HomeMy WebLinkAboutBldg plans - 602014-Rev1 - Digital Sealed, 11.3.200 0 0 1. THESE PLANS PERTAIN ONLY TO THE STRUCTURE, INCLUDING MAIN WIND FORCE RESISTING SYSTEM, COMPONENTS AND CLADDING, AND BASE RAIL ANCHORAGE. OTHER DESIGN ISSUES, INCLUDING BUT NOT LIMITED TO PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY SET -BACKS, FINISH FLOOR ELEVATION AND SLOPE, OR OTHER LOCAL ZONING REQUIREMENTS ARE THE RESPONSIBILITY OF OTHERS. 2. THIS STRUCTURE IS DESIGNED AS A NON -HABITABLE UTILITY/STORAGE BUILDING (RISK CATEGORY 1) CAPABLE OF SUPPORTING DEAD LOAD OF THE STRUCTURE AND APPLICABLE LIVE AND WIND LOADS. IMPROVEMENTS NOT SPECIFICALLY ADDRESSED HEREIN, INCLUDING DOORS, WINDOWS, OR OTHER COMPONENTS NOT LISTED IN THE FBC APPROVED PRODUCTS LIST, AND NOT PROVIDED AND INSTALLED BY CARPORTS ANYWHERE, INC., WHICH EXERT ADDITIONAL LOADS ON THE STRUCTURE SHALL BE AT THE OWNER'S RISK. CARPORTS ANYWHERE NOR THE ENGINEERING DESIGN SHALL NOT BE RESPONSIBLE FOR STRUCTURAL DAMAGE OR FAILURE DUE TO THE APPLICATION OF ADDITIONAL LOADS. 3. THIS BUILDING IS EXEMPT FROM THE FBC ENERGY CONSERVATION CODE PER SECTION C101.4.2. 4. ALL STEEL TUBING SHALL BE 50 KSI STEEL AND MEETS/EXCEEDS GALVANIZATION PER ASTM A1003/A1003M-15. 5. PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY SET -BACKS, AND/OR OTHER LOCAL CODE REQUIREMENTS ARE THE RESPONSIBILITY OF THE OWNER. 6. ROOF AND WALL SHEATHING SECURED WITH #12-14x1" SELF -DRILLING SCREWS WITH SEAL WASHERS ® 6" O.C. MAX. 7. FIELD FRAMING CONNECTIONS SECURED WITH #12-14x3/4" SELF -DRILLING SCREWS. 8. ALL SHOP FRAMING CONNECTIONS ARE TO BE WELDED. NO WELDING ONSITE. ALL WELDING DONE IN SHOP BY A CERTIFIED WELDER. 9. CONCRETE EXPANSIONS ANCHORS ARE TO BE MINIMUM 1/2" DIAMETER & 2,500LB TENSILE STRENGTH. 10. 12 OR 14GA. FRAMING IS 2.5"x2.5" TUBE STEEL. NIPPLES ARE 2.25"x2.25" TUBE STEEL. 2'-6" 0 34'- WINDOW r--------------------------------------w------------------------------------------------------------- i i MIN. 2,500 PSI 4" CONCRETE SLAB WITH 10GA. W.W.F. FIBER MESH) AND 12"02" REINFORCED FOOTER PER ------------------------------WINDOW ------------ 0'- I"x54" EXPANSION ANCHOR WITHIN 6" OF EACH POST/TRUSS ALONG SIDES AND EVERY OTHER END -WALL POST 2" MIN. —I H- /-BASE RAIL GRADE — 1 I —III —I =1II IIIIIIIII111 �6" I-12"— MINIMUM SOIL BEARING CAPACITY 500 PSF(TYP.) SUB -GRADE SOILS: -TO BE TERMITE TREATED AND COVERED WITH 6 MIL VAPOR RETARDANT PER SECTION R318 AND 1816 OF THE 2017 FLORIDA BUILDING CODE, 6TH EDITION CONCRETE: -MINIMUM 2,500 PSI COMPRESSIVE STRENGTH AT 28 DAYS -ALL OPEN AREAS OF CONCRETE OUTSIDE OF THE PROPOSED STRUCTURE SHALL BE DESIGNED TO SLOPE AWAY FROM THE STRUCTURE REINFORCING STEEL (REBAR) REQUIREMENTS: -MINIMUM GRADE 40 STEEL -REBAR MAY BE BENT IN SHOP OR FIELD PROVIDED: -THE REBAR IS BENT COLD -THE DIAMETER OF THE BEND MEASURED ON THE INSIDE DOES NOT EXCEED 6-BAR DIAMETERS: AND -REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT EXCEPT IN CASES WHERE DOWELS NEED TO BE BENT TO ALIGN WITH A VERTICAL CELL. THESE REBAR MAY BE BENT NOT TO EXCEED TO SLOPE OF 1" HORIZONTALLY TO 6" VERTICALLY. -COVER: -2" COVER MINIMUM WHERE THE CONCRETE IS CAST AGAINST AND PERMANENTLY IN CONTACT WITH SOIL OR WEATHER, AND 14" ELSEWHERE. REBAR EMBEDDED IN GROUTED CELLS SHALL HAVE A MINIMUM CLEAR DISTANCE OF 4" FOR FINE GROUT, AND 4" FOR COARSE GROUT BETWEEN REBAR AND ANY FACE OF A CELL. REBAR USED IN MASONRY WALLS SHALL HAVE A MASONRY COVER (INCLUDING GROUT) OF NOT LESS THAN 2" FOR MASONRY UNITS WITH FACE EXPOSED TO EARTH OR WEATHER, AND 14" FOR MASONRY UNITS NOT EXPOSED TO EARTH OR WEATHER. GALVANIZATION: -METAL ACCESSORIES FOR USE IN EXTERIOR WALL CONSTRUCTION AND NOT DIRECTLY EXPOSED TO WEATHER SHALL BE GALVANIZED IN ACCORDANCE WITH ASTM A 153, CLASS B-2. METAL PLATE CONNECTORS, SCREWS, BOLTS, AND NAILS EXPOSED DIRECTLY TO WEATHER SHALL BE STAINLESS STEEL OR HOT DIPPED GALVANIZED. 0' ---------------------------------------------------------------------WINDOW -------------------------------------- ri L2,500 PSI 4" CONCRETE SLAB WITH 10GA. W.W.F. OR FIBER MESH (2) #5 REBAR CAD 6" O.C. CONTINUOUS WITH MINIMUM 12" OVERLAP SPLICE CONCRETE FOUNDATION/BASE RAIL ANCHOR DETAIL 7' 12 ----- sWINGFNG- -- DOOR _0". 2 5" PLAN VIEW DOOR FRAMING " RECESS 4 DOOR WIDTH ELEVATION VIEW DOOR FRAMING RECESS •75' ,,T 4„ DOOR WIDTH OPTIONAL ROLL —UP DOOR CONCRETE SPLASH —GUARD RECESS 2" REINFORCED FOOTER ------------------------------------------------- -------------------------------- WINDOW 0' 111 i o ROLL1UP DOOR CODE VERSION FBC 2017 6th Edition, ASCE-7-10 MANUFACTURER CARPORTS ANYWHERE BUILDING TYPE UTILITY STRUCTURE CONSTRUCTION TYPE II-B RISK CATEGORY I FIRE PROTECTION NONE FIRE SUPPRESSION SYSTEM INONE OCCUPANCY JUTILITY, U WIND SPEED Vult-150moh ENCLOSURE ENCLOSED INTERNAL PRESSURE COEFF. +/- 0.18 IMPORTANCE FACTOR 1.0 ROOF DEAD LOAD 1OPSF ROOF LIVE LOAD 20PSF OR 3001b P.L. FLOOR DEAD LOAD 1OPSF FLOOR LIVE LOAD 50PSF "R"RATING OF WALLS,FLOOR,ROOF N/A MODULES PER BUILDING 1 HURRICANE PROTECTION USAGE NO HURRICANE SHELTER USAGE NO SQUARE FOOTAGE 1,200 SQ. FT. REVISIONS 1 1 IREDESIGNED LENGTH & WIDTH 110/30/20 I MTB II 1—M, o,. MTB DATE: 7/30/20 LOCATION: 702 Anita St., Ft. Pierce SIZE: 60'L X 20'W X 14'H L\CENSF NO. 64608 i 2 STATE OF 44/ FL0R10P: ON A l l l l I- Digitally signed by Matthew --L Baldwin Date:2020.10.30 10:20:07-04'00' PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES z Matthew T. Baldwin P.E. Q Florida License #64608 Sheet: CA-1 OF 4 Q3 12 _e13" .-'13. ._e13• ``� 16 WW�� 14''-00" CAM BM CODE INFORMATION PRINTED COPIES OF THIS DOCUMENT CODE VERSION FBC 2017 6th Edition, ARE NOT CONSIDERED SIGNED AND ASCE-7 MANUFACTURER CARPORTSANYWHERE " _,. SEALED AND THE SHA AUTHENTICATION BUILDING TYPE UTILITY STRUCTURE ROLL-UPCODE MUST BE VERIFIED ON ANY CONSTRUCTION TYPE 11-B 0 DOOR 0 o •-p^ ELECTRONIC COPIES RISK CATEGORY I FIRE PROTECTION NONE FIRE SUPPRESSION SYSTEM NONE DOORR �j ROLL OCCUPANCY UTILITY, U WIND SPEED Vult-150mph EXPOSURE B ENCLOSURE ENCLOSED INTERNAL PRESSURE COEFF. +/- 0.18 3'-0" IMPORTANCE FACTOR 1.0 ROOF DEAD LOAD 1OPSF 2'-10j" 2'-1Oj" ROOF LIVE LOAD 20PSF OR 3001b P.L. 20'-0" FRONT END WALL 20'-0" REAR END WALL FLOOR DEAD LOAD 1OPSF FLOOR LIVE LOAD 50PSF "R"RATING OF WALLS, FLOOR, ROOF N/A MODULES PER BUILDING 1 HURRICANE PROTECTION USAGE NO HURRICANE SHELTER USAGE NO SQUARE FOOTAGE 1,200 SQ. FT. REVISIONS REV DESCRIPTON DATE BY 1 REDESIGNED LENGTH & WIDTH 10/30/20 MTB O.C. MAX. 0 i 2'-6" WINDOW ,I N WINDOW N DRAWN BY: MTB SWINGING DOOR 14 -" DATE: 7/30/20 " 10'-2, LOCATION: 702 Anita St., Ft. Pierce 3'-0" SIZE: 60'L X 20'W X 14'H •_„ '-11 '-11 '-11 '-11 60 -0" LEFT SIDE WALL W O.C. MAX. CD Z o � 2'-6" Q WINDOW N N WINDOW 10' 4 10'-2,b" LZL_ Matthew T. BOIdWin P.E. -1 IN" '-11 '-11 '-11 '-11 '-11 '-11 '-11 " '-11 " '-11 '-11 LLI Florida License #664608 RIGHT SIDE WALL 60'-0" Sheet: CA-2 Cr 4 WINDOW WINDOW PRINTED COPIES OF THIS DOCUMENT CODE VERSION FBC 2017 6th Edition, ARE NOT CONSIDERED SIGNED AND ASCE-7 SEALED AND THE SHA AUTHENTICATION MANUFACTURER CARPORTSS ANYWHERE BUILDING TYPE UTILITY STRUCTURE CODE MUST BE VERIFIED ON ANY CONSTRUCTION TYPE II—B ELECTRONIC COPIES RISK CATEGORY I FIRE PROTECTION INONE FIRE SUPPRESSION SYSTEM INONE OCCUPANCY JUTILITY, U WIND SPEED Vult-150mph ENCLOSURE ENCLOSED INTERNAL PRESSURE COEFF. +/— 0.18 IMPORTANCE FACTOR 1.0 ROOF DEAD LOAD 1OPSF 20'-0" I 20.-0" ROOF LIVE LOAD 20PSF OR 3001b P.L. FLOOR DEAD LOAD 10PSF FRONT REAR END WALL FRONT REAR END WALL FLOOR LIVE LOAD 50PSF "R"RATING OF WALLS, FLOOR, ROOF N/A MODULES PER BUILDING 1 HURRICANE PROTECTION USAGE NO HURRICANE SHELTER USAGE NO SQUARE FOOTAGE 11,200 SQ. FT. REVISIONS 1 1 IREDESIGNED LENGTH & WIDTH 110/30/20 1 MTB II SWINGING DOOR WINDOW DRAWN BY: MTB DATE: 7/30/20 LOCATION: 702 Anita St., Ft. Pierce SIZE: 60'L X 20'W X 14'H LEFT SIDE WALL o'—o" _W > z W W Matthew T. Baldwin P.E. Florida License E[ WINDOW D-D" RIGHT SIDE WALL w #64608 heet: CA-3 OF 4 I MINIMUM 6" TS NIPPLE. NIPPLE MINIMUM 6" TS NIPPLE. NIPPLE SECURED TO WALL POST WITH SECURED TO WALL POST WITH SC)REWS 14xj" SELF —DRILLING SC) 12 14xi" SELF —DRILLING jj'/ NIPPLE TO 2"x2"x2" 16 GA. ANGLE CLIP VV \\ BASE RAIL NIPPLE TO 13s" T BASE RAI is � SECURED WITH (4) #12-14xi" bZ SELF —DRILLING SCREWS POST TO BASE RAIL CONNECTION 2"x2"x2" 16 GA. ANGLE CLIP SECURED WITH (4) #12-14xj" SELF —DRILLING SCREWS NON—STRUCTURAL HEADER OR WINDOW RAIL TO POST DETAIL INTERIOR #12-14xi" SELF —DRILLING SCREWS ® 10" O.C. MAX., 3" MAX. FROM CORNERS HORIZONTALLY/ 4" MAX. FROM CORNERS VERTICALL` EXTERIOR DOOR FRAME TO POST CONNECTION END POST TO BASE RAIL CONNECTION 18" 2"x2"x2" 16 GA. ANGLE CLIP SECURED WITH (4) #12-14xi" SELF —DRILLING SCREWS 2"x2"x2" 16 GA. ANGLE CLIP SECURED WITH (4) #12-14xi" SELF —DRILLING SCREWS SINGLE OR DOUBLETS HEADER INTERMEDIATE POST TO HEADER/BASE RAIL/OR HEADER CONNECTION WINDOW RAIL DETAIL DETAIL OPTION 1 2"x2"x2" 16 GA. ANGLE CLIP SECURED WITH (4) #12-14xi" SELF —DRILLING SCREWS VARIES t TD. MAX. SPACING if 3" MIN. 4 j STD. MAX. SPICING ' VARIES > SIDE WALL ROLL —UP DOOR/FRAME OUT HEADER DETAIL INSTALL PER MANUFACTURERS INSTRUCTIONS #14x1" SELF —DRILLING SCREWS ® 6" O.C. MAX. & 6" MAX. FROM CORNERS ROLL —UP DOOR TO POST CONNECTION DESIGN PRESSURES — 150 Mph ROOF + 19.3/-41 .4 WALLS +20.0/-22.2 DOORS +20.0/-22.2 WINDOWS +20.0/-22.2 1 2 3 4 5 ZONE +9.3 —21.9 +12.3 —35.1 +19.3 —41.4 +18.8 —21.9 +20.0 —22.2 26 GAUGE ROOF SHEATHING SECURED WITH (1)#12-14xj" SELF —DRILLING SCREWS '2-1-2-1' (6" O.C. (9" O.C. MAX.)) 1" 16 GAUGE FURRING CHANNEL 48" O.C. MAX. SECURED WITH (2)#12-14x1" SELF —DRILLING SCREWS TO EACH RAFTER. ROOF PANEL CONNECTIO VERTICAL SHEATHING OPTION IPPLE TO TRUSS 1 "x2j" 16 GA. U—CHANNEL BRACE, MIN. 24" UP TO 7' POST, 0 r 48" OVER 7' POST. MIN. 45' TO MAX. 60' FROM HORIZ. (EXCLUDE END —WALLS). SECURED WITH (4)#12-14xj" SELF —DRILLING SCREWS. MINIMUM 6" TS NIPPLE. NIPPLE SECURED TO WALL POST WITH (4)#12-14xj" SELF —DRILLING SCREWS BOX SAVE RAFTER TO POST CONNECTION DETAIL TO PILE MINIMUM 6" TS NIPPLE. NIPPLE SECURED TO WALL POST WITH 12-14xi" SELF —DRILLING EWS SINGLE OR DOUBLETS HEADER HEADER CONNECTION DETAIL OPTION 2 MINIMUM 6" TS NIPPLE. NIPPLE SECURED TO WALL POST WITH (4)#12-14xi" SELF —DRILLING SCREWS POST TO TRUSS CONNECTION PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES APPROVED PRODUCTS APPROVAL NO. ROOF SHEATHING Carports Anywhere FL27402.1 — R 1 Hampton Rib Roof Panel WALL SHEATHING Carports Anywhere FL27403.1 Hampton Rib Wall Panel SWINGING DOOR ELIXER DOOR AND METAL COMPANY FL17996.5 407 STEEL DOOR ROLL —UP DOOR JANUS INTERNATIONAL CORPORATION FL21450.3 SERIES 3100 WINDOW POCOHONTAS ALUMINUM COMPANY, INC. FL12940—R5 MODEL 100VS CODE VERSION BUILDING TYPE UTILITY STRUCTURE CONSTRUCTION TYPE II—B RISK CATEGORY I FIRE PROTECTION NONE FIRE SUPPRESSION SYSTEM NONE OCCUPANCY UTILITY, U WIND SPEED Vult-150mDh ENCLOSURE ENCLOSED INTERNAL PRESSURE COEFF. +/— 0.18 IMPORTANCE FACTOR 1.0 ROOF DEAD LOAD 10PSF ROOF LIVE LOAD 20PSF OR 3001b P.L. FLOOR DEAD LOAD 1OPSF FLOOR LIVE LOAD 50PSF VRATING OF WALLS, FLOOR, ROOF N/A MODULES PER BUILDING 1 HURRICANE PROTECTION USAGE NO HURRICANE SHELTER USAGE NO SQUARE FOOTAGE 1,200 SQ. FT. REVISIONS 1 1 (REDESIGNED LENGTH & WIDTH 110/30/20 1 MTB II UKAWN er: MTB DATE: 7/30/20 LOCATION: 702 Anita St., Ft. Pierce SIZE: 60'L X 20'W X 14'H J Q Matthew T. Baldwin P.E. < Florida License #64608 w W o Sheet: CA-4 OF 4