HVAC Load Calculations
for
CCH.LLC
499 Corte Madera Lane, Unit 2
West Palm Beach, FL 33401
Prepared By:
Ken Fonorow
Florida H.E.R.O., Inc.
15220 NW 5th Ave
Newberry, FI 32669
(352)472-5661
Wednesday, July 3, 2019
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
Rhvac - Residential & Light Commercial HVAC Loads
Florida H.E.R.O.
Newberry, FL 32669
Project Report
General Project Information
Project Title:
Designed By:
Project Date:
Project Comment:
Client Name:
Client Address:
Client City:
Client Phone:
Client E-Mail Address:
Company Name:
Company Representative:
Company Address:
Company City:
Company Phone:
Company E-Mail Address:
Company Website:
Design Data
Reference City:
Building Orientation:
Daily Temperature Range:
Latitude:
Elevation:
Altitude Factor:
CCH-3712 Tananger
Ken Fonorow
6/31 /2019
Custom Model
CCH.LLC
499 Corte Madera Lane, Unit 2
West Palm Beach, FL 33401
954 304-3755
Christopher_ Cummings@live.com
Florida H.E.R.O., Inc.
Ken Fonorow
15220 NW 5th Ave
Newberry, FI 32669
(352) 472-5661
ken@floridahero.com
www.floridahero.com
Outdoor
D[y Bulb
Winter: 42
Summer: 90
Check Figures
Fort Pierce, Florida
Front door faces East
Medium
27 Degrees
25 ft.
0.999
Outdoor Outdoor Indoor Indoor
Wet Bulb Rel.Hum Rel.Hurn 1 y Bulb
39.4 n/a n/a 72
78 59% 50% 75
Elite Software Development, Inc.
CCH-3712 Tananper
Page 2
Grains
Difference
n/a
61
Total Building Supply CFM: 1,000
CFM Per Square ft.: 0.417
Square ft. of Room Area: 2,400
Square ft. Per Ton: 1,000
Volume (ft'): 24,002
Building Loads
Total Heating Required Including Ventilation Air:
25,626
Btuh 25.626 MBH
Total Sensible Gain:
21,017
Btuh 73 %
Total Latent Gain:
7,787
Btuh 27 %
Total Cooling Required Including Ventilation Air:
28,803
Btuh 2.40 Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\Users\Owner\Desktop\AII .Rh Files\AII .rh9 findings\CCH-3712 Tanager.rh9 Wednesday, July 3, 2019, 10:25 AM
Rhvac - Residential & Light Commercial HVAC Loads
Elite Software Development, Inc.
Florida H.E.R.O.
CCH-3712
Tananger
Newberry, FL 32669
Page 3
Miscellaneous Report
System 1 Whole House
Outdoor
Outdoor
Outdoor
Indoor
Indoor
Grains
Input Data
Dry Bulb
Wet Bulb
Rel.Hum
Rel.Hum
Dry Bulb
Difference
Winter:
42
39.4
80%
n/a
72
n/a
Summer:
90
78
59%
50%
75
61.09
Duct Sizing Inputs
Main
Trunk
Runouts
Calculate:
Yes
Yes
Use Schedule:
Yes
Yes
Roughness Factor:
0.15000
0.15000
Pressure Drop:
0.1000
in.wg./100 ft.
0.1000
in.wg./100 ft.
Minimum Velocity:
650
ft./min
450
ft./min
Maximum Velocity:
900
ft./min
750
ft./min
Minimum Height:
0
in.
0
in.
Maximum Height:
0
in.
0
in.
Outside Air Data
Winter
Summer
Infiltration Specified:
0.220
AC/hr
0.110 AC/hr
88
CFM
44 CFM
Infiltration Actual:
0.220
AC/hr
0.110 AC/hr
Above Grade Volume:
X
24,002
Cu.ft.
X 24,002
Cu.ft.
X
5,280
0.0167
Cu.ft./hr
2,640 Cu.ft./hr
X 0.0167
Total Building Infiltration:
88
CFM
44 CFM
Total Building Ventilation:
75
CFM
75 CFM
---System 1---
Infiltration & Ventilation Sensible Gain Multiplier: 16.49 = (1.10 X 0.999 X 15.00 Summer Temp. Difference)
Infiltration & Ventilation Latent Gain Multiplier: 41.50 = (0.68 X 0.999 X 61.09 Grains Difference)
Infiltration & Ventilation Sensible Loss Multiplier: 32.97 = (1.10 X 0.999 X 30.00 Winter Temp. Difference)
Winter Infiltration Specified: 0.220 AC/hr (88 CFM), Construction: Semi -Tight
Summer Infiltration Specified: 0.110 AC/hr (44 CFM), Construction: Semi -Tight
C:\Users\Owner\Desktop\AII .Rh Files\All .rh9 findings\CCH-3712 Tanager.rh9 Wednesday, July 3, 2019, 10:25 AM
Rhvac - Residential & Light Commercial HVAC Loads
Florida H.E.R.O.
Newberry, FL 32669
Duct Size Preview
Elite Software Development, Inc.
CCH-3712 Tananqer
Page 4
Room or
Duct Name
Source
Minimum
Veloci
Maximu
Veloci
Rough
Facto
Desig SP
U10 Loss
Duc jDuc
Veloci
I Htg
tj
Lengt -Flo�x
Clg Act.
-EIQ FJ- _.
Duct
Sage
Svstem 1
Supply Runouts
Zone 1
1-Master Bedroom
Built -In
450
750
0.15
0.1
503.4
160
: '
_762-Master
176
1-
WIC 1
Built -In
450
750
0.15
0.1
129
27
11
11
1
3-Master WIC 2
Built -In
450
750
0.15
0.1
34.7
1
3
3
1
4-Master Bath
Built -In
450
750
0.15
0.1
465.4
98
9 "
91
1-
5-Master Bath WC
Built -In
450
750
0.15
0.1
192.5
24
_
-7
17
1
6-Bath 2
Built -In
450
750
0.15
0.1
45.4
2
4
1
7-BR3
Built -In
450
750
0.15
0.1
333.8
63���
LLL:�66
66
1-
8-Entry
Built -In
450
750
0.15
0.1
363.5 36
L4
9-Great Room
Built -In
450,
750
0.15
0.1
454.3
114'178
178
2-
10-Dinina
Built -In
450
750
0.15
0.1
458.6 13J
� W 90
90
1-
11-Kitchen
Built -In
450
750
0.15
0.1
478.7 79
`128'
128
1-
12-Laundry
Built -In
450
750
0.15
0.1
149.7 2
3r 13
13
1
13-BR 1
Built -In
450
750
0.15
0.1
342.7 88
6
67
1--
14-Guest Bath
Built -In
450
750
0.15
0.1
374.9 65
3a
33
1
15-BR 2
Built -In
450
750
0.15
0.1
362.1
89E
. 71
71-
1--
16-Garage Entry
Built -In
450
750
0.15
0.1
0
23
20
.......................0:
20
0-
Other Ducts in System 1
Supply Main Trunk
Built -In
650
900
0.15
0.1
734.7 1,000;
'1066
1,000 14x1
Summary
Svstem 1
Heatina Flow: 1000
CoolinQ Flow: 1000
C:\Users\Owner\Desktop\All .Rh Files\AII .rh9 findings\CCH-3712 Tanager.rh9 Wednesday, July 3, 2019, 10:25 AM
Rhvac - Residential & Light Commercial HVAC Loads
Florida H.E.R.O.
Newberry, FL 32669
Total Building Summary Loads
Component
Description
VYN 29 23: Glazing-Vyn Fr Dbl Pn U .29 SHGC .23,
ground reflectance = 0.23, outdoor insect screen with
50% coverage, medium color blinds at 45' with 25%
coverage, U-value 0.29, SHGC 0.23
VYN 29 23: Glazing-Vyn Fr Dbl Pn U .29 SHGC .23,
ground reflectance = 0.23, outdoor insect screen with
50% coverage, medium color blinds at 45' with 50%
coverage, U-value 0.29, SHGC 0.23
VYN 29 23: Glazing-Vyn Fr Dbl Pn U .29 SHGC .23,
ground reflectance = 0.23, U-value 0.29, SHGC 0.23
SGD Al 55 25: Glazing -Sliding Glass Door Al Fm U 62
SHGC 22, ground reflectance = 0.32, medium color
blinds at 450 with 25% coverage, U-value 0.55,
SHGC 0.25
VYN 29 23: Glazing-Vyn Fr Dbl Pn U .29 SHGC .23,
ground reflectance = 0.23, U-value 0.29, SHGC 0.23
VYN 29 23: Glazing-Vyn Fr Dbl Pn U .29 SHGC .23,
ground reflectance = 0.32, outdoor insect screen with
50% coverage, medium color blinds at 45' with 50%
coverage, U-value 0.29, SHGC 0.23
11 P: Door -Metal - Polyurethane Core, U-value 0.29
13A-6ocs: Wall -Block, board insulation only, R-6 board
insulation, open core, siding finish, U-value 0.111
12C-Osw: Wall -Frame, R-13 insulation in 2 x 4 stud
cavity, no board insulation, siding finish, wood studs,
U-value 0.091
1613-38: Roof/Ceiling-Under Attic with Insulation on Attic
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Dark
Asphalt Shingles or Dark Metal, Tar and Gravel or
Membrane, R-38 insulation, U-value 0.026
22A-pl: Floor -Slab on grade, No edge insulation, no
insulation below floor, any floor cover, passive, light
dry soil, U-value 0.989
Subtotals for structure:
People:
Equipment:
Lighting:
Ductwork:
Infiltration: Winter CFM: 88, Summer CFM: 44
Ventilation: Winter CFM: 75, Summer CFM: 75
Exhaust: Winter CFM: 75, Summer CFM: 75
AED Excursion:
Total Building Load Totals:
Elite Software Development, Inc.
CCH-3712 Tananqer
Page 5
Area
Sen
Lat
Sen
Total
Quan
Loss
Gain
Gain
Gain
102
887
0
1,592
1,592
120
1,044
0
1,026
1,026
40
348
0
754
754
72
1,188
0
993
993
6
52
0
55
55
18
157
0
506
506
45.4
395
0
342
342
1831.3
6,100
0
2,704
2,704
268.6
734
0
526
526
2400.1
1,870
0
3,122
3,122
252 7,476
0
0
0
20,251
0
11,620
11,620
6
1,200
1,380
2,580
1,650
3,425
5,075
0
0
0
0
0
0
0
2,902
1,824
723
2,547
2,473
3,113
1,236
4,349
0
0
2,632
2,632
25,626
7,787
21,017
28,803
Check Figures
Total Building Supply CFM: 1,000 CFM Per Square ft.:
Square ft. of Room Area: 2,400 Square ft. Per Ton:
Volume (ft'): 24,002
Building Loads
Total Heating Required Including Ventilation Air:
25,626
Btuh
Total Sensible Gain:
21,017
Btuh
Total Latent Gain:
7,787
Btuh
Total Cooling Required Including Ventilation Air:
28,803
Btuh
Notes
Rhvac is an ACCA approved Manual J, D and S computer program.
0.417
1,000
25.626 MBH
73 %
27 %
2.40 Tons (Based On Sensible + Latent)
C:\Users\Owner\Desktop\AII .Rh Files\All .rh9 find ings\CCH-3712 Tanager.rh9 Wednesday, July 3, 2019, 10:25 AM
Rhvac - Residential & Light Commercial HVAC Loads
Florida H.E.R.O.
Newberry, FL 32669
Total Building Summary Loads (cont'd)
Elite Software Development, Inc.
CCH-3712 Tananqer
Page 6
Notes
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\Users\Owner\Desktop\AII .Rh Files\AII .rh9 findings\CCH-3712 Tanager.rh9 Wednesday, July 3, 2019, 10:25 AM
Rhvac - Residential & Light Commercial HVAC Loads
Florida H.E.R.O.
Newberry, FL 32669
Equipment Data - System 1 - Whole House
Cooling
System Type:
Outdoor Model:
Indoor Model:
Tradename:
Outdoor Manufacturer:
AHRI Reference No.:
Capacity:
Efficiency:
Heating
System Type:
Model:
Manufacturer:
Capacity:
Efficiency:
Standard Air Conditioner
4TTR6030J1
TEM6AOB30H21+TDR
XR16
TRANE
8626669
29,200
16.5 SEER
Electric Resistance
TAM7AOC36
Trane
25
0%
Elite Software Development, Inc.
CCH-3712 Tananger
Page 7
This system's equipment was selected in accordance with ACCA Manual S.
Manual S equipment sizing data: SODB: 90F, SOWB: 78F, WODB: 42F, SIDB: 75F, SIRH: 50%, WIDB: 72F, Sen. gain:
21,017 Btuh, Lat. gain: 7,787 Btuh, Sen. loss: 25,626 Btuh, Entering clg. coil DB: 76.1F, Entering clg. coil WB: 63.91F,
Entering htg. coil DB: 69.817, Clg. coil TD: 20F, Htg. coil TD: 70F, Req. clg. airflow: 900 CFM, Req. htg. airflow: 301 CFM
C:\Users\Owner\Desktop\AII .Rh Files\All .rh9 findings\CCH-3712 Tanager.rh9 Wednesday, July 3, 2019, 10:25 AM
Rhvac - Residential & Light Commercial HVAC Loads
Elite Software Development, Inc.
Florida H.E.R.O.
CCH-3712
Tananger
Newberry, Fl- 32669
Page 8
System 1 Room Load Summary
Htg
Min
Run
Run
Clg
Clg
Min
Act
Room
Area
Sens
Htg
Duct
Duct
Sens
Lat
Clg
Sys
No Name
SF
Btuh
CFM
Size
Vel
Btuh
Btuh
CFM
CFM
---Zone 1---
1 Master Bedroom
333
3,707
48
1-8
503
3,475
694
158
176
2 Master WIC 1
40
627
8
1-4
129
223
58
10
11
3 Master WIC 2
40
31
0
1-4
35
60
0
3
3
4 Master Bath
192
2,271
30
1-6
465
1,808
697
82
91
5 Master Bath WC
28
554
7
1-4
192
332
90
15
17
6 Bath 2
52
41
1
1-4
45
78
250
4
4
7 BR 3
181
1,453
19
1-6
334
1,297
109
59
66
8 Entry
72
827
11
1-4
364
628
44
29
32
9 Great Room
389
2,645
34
2-6
454
3,529
735
161
178
10 Dining
176
3,003
39
1-6
459
1,781
255
81
90
11 Kitchen
258
1,819
24
1-7
479
2,531
707
115
128
12 Laundry
57
44
1
1-4
150
258
250
12
13
13 BR 1
232
2,045
27
1-6
343
1,331
171
61
67
14 Guest Bath
72
1,496
19
1-4
375
647
396
29
33
15 BR 2
192
2,052
27
1-6
362
1,406
182
64
71
16 Garage Entry
87
538
7
0-0
0
397
36
18
20
Ventilation
2,473
1,236
3,113
System 1 total
2,400
25,626
301
21,017
7,787
900
1,000
System 1 Main Trunk Size:
14x14
in.
Velocity:
735
ft./min
Loss per 100 ft.:
0.348
in.wg
Cooling System Summary
Cooling
Sensible/Latent
Sensible
Latent
Total
Tons
Split
Btuh
Btuh
Btuh
Net Required:
2.40
73% / 27%
21,017
7,787
28,803
Actual:
2.43
77% / 23%
22,484
6,716
29,200
Equipment Data
Heating
System
Cooling System
Type:
Electric Resistance
Standard Air Conditioner
Model:
TAM7AOC36
4TTR6030J1
Indoor Model:
TEM6AOB30H21+TDR
Brand:
XR16
Efficiency:
0%
16.5 SEER
Sound:
0
0
Capacity:
25 Btuh
29,200 Btuh
Sensible Capacity:
n/a
22,484 Btuh
Latent Capacity:
n/a
6,716 Btuh
AHRI Reference No.:
n/a
8626669
This system's equipment was selected in accordance with ACCA Manual S.
Manual S equipment sizing data: SODB: 90F, SOWB: 78F, WODB: 42F, SIDB: 75F, SIRH: 50%, WIDB: 72F, Sen. gain:
21,017 Btuh, Lat. gain: 7,787 Btuh, Sen. loss: 25,626 Btuh, Entering clg. coil DB: 76.1F, Entering clg. coil WB: 63.91F,
Entering htg. coil DB: 69.8F, Clg. coil TD: 20F, Htg. coil TD: 70F, Req. clg. airflow: 900 CFM, Req. htg. airflow: 301 CFM
C:\Users\Owner\Desktop\All .Rh Files\AII .rh9 findings\CCH-3712 Tanager.rh9 Wednesday, July 3, 2019, 10:25 AM