HomeMy WebLinkAboutTruss®=LIFE SAFETY WARNING
This symbol identifies Life Safety Warnings that should be read
given special attention by all persons installing trusses.
5PAGING NOTE
ALL TRUSSES ARE TO BE SET
AT 2'-O: ON CENTER
EXCEPT AS NOTED
MULTIPLE PLY TRUSSES MUST BE
ASTENED TOGETHER PER ENGINEERING
BEFORE SETTING. REFER TO
ENGINEERING DRAWING TO DETERMINE
A& IF MULTIPLE PLY.
DON'T LIFT TRUSSES
WITH SPANS LONGER THAN
30' BY THE PEAK.
CONSULT BCSI
30' Span or less & 30' to 60' Span
o`degrees Spreaider Bar
or less
i
1 /2 _� - ' ag �_ Approz 2/3 to
Tag Line Span approx.: Line 1/2 of Span
REFER TO BCSI REFER TO BCSI
Truss must be set this way if crane used Truss must be set this way if he used
Truss is on example, your truss racy not match This is on example, truss may. not match.
Insist crane operator sets truss this way, Insist crone operator .sets truss this way..
U REPRESENTS A HANGER
- Carrying Girder
' Fnr Tri ice to Tri ice
" SEAT
PLATES BY CHAMBERS
INDICATES LOAD BEARING WALL
REQUIRED BY TRUSSES
SUPPLIED BY BUILDER
AT A HEIGHT OF 8'-1"
ABOVE FINISHED FLOOR
12
4.00
M
upset--1/4" heel=315/16"
PLUMB CUT END
1'
2 x 4 Top Chord
WALL HEIGHT 8'-1"
TYPICAL END DETAIL
12
4.00 IF --
to
Lo
s
2.00 $�
th
2
upset=1/4" heel=315/16"
PLUMB CUT END
2 x 4 Top Chord
+
WALL HEIGHT 8'-1"
END DETAIL: A
I
i
L
The Architect's or Architect's repYesehtative's j
shop drawing approval is NOT a.
TH CRANE OPERATOR IN ADVANCE FOR A SPREADER BARnip
, OF 171 �, 1 I LENGTH Theeontractor'ld ,,,acn:eraetor_
for checking field measurementsnand
e
n trusses until they are braced per BCSI properly nailed to straps & hangers °approval coves generrf roof shape
reviewof trus a pe,
GARAGE LEFT
structure from' strapprng, and loadi
gravit rig on
their respec 9 end uplift loads and
Approved By:.. ..
--- --- - - -- — - —— FABRICATION AGREEMENT
TRUSSES CANNOT BE STARTED UNTIL THIS AGREEMENT IS SIGNED &RETURNED
20' --- - 14
'Ria Iagal description of the property where the trusses will be Installed is:
The undersigned acknowledges and agreea: j
I'; Trusses will be made In strict accordance with this t uss placement drag am tryout,
which Is the sole authority for determiningsuccessful fabrication of the trusses.
2. All dimensions In this layout have been verified by the undersigned,
.3. Unless written notice Is provided by certified mall to Chambers Truss wit tan (tD)
days of delivery the undersigned agrees that no backcharges will be allowed, In the event
such written notes Is furnished Chambers Truss shell have three (3) busytass days in whi—
'to begin repairs required, or to substitute other trusses, at Chambers oplin,
4. The undersigned acknowledges mcalpt of "SCSI 1-03" summary sheet by'fP18 WTCv1.
S. Delivery Is to job site, It Is the buyeee'responslb-03- to make the Job site suitable for j
delivery. Chambers Truss has the cola authority, to determine the suitability of the job site of a
portion of the Job site for delivery, Chambers Truss will be responsible for dump delivery only.
The buyer is responsible for additional delivery expenses If Chambers Truss has to redeliver
because job site Is riot prepared for delivery or buyer Is not prepared for delivery of trusses. '
Buyer Is responsible to Chambers Truss for towing costs due to site conditions.
8. Prim as shown In paragraph 7 below is subject to change If any changes are, made Ica
this layout. A $50 per hour fee for revisions may be charged by Chambers Truss,
,7: This Ia a PURCHASE ORDER to Chambers, Truss of the sum agreed to, or if nk
on delivery. Invoice may, be made at scheduled date bf delivery If
agreement a reasonable price. Invoice will be made on delivery and paid within terms of not
' buyer cannot accept
delivery of fabricated trusses. The undersigned agrees to pay Chambers. Truss reasonable
attorneys fee for collections In event of payment not timely made. 1-12 %gper month service
charge will be added for all sums not paid within terms.
. S. Signature or initials anywhere on this sheet constitutes agreement to all terns heroin. P
9: In consideration of Chambers Truss extending credit for this material the undersigned i
unconditionally guarantees payment when due of any and all Indebtedness owed to
Chambers Truss by any entity receiving material and the undersigned agrees to pay such j•
Indebtedness Including attorneys fees, If default In payment for material be made by the
recipient.
10. In the event of any litigation concerning this agreement, the Items furnished hereunder
or payments referred to herein, the, parties agree that the sole venue for any such action wilt
be Saint I:ucle, County, Florida.
11. Design responsibilities are per-Natlonal Standard And Recommended Guidelines On I
Responsibilities For Coristructlon Using Metal Plate Connected Wood Trusses
ANSVrPINWTCA 4 - 2002 -
DATED J.
Sf(3NED
FOR TITLE
Asp wdorbarmaybe reg4ued pW'ECSI1-03"fo pleventirgtay& d mage. .
MUltiple ply trusses must be fastened togtithar per engineering
before they are se$ failure to do so can result In roof collapse.
Temporary and permanent bracing are required and can save life
and property and is the responsibility of the truss erector.
Study the contents of the Information packet included on delivery ii
before setting trusses.
Trusses mtistbesetandbraced per design tDpir entinjuldamage,
Trusses must be sat plumb and square
Do not set bunks or stack of plywood, roofing material or any
other concentrated loads on trusses, this can cause collapse.
CIONOT SET TRUSSES USING THIS LAYOUT `
USE LAYOUT DELIVERED WITH TRUSSES TO SET TRUSSES I
CHAMBERS TRUSS INC
3106 Oleander Avenue
Fort Mercer Florida 34982 -6423
800-551-5932
Fort Pierce 772-465.2012 Fax 772-465-8711
Vero Beach 772-569-2012 Stuart 772-286-3302 '
I
92.0/93.2 MITEK 4.2.
DESIGN CRITERIA
County SAINT LUCIE
Building Department SAINT LUCIE COUNTY
a Wind Design Criteria ASCE 7-2010 1
Wind Design Method MWFRS/C-C hybrid Wind ASCE 7-1
'o p Roofing Material Shingle or Shake
T =N Loading in PSF Roof R.D.L.
N ` Z ` Top Chord Live 20
° Top Chord Dead 7 4.2
0
E' r Bottom Chord Live 10 Non -Concurrent i
` Bottom Chord Dead 10 3 „
U) I TOTAL Load ` 37 7.2
M o Duration Factor 1.25
v m Wind Speed 165mph
Top Chord C.B. Sheeting by builder.
. Bottom Chord C.B. She
eting b
z� � 9 Y builder.
u Highest Mean Height 14!-0"
Building Type ENCLOSED
Building Category II:Non Restrictive
Exposure Category C
Barrier Island No
Conforms to FBC 2017
R.D.L.=Restrainin Dead Load C.B.=Continuous Bracin €
Verify DESIGN CRITERIA shown above with the j
building department and your engineer.
Design Criteria is the responsibility of the
Illy Building Designer and/or Engineer of Record!
Chambers Truss Inc. Drawing Name: Ml13231!
Scale: 1 /4 = 1'
(� 72 total trusses, 13 different trusses.
r— MI 4: SAE ACAD: SAE Reviewed By:
Date:04/24/12 Revised:02/21/18
3'-4" 6-4"FOR . Revised: 3/05/2020
Ti-10" _ e
® WYNNE BUILDING CORP.
-- � DESCRIPTION•
GARAGE RIGHT I�Lds�w4Eac�,bALTON
?-nr)E COMPL4MOECUSTOMER INITIALS EACH PAGE
13 TRUSS DRAWINGS ARE ATTACHED TO LAYOU'ft)cIE CVITT323 76
Ror
l moms
MiTek
tea. S
RE: M11323 MiTek USA, Inc.
M11323 6904 Parke East Blvd.
Tampa, FL 33610-4115
Site Information:
Customer: WYNNNE DEVELOPEMENT CORP Project -Name: M11323
Lot/Block: Model: CARLTON
Address: N/A Subdivision:
City: PORT ST LUCIE State: FL
General Truss Engineering Criteria & Design Loads (Individual Truss Design Drawings Show Special
Loading Conditions):
Design Code: FBC2017/TP12014
Design Program: MiTek 20/20 8.1
Wind Code: ASCE 7-10
Wind Speed: 165 mph
Roof Load: 37.0 psf
Floor Load: N/A psf
This package includes 13 individual, dated
Truss Design Drawings and 0 Additional Drawings.
With my seal affixed to this
sheet, I hereby
certify that I am the Truss Design Engineer and this index sheet
conforms to 61 G15-31.003, section 5 of the Florida Board
of Professional Engineers Rules.
No. Seal#
1 T19884596
2 T19884597
Truss Name
A
A5
Date
7/31/2020
7/31/2020
FILE uff NIJ%ff
3- T19884598
A6
7/31/2020
4 T19884599
A7
7/31/2020
5 T19884600
A8
7/31/2020
6 T19884601
A9
7/31/2020
7 T1988460
8 T19884603
GRA
GRB
7/31/2020
7/31/2020
REVIEWED
REVIEWED FOR
9 T19884604
J2
7/31/2020
CODE COMPLIANCE
10
1T19884606
J6
7/31/2020
��® LUCIE®LNTY
12 T19884607
J8
7/31/2020
13 T19884608
KJ8
7/31/2020
0In,�
This item has been electronically signed and sealed by Velez, Joaquin using a Digital Signature.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies
The truss drawing(s) referenced above have been prepared by
MiTek USA, Inc under my direct supervision
based on the parameters provided by Chambers Truss. ��OPQU I N
Truss Design Engineer's Name: Velez, Joaquin E NgF,,�
My license renewal date for the state of Florida is February 28, 2021.
Florida COA: 6634 No 68182
IMPORTANT NOTE: The seal on these truss component designs is a certification
that the engineer named is licensed in the jurisdiction(s) identified and that the
designs comply with ANSI/TPI 1. These designs are based upon parameters
shown (e.g., loads, supports, dimensions, shapes and design codes), which were
given to MiTek. Any project specific information included is for MiTek
customers file reference purpose only, and was not taken into account in the preparation of
these designs. MiTek has not independently verified the applicability of the design
parameters or the designs for any particular building. Before use, the building designer
should verify applicability of design parameters and properly incorporate these designs
into the overall building design per ANSI/TPI 1, Chapter 2.
�r
:1 0: STATE OF
11111
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610 July 31, 2020
1 of 1 Velez, Joaquin
Job
Truss
Qty
Ply
M11323
VrussMType
M11323
A
N
9
1
Job Reference o tional
" Chambers Truss, Inc., Fort Pierce, FL 8,240 s Mar 9 2020 MTek Industries, Inc. Fri Apr 3 07:54:27 2020 Page 1
ID:a3B4PavKnnZweXyJckSFBgyuFUN-bAjL909k_1 Hpv5SDpc_pEKrtnVLQuvtwTtLrJWzUUjw
L0-0, 6-7-13 12.4-13 17-0-0 21-7-3 27-4-3 34-o-0 35 0-q
i-010 6-7-13 5-9-0 4-7-3 4-7-3 5-9-0 6-7-13 -0-0
3x6 =
4.00 12 4x5 =
27
17 15 "" "' 14 12
2x3 II 4x6 = 3x8 =
3x8 = 4x6 = 2x3 II
Scale = 1:57.8
3x6 =
1 �
IA
6
6-7-13 12-4-13 21-7-3 27.4-3
34-0-0
6-7-13 5-9-0 9-2-7 5-9-0
6-7-13
Plate Offsets (X,Y)—
[2:0-0-2,Edge), [10:0-0-2,Edge)
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in (loc) I/deft Lid
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.39
Vert(LL) 0.32 14-15 >999 360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.58
Vert(CT) -0.61 14-15 >670 240
BCLL 0.0
Rep Stress Incr YES
WB 0.65
Horz(CT) 0.12 10 file file
BCDL 10.0
Code FBC2017/TPI2014
Matrix -MS
Weight: 163 lb FT = 0%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 3-7-12 oc purlins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 4-11-7 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 10=0-8-0
Max Horz 2=-179(LC 8)
Max Uplift 2=-832(LC 10), 10=-832(LC 10)
Max Grav 2=1362(LC 1), 10=1362(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-3419/2395, 3-5=-2771/2031, 5-6=-2770/2152, 6-7=-2770/2152, 7-9=-2771/2031,
9-10=-3419/2395
BOT CHORD 2-17=-2132/3213,15-17=-2132/3213,14-15=-1269/2000,12-14=-2132/3213,
10-12=-2132/3213
WEBS 6-14=-635/983, 7-14=-313/362, 9-14=-689/499, 6-15=-635/983, 5-15=-313/362,
3-15=-689/499
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-4-13, Interior(1) 2-4-13 to 13-7-3, Exterior(2) 13-7-3
to 20-4-13, Interior(1) 20-4-13 to 31-7-3, Exterior(2) 31-7-3 to 35-0-0 zone;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
This item has been
will fit between the bottom chord and any other members, with BCDL = 10.Opsf.
electronically Signed and
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb)
sealed by Velez, Joaquin, PE
2=832, 10=832.
using a Digital Signature.
6) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 50 lb down and 47 lb up at
Printed copies of this
15-0-0, and 50 lb down and 47 lb up at 19-0-0 on top chord. The design/selection of such connection device(s) is the responsibility
of others.
document are not considered
7) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
Signed and sealed and the
signature must be verified
LOAD CASE(S) Standard
on any electronic copies.
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (plf)
Joaquin Velez PE No.68182
Vert: 1-6=-54, 6-11=-54, 18-21=-20
MiTek USA, Inc. FL Cert6634
Concentrated Loads (lb)
6904 Parke East Blvd. Tampa FL 33610
Vert: 26=-50(F) 27=-50(F)
Date:
April 3,2020
® WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5119/2020 BEFORE USE.
Design valid for use only with MITek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall MOW
building design. Bracing indicated is to prevent buckling. of individual truss web and/or chord members only. Additional temporary and permanent bracing iVliTe k•
is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSYTP11 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information avallable from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty,
Ply
M11323
T19884597
M11323
A5
SPECIAL
9
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:28 2020 Page 1
ID:2GIScwwyY5hnGhXVARzUkuyuFUM-3MHjMkAMIKQgXE1 PNJV2mXOxRucedNo4iX50ryzUUjv
1-0-0 7-8-5 1 10-6 4 17-0-0 20-4-8 26 4-0 34-0-0 5 0-
0-0 7-8-5 2-9-15 6 5 12 3 4-8 5-11-8 7-8-0 -0-0
�1
0
5x8 MT18HS 11
4.00 12
Scale = 1:59.8
13 12
5x12 = 2x3 II 3x6 =
3x12 = 2.00 12
10-6-4 19-10-4
5.11-8 7-8-0
Plate Offsets (X,Y)—
[2:0-1-15,Edge], [4:0-3-0,Edge], [10:0-0-6,Edge]
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in
(loc) I/deft Ud
PLATES
GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.85
Vert(LL) 0.76
14 >539 360
MT20
244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.90
Vert(CT) -1.18
13-14 >344 240
MT18HS
244/190
BCLL 0.0
Rep Stress Incr YES
WB 0.60
Horz(CT) 0.36
10 n/a n/a
BCDL 10.0
Code FBC2017frP12014
Matrix -MS
Weight: 155 lb
FT = 0%
LUMBER-
BRACING.
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 1-7-8 oc puffins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied or 3-9-12 oc bracing.
WEBS 2x4 SP No.3 *Except*
WEBS
1 Row at micipt 6-14
6-14: 2x4 SP M 30
OTHERS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 10=0-8-0
Max Horz 2=-179(LC 8)
Max Uplift 2=-803(LC 10), 10=-803(LC 10)
Max Grav 2=1312(LC 1), 10=1312(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-5529/3776, 3-5=-5164/3538, 5-6=-5209/3667, 6-7=-2424/1902, 7-9=-2462/1813,
9-10=-3195/2210
BOT CHORD 2-14=-3466/5266, 13-14=-1305/2115, 12-13=-1948/2995, 10-12=-1948/2995
WEBS 3-14=-355/314, 5-14=-293/354, 6-14=-2175/3326, 6-13=-279/534, 7-13=-237/277,
9-13=-786/560, 9-12=0/269
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10: Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-4-13, Interior(1) 2-4-13 to 13-7-3, Exterior(2) 13-7-3
to 20-64, Interior(1) 20-6-4 to 31-7-3, Exterior(2) 31-7-3 to 35-0-0 zone;C-C for members and forces & MWFRS for reactions shown;
Lumber DOL=1.60 plate grip DOL=1.60
3) All plates are MT20 plates unless otherwise indicated.
This item has been
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
electronically signed and
5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
sealed by Velez, Joaquin, PE
will fit between the bottom chord and any other members.
using a Digital Signature.
6) Bearing at joint(s) 2 considers parallel to grain value using ANSUTPI 1 angle to grain formula. Building designer should verify
Printed Copies of this
capacity of bearing surface.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
document are not considered
2=803,10=803.
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII.7473 rev. 5119/2020 BEFORE USE.
--
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property Incorporate this design into the overall
r
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTek
is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANS11TP/1 Quality Criteria, DSB-89 and BCS/ Building Component
6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601
Tampa, FL 36610
Job
Truss
Truss Type
Ply
M11323
T19884598
M11323
A6
�Qty
SPECIAL
1
1
Job Reference (optional)
Chambers Truss, Inc.; Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:29 2020 Page 1
I D:2G IScwwyY5hnG hXVARzU kuyu FUM-YYr6a4B_W eYX90cbw00 HJ Ix7ilyPMm6DxBgy00zU Uju
1-0-0 8-11-11 16-0-0 18-0-0 20-4-8 25-11-15 34-0-0 5-0
-0-0 8-11-11 7-0-5 2-M 2-4-8 5-7-7 8-0-1 -0-0
4.00 12
3x12 = 2.00 12
10-6-4
LOADING (psf)
SPACING-
2-0-0
TCLL
20.0
Plate Grip DOL
1.25
TCDL
7.0
Lumber DOL
1.25
BCLL
0.0
Rep Stress Incr
YES
BCDL
10.0
Code FBC2017/TPI2014
LUMBER -
TOP CHORD 2x4 SP M 30 'Except*
3-5,6-7: 2x4 SP M 31
BOT CHORD 2x4 SP M 30
WEBS
2x4 SP No.3 *Except*
5-14: 2x4 SP M 30
OTHERS
2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 9=0-8-0
Max Horz 2=-169(LC 8)
Max Uplift 2=-803(LC 10), 9=-803(LC 10)
Max Grav 2=1312(LC 1), 9=1312(LC 1)
6x10 MT18HS =
56 =
I'd 11
5x6 = 2x3 II
3x6 =
Scale = 1:61.9
CSI.
DEFL.
in (loc) I/defl Ud
PLATES
GRIP
TC 0.81
Vert(LL)
0.69 14 >590 360
MT20
244/190
BC 0.93
Vert(CT)-0.9214-17 >443 240
MT18HS
244/190
WB 0.86
Horz(CT)
0.34 9 n/a n/a
Matrix -MS
Weight: 157 lb
FT = 0%
BRACING -
TOP CHORD
Structural wood sheathing directly applied or 2-2-0 oc puriins.
BOT CHORD
Rigid ceiling directly applied or 2-2-0 oc bracing.
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 24=-5491/3336, 4-5=-5095/3071, 5-6=-2314/1551, 6-8=-2398/1533, 8-9=-3199/1981
BOT CHORD 2-14=-3040/5224, 13-14=-1195/2361, 12-13=-1123/2199, 11-12=-1731/3001,
9-11=-1731/3001
WEBS 4-14=-492/513, 5-14=-1707/2959, 5-13=-405/196,6-13=-179/522, 8-12=-893/660,
8-11=0/303
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-4-13, Interior(1) 2-4-13 to 31-7-3, Exterior(2) 31-7-3
to 35-0-0 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
7) Bearing atjoint(s) 2 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify
capacity of bearing surface.
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
2=803, 9=803.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
®WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII.7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and is for an Individual building component, note
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design Into the overall rtil•Y
building design. Bracing Indicated Is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek*
Is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI17P11 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safetylnformadon available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Ply
M11323
T19884599
M11323
A7
SPECIAL
�Qty
1
1
Job Reference (optional)
Chambers Truss, Inc., Fart Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:30 2020 Page 1
ID:WSJgpGwalPpeur6hk9UjG5yuFUL-OIPUnQCcHygOmYBnUkXWryTI Fi145CtN9gaVwrzUUjt
1-0-0 8-10-10 14-0-0 20-0-0 25-11-15 34-0-0 5-0-
-0-0 8-10-10 5-1-6 6-0-0 5-11-15 8-0-1 -0-0
�1
6
Ann
3x12 = 2.00 12
5x8 =
5x6 =
LOADING (psf)
SPACING-
2-0-0
CSI.
TCLL
20.0
Plate Grip DOL
1.25
TC 0.83
TCDL
7.0
Lumber DOL
1.25
BC 0.90
BCLL
0.0
Rep Stress Incr
YES
WB 0.95
BCDL
10.0
Code FBC2017/TPI2014
Matrix -MS
LUMBER -
TOP CHORD
2x4 SP M 30
BOT CHORD
2x4 SP M 30
WEBS
2x4 SP No.3 `Except`
4-11: 2x4 SP M 30
REACTIONS.
(size) 2=0-8-0, 7=0-8-0
Max Horz 2=-149(LC 8)
Max Uplift 2=-803(LC 10). 7=-803(LC 10)
Max Grav 2=1312(LC 1), 7=1312(LC 1)
IV
5x12 =
2x3 11
3x6 =
Scale = 1:60.8
DEFL.
in (loc)
I/clef!
Ud
PLATES
GRIP
Vert(LL)
0.66 11
>616
360
MT20
244/190
Vert(CT)
-1.1010-11
>369
240
MT18HS
244/190
Horz(CT)
0.34 7
n/a
n/a
Weight: 147 lb
FT = 0%
BRACING-
TOP CHORD Structural wood sheathing directly applied or 2-2-0 oc purlins
BOT CHORD Rigid ceiling directly applied or 4-0-2 oc bracing.
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-5484/3370, 3-4=-5116/3126, 4-5=-2229/1544, 5-6=-2448/1599, 6-7=-3169/1993
BOT CHORD 2-11 =-3071/521 9, 10-11=-1590/2874, 9-1 0=-1 73812968, 7-9=-1738/2968
WEBS 3-11=-419/443, 4-11 =-1 466/2647, 4-1 0=-8 12/448, 5-10=-205/487, 6-10=-785/575,
6-9=0/272
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-4-13, Interior(1) 2-4-13 to 31-7-3, Exterior(2) 31-7-3
to 35-0-0 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) ` This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
7) Bearing atjoint(s) 2 considers parallel to grain value using ANSIfrPI 1 angle to grain formula. Building designer should verify
capacity of bearing surface.
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb)
2=803, 7=803.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
®WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and is for an individual building component, not
Not
a truss system. Before use, the building designer must verify the applicability of design parameters and property Incorporate this design Into the overall
building design. Bracing Indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTek'
is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPI1 Quality Criteria, DSB-89 and BCSI Building Component
6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601
Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
M11323
T19884600
M11323
AS
SPECIAL
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:31 2020 Page 1
I D: WSJgpGwa I Ppeur6hk9Uj G5yuFU L-Uxzs_mC E2FoFOiI_2 R210AOTj6eKgjE WOUJ2SHzU Ujs
1-0-0 8-8-4 12-0-0 15-8-4 20-4-8 22-0-0 24-8-12 34-0-0 5-0
-0-0 8-8-4 3 3-12 3-8-4 4-8-4 1-7-8 2-8-12 i 9-3-4 14
Scale = 1:60.6
4.00 12
5x6 =
3x4 =
4 21 5
2x3 11 5x8 =
6 22 7 2.3
N
IA
6
12 11
3x12
5x12 = 3x4 = 4x5 =
= 2.00 12
10-6-4 20-4-8 22-0-0 34-M
10.6-4 9-10-4 1-7-8 12-M
Plate Offsets (X,Y)—
[2:0-1-15,Edge], [7:0-5-8,0-2-8]
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in (loc) I/deft Lid
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.78
Vert(LL) 0.65 12-13 >624 360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.90
Vert(CT) -1.08 12-13 >379 240
MT18HS 244/190
BCLL 0.0
Rep Stress Incr YES
WB 0.69
Horz(CT) 0.33 9 n/a n/a
BCDL 10.0
Code FBC2017/TPI2014
Matrix -MS
Weight: 154 lb FT = 0%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 2-2-0 oc purlins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 3-11-11 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 9=0-8-0
Max Horz 2=-129(LC 8)
Max Uplift 2=-803(LC 10), 9=-803(LC 10)
Max Grav 2=1312(LC 1), 9=1312(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=5488/3444, 34=-5117/3183, 4-5=-3911/2497, 5-6=-2576/1770, 6-7=-2586/1779,
7-8=-2663/1762,8-9=-3021/1971
BOT CHORD 2-13=-3143/5224, 12-13=-1956/3292, 11-12=-1369/2481, 9-11 =-1 705/2827
WEBS 3-13=-396/420, 4-13=-1028/1721, 5-13=-300/797, 5-12=-894/601, 6-12=-265/263,
7-12=-294/391,7-11=-374/691,8-11=-535/502
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-4-13, Interior(1) 24-13 to 31-7-3, Exterior(2) 31-7-3
to 35-0.0 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
This item has been
will fit between the bottom chord and any other members.
electronically Signed and
7) Bearing atjoint(s) 2 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify
sealed by Velez, Joaquin, PE
capacity of bearing surface.
using a DiDi
Digital Signature.
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb)
Printed this
2=803, 9=803.
copies of
rp
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
® WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mil-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TP/1 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
City
Ply
M11323
];HP
T19884601
M11323
A9
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:32 2020 Page 1
ID:_etC1 cxC3ixW?huts?ypJyuFUK-y7XEC6DspZw6OsKAc9Z_xNZ18W4CZ7Mfd83c?jzUUjr
-0 6-7-15 10-0-0 15-2-14 20-4-0 24-0-0 27 4-1 34-0-0
0-0 6-7.15 3-4-1 5-2-14 5-1-2 3-8-0 3 4-1 6-7-15 -0-0
4.00 12
3x5 =
44 = 3x4 = 2x3 II 4x8 =
4 24 525 26 6 27 7
15 14 13 12 11
3x8 = 3x6 =
6x8 = 3x6 = 3x4 =
Scale=1:58.6
3x5
10-0-0
20A-0
24-0-0
34-0-0
10-0-0
1OA-0
3-8-0
10-0-0
Plate Offsets (X,Y)—
[2:0-0-14,Edgel, [7:0-5-4,0-2-01,[9:0-3-14,0-1-8j
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL.
in (loc)
I/defl
L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.35
Vert(LL)
-0.18 11-21
>917
360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.54
Vert(CT)
-0.38 11-21
>432
240
BCLL 0.0
Rep Stress Incr YES
WB 0.89
Horz(CT)
0.02 13
n/a
n/a
BCDL 10.0
Code FBC2017/TPI2014
Matrix -MS
Weight: 156 lb FT = 0%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 5-11-9 oc pudins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 6-0-0 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 9=0-8-0, 13=0-8-0
Max Horz 2=109(LC 9)
Max Uplift 2=430(LC 10), 9=-249(LC 10), 13=-928(LC 10)
Max Grav 2=685(LC 19). 9=386(LC 20), 13=1616(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-1275/1025, 3-4=-913/708, 4-5=-829/705, 5-6=-565/807, 6-7=-565/807,
7-8=-104/278, 8-9=-341/235
BOT CHORD 2-15=-836/1187, 13-15=-34/309, 11-13=-256/348, 9-11 =-1 241304
WEBS 3-15=-425/501, 5-15=-444/665, 5-13=-1215/1079, 6-13=-264/300, 7-11=-255/396,
8-11=-461/521, 7-13=-837/703
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-4-13, Interior(1) 2-4-13 to 5-2-5, Exterior(2) 5-2-5 to
14-9-11, Interior(1) 14-9-11 to 19-2-5, Exterior(2) 19-2-5 to 28-9-11, Interior(1) 28-9-11 to 31-7-3, Exterior(2) 31-7-3 to 35-0-0
zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
'
This item has been
5) This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
electronically signed and
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb)
sealed by Velez, Joaquin, PE
2=430, 9=249,13=928.
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
®WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design into the overall ppr
iTe k•
building design. Bracing indicated Is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the iVl
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/7P/1 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Ply
M11323
T19884602
M11323
GRA
HIP
�Qty
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2UZU Mi I ex. InousmeS, Inc. I-n Apr 3 u/:b4:ss zuzu rage 1
ID: etClcxC3ixVV?huls?ypJyuFUK-QK4cPSEUat2zdOvM9s4DTb5n5vPvlY6proo9XAzUUjq
�1-0-0 8-0-0 11-1-1 17-0-0 18-6-0 , 22-2-2 26-0-0 , 34-0-0 a5-0-q
-0-0 8-0-0 3-1-1 5-10-15 1-6-0 3 8-2 3%-14I-0-0'
�1
6
THIS TRUSS IS NOT SYMMETRIC.
PROPER ORIENTATION IS ESSENTIAL.
4x4 =
Scale=1:60.6
29 -" 27 26 -- 24
3x5 —_ 3x6 II 3x6 = 6x8 = 3x6 = 6x8 = 4x4 =
6x8 =
TRUSS DESIGNED FOR WIND LOADS IN THE PLANE
OF THE TRUSS ONLY. FOR STUDS EXPOSED TO WIND
(NORMAL TO THE FACE), SEE STANDARD INDUSTRY
GABLE END DETAILS AS APPLICABLE, OR CONSULT
QUALIFIED BUILDING DESIGNER AS PER ANSlrrPI 1.
8-0-0 3-1-1 1 7-4-15 7-6-0 18-0-0
Plate Offsets (X,Y)—
[2:0-2-2,Edge], [3:0-3-8,Edge], [21:0-3-8,Edge], [24:0-3-8,0-3-0], [27:0-3-8,0-3-0]
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in (loc) I/deft Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.91
Vert(LL) 0.20 24-35 >914 360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.57
Vert(CT) -0.24 29-32 >552 240
BCLL 0.0
Rep Stress Incr NO
WB 0.98
Horz(CT) 0.02 22 We n/a
BCDL 10.0
Code FBC2017/TP12014
Matrix -MS
Weight: 194 lb FT = 0%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 4-2-5 oc pudins.
BOT CHORD 2x4 SP M 30 Except:
WEBS 2x4 SP No.3 1 Row at midpt 8-21
BOT CHORD Rigid ceiling directly applied or 6-0-0 oc bracing.
JOINTS 1 Brace at Jt(s): 7, 8, 19, 17, 14
REACTIONS. All bearings 0-8-0.
(lb) - Max Horz 2=-179(LC 6)
Max Uplift All uplift 100 lb or less at joint(s) except 2=-351(LC 8), 27=-1168(LC 8), 26=-1495(LC 8),
22=-625(LC 8)
Max Grav All reactions 250 lb or less atjoint(s) except 2=487(LC 17), 27=2232(LC 13), 26=2929(LC 14),
22=984(LC 14)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
TOP CHORD 2-3=-621/387,3-5=-304/838, 5-7=-588/1209, 7-8=-588/1209, 8-12=-588/1209,
12-13=-588/1209, 13-15=-588/1209, 15-16=-588/1209, 16-18=-588/1209,
18-20=-2230/1280, 20-21=-2230/1280, 21-22=-2271/1263, 6-9=-126/305, 9-11=-106/363,
11-14=-193/412,14-17=-94/271,19-21=-1431272
BOT CHORD 2-29=-247/677, 27-29=1891540, 26-27=-779/446, 24-26=411/653, 22-24=-1083/2108
WEBS 3-29=-500/1176, 3-27=1766/911, 5-27=-748/622, 5-26=-546/351, 13-26=-946/617,
18-26=-2412/1474,18-24=-846/1780,21-24=-35/351,4-5=608/514,19-20=335/305,
14-15=-556/407,11-12=-254/54
NOTES-
1) Unbalanced roof live loads have been considered for this design.
This item has been
2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
Il; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
electronically signed and
3) Provide adequate drainage to prevent water ponding.
Sealed by Velez, Joaquin, PE
4) All plates are 2x3 MT20 unless otherwise indicated.
using a Digital Signature.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
•
Printed copies of this
6) This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
document are not considered
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 351 lb uplift at joint 2, 1168 lb uplift at
signed and sealed and the
joint 27, 1495 lb uplift at joint 26 and 625 lb uplift at joint 22.
Signature must be Verified
8) Girder carries hip end with 8-0-0 end setback.
On an electronic copies.
y p
9) Graphical puriin representation does not depict the size or the orientation of the pudin along the top and/or bottom chord.
Joaquin Velez PE No.68182
10) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 967 lb down and 461 lb up at
MiTek USA, Inc. FL Cert 6834
26-0-0, and 967 lb down and 461 lb up at 8-0-0 on bottom chord. The design/selection of such connection device(s) is the
6904 Parke East Blvd. Tampa FL 33610
responsibility of others.
Date:
11) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
April 3,2020
andard
Z.
®WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall Not
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and tress systems, see ANS11TP/1 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Ply
T19884602
M11323
GRA
�Qty
HIP
1
1
�M`11323
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL
8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:33 2020 Page 2
ID:_etcl cxC3ixVV?huls?ypJyuFUK-QK4cPSEUat2zdOvM9s4DTb5n5vPvlY6proo9XAzUUjq
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (plf)
Vert: 1-3=54, 21-23=-54, 29-30=-20,24-29=-47(F=-27),24-33=-20,3-11=-126(F=-72), 11-21=-126(F=-72)
Concentrated Loads (lb)
Vert: 29=-641(F) 24=-641(F)
®WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 10II.7473 rev. 5119/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not
bet
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated is to prevent buckling of Individual truss web and/or chard members only. Additional temporary and permanent bracing
MiTek
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIMP/1 Quality Criteria, DSB-89 and BCSI Building Component
6904 Parke East Blvd.
Safety Information avaiiabie from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601
Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
M11323
T19884603
M11323
GRB
HIP
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:34 2020 Page 1
I D: SrRaEyyrgO4M78G4ra W BL WyuF UJ-u W e?d oF7LAApF9UZjacSOo e_iJjP10by4Sr3czU Ujp
8-0-0 13-8-0 17-0-0 20.4-0 26-0-0 34-0-0
I�0-0 8-0-0 5-8-0 3-0-0 3-4-0 5-8-0 8-0-0 -0-0
Scale = 1:58.6
4x6 =
5x12 MT18HS = 4x10 =
4.00 12 2x3 II 46 = 2x3 II
3 23 4. 5 6 7 24
3x6 5x6 = 6x12 =
6x12 = 5x6 =
5x12 MT18HS =
3x6 11
4x6 =
8-0-0 13-8-0
20 4-0
26-0-0
34-0-0
8-0-0 5-8-0
6--8
5-8-0
8-0-0
Plate Offsets (X Y)—
[3:0-9-0 0-2-8] [5:0-3-O,Edge],[8:0-9-0,0-2-8]
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL.
in (loc) I/deft Ud
PLATES
GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.80
Vert(LL)
0.22 16-19 >999 360
MT20
244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.68
Vert(CT) -0.30 16-19 >820 240
MT18HS
2441190
BCLL 0.0
Rep Stress Incr, NO
WB 0.90
Horz(CT)
0.06 9 n/a n/a
BCDL 10.0
Code FBC2017/TPI2014
Matrix -MS
Weight: 153 lb
FT = 0%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 3-1-14 oc purlins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied or 5-3-14 oc bracing.
WEBS 2x4 SP No.3 *Except'
WEBS
1 Row at midpt 3-14, 8-13, 6-13
4-14,7-13: 2x6 SP No.2
REACTIONS. (size) 2=0-8-0, 13=0-8-0, 9=0-8-0
Max Horz 2=90(LC 7)
Max Uplift 2=-853(LC 8), 13=-2590(LC 8), 9=-345(LC 8)
Max Grav 2=1451(LC 13), 13=4743(LC 15), 9=528(LC 14)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-3625/1950, 3-4=-2080/1236, 4-6=-2080/1236, 6-7=-1296/2589, 7-8=-1296/2589,
8-9=-751 /370
BOT CHORD 2-16=-1729/3460, 14-16=-1753/3525, 11-13=-262/733, 9-11=-241/668
WEBS 3-16=-435/1209, 3-14=-1552/774, 4-14=-837/691, 7-13=-878/713, 8-13=-3635/1919,
8-11=-432/1204,6-14=-1453/2814,6-13=-3198/1807
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
'
This item has been
6) This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
electronically signed and
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 853 lb uplift at joint 2, 2590 lb uplift at
sealed by Velez, Joaquin, PE
joint 13 and 345 lb uplift at joint 9.
using a Digital Signature.
8) Girder carries hip end with 8-0-0 end setback.
Printed copies S Of this
p
9) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 967 lb down and 461 lb up at
26-0-0, and 967 lb down and 461 lb up at 8-0-0 on bottom chord. The design/selection of such connection device(s) is the
document are not considered
responsibility of others.
signed and sealed and the
10) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
signature must be verified
LOAD CASE(S) Standard
on any electronic copies.
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6634
Uniform Loads (plf)
Vert: 1-3=-54, 3-8=-131(F=-77), 8-10=-54, 16-17=-20, 11-16=49(F=-29), 11-20=-20
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
a
® WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mil-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall Welk'
/�g
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing IYI iTe k•
Is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSUIpIf Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
M11323
GRB
HIP
11
[M111323T19884603
o tional
Chambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:35 2020 Page 2
ID:SrRaEyyrg04M78G4raW BLWyuFUJ-MiCNg7G16UIgtJ31HH7hYOB9Sj3emSr6J6HGb2zUUjo
LOAD CASE(S) Standard
Concentrated Loads (Ib)
Vert: 16=-641(F) 11=-641(F)
®WARNING -Verify design parameters aQd READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mll-7473 rev. 5119/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design into the overall my
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing Mire k•
Is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 Quality Criteria, DSB-89 and BCS/ Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Ply
M11323
T19884604
M11323
J2
MONO TRUSS
�Qty
8
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:35 2020 Page 1
ID:xl?zSlzTbJCDIIrGPH1 QukyuFUI-MiCNg7G16U IgtJ31HH7hYOBJ7jCDmgz6J6HGb2zUUjo
-1-0-0 2-0-0
1-0-0 2-0-0
Scale = 1:7.8
3x4 =
2-0-0
2-0-0
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL. in (loc) I/defl Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.18
Vert(LL) -0.00 7 >999 360
MT20 244/190
TCDL 7.0
Lumber DOL
1.25
BC 0.07
Vert(CT) -0.00 7 >999 240
BCLL 0.0
Rep Stress Incr
YES
WB 0.00
Horz(CT) -0.00 3 n/a n/a
BCDL 10.0
Code FBC20171rP12014
Matrix -MP
Weight: 8 lb FT = 0%
LUMBER-
BRACING -
TOP CHORD 2x4 SP No.3
TOP CHORD Structural wood sheathing directly applied or 2-0-0 oc purlins.
BOT CHORD 2x4 SP No.3
BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 3=Mechanical, 2=0-8-0, 4=Mechanical
Max Horz 2=67(LC 10)
Max Uplift 3=-28(LC 10), 2=-136(LC 10), 4=-3(LC 7)
Max Grav 3=39(LC 15), 2=141(LC 1), 4=31(LC 3)
FORCES. (lb) - Max. Comp./Max. Ten. - All farces 250 (lb) or less except when shown.
NOTES-
1) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) zone;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 28 lb uplift at joint 3, 136 lb uplift at joint
2 and 3 lb uplift at joint 4.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
®WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mll-7473 rev. 6/1912020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design Into the overall MiTek*
building design. Bracing Indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing 1 VliTek•
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANS8TP11 Quality Criteria, DSB-89 and BCS/ Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
M11323
T19884605
M11323
J4
MONO TRUSS
8
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL
3x4 =
8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:36 2020 Page 1
ID:PDYLfd_5MdK4MSQTz?ZfRxyuFUH-gvml2TGNtoQXUTexr?ew5DjQW7UmV7DFYml pBUzUUjn
4-0-0 ,
Scale = 1:11.1
4-0-0
4-0-0
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in
(loc) I/deft Lid
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.39
Vert(LL) 0.02
4-7 >999 360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.37
Vert(CT) -0.02
4-7 >999 240
BCLL 0.0
Rep Stress Incr YES
WB 0.00
Horz(CT) -0.00
3 n/a n/A
BCDL 10.0
Code FBC2017/TPI2014
Matrix -MP
Weight: 14 lb FT = 0%
LUMBER-
BRACING -
TOP CHORD 2x4 SP No.3
TOP CHORD
Structural wood sheathing directly applied or 4-0-0 oc puffins.
BOT CHORD 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 3=Mechanical, 2=0-8-0, 4=Mechanical
Max Horz 2=104(LC 10)
Max Uplift 3=-80(LC 10), 2=161(LC 10), 4=-7(LC 10)
Max Grav 3=90(LC 1), 2=207(LC 1), 4=69(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All farces 250 (lb) or less except when shown.
NOTES-
1) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) zone;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 80 lb uplift at joint 3, 161 lb uplift at joint
2 and 7 lb uplift at joint 4.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
®WARNING -Verily design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mll-7473 rev. 5/19/2020 BEFORE USE. '
Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall
building design. Bracing Indicated Is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MOW
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP/1 Quality Criteria, DSB-89 and BCS/ Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
T19884606
M11323
J6
MONO TRUSS
8
1
�1011323
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:36 2020 Page 1
I D:tP6jtzj7xSx_c_fXi4uz9yuFUG-gvml2TGNtoQXUTexI?ew5DjR?7MUV7DFYm 1 p8UzUUjn
1-0-0 6-0-0
1-o6-0-0
Scale=1:14.6
3x4 =
6-0-0
6-0-0
LOADING (psi)
SPACING- 2-0-0
CSI.
DEFL, in
(loc) I/dell L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.36
Vert(LL) 0.11
4-7 >629 360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.83
Vert(CT) -0.12
4-7 >617 240
BCLL 0.0
Rep Stress Incr YES
WB 0.00
Horz(CT) -0.00
3 n/a n/a
BCDL 10.0
Code FBC2017rrP12014
Matrix -MP
Weight: 20 lb FT = 0%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 6-0-0 oc puriins.
BOT CHORD 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 3=Mechanical, 2=0-8-0, 4=Mechanical
Max Horz 2=142(LC 10)
Max Uplift 3=-131(LC 10), 2=-194(LC 10), 4=-8(LC 10)
Max Grav 3=145(LC 1), 2=279(LC 1), 4=102(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
NOTES-
1) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) zone;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 131 lb uplift at joint 3, 194 lb uplift at
joint 2 and 8 lb uplift at joint 4.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cott 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
®WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII.7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design into the overall I m�
building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing IY/iTe k♦
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI17P/1 quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Grain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
3T1M11323
J8
MONO TRUSS
20
1b
M1132
Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL
1-0-0
3x5 =
8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:37 2020 Page 1
I D:lP6jtzJ7xSx_c_fXi4uz9yuFUG-J5K7FpH?d5YO6d D8Oi99eRGYgXquEaTPmQmNgxzU Ujm
Scale=1:17.4
8-0-0
8-0-0
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in
(loc) I/dell Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.62
Vert(LL) 0.26
4-7 >367 360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.38
Vert(CT) -0.30
4-7 >319 240
BCLL 0.0
Rep Stress Incr YES
WB 0.00
Horz(CT) -0.00
3 n/a n/a
BCDL 10.0
Code FBC2017/TP12014
Matrix -MP
Weight: 26 lb FT = 0%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 6-0-0 oc purlins.
BOT CHORD 2x4 SP M 31
BOT CHORD
Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 3=Mechanical, 2=0-8-0, 4=Mechanical
Max Horz 2=180(LC 10)
Max Uplift 3=-175(LC 10), 2=-228(LC 10), 4=-15(LC'10)
Max Grav 3=188(LC 1), 2=352(LC 1), 4=145(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
NOTES-
1) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) -1-0-0 to 2-4-13, Interior(1) 2-4-13 to 3-1-13, Exterior(2) 3-1-13
to 7-11-8 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 175 lb uplift at joint 3, 228 lb uplift at
joint 2 and 15 lb uplift at joint 4.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
®WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design Into the overall�e
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek♦
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding She
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TP/1 Quality Criteria, OSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Tmss
Truss Type
City
Ply
M11323
T19884608
M11323
KJ8
MONO TRUSS
4
1
Job Reference (optional)
"Chambers Truss, Inc., Fort Pierce, FL 8.240 s Mar 9 2020 MiTek Industries, Inc. Fri Apr 3 07:54:38 2020 Page 1
ID: Lcg54J?Lu EancmZr4Qb7 W MyuFU F-n HuVT9ldOPg FknoKyPg OAeooawB GzwZY?4WwCNzU Ujl
-1-5-0 7-3-4 11-3-0
1-5-0 7-3-4 3-11-12
3x4 = o
Scale=1:20.3
3x4 =
7-3-4
11-3-0
7-3-4
3-11-12
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL, in
(loc) I/deft Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.29
Vert(LL) 0.07
7-10 >999 360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.30
Vert(CT) -0.12
7-10 >999 240
BCLL 0.0
Rep Stress Incr NO
WB 0.46
Horz(CT) 0.02
6 n/a n/a
BCDL 10.0
Code FBC2017/iP12014
Matrix -MS
Weight: 44 lb FT = 0%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 6-0-0 oc purlins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied or 8-9-6 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 4=Mechanical, 2=0-11-5, 6=Mechanical
Max Horz 2=244(LC 8)
Max Uplift 4=-205(LC 8), 2=-305(LC 8), 6=-286(LC 8)
Max Grav 4=245(LC 13), 2=466(LC 1), 6=590(LC 13)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-1151/523
BOT CHORD 2-7=-687/1126, 6-7=-687/1126
WEBS 3-7=0/330, 3-6=-1236/755
NOTES-
1) Wind: ASCE 7-10; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=14ft; B=52ft; L=34ft; eave=6ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 205 lb uplift at joint 4, 305 lb uplift at
joint 2 and 286 lb uplift at joint 6.
6) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
LOAD CASE(S) Standard
This item has been
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
electronically signed and
Uniform Loads (plf)
sealed by Velez, Joaquin; PE
Vert: 1-2=-54
Trapezoidal Loads (calf)
using a Digital Signature.
Vert: 2=0(F=27, 8=27)-to-4=-152(F=-49, B=-49), 8=0(F=10, B=10)-to-5=-56(F=-18, B=-18)
tco ine
copies of this
Prp
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.66182
MiTek USA, Inc. FL Cart6634
6904 Parke East Blvd. Tampa FL 33610
Date:
April 3,2020
®WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design Into the overall �•
building design. Bracing indicated Is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek`
is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TP/f Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Symbols
PLATE LOCATION AND ORIENTATION
Center plate on joint unless x, y
offsets are indicated.
Dimensions are in ft-in-sixteenths.
Apply plates to both sides of truss
and fully embed teeth.
O'11fi r
-
-I-
For 4 x 2 orientation, locate
plates 0- '18' from outside
edge of truss.
This symbol indicates the
required direction of slots in
connector plates.
Plate location details available in MiTek 20/20
software or upon request.
PLATE SIZE
The first dimension is the plate
4 x 4 width measured perpendicular
to slots. Second dimension is
the length parallel to slots.
LATERAL BRACING LOCATION
Indicated by symbol shown and/or
by text in the bracing section of the
output. Use T or I bracing
if indicated.
BEARING
Indicates location where bearings
(supports) occur. Icons vary but
reaction section indicates joint
number where bearings occur.
Min size shown is for crushing only.
Industry Standards:
ANSI/TPl1: National Design Specification for Metal
Plate Connected Wood Truss Construction.
DSB-89: Design Standard for Bracing.
BCSI: Building Component Safety Information,
Guide to Good Practice for Handling,
Installing & Bracing of Metal Plate
Connected Wood Trusses.
Numbering System
6-4-8 dimensions shown in ft-in-sixteenths
(Drawings not to scale)
2 3
TOP CHORDS
O
2
U
0-
0
8 7 6 5
JOINTS ARE GENERALLY NUMBERED/LETTERED CLOCKWISE
AROUND THE TRUSS STARTING AT THE JOINT FARTHEST TO
THE LEFT.
CHORDS AND WEBS ARE IDENTIFIED BY END JOINT
NUMBERS/LETTERS.
PRODUCT CODE APPROVALS
ICC-ES Reports:
ESR-1311, ESR-1352, ESR1988
ER-3907, ESR-2362, ESR-1397, ESR-3282
Trusses are designed for wind loads in the plane of the
truss unless otherwise shown.
Lumber design values are in accordance with ANSI/TPI 1
section 6.3 These truss designs rely on lumber values
established by others.
© 2012 MiTek@ All Rights Reserved
� 1♦
Bill
MiTeke
MiTek Engineering Reference Sheet: Mll-7473 rev. 5/19/2020
A General Safety Notes
Failure to Follow Could Cause Property
Damage or Personal Injury
1. Additional stability bracing for truss system, e.g.
diagonal or X-bracing, is always required. See BCSI.
2. Truss bracing must be designed by an engineer. For
wide truss spacing, individual lateral braces themselves
may require bracing, or alternative Tor I
bracing should be considered.
3. Never exceed the design loading shown and never
stack materials on inadequately braced trusses.
4. Provide copies of this truss design to the building
designer, erection supervisor, property owner and
all other interested parties.
5. Cut members to bear tightly against each other.
6. Place plates on each face of truss at each
joint and embed fully. Knots and wane at joint
locations are regulated by ANSI/TPI 1.
7. Design assumes trusses will be suitably protected from
the environment in accord with ANSI/TPI 1.
8. Unless otherwise noted, moisture content of lumber
shall not exceed 19% at time of fabrication.
9. Unless expressly noted, this design is not applicable for
use with fire retardant, preservative treated, or green lumber.
10. Camber is a non-structural consideration and is the
responsibility of truss fabricator. General practice is to
camber for dead load deflection.
11. Plate type, size, orientation and location dimensions
indicated are minimum plating requirements.
12. Lumber used shall be of the species and size, and
in all respects, equal to or better than that
specified.
13. Top chords must be sheathed or pudins provided at
spacing indicated on design.
14. Bottom chords require lateral bracing at 10 ft. spacing,
or less, if no ceiling is installed, unless otherwise noted.
15. Connections not shown are the responsibility of others.
16. Do not cut or alter truss member or plate without prior
approval of an engineer.
17. Install and load vertically unless indicated otherwise.
18. Use of green or treated lumber may pose unacceptable
environmental, health or performance risks. Consult with
project engineer before use.
19. Review all portions of this design (front, back, words
and pictures) before use. Reviewing pictures alone
is not sufficient.
20. Design assumes manufacture in accordance with
ANSI/TPI 1 Quality Criteria.
21.The design does not take into account any dynamic
or other loads other than those expressly stated.