HomeMy WebLinkAboutREGULATOR SPECS - 11-3-20Bulletin LP -7: R122H
Type R122H First -Stage Regulator
Introduction
The Type R122H is an Underwriters Laboratories listed
regulator designed for Two -Stage LP -Gas systems.
The unit is designed to reduce the tank pressure to an
outlet pressure of 10 psig. The compact size makes it
ideal for small domestic applications and underground
tanks. The outlet pressure setting is nonadjustable
and is factory set at a nominal 10 psig. Screened drip -
lip vents are oriented over the outlet as standard.
Features
20 Year Recommended Replacement Life — The
R122H is designed using rugged time proven
design concepts and constructed of corrosion
resistant materials, both internally and externally.
With proper installation and periodic inspection and
maintenance the R122H regulator will meet a 20
Year Recommended Replacement Life.
• Dual Gauge Taps — Built-in 118 inch NPT gauge
taps orificed to a number 54 drill size on both
the inlet and outlet side of the regulator allow for
easy testing.
• Durability — A fluorocarbon valve disc is utilized
to improve lockup performance in systems with
contaminated gas.
• Improved Regulation — A large fabric -reinforced
diaphragm and stabilizer clip deliver accurate and
stable regulation.
• Easy Installation — The units compact size and
easily accessible inlet and outlet wrench flats make
installation easy even in the tightest installations.
FISHER
March 2010
Figure 1. Type R122H First -Stage Regulator
Superior Overpressure Protection — The
combination of a high capacity relief valve and large
vent provide overpressure protection that exceeds
UL standards. When used in conjunction with a
R622 or R652, the two-stage system will limit the
downstream pressure from the second -stage to 2
psig even in a double failure situation.
• Corrosion -Resistant — Added corrosion resistance
from an internal and external coating process for all
castings prior to painting, stainless steel relief valve
spring and retainer and a corrosion resistant relief
valve seat.
• Positive Draining Spring Case — When installed
properly with the spring case vent pointed down,
the design allows moisture formed in the spring
case to drain out limiting the problems with
corrosion and freezing water in the spring case.
EMERSON_
Process Management
Bulletin LP -7: R122H
Table T. Ordering Information
TYPE NUMBER CAPACITY STUIHR CONNECTIONS
PROPANEIII INLET x OUTLET NOMINAL OUTLET SETTING
R122H-AA.! 1.100,000 1/4 -inch x 1/2 -trim NPT 10 ps19 (0,69 bar)
1. Capacity is based on 30 PSIG (2.07 bar) inlet pressure and 20% droop.
114.18 NP
Figure 2. Type R 122H Dimensions INCHES
(mm)
LP -Gas Equipment
Emerson Process Management
Regulator Technologies, Inc.
USA - Headquarters
McKinney, Texas 75069-1872 USA
Telephone; 1 (800) 558-5853
Telephone: 1 (972) 548-3574
For farther information visit www.fisheffegulators.com/lp
The Emerson logo is a trademark and servtce mark of Emerson Electric Co. All other marks are the property of their pmspecttve owners. Fisher Is a mark owned by Ratter Controta. Inc.. a
business of Emerson Process Management
The oonterds of tMs publication are presented for informational purposes only, and wht18 every effort has teen made to ensure their accuracy they are not to be construed as warranges or
4uararttees. ewess or Implied, regarding ute products or servloes described herein of their use or appiicabtllty. We reserve the right to modtfy or tmprove Ute designs or specMcattons of such
products at any tate vdtttout notice.
Emerson Process Management does not assume responsibility for the selection. use or maintenance of any product. Responsibility for proper setertrton. use and maintenance of any Emersm
Process Managerrtertt product rematne solely with the purchaser.
O
1
EMERSON.
*Emerson Process Management Regulator Technologies, Inc., 2003.2010; Ail Rights Reserved Process Management
Bulletin 71.1:R622
Type R622 Pressure Reducing Regulator
• Compact Desion
• Prote
Scree
June 2010
Wink -ity
• Inlet and Outlet Pressure Gauge Taps
Figure 1. Type R622 Pressure Reducing Reguletor
Introduction
Type R622 direct -operated. spring-loaded regulators
provide economical pressure reducing control in
a variety of residential. commercial. and industrial
FISHER'
Relief
Veight
applications. These regulators can be used with
natural. manufactured. or propane gases and have the
same inlet and outlet pressure capabilities.
EMERSON.
G
Bulletin 71.1:R622
ecifications
Body Size and End Connection Style()
112 NPT inlet and outlet
Maximum Allowable Inlet Pressure()
Operating: 125 psig (8,6 bar)
Emergency: 125 psig (8,6 bar)
Except 1.8 to 2.2 -inches w.c. (4 to 5 mbar) spring
range which has operating and emergency
pressures of 60 psig (4,1 bar)
Maximum Allowable Outlet (Casing) Pressure()
Operating to Avoid Internal Part Damage:
3 psid (0,21 bar d) above outlet pressure setting
Emergency: 20 psi (1,4 bar)
Outlet Pressure Ranges
See Table 1
Orifice Size
1!8 -inch (3,2 mm) orifice
Flow Coefficients
Wide -Open C. for Relief Sizing: 12.5
Wide -Open Cv for Relief Sizing: 0.36
Cl: 35
IEC Sizing Coefficients
XT: 0.78
Fp: 0.82
FL: 0.89
Flow Capacities
See Table 2
Pressure Registration
Internal
Relief Performance
See Figure 4
Internal Relief Performance
Start -to -Discharge is 8 to 22 -inches w.c.
(20 to 55 mbar) for setpoints from
1.8 to 20 -inches w.c. (4 to 50 mbar)
Start -to -Discharge is 140 to 200% over setpoint
from 20 -inches w.c. to 2.2 psig (50 to 152 mbar)
Spring Case Vent Connections
314 NPT with removable screen
Temperature Capabilities()
-20° to 160°F (-29° to 71 °C)
Approximate Weight
2.35 pounds (1 kg)
Construction Materials
Body, Spring Case, Diaphragm Plate, and
Orifice: Aluminum
Diaphragm, Disk, and O-ring: Nitrile (NBR)
Adjusting Screw and Pushpost: Delrin®
Closing Cap: ASA Thermoplastic (UV -Ray Resistant)
Control Spring: Zinc -plated steel
Machine Screw, Spring Seat,
and Lever: Zinc -plated steel
Valve Stem: Zinc
Relief Valve Spring, Relief Spring Retainer,
Lever Pin, and Vent Screen: Stainless steel
1. The preswaftemper lure laths in osis Bulletin or any applicable standard limdabon should not ne exceeded.
Deirtno is a mark owned by E I. du Pont de Nemours and Co.
In addition, Type R622 regulators have internal relief
across the diaphragm to help minimize overpressure.
Any outlet pressure above the start -to -discharge point
of the non-adjustable relief valve spring moves the
diaphragm off of the relief valve seat, allowing excess
pressure to bleed out through the screened spring
case vent.
Table 1. Outlet Pressure Ranges
Specifications
The Specifications section lists specifications for Type R622
Pressure Reducing Regulators. As it originally comes
from the factory, specifications for a given regulator
are stamped on the spring case nameplate.
OUTLET PRESSURE RANGE
CONTROL SPRING PART
NUMBER
CONTROL SPRING
COLOR CODE
SPRING WIRE DIAMETER.
INCHES (mm)
SPRING FREE LENGTH,
INCHES (mm)
1.8 to 2.24riches w.c. (4 to 5 mbar)
T 14453700/2
Purple
0.051 (1,30)
3.40 (86.4)
5 to 7 -inches w.c. (12 to 17 mbar)
T14398MO12
Orange
0.062 (1,58)
3.40 (86,4)
6.5 to 94netes w.c. (16 to 22 mbar)
T 14399T0012
Yellow
0.067 (1,70)
3.61 (91.7)
9 to 13 -aches w.c. (22 to 32 mbar)
T 1440070012
Sliver
0.072 (1,83)
4.10 (104)
13 to 204nches w.c. (32 to 50 mbar)
T14401T0012
Gray
0.080 (2,03)
3.60 (91,4)
16 to 35 -triches w.c_ (40 to 87 mbar)
T 14402T0012
Pink
0.093 (2,36)
3.52 (89.4)
1 to 2.2 psig (69 to 152 mbar)
T14403T0012
Light Blue
0105(2.67)
3.66 (93,0)