HomeMy WebLinkAboutEnergy Calculation Form & Manual J's Project Summary Job: wrightsoft Byte: Dec 06,2016 MAIN QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM Project Information ' For. DAY RESIDENCE 7967 PLANTATION LAKES DRIVES, PORT ST LUCIE, FL Notes: besign Inf ormation Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 °F Outside db 90 °F Inside db 70 °F Inside db 75 °F Design TD 28 °F Design TD 15 of Daily range M Relative humidity 50 % Moisture difference 61 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 21817 Btuh Structure 20752 Btuh Ducts 4875 Btuh Ducts 936 Btuh Central vent (0 cfm) 0 Btuh . Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 26692 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 20604 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3798 Btuh Ducts 1936 Btuh Heating Cooling Central vent(0 cfm) 0 Btuh Area(ftp 1934 1934 Equipment latent load 5734 Btuh Volume(ft3) 20275 20275 Air changesthour 0.25 0.13 Equipment total load 26338 Btuh Equiv.AVF(cfm) 86 43 Req. total capacity at 0.70 SHR 2.5 ton Heating Equipment Summary Cooling Equipment Summary Make Make Rheem Trade Trade RHEEM Model Cond RA1630AJlNA AHRI ref Coil RH1T3621HTANJA AHRI ref 8080143 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 8.1 kW Sensible cooling 21000 Btuh Heating output 27668 Btuh Latent cooling 9000 Btuh Temperature rise 25 °F Total cooling 30000 Btuh Actual air flow 1000 cfm Actual air flow 1000 cfm Air flow factor 0.037 cfm/Btuh Air flow factor 0.046 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.79 Calculations approved b ACCA to meet all requirements of Manual J 8th Ed. ' Y PP Y2016-Dec- 6 10 7 -F�- wrightsoftP Right-Suite®Universal 2017 17.0.08 RSU08101 Page 1 14CCK ...ft WAC\DAY RESIDENCE M.A.CORSONAND ASSOC.rup Calc=MJ8 Front Door faces: W Project Summary Date: Dec 06,2016 - - wrightsoft MASTER By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:OUICKCALCS@_AOL.COM Project Information For. DAY RESIDENCE 7967 PLANTATION LAKES DRIVES, PORT ST LUCIE, FL Notes: Design Information Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 °F Outside db 90 °F Inside db 70 °F Inside db 75 °F Design TD 28 °F Design TD 15 °F Daily range M Relative humidity 50 % Moisture difference 61 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 14908 Btuh Structure 10034 Btuh Ducts 2246 Btuh Ducts 3351 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 17155 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 12716 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2486 Btuh Ducts 885 Btuh Heating cooling Central vent (0 cfm) 0 Btuh Area(ftp 921 921 Equipment latent load 3370 Btuh Volume(ft3) 10099 10099 Air changes/hour 0.45 0.23 Equipment total load 16086 Btuh Equiv.AVF(cfm) 76 38 Req. total capacity at 0.70 SHR 1.5 ton Heating Equipment Summary Cooling Equipment Summary Make Make Rheem Trade Trade RHEEM Model Cond RA1618AJ1NA AHRI ref Coil RH1T2417STANJA AHRI ref 7940565 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 5.0 kW Sensible cooling 12600 Btuh Heating output 17155 Btuh Latent cooling 5400 Btuh Temperature rise 26 °F Total cooling 18000 Btuh Actual airflow 600 cfm Actual airflow 600 cfm Air flow factor 0.035 cfm/Btuh Air flow factor 0.045 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.80 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. F1t50ft` 2016-Dec-0610:33:27 Wrl g Right-Suite®Universal 2017 17.0.08 RSU08101 Page 2 ..ft HVAC\DAY RESIDENCE M.A.CORSON AND ASSOC.rup Calc=MJ8 Front Door faces: W -r-wrightsofC Right-JO Worksheet Job: 1 AIN Date: Dec 06,2016 By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name MAIN MUD ROOM 2 Exposed wall 144.2 ft 1.0 ft 3 Room height 10.5 ft 9.3 ft heaticool 4 Room dimensions 9.0 x 8.0 ft 5 Room area 1933.5 ft2 72.0 ft' Ty Construction U-value Or HTM Area (fY) Load Area (ftp Load number (Btuh/ft2°F) (Btuhlft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AAocs 0.143 n 4.00 2.19 558 505 2022 1105 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 18 0 328 270 0 0 0 0 2 glazing,cir low-e 0.650 n 18.20 14.99 15 0 273 225 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 20 0 364 300 0 0 0 0 11 2 glazing,clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 13AAocs 0.143 a 4.00 2.19 488 235 943 515 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 30.39 12 2 218 365 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 20 1 364 648 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 25 2 455 811 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.65 36 2 655 1175 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 33.10 160 6 2912 . 5295 0 0 0 0 V1J 13A-4ocs 0.143 se 4.00 2.19 39 17 67 37 0 0 0 0 L-G 2 glazing,clr low-e 0.650 se 18.20 23.31 23 7 413 528 0 0 0 0 13A-4ocs 0.143 s 4.00 2.19 258 162 647 354 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 12 12 221 182 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 36 36 655 540 0 0 0 0 2 glazinq,clr low-e 0.650 s 18.20., 14.99 48 48 874 720 0 0 0 0 w' 13A-4ocs 0.143 sw 0.00 0.00 0 0 0 0 0 0 0 0 13AAocs 0.143 w 4.00 2.19 93 81 324 177 9 9 37 20 2 glazing,clr low-e 0.650 w 18.20 27.01 3 1 55 81 0 0 0 0 2 glazing,clr low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr iow-e 0.650 w 18.20 31.52 9 1 164 284 0 0 0 0 2 glazing,clr low-e 0.650 w_ 0.00 0.00 0 0 0 0 0 0 0 0 W 13A-4ocs 0.143 nw 0.00 0.00 0 0 0 0 0 0 0 0 C16A-30md 0.032 0.90 2.24 1934 1934 1732 4331 72 72 65 161 F. 22A-tph 1.358 38.02 0.00 1934 144 5482 0 72 1 38 0 6 c)AED excursion 0 -5 Envelope loss/gain 19168 17942 140 177 12 a) Infiltration 2649 710 17 5 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 2100 10 Subtotal(lines 6 to 13) 21817 20752 157 161 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 21817 20752 157 181 15 Duct loads 22o 5%1 4875 936 22% 0%1 35 0 Total room load 26692 21688 192 181 Air required(cfm) 1000 1000 7 8 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. AJ wrightsc2ft' 2016-Dec-0610:33:27 �4CCA Right-Suite®Universal 2017 17.0.08 RSU08101 Page 1 ..It HVACIDAY RESIDENCE M.A.CORSONAND ASSOC.rup Calc=MJ8 Front Door faces: W - -wrightsoft° Right-J®Worksheet Job: MAIN By: Dec 06,2016 sy: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@4OL.COM 1 Room name PANTRY BEDROOM 2 2 Exposed wall 0 ft 14.0 ft 3 Room height 9.3 ft heat/cool 9.3 ft heat/cool 4 Room dimensions 1.0 x 34.0 ft 1.0 x 186.0 ft 5 , Room area 34.0 ft' 186.0 ft' Ty Construction U-value Or HTM Area (ftp Load Area (ft2) Load number (Btuh/ft'°F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 130 115 461 252 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 15 0 273 225 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 11 2 glazing,clr low-e _ 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0.143 a 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.65 0 0 0 0 0 0 0 0 2 glazing,clr low a 0.650 a 18.20 _ 33.10 0 0 0 0 0 0 0 0 13AAocs 0.143 se 4.00 2.19 0 0 0 0 0 0 0 0 LG 2 glazing,clr low-e 0.650 se 18.20 23.31 0 0 0 0 0 0 0 0 13AAocs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0,650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 W 13A-4ocs 0.143 sw 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 27.01 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 w 18.20 31.52 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 W 13A-4ocs 0.143 nw 0.00 0.00 0 0 0 0 0 0 0 0 C _ 16A-30md 0.032 0.90 2.24 34 34 30 76 186 186 167 417 F 22A-tph 1.358 38.02 0.00 34 0 0 0 186 14 532 0 r 6 c)AED excursion -2 -25 Envelope loss/gain 30 74 1433 869 12 a) Infiltration 0 0 240 64 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other o 1 0 Subtotal(lines 6 to 13) 30 74 1673 933 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 30 74 1673 933 15 Duct loads 22% 34%1 7 26 22% 0ool 374 0 Total room load 37 100 2047 933 Air required(cfm) 1 5 77 43 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsc2ft` 2016-Dec-06 10:33:27 Right-Suite@ Universal 2017 17.0.08 RSU08101 Page 2 A ...ft HVAC\DAY RESIDENCE M.A.CORSON AND ASSOC.rup Calc=MJ8 Front Door faces: W - wrightsoft• Right-JO Worksheet Job: MAIN Date: Dec 06,2016 By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax 772466-6796 Email:QUICKCALCS@AOL.COM 1 Room name BATH 2 WIC 2 2 E)gmed wall 6.0 ft 0 ft 3 Room height 9.3 ft heat/cool 9.3 ft heat/cool 4 Room dimensions 6.0 x 10.0 ft 1.0 x 38.0 ft 5 Room area 60.0 ft' 38.0 ft2 ' Ty Construction U-value Or HTM Area (ft') Load Area (ft2) Load number (Btuh/f:2°F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cocl Gross N/P/S Heat Cool Gross N/P/S Heat Cool ' 6 13A4ocs 0.143 n 4.00 2.19 56 47 187 102 0 0 0 0 2 glazing,cir low-e 0.650 n 18.20 14.99 9 0 164 135 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 11 2 glazing,clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0.143 a 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.65 0 0 0 0 0 0 0 0 2 qlazinq,clr low-e 0.650 a 18.20 33.10 0 0 0 0 0 0 0 0 V1J 13A-4ocs 0.143 se 4.00 2.19 0 0 0 0 0 0 0 0 I-G 2 glazing,clr low-e 0.650 se 18.20 23.31 0 0 0 0 0 0 0 0 13A-4ocs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 W 13AAocs 0.143 sw 0.00 0.00 0 0 0 0 0 0 0 0 13AAocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 27.01 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 w 18.20 31.52 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 W 13A- 4ocs 0.143 nw 0.00 0.00 0 0 0 0 0 0 0 0 C 16A-30md 0.032 0.90 2.24 60 60 54 134 38 38 34 85 F 22A-tph 1.358 38.02 0.00 60 6 228 0 38 0 0 0 6 c)AED excursion -10 -2 Envelope loss/gain 633 361 34 83 12 a) Infiltration 103 28 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal pines 6 to 13) 1 736 389 34 83 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 1 4 14 Subtotal 736 389 36 86 15 Duct loads 22% 34% 164 134 22% 34% 8 30 Total room load 900 523 43 116 Air required(cfm) 1 34 24 2 5 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsc3ft" 2016-Dec-06 10:33:27 Right-Suite®Universal 2017 17.0.08 RSUD8101 Page 3 It WACIDAY RESIDENCE M.A.CORSONAND ASSOC.rup Calc=MJ8 Front Door faces: W -11:2-wrightsoft' Right-JO Worksheet Job: MAIN Date: Dec 06,zoos By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name CLST 3 BEDROOM 3 2 E)q)osed well 0 ft 13.0 ft 3 Room height 9.3 ft heat/cool 9.3 ft heat/cool 4 Room dimensions 9.0 x 2.0 ft 1.0 x 177.0 ft 5 Room area 18.0 ft' 177.0 ftp ' TY Construction U-value Or HTM Area (ft') Load Area (ftp Load number (Btuh/ft;°F) (Btuh/ft� or perimeter (ft) (Stuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AAocs 0.143 n 4.00 2.19 0 0 0 0 121 101 404 221 2 glazing,or low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 .0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 20 0 364 300 11 2 glazing„clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 13A4ocs 0.143 a 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 a 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 a 18.20 32.65 0 0 0 0 0 0 0 0 2 glazinq,clr low:e _ 0.650 a 18.20 33.10 0 0 0 0 0 0 0 0 W 13A-4ocs 0.143 se 4.00 2.19 0 0 0 0 0 0 0 0 L- G 2 glazing,cir low-e 0.650 se 18.20 23.31 0 0 0 0 0 0 0 0 13A-4ocS 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 77= _ 2 glazing,cir low-e 0.650 s_ 18.20 14.99 0 0 0 0 0 0 0 0 W' 13A-4ocs 0.143 sw 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 27.01 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 31.52 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 W 13A-4ocs 0.143 nw 0.00 0.00 0 0 0 0 0 0 0 0 C 16A-30md 0.032 - 0.90 2.24 18 18 16 40 177 177 159 396 F 22Artph 1.358 - 38.02 0.00 18 0 0 0 177 13 494 0 6 c)AED excursion -1 -26 Envelope loss/gain 16 39 1421 892 12 a) Infiltration 0 0 223 60 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 116 39 11644 951 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -16 -39 131 155 14 Subtotal 0 0 1775 1106 15 Duct loads 22% 34% 0 0 22% 0% 397 0 Total room load 0 0 2171 1106 Air required(cfm) 0 0 81 51 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft` 2016-Dec-06 10:33:27 Right-Suite®Universal 2017 17.0.08 RSU08101 Page 4 ACCk ..ft HVAC\DAY RESIDENCE M.A.CORSONAND ASSOC.rup Calc=MJ8 Front Door faces: W El wrightsoft' Right-JO Worksheet Job: MAIN Date: Dec Os,zoos By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name BATH 3 HALL 2 E)qposed wall 6.0 ft 4.2 ft 3 Room height 9.3 ft heat/cool 9.3 ft heat/cool 4 Room dimensions 6.0 x 11.0 ft 1.0 x 45.5 ft 5 Room area 66.0 W 45.5 ft2 ' Ty Construction U-value Or HTM Area (W) Load Area (ft') Load number (Btuh/ft2°F) (Btuh/ft� or perimeter (ft) (Bt h) or perimeter (ft) (Btuh) Heat Cool Gross I N/P/S Heat Cool Gross N/P/S Heat Cool ' 6 13A-4ocs 0.143 n 4.00 2.19 56 47 187 102 0 0 0 0 2 glazing,cir low-e 0.650 n 18.20 14.99 9 0 164 135 0 0 0 0 2 glazing,cir low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 11 2 glazing,cir low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 13AAocs 0.143 a 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 a 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 a 18.20 32.65 0 0 0 0 0 0 0 0 2 glazinq,cir low-e, .. 0.650 a 18.20 33.10 0 0 . 0 0 0 0 0 0 W 13AAocs 0.143 se 4.00 2.19 0 0 0 0 39 17 67 37 I---G- 2 glazing,cir low-e 0.650 se 18.20 23.31 0 0- 0 0 23 7 413 528 13A-4ocs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2,giazing,cirlow-60.650 s _ 18.20 14.99 0 0 0 0 0 0 0 0 W 13A-4ocs 0.143 sw 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 w 18.20 27.01 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 w 18.20 31.52 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 1N _ 13AAocs 0.143 nw _ 0.00 0.00 0 0 0 0 0 0 0 0 C 16A-30md 11.032 0.90 2.24 66 66 59 148 46 46 41 102 F' - 22A-tpli - 1.358 38.02 0.00 66 6 228 0 46 4 158 0 6 c)AED excursion -11 140 Envelope loss/gain 638 374 679 807 12 a) infiltration 103 28 73 19 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 00 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 1 741 402 752 827 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 154 169 -752 -827 14 Subtotal 895 571 0 0 15 Duct loads 22% 34% 200 196 220/634% 0 0 Total room load 1095 767 0 0 Air required(cfm) 1 41 35 0 Or Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrlghtsoft- 2016-Dec-06 10:33:27 Right-Suite®Universal 2017 17.0.08 RSU08101 Page 5 ...It HVAC\DAY RESIDENCE M.A.CORSONAND ASSOC.rup Calc=MJ8 Front Door faces: W -e} wrightsoft Right-JO Worksheet Job: MAIN Date: Dec 06,2016 By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM • 1 Room name GAMEROOM DINING 2 E)q)osed wall 56.0 ft 17.0 It 3 Room height 9.3 ft heat/cool 11.3 ft heat/cool 4 Room dimensions 1.0 x 355.0 ft 1.0 x 209.0 ft 5 Room area 355.0 ft2 209.0 ft' ' Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 195 195 782 427 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 11 2 glazing,clr low-e_ 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 13AAocs 0.143 a 4.00 2.19 158 113 453 247 102 54 215 117 2 glazing,clr low-e 0.650 a 18.20 30.39 0 0 0 0 12 2 218 365 2 glazing,clr low-e 0.650 a 18.20 32.42 20 1 364 648 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 25 2 455 811 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.65 0 0 0 0 36 2 655 1175 2 glazing,clr low-e 0.650 a 18.20 33.10 0 0 0 0 0 0 0 0 13AAocs 0.143 se 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 se 18.20 23.31 0 0 0 0 0 0 0 0 13AAocs 0.143 s 4.00 2.19 167 119 478 261 90 42 169 92 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 12 12 221 182 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 36 36 655 540 2 glazing,clr low-e 0.650 s 18.20 . 14.99 48 48 874 720 0 0 0 0 w 13A-4ocs 0.143 sw 0.00 0.00 0 0 0 0 0 0 0 0 13AAocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 27.01 0 0 0 0 0 0 0 0 2 glazing,clrlow-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 31.52 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 W 13AAocs 0.143 nw 0. 00 0.00 0 0 0 0 0 0 0 0 C _ 16A-30md 0.032 0.90 2.24 355 355 318 795 209 209 187 468 F 22A-tph 1.358 - 38.02 0.00 355 56 2129 0 209 17 646 0 6 c)AED excursion -109 -103 Envelope loss/gain 5853 3801 2968 2837 12 a) Infiltration 960 257 354 95 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 900 Subtotal(lines 6 to 13) 6813 4058 3322 3832 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 235 259 244 275 14 Subtotal 7048 4317 3567 4107 15 Duct loads 1 22% 0%11575 0 22% 0% 7971 0 ITTotal room load 8624 4317 4364 4107 Air required(cfm) 323 1991 11 163 189 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 40-wright5oft' 2016-Dec-06 10:33:27 Right-Suite®Universal 2017 17.0.08 RSU08101 Page 6 ..ft HVAC\DAY RESIDENCE M.A.CORSONAND ASSOC.rup Calc=MJ8 Front Doorfaces: W +wrightsoft' Right-J®Worksheet Job: MAIN Date: Dec 06,2016 s By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name KITCHEN GREAT ROOM 2 Exposed wall 0 ft 18.0 ft 3 Room height 12.0 ft heat/cool 12.7 ft heat/cool 4 Room dimensions 14.0 x 14.0 ft 22.0 x 18.0 ft 5. Room area 196.0 ft2 396.0 ft2 ' Ty Construction U-value Or HTM Area (ftp) Load Area (ft2) Load number (Btuh/ft'°F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4oCS 0.143 n 4.00 2.19 0 0 0 0 0 . 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 11 2 glazing,clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0.143 a 4.00 2.19 0 0 0 0 229 69 275 150 2 glazing,clr low-e 0.650 a 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.65 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 33.10 0 0 0 0 160 6 2912 5295 -W 13A-4ocs 0.143 se 4.00 2.19 0 0 0 0 0 0 0 0 L-G 2 glazing,clr low-e 0.650 se 18.20 23.31 0 0 0 0 0 0 0 0 13A-4ocs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 VV 13A-4ocs 0.143 sw 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 27.01 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 31.52 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 W 13AAccs 0.143 nw 0.00 0.00 0 0 0 0 0 0 0 0 C 16X30md 0.032 - 0.90 _ 2.24 196 196 176 439 396 396 355 887 F 22A-tph 1.358 - 38.02 0.00 196 0 0 0 396 18 684 0 6 c)AED excursion -43 23 Envelope loss/gain 176 396 4226 6356 12 a) Infiltration 0 0 421 113 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 2300 0 0 0 Appliances/other 1 1 1200 10 Subtotal(lines 6 to 13) 176 1596 4647 6469 Less eQemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 2 5 0 0 14 Subtotal 178 1602 4647 6469 15 Ductloads 22% 34% 40 551 22% 0% 1039 0 Total room load 218 2153 5686 6469 Air required(cfm) 1 1 8 99 213 298 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. AICA- wrightsoft` 2016-Dec-06 10:33:27 Right-Suite@)Universal 2017 17.0.08 RSU08101 Page 7 ft HVACIDAY RESIDENCE M.A.CORSONAND ASSOC.rup Calc=MJ8 Front Door faces: W 'wri htsoftRight-M)Worksheet Job: 9 Date: Dec 06,2016 MAIN S By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772466-6799 Fax 772-466-6796 Email:OUICKCALCS@4OL.COM 1 Room name LAUNDRY 2 Exposed wall 9.0 ft 3 Room height 9.3 ft heat/cool 4 Room dimensions 9.0 x 9.0 ft 5 Room area 81.0 ft' • Ty Construction U-value Or HTM Area (ft) Load Area Load number (Btuh/ft'°F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool ' 6 13AAocs 0.143 n 4.00 2.19 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 11 2 glazing,clr low-e - 0.650 n 0.00 0.00 0 0 0 0 13AAocs 0.143 a 4.00 2.19 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 30.39 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.65 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 33.10 0 0 0 0 W 13AAocs 0.143 se 4.00 2.19 0 0 0 0 _G. 2.glazing,clr low-e 0.650 se 18.20 23.31 0 0 0 0 13AAocs 0.143 s 4.00 2.19 0 0 0 0 2 glazing,cir low-e 0.650 s 0.00 0.00 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 2 glazing,cir low-e 0.650 s 0.00 0.00 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 _W 13AAocs 0.143 sw 0.00 0.00 0 0 0 0 13AAocs 0.143 w 4.00 2.19 84 72 287 157 2 glazing,clr low-e 0.650 w 18.20 27.01 3 1 55 81 2 glazing,clr low-e 0.650 w 0.00 0.00 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 31.52 9 1 164 284 2 glazing,clr low-e 0.650 w 0.00 0.00 0 0 0 0 w 13AAocs 0.143 nw 0.00 0.00 0 0 0 0 C 16A-30md 0.032 - 0.90 2.24 81 81 73 181 F 22A-tph 1.358 - 38.02 0.00 81 9 342 0 6 c)AED excursion 173 Envelope loss/gain 920 876 12 a) Infiltration 154 41 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 0 Subtotal pines 6 to 13) 1075 917 Less extemal load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 1075 917 15 Duct loads 22% 0% 240 0 Total room load 1315 9171 1 Air required(cfm) 1 49 42 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrighttsoft' 2016-Dec-06 10:33:27 Right-Suite@ Universal 2017 17.0.08 RSUD8101 Page 8 ft HVAC\DAY RESIDENCE M.A.CORSONAND ASSOC.rup Calc=MJ8 Front Door faces: W - wri htscAt' Right-JO Worksheet Job: 9 MASTER Date: Dec 06,2016 By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name MASTER M WIC 1 2 Exposed wall 112.4 it 11.0 ft 3 Room height 11.0 ft 9.3 ft heaVcool 4 Room dimensions 11.0 x 10.0 ft 5 Room area 921.0 ftz 110.0 ftz ` TY Construction U-value Or HTM Area (ftp Load Area (ft2) Load number (Btuh/ft2°F) (Btuhlft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat I Cool Gross I N/P/S Heat Cool Gross N/P/S Heat Cool ' 6 13AAocs 0.143 n 4.00 2.19 178 154 618 338 0 0 0 0 2 glazing,cir low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 11 - 2 glazing,cir low-e . 0.650 n 18.20 14.99 24 0 437 360 0 0 0 0 13AAocs 0.143 a 4.00 2.19 193 148 592 323 0 0 0 0 2 glazing,clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 20 1 364 648 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 25 2 455 811 0 0 0 0 2 glazing,clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 2 qlazinq,clr low-e 0.650 a 0.00 0.00 0 0 -- 0 0 0 0 0 0 yJ 13AAocs 0.143 se 0.00 0.00 0 0 0 0 0 0 0 0 l- a 2 glazing,.clr low-e 0.650 se 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0.143 s 4.00 2.19 520 480 1920 1049 102 102 410 224 2 glazing,clr low-e 0.650 s 18.20 14.99 4 4 73 60 0 0 0 0 2 glazing,cir low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 16 16 291 240 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 20 20 364 300 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 W 13A-4ocs 0:143 sw 4.00 2.19 51 51 204. 111 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 275 215 859 469 0 0 0 0 2 glazing,clr low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 30.39 12 2 218 365 0 0 0 0 2 glazing,clr low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 w 18.20 _ _ 32.93 48 2 874 1581 0 0 0 0 W 13AAocs 0.143 nw 4.00 2.19 51 51 204 111 0 0 0 0 C 16A-30md 0.032 0.90 2.24 921 921 825 2063 110 110 99 246 F, 22 tph 1.358 - 38.02 0.00 921 112 4275 0 110 11 418 0 6 c)AED excursion 119 -36 Envelope loss/gain 12572 8948 926 434 12 a) Infiltration 2336 626 189 51 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 2 460 0 0 Appliances/other 01 1 0 Subtotal(lines 6 to 13) 14908 10034 1115 485 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 24 55 14 Subtotal 14908 10034 1139 540 15 Duct loads 15% 33% 2246 3351 15% 33% 172 180 Total room load 17155 13385 1310 721 Air required(cfm) 1 600 600 46 32 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wright6oft` 2016-Dec-06 10:33:27 Right-Suite@ Universal 2017 17.0.08 RSU08101 Page 9 �� ...tt HVAC\DAY RESIDENCE M.A.CORSONAND ASSOC.rup Calc=MJB Front Door faces: W _rF wrightsoft Right-JO Worksheet Job: Date: Dec 06,zoos MASTER QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name MASTER BATH M TOILET 2 E)q)osed wall 39.4 ft 0 ft 3 Room height 12.0 ft heat/coot 9.3 ft heat/cool 4 Room dimensions 1.0 x 238.0 ft 6.0 x 3.0 ft 5 Room area 238.0 ftz 18.0 ft2 Ty Construction U-value Or HTM Area (ftp Load Area (ftp Load number (Btuh/f:2 F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 60 60 240 131 0 0 0 0 2 glazing,clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 11 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 13A-4ocs 0.143 a 4.00 2.19 12 12 48 26 0 0 0 0 2 glazing,clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0.143 se 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 se 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0.143 s 4.00 2.19 180 160 641 350 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 4 4 73 60 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 16 16 291 240 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 W_ 13A-4ocs 0.143 sw 4.00 2.19 51 51 204 111 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 120 108 432 236 0 0 0 0 2 glazing,clr low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 30.39 12 2 218 365 0 0 0 0 2 glazing,clr low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,c_Ir low-e 0.650 w 18.20 32.93 0 0 0 0 0 0 0 0 W. 13A4ocs 0.143 nw 4.00 2.19 51 51 204 111 0 0 0 0 C 16A-30md 0.032 0.90 2.24 238 238 213 533 18 18 16 40 F_ 22A-tph 1.358 38.02 0.00 238 39 1499 0 18 0 0 0 6 c)AED excursion -24 -3 Envelope loss/gain 4063 2140 16 38 12 a) Infiltration 874 234 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal Qines 6 to 13) 4937 2374 16 38 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 11 25 4 10 14 Subtotal 4948 2400 20 48 15 Duct loads 15% 33% 746 802 15% 33% 3 16 Total room load 5693 3201 24 64 Air required(cfm) 199 143 1 1 3 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. +I&- wWrightsaft- 2016-Dec-0610:33:27 Right-Suite@ Universal 2017 17.0.08 RSUD8101 Page 10 ft HVAC\DAY RESIDENCE M.A.CORSONAND ASSOC.rup Calc=MJ8 Front Door faces: W -I+wrightsofC Right-JO Worksheet Job: MASTER Date: Dec Os,Zoos r� By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fa)c 772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name M ENTRY M LINEN 2 Fposed wall O ft O ft 3 Room height 9.3 ft heat/cool 9.3 ft heat1cool 4 Room dimensions 1.0 x 70.0 ft 4.0 x 2.0 ft 5 Room area 70.0 ft2 8.0 ft' Ty Construction U-value Or HTM Area (ftp) Load Area (ftp Load number (Btuh/ft-°F) (Btuh/ft�. or perimeter (ft) (Btuh) or perimeter (ft) (Bt h) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-40cs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 11 2 glazing,clr low-e _ 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 13A-4ocs 0.143 a 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 VV 13A-4ocs 0.143 se 0.00 0.00 0 0 0 0 0 0 0 0 I- -G 2 glazing,clr low-e 0.650 se 0.00 0.00 0 0 0 0 0 0 0 0 13AAocs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 _ 0 0 0 0 0 0 W 13AAocs 0.143 sw 4.00 2.19 0 0 0 0 0 0 0 0 13A•4ocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e_ 0.650 w 18.20 32.93 0 0 0 0 0 0 0 0 VV 13A-4ocs 0.143 nw 4.00 2.19 0 0 0 0 0 0 0 0 C_ 16A-30md 0.032 0.90 2.24 70 70 63 157 8 8 7 18 F 22A-tph 1.358 38.02 0.00 70 0 0 0 8 0 0 0 6 c)AED excursion 11 1 Envelope loss/gain 63 146 7 17 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 1 0 Subtotal(lines 6 to 13) 63 146 7 17 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -63 -146 -7 -17 14 Subtotal 0 0 0 0 15 Duct loads 15% 33% 0 0 15% 33% 0 0 Total room load 0 0 0 0 Air required(cfm) 0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 4* wrightsc2ft' 2016-Dec-06 10:33:27 A`. Right-Suite®Universal 2017 17.0.08 RSUD8101 Page 11 It HVAC\DAY RESIDENCE M.A.CORSONAND ASSOC.rup Calc=MJB Front Door faces: W wri htsofC Right-JO Worksheet Job: e MASTER Date: Dec 06,2016 BY: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name M WIC 2 MASTER SUITE 2 Eposed wall 8.0 ft 45.0 ft 3 Room height 9.3 ft heattcool 11.3 ft heat/cool 4 Room dimensions 12.0 x 5.0 ft 21.0 x 16.0 ft 5 Room area 60.0 ft2 336.0 ftz • Ty Construction Ll-value Or HTM Area (ft2) Load Area (ftp Load number (Btuh/ft'°F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 ' 13A-4ocs 0.143 n 4.00 2.19 28 28 112 61 90 66 266 145 2 glazing,clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 11 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 24 0 437 360 13AAocs 0.143 a 4.00 2.19 0 0 0 0 181 136 544 297 2 glazing,clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 20 1 364 648 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 25 2 455 811 2 glazing,clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 yJ 13AAocs 0.143 se 0.00 0.00 0 0 0 0 0 0 0 0 I-G 2 glazing,clr low-e 0.650 se 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0.143 s 4.00 2.19 0 0 0 0 237 217 870 475 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 20 20 364 300 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 _ s 0.00 0.00 0 0 0 0 0 0 0 0 W 13A-4ocs 0.143 sw 4.00 2.19 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 47 47 186 102 0 0 0 0 2 glazing,clr low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 32.93 0 0 0 0 0 0 0 0 W 13AAocs 0.143 nw 4.00 2.19 0 0 0 0 0 0 0 0 C 16A-30md 0.032 0.90 2.24 60 60 54 134 336 336 301 753 F 22A-tph 1.358 38.02 0.00 60 8 304 0 336 45 1711 0 6 c)AFD excursion -23 -311 Envelope loss/gain 656 274 5312 3478 12 a) Infiltration 137 37 938 251 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 2 460 Appliances/other 0 0 Subtotal(lines 6 to 13) 793 311 6249 4190 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 15 35 16 37 14 Subtotal 808 346 6265 4226 15 Duct loads 15% 33% 122 116 15%133% 9441 1412 Total room load 930 462 7209 5638 Air required(cfm) 33 21 252 253 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsc3ft- 2016-Dec-06 10:33:27 Right-Suite@ Universal 2017 17.0.08 RSU08101 Page 12 ...It HVAC\DAY RESIDENCE M.A.CORSONAND ASSOC.rup Calc=MJ8 Front Door faces: W -F wrightsoft Right-JO Worksheet Job: MASTER Byte: Dec Os,zoos r QUICK CALCS, INC. 1 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466.6796 Email:QUICKCALCS -AOL.COM 1 Room name FOYER 2 E)posed wall 9.0 ft 3 Room height 12.0 ft heat/cool 4 Room dimensions 9.0 x 9.0 ft 5 Room area 81.0 ft, ' Ty Construction U-value Or HTM Area (W) Load Area Load number (Btuh/ftz'F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-flocs 0.143 n 4.00 2.19 0 0 0 0 2 glazing,clr low-e 0.650 n 0.00 0.00 0 0 0 0 2 glazing,cir low-e 0.650 n 0.00 0.00 0 0 0 0 2 glazing,cir low-e 0.650 n 0.00 0.00 0 0 0 0 11 2 glazing,cir low-e 0.650 n 18.20 14.99 0 0 0 0 13A-4ocs 0.143 a 4.00 2.19 0 0 0 0 2 glazing,clr low-e 0.650 a 0.00 0.00 0 0 0 0 2 glazing,cir low-e 0.650 a 18.20 32.42 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 2 glazing,clr low-e 0.650 a 0.00 0.00 0 0 0 0 2 glazing,cir low-e 0.650 a 0.00. 0.00 0 0 0 0 V�J 13AAocs 0.143 se 0.00 0.00 0 0 0 0 �-G 2 glazing,cir low-e 0.650 se 0.00 0.00 0 0 0 0 13AAocs 0.143 s 4.00 2.19 0 0 0 0 2 glazing,cir low-e 0.650 s 18.20 14.99 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 2 glazing,cir low-e 0.650 s 18.20 14.99 0 0 0 0 2 glazing,cir low-e 0.650 s 18.20 14.99 0 0 0 0 2 glazing,cir low-e 0.650 s 0.00 0.00 0 0 0 0 2 glazing,clr low-e 0.650 s 0.00 0.00 0 0 0 0 w 13A-4ocs 0.143 sw 4.00 2.19 0 0 0 0 13AAocs 0.143 w 4.00 2.19 108 60 240 131 2 glazing,cir low-e 0.650 w 0.00 0.00 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 30.39 0 0 0 0 2 glazing,cir low-e 0.650 w 0.00 0.00 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 32.93 48 2 874 1581 W_ 13A4ocs _ 0.143 nw 4.00 2.19 0 0 0 0 C _ 16A,30md 0.032 0.90 2.24 81 81 73 181 F 22A-tph 1.358 38.02 0.00 81 9 342 0 6 c)AED excursion 527 Envelope loss/gain 1529 2420 12 a) Infiltration 199 53 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 0 Subtotal(lines 6 to 13) 1728 2474 Less edemal load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 1728 2474 15 Duct loads 15% 33% 260 826 Total room load 1988 3300 Air required(cfm) 70 148 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 4-111- WrIQIf1tt50fC" 2016-Dec-0610:33:27 ACCI� Right-Suite®Universal 2017 17.0.08 RSU08101 Page 13 ..ft HVAC\DAY RESIDENCE M.A.CORSONAND ASSOC.rup Calc=MJ8 Front Door faces: W - Duct System Summar Job. wrightsoft Date- Dec 06,2016 MAIN By. QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM Project • • i For: DAY RESIDENCE 7967 PLANTATION LAKES DRIVES, PORT ST LUCIE, FL Heating Cooling External static pressure 0 in H2O 0 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 0 in H2O 0 in H2O Supply/ return available pressure 0.000/0.000 in H2O 0.000/0.000 in H2O Lowest friction rate 0 in/100ft 0 in/100ft Actual air flow 1000 cfm 1000 cfm Total effective length(TEL) 177 ft Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln (ft) Trunk BATH 2 h 523 34 24 0 0 Ox 0 VIFx 14.9 115.0 st2 BATH 3 h 767 41 35 0 0 Ox 0 VIFx 31.2 135.0 st5 BEDROOM 2 h 933 77 43 0 0 Ox 0 VIFx 10.1 115.0 st2 BEDROOM 3 h 1106 81 51 0 0 Ox 0 VIFx 29.1 135.0 st5 DINING c 2053 82 95 0 0 Oxo VIFx 27.3 115.0 st1 DINING-A c 2053 82 95 0 0 Oxo VIFx 31.7 135.0 st5 GAMEROOM h 2158 162 100 0 0 0x0 VIFx 41.6 135.0 st5 GAMEROOM-A h 2158 162 100 0 0 0x0 VIFx 39.2 135.0 st5 GREAT ROOM c 3234 107 149 0 0 Ox 0 VIFx 35.3 135.0 st4 GREAT ROOM-A c 3234 107 149 0 0 Ox 0 VIFx 34.6 135.0 st4 KITCHEN c 2153 8 99 0 0 Ox 0 VIFx 16.3 115.0 st1 LAUNDRY h 917 49 42 0 0 Ox 0 VIFx 20.1 115.0 st1 MUD ROOM c 181 7 8 0 0 Ox 0 VIFx 20.1 115.0 SO PANTRY c 100 1 5 0 0 Ox 0 VIFx 8.3 115.0 st2 WIC 2 c 116 2 5 0 0 Ox 0 VIFx 10.9 115.0 st2 SupplyDetail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (Cfm) FR (fpm) (in) (in) Material Trunk st4 Peak AVF 213 298 0 0 0 0 x 0 VinlFlx st1 st1 Peak AVF 359 543 0 0 0 0 x 0 VinlFlx st5 Peak AVF 527 380 0 0 0 0 x 0 VinlFlx st2 st2 Peak AVF 641 457 0 0 0 0 x 0 VinlFlx 2016-Dec-06 10:33:29 wrightsoft' Right-Suite@ Universal 2017 17.0.06 RSU08101 _ gPage 1 14CCEi ...ft HVAC\DAY RESIDENCE M.A.CORSON AND ASSOC.rup Calc=MJ8 Front Door faces: W Return Branch Detail Table Grill HtgClg TEL Design Veloc Diam H x W Stud/Joist Duct w Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk rb2 0x0 1000 1000 0 0 0 0 Ox 0 VIFx - r 2016-Dec-06 10:33:29 wrightsoft' Right-Suite®Universal 2017 17.0.08 RSU08101 Page 2 AMA...lt HVAC\DAY RESIDENCE MA CORSONAND ASSOC.rup Calc=MJ8 Front Doorfaces: W Duct System Summa Job: —A � - wrightsoft MASTER Date: Dec 06,2016 By: A QUICK CALCS, INC. ,t 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM Project Information For. DAY RESIDENCE 7967 PLANTATION LAKES DRIVES, PORT ST LUCIE, FL s Heating Cooling External static pressure 0 in H2O 0 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 0 in H2O 0 in H2O Supply/return available pressure 0.000/0.000 in H2O 0.000/0.000 in H2O Lowest friction rate 0 in/100ft 0 in/100ft Actual air flow 600 cfm 600 cfm Total effective length(TEL) 186 ft Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln(ft) Trunk FOYER c 3300 70 148 0 0 Ox 0 VIFx 29.7 115.0 st3 M TOILET c 64 1 3 0 0 Ox 0 VIFx 31.9 115.0 st3 M WIC 1 h 721 46 32 0 0 Ox 0 VIFx 48.6 135.0 st7 M WIC 2 h 462 33 21 0 0 0x0 VIFx 28.3 115.0 st3 MASTER BATH h 3201 199 143 0 0 Ox 0 VIFx 37.0 115.0 st3 MASTER SUITE c 2819 126 126 0 0 Oxo VIFx 50.6 135.0 st7 MASTER SUITE-A c 2819 126 126 0 0 Ox 0 VIFx 49.4 135.0 st7 Supply Trunk Detail Table Trunk Htg Cig Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk St7 Peak AVF 298 285 0 0 0 0 x 0 VinlFlx st3 st3 Peak AVF 600 600 0 0 0 0 x 0 VinlFlx TableReturn ,Branch Detail Grill Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk rb1 Oxo 600 600 0 0 0 0 Ox 0 VIFx c wri htSoft' 2016-Dec-0610:33:29 9 Right-Suite®Universal 2017 17.0.08 RSU08101 Page 3 �� ...It HVAC\DAY RESIDENCE M.A.CORSONAND ASSOC.rup Calc=MJ8 Front Door faces: W FDOH in St. Lucie County ;. Environmental Health Sit Plan Approved for Construction SupeGENERAL NOTES edes All Previous Site Plans for 5�.-5F'17/37 3 &Well# DaTP Reviewed , .----•--------------------------------------- ::_ ... _ r nAsrER eaTu:�r 24 9� iib -....._. •�7 � � '� ��tl • 3. : ............... �R POOL ........,� -- -- -..... - -- •mrwnsu., .. ....... ................. _._._. ..... y ..... ............... ..... , O a .......... SPA ❑ GR �T ROOM . YER i b ENTR :• ........................ s................ - - ........---------............ ....... - e. - - L At NDR e ?p • •• - a :aa DININCs _ _ � E OV.PORCH o. d o K11. �. .= — i b j iwzq .......... civ „�a..� :P �, ..a. ............ ............................. a S n . � Y PANTRY ............................... ...........K •. .m • r• - • r rr 4� ' GARACsE Z4J: ��k1MER0 M� ® H s EDR H sb �' •'--'•----' �a BEDROOM'2 CART PQ i i e a Qda ..n JE lrLO®R IPLAN 114 go s®ou A ^ .r "Jtl s:�ren NS b#gua 110: s _ 01P b1su bhLr-)ASq DL C Ou?fLncf!,.)u Euitt,te.O+d1WGUf9t HSSIJP L co !u ?F* r"act conuo