Nails, Clips)
June 1996
Celotex Corporation
Testing Services
520111-3
520191-2-1
Static Uplift Testing
TAS 101
Dec. 1998
March 1999
Walker Engineering, Inc. Calculations Aerodynamic Multiplier 09/01/16
Walker Engineering, Inc. Evaluation
Calculations
Restoring Moments Due to
Gravity
09/01/16
American Test Lab of South Florida RT0617.03-16 TAS 112 06/29/16
PRI Construction Materials Technologies COPO-002-02-10 Static Uplift Testing
TAS 101 (Adhesive Set)
10/12/2016
PRI Construction Materials Technologies COPO-002-02-02 Static Uplift Testing
TAS 101 (Adhesive Set)
10/12/2016
PRI Construction Materials Technologies COPO-002-02-01 Static Uplift Testing
TAS 101 (Adhesive Set)
10/12/2016
NOA No.: 19-1021.11
Expiration Date: 04/26/22
Approval Date: 11/21/19
Page 4 of 7
3. LIMITATIONS:
3.1 Fire classification is not part of this acceptance.
3.2 For mortar or adhesive set tile applications, a static field uplift test in accordance with TAS 106 may
require, refer to applicable building code.
3.3 Applicant shall retain the services of a Miami-Dade County Certified Laboratory to perform quarterly test in
accordance with TAS 112, appendix ‘A’. Such testing shall be submitted to the Department of Regulatory
and Economic Development – Product Control Section for review.
3.4 Minimum underlayment shall be in compliance with the applicable Roofing Applications Standards listed
section 4.1 herein.
3.5 Minimum slope 4/12 for mechanically attached tiles.
3.6 30/90 hot mopped underlayment applications may be installed perpendicular to the roof slope unless stated
otherwise by the underlayment material manufacturers published literature.
3.7 This acceptance is for wood deck applications. Minimum deck requirements shall be in compliance with
applicable building code.
4. INSTALLATION
4.1 Barcelona 900 Concrete Roof Tile and its components shall be installed in strict compliance with Roofing
Application Standard RAS 118, RAS 119, and RAS 120.
4.2 Data For Attachment Calculations
Table 1: Average Weight (W) and Dimensions (l x w )
Tile Profile Weight-W (lbf) Length-l (ft.) Width-w (ft.)
Barcelona 900 11.5 1.417 1.08
Table 2: Aerodynamic Multipliers - λ (ft3)
Tile Profile λ (ft3)
Batten Application
λ (ft3)
Direct Deck Application
Barcelona 900 0.286 0.301
Table 3: Restoring Moments due to Gravity - Mg (ft.-lbf)
Tile
Profile
2":12" 3":12" 4":12" 5":12" 6":12" 7":12" or
greater
Barcelona
900
Battens Direct
Deck
Battens Direct
Deck
Battens Direct
Deck
Battens Direct
Deck
Battens Direct
Deck
Battens Direct
Deck
N/A 7.07 N/A 7.00 6.19 6.90 6.06 6.76 5.92 6.60 5.76 6.42
NOA No.: 19-1021.11
Expiration Date: 04/26/22
Approval Date: 11/21/19
Page 5 of 7
Table 4: Attachment Resistance Expressed as a Moment - Mf (ft.-lbf)
for Mechanically Attached Systems
Tile
Profile
Fastener Type Direct Deck
(min 15/32”
plywood)
Direct Deck
(min. 19/32”
plywood)
Battens
Barcelona 900 2-10d Ring Shank Nails 28.6 41.2 19.4
1-10d Smooth or Screw Shank
Nail
5.1 6.8 2.8
2-10d Smooth or Screw Shank
Nails
6.9 9.2 7.3
1 #8 Screw 20.7 20.7 18.1
2 #8 Screw 43.2 43.2 29.8
1-10d Smooth or Screw Shank
Nail (Field Clip)
23.1 23.1 19.0
1-10d Smooth or Screw Shank
Nail (Eave Clip)
29.3 29.3 24.0
2-10d Smooth or Screw Shank
Nails (Field Clip)
27.6 27.6 38.6
2-10d Smooth or Screw Shank
Nails (Eave Clip)
38.1 38.1 41.8
Table 5: Attachment Resistance Expressed as a Moment - Mf (ft-lbf)
for Mechanically Attached Systems
Tile
Profile
Fastener Type Direct Deck
(min 15/32”
plywood)
Direct Deck
(min. 19/32”
plywood)
Battens
Barcelona 900 2-10d Ring Shank Nails1 33.1 48.1 45.2
1 Installation with a 4" tile headlap and fasteners are located a min. of 2½” from head of tile.
Table 6: Attachment Resistance Expressed as a Moment Mf (ft-lbf)
for Two Paddy Adhesive1 Set Systems
Tile
Profile
Tile Application Minimum Attachment
Resistance
Barcelona 900 Tile Bond™One Component Roof Tile Adhesive
29.32
ICP Adhesives Polyset® AH-160 two-component foam
29.33
DAP Foam Touch N Seal StormBond® 2 Roof Tile Adhesive
664
1 See manufactures component approval for installation requirements.
2 TILE BONDTM Roof Tile Adhesive; Average weight per paddy 10.7 grams.
3 ICP Adhesives and Sealants, Inc.’s ICP Adhesives Polyset AH-160; Average weight per paddy 8 grams.
4 DAP Foam Touch N Seal StormBond® Roof Tile Adhesive Two-Component; Average weight per paddy 8 grams.
NOA No.: 19-1021.11
Expiration Date: 04/26/22
Approval Date: 11/21/19
Page 6 of 7
Table 7: Attachment Resistance Expressed as a Moment - Mf (ft-lbf)
for Single Paddy Adhesive Set Systems
Tile
Profile
Tile Application
Minimum Attachment
Resistance
Barcelona 900 ICP Adhesives Polyset® AH-160 two-component foam 66.5 5
ICP Adhesives Polyset® AH-160 two-component foam 38.7 6
DAP Foam Touch N Seal StormBond® 2 63 7
DAP Foam Touch N Seal StormBond® 2 82 8
5 Large paddy placement of 63 grams
6 Medium paddy placement of 24 grams
7 Medium paddy placement of 30 grams
8 Large paddy placement of 60 grams
Table 8: Attachment Resistance Expressed as a Moment - Mf (ft-lbf)
for Mortar Set Systems
Tile
Profile
Tile
Application
Attachment
Resistance
Barcelona 900 Mortar Set9 24.5
9 See specific mortar manufacturers Notice of Acceptance
5. LABELING
5.1 All tiles shall bear the imprint or identifiable marking of the manufacturer's name or logo as de tailed
below, or following statement: "Miami-Dade County Product Control Approved".
OR
LABEL FOR BARCELONA 900 TILE (LAKE WALES FL PLANT 2)
LOCATED UNDERNEATH TILE
6. BUILDING PERMIT REQUIREMENTS
6.1 Application for building permit shall be accompanied by copies of the following:
6.1.1 This Notice of Acceptance.
6.1.2 Any other documents required by the Building Official or applicable building code in order to
properly evaluate the installation of this system.
NOA No.: 19-1021.11
Expiration Date: 04/26/22
Approval Date: 11/21/19
Page 7 of 7
PROFILE DRAWING
BARCELONA 900 CONCRETE ROOF TILE
END OF THIS ACCEPTANCE